manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. GE
  6. •
  7. Relay
  8. •
  9. GE CEX57D User manual

GE CEX57D User manual

Other manuals for CEX57D

1

This manual suits for next models

2

Other GE Relay manuals

GE P4A User manual

GE

GE P4A User manual

GE SBC223 User manual

GE

GE SBC223 User manual

GE GSY51A User manual

GE

GE GSY51A User manual

GE Multilin DBT User manual

GE

GE Multilin DBT User manual

GE CEY53A User manual

GE

GE CEY53A User manual

GE 750 User manual

GE

GE 750 User manual

GE IFCV51AD User manual

GE

GE IFCV51AD User manual

GE F60 User manual

GE

GE F60 User manual

GE MDP User manual

GE

GE MDP User manual

GE MiCOM P40 Agile P14D User manual

GE

GE MiCOM P40 Agile P14D User manual

GE MDP User manual

GE

GE MDP User manual

GE IBCG51M User manual

GE

GE IBCG51M User manual

GE UR series How to use

GE

GE UR series How to use

GE 750 User manual

GE

GE 750 User manual

GE P642 User manual

GE

GE P642 User manual

GE IAV54E User manual

GE

GE IAV54E User manual

GE IJCS2A User manual

GE

GE IJCS2A User manual

GE b30 Use and care manual

GE

GE b30 Use and care manual

GE IAC59A User manual

GE

GE IAC59A User manual

GE ICR51A User manual

GE

GE ICR51A User manual

GE ACR11B User manual

GE

GE ACR11B User manual

GE JBCV51M User manual

GE

GE JBCV51M User manual

GE IBCG51M*Y1A Series User manual

GE

GE IBCG51M*Y1A Series User manual

GE P50 Agile P253 User manual

GE

GE P50 Agile P253 User manual

Popular Relay manuals by other brands

Woodward BU1-DC2 manual

Woodward

Woodward BU1-DC2 manual

ABB SSR32 product manual

ABB

ABB SSR32 product manual

Siemens SIRIUS 3UG4633 operating instructions

Siemens

Siemens SIRIUS 3UG4633 operating instructions

Siemens SIRIUS 3TK2824 A.20 Series Original operating instructions

Siemens

Siemens SIRIUS 3TK2824 A.20 Series Original operating instructions

Shelly Pro Series user manual

Shelly

Shelly Pro Series user manual

ABB RELION REF615R manual

ABB

ABB RELION REF615R manual

Kemo Electronic B197 quick guide

Kemo Electronic

Kemo Electronic B197 quick guide

Seg MRM3 manual

Seg

Seg MRM3 manual

Basler BE1-700C manual

Basler

Basler BE1-700C manual

CD Automation REVEX 2PH 280A user manual

CD Automation

CD Automation REVEX 2PH 280A user manual

ABB SPAJ 142 C User manual and technical description

ABB

ABB SPAJ 142 C User manual and technical description

Ruelco 1S04 Operation manual

Ruelco

Ruelco 1S04 Operation manual

Basler V3E Z1P B2C1F instruction manual

Basler

Basler V3E Z1P B2C1F instruction manual

Kyongbo Electronics GDR-D01 user manual

Kyongbo Electronics

Kyongbo Electronics GDR-D01 user manual

Eaton easyE4 series Application note

Eaton

Eaton easyE4 series Application note

Siemens BD2-AK03X/FS Series installation instructions

Siemens

Siemens BD2-AK03X/FS Series installation instructions

Leuze MSI-SR5B Original operating instructions

Leuze

Leuze MSI-SR5B Original operating instructions

Littelfuse SE-330AU manual

Littelfuse

Littelfuse SE-330AU manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

GEK
-
49778
D
INSTRUCTIONS
ANGLE
-
IMPEDANCE
RELAY
TYPES
:
CEX
57
D
CEX
57
E
CEX
57
F
GE
Power
Management
205
Great
Valley
Parkway
Malvern
,
PA
19355
Telephone
:
(
610
)
251
-
7000
www
.
ge
.
com
/
edc
/
pm
Courtesy of NationalSwitchgear.com
GEK
-
49778
CONTENTS
PAGE
DESCRIPTION
APPLICATION
CEX
57
D
AND
CEX
57
F
CEX
57
E
RATINGS
CONTACTS
OPERATING
PRINCIPLES
CHARACTERISTICS
ANGLE
-
IMPEDANCE
UNIT
UPPER
UNIT
LOWER
UNIT
TAPPED
AUTOTRANSFORMER
BURDENS
CURRENT
CIRCUIT
POTENTIAL
CIRCUIT
CALCULATION
OF
SETTINGS
rflNCTRlirTTON
RECEIVING
,
HANDLING
AND
STORAGE
ACCEPTANCE
TESTS
VISUAL
INSPECTION
MECHANICAL
INSPECTION
ELECTRICAL
TESTS
ELECTRICAL
TESTS
-
AUXILIARY
UNIT
(
CEX
57
F
ONLY
)
INSTALLATION
PROCEDURE
LOCATION
MOUNTING
CONNECTIONS
VISUAL
INSPECTION
MECHANICAL
INSPECTION
INSPECTION
ANGLE
-
IMPEDANCE
TESTS
PERIODIC
CHECKS
AND
ROUTINE
MAINTENANCE
CONTACT
CLEANING
SERVICING
CONTROL
SPRING
ADjuSTMENT
*
.
*
.
!
!
!
.
.
ANGLE
OF
MAXIMUM
TORQUE
ADJUSTMENT
BASIC
REACH
OHMS
CORE
ADJUSTMENT
RENEWAL
PARTS
3
3
3
4
4
4
4
6
6
6
7
7
8
8
8
9
10
11
12
12
12
12
OHM
UNIT
13
14
14
14
14
14
14
14
14
15
15
16
16
16
17
18
18
(
COVER
PHOTO
8042958
)
2
Courtesy of NationalSwitchgear.com
GEK
-
49778
ANGLE
-
IMPEDANCE
RELAY
TYPES
:
CEX
57
D
CEX
57
E
CEX
57
F
DESCRIPTION
Type
CEX
57
relays
are
high
speed
induction
cup
-
type
devices
with
ohm
unit
characteristics
that
can
be
set
parallel
to
the
impedance
of
a
transmission
line
.
The
relays
are
designed
for
use
with
other
protective
devices
in
blinder
applications
to
restrict
the
tripping
area
of
the
tripping
units
used
in
a
protective
relay
scheme
.
Or
,
they
may
be
used
in
applications
where
tripping
is
required
during
an
out
-
of
-
step
condition
.
instruction
book
.
These
applications
are
discussed
in
the
APPLICATION
section
of
this
Type
CEX
57
relays
each
contain
two
cup
-
type
units
,
and
they
are
mounted
in
an
M
2
size
case
.
The
CEX
57
F
relay
also
contains
an
auxiliary
telephone
-
type
unit
.
Internal
connections
for
the
relays
are
shown
in
Figures
9
,
10
and
11
;
typical
external
connections
are
shown
in
Figure
5
.
Outline
and
panel
drilling
dimensions
are
shown
in
Figure
14
.
APPLICATION
The
CEX
57
relays
were
designed
specifically
for
use
in
blinder
applications
,
or
in
applications
to
initiate
tripping
during
an
out
-
of
-
step
condition
.
Three
models
of
the
relay
are
available
:
CEX
57
D
,
CEX
57
E
and
CEX
57
F
.
Typical
applications
for
each
of
these
relays
are
as
follows
:
CEX
57
D
AND
CEX
57
F
The
CEX
57
D
and
CEX
57
F
relays
are
used
in
blinder
applications
to
restrict
the
area
of
the
tripping
functions
used
in
a
transmission
line
protective
relaying
scheme
(
see
Figure
4
)
.
Either
three
CEX
57
D
or
three
CEX
57
F
relays
are
required
.
Basically
,
tripping
will
be
permitted
only
when
the
fault
impedance
plots
within
the
reach
of
the
mho
tripping
function
AND
both
of
the
ohm
units
.
Since
the
right
hand
ohm
unit
will
operate
only
for
faults
to
the
left
of
it
,
both
units
can
operate
simultaneously
only
for
faults
that
plot
between
them
.
The
tripping
function
(
mho
)
will
provide
correct
directional
action
,
and
limit
the
reach
in
the
forward
direction
.
The
contacts
of
the
CEX
57
D
ohm
units
are
brought
out
separately
,
and
are
externally
connected
in
series
with
the
contacts
of
the
corresponding
mho
tripping
function
to
provide
supervision
(
see
Figure
5
C
)
.
The
contacts
of
the
CEX
57
F
relay
are
These
instructions
do
not
purport
to
cover
all
details
or
variations
in
equipment
nor
to
provide
for
every
possible
contingency
to
be
met
in
connection
with
installation
,
operation
or
maintenance
.
Should
further
information
be
desired
or
should
particular
problems
arise
which
are
not
covered
sufficiently
for
the
matter
should
be
referred
to
the
General
Electric
Company
.
the
purchaser
'
s
purposes
.
To
the
extent
reguired
the
products
described
herein
meet
applicable
ANSI
,
but
no
such
assurance
is
given
with
respect
to
local
codes
and
ordinances
because
they
vary
greatly
.
IEEE
and
NEMA
standards
;
3
Courtesy of NationalSwitchgear.com
GEK
-
49778
internally
connected
in
series
,
and
are
used
to
operate
the
internal
mounted
auxiliary
telephone
relay
.
The
contacts
of
this
auxiliary
relay
are
then
used
to
supervise
the
corresponding
mho
tripping
function
(
see
Figure
5
B
)
.
CEX
57
E
The
Type
CEX
57
E
relay
was
designed
specifically
for
use
with
Type
GSY
or
NAA
relays
,
which
provide
the
additional
functions
required
to
implement
an
out
-
of
-
step
tripping
scheme
.
Only
one
CEX
57
E
relay
is
required
in
these
applications
.
The
CEX
-
NAA
combination
is
primarily
for
application
to
transmission
lines
,
combination
is
primarily
for
application
to
generators
.
Specific
details
on
the
operation
of
either
of
these
schemes
can
be
found
in
the
appropriate
NAA
or
GSY
relay
instruction
books
.
For
further
information
,
and
exact
model
numbers
of
these
relays
,
contact
the
nearest
General
Electric
District
Sales
Office
.
The
CEX
-
GSY
RATINGS
The
Type
CEX
57
relays
covered
by
these
instructions
are
rated
120
volts
,
five
amperes
,
for
either
50
or
60
hertz
.
They
have
three
basic
minimum
ohmic
reaches
that
are
set
by
a
double
set
of
taps
on
each
unit
.
The
taps
are
0.5
,
1.5
or
3.0
ohms
(
phase
-
to
-
nuetral
)
when
the
maximum
torque
angle
is
set
for
five
degrees
lead
(
current
leads
voltage
)
.
The
reach
of
the
unit
can
be
increased
from
minimum
ohms
(
100
percent
tap
)
to
ten
time
the
minimum
ohms
(
ten
percent
tap
)
by
means
of
taps
in
the
potential
circuit
.
The
relay
can
be
set
for
an
ohmic
reach
between
0.5
ohms
and
30
ohms
.
TABLE
I
TAP
RANGE
IN
RANGE
IN
AMPERES
ONE
SECOND
CURRENT
RATING
CONTINUOUS
CURRENT
RATING
USED
OHMS
0.5 0.5
-
5
8.2
-
40
100
amperes
100
amperes
5
amperes
1.5
1.5
-
15
5.0
-
40
5
amperes
3.0
3.0
-
30
3.5
-
40
100
amperes
5
amperes
CONTACTS
The
contacts
of
the
Type
CEX
57
relay
will
close
and
carry
30
amperes
DC
momentarily
.
However
,
the
circuit
breaker
trip
circuit
must
be
opened
by
an
auxiliary
switch
contact
or
other
suitable
means
,
since
the
relay
contacts
have
no
interrupting
rating
.
OPERATING
PRINCIPLES
The
units
in
the
Type
CEX
57
relay
are
four
-
pole
induction
cylinder
units
(
see
Figure
2
)
,
with
schematic
connections
as
shown
in
Figure
6
.
impedance
at
an
angle
.
The
two
front
coils
and
the
two
back
coils
are
energized
with
These
units
measure
4
Courtesy of NationalSwitchgear.com
GEK
-
49778
delta
currents
to
produce
polarizing
flux
.
The
same
delta
current
flows
through
the
operating
coil
to
produce
an
operating
flux
.
The
phase
-
to
-
phase
voltage
is
applied
to
the
restraint
coil
to
produce
a
restraint
flux
.
The
torque
produced
by
the
unit
results
from
the
interaction
of
the
fluxes
.
The
torque
,
therefore
,
is
as
shown
below
:
TR
Torque
=
I
x
I
x
Tg
-
I
x
E
x
x
cos
(
0
-
9
)
100
I
=
delta
current
(
I
/
\
-
Ig
)
TB
=
basic
reach
tap
E
=
phase
-
phase
voltage
(
E
/
\
B
)
TR
=
restraint
tap
in
percent
0
=
angle
between
(
1
^
-
Ig
)
and
E
^
B
0
=
maximum
torque
angle
of
the
relay
At
the
relay
balance
point
,
the
torque
is
zero
.
where
:
TR
0
=
I
x
I
x
TB
-
I
x
E
x
X
cos
(
0
-
0
)
100
TR
x
cos
(
0
-
0
)
=
I
X
I
x
TB
=
I
x
E
x
100
TR
x
cos
(
0
-
0
)
=
I
x
TB
=
E
x
-
cos
(
0
-
0
)
=
-
5
-
x
100
100
I
TR
The
phase
-
to
-
phase
voltage
(
E
)
divided
by
the
delta
current
is
equal
to
the
phase
-
to
-
neutral
ohms
(
Z
)
.
Therefore
:
Z
cos
(
0
-
0
)
=
^
x
100
TR
For
example
,
if
the
basic
reach
taps
(
TB
)
are
set
for
1.5
ohms
,
and
the
restraint
tap
(
TR
)
is
set
for
50
percent
,
then
the
relay
reach
(
Z
)
will
be
:
x
100
=
3
ohms
(
phase
-
to
-
neutral
)
1.5
Z
cos
(
0
-
9
)
=
50
The
equation
,
TB
Z
cos
(
0
-
9
)
=
x
100
TR
is
the
equation
for
a
straight
line
when
plotted
on
an
R
-
X
diagram
(
Figure
3
)
.
The
equation
also
gives
a
straight
line
if
Z
and
0
are
plotted
on
polar
paper
(
Figure
4
)
.
5
Courtesy of NationalSwitchgear.com
GEK
-
49778
By
selecting
values
for
TB
and
TR
,
the
characteristic
can
be
adjusted
to
be
at
any
distance
from
0.5
to
30
ohms
from
the
origin
.
This
30
ohm
limitation
is
based
on
TR
never
being
less
than
ten
percent
,
its
minimum
recommended
value
.
The
angle
of
maximum
torque
(
0
)
can
be
adjusted
to
be
any
angle
between
5
degrees
lead
and
35
degrees
lead
for
the
top
unit
.
The
bottom
is
identical
to
the
top
unit
,
except
its
polarity
is
reversed
so
that
the
maximum
torque
angle
is
adjustable
from
5
plus
180
,
or
185
degrees
,
to
35
plus
180
,
or
215
degrees
.
The
upper
potentiometer
on
each
unit
(
PI
for
the
upper
unit
and
P
2
for
the
lower
unit
)
is
used
to
set
the
angle
of
maximum
torque
.
With
the
potentiometer
set
for
zero
ohms
,
the
angle
of
maximum
torque
will
be
between
25
and
30
degrees
(
current
leads
voltage
)
.
If
a
jumper
is
added
to
connect
stud
13
to
stud
14
,
and
a
second
jumper
to
connect
stud
15
to
stud
16
,
then
the
angle
of
maximum
torque
can
be
adjusted
to
be
between
5
degrees
and
25
degrees
by
using
the
PI
potentiometer
for
the
upper
unit
,
and
the
P
2
potentiometer
for
the
lower
unit
.
If
jumpers
are
not
added
,
then
these
same
two
potentiometers
(
PI
for
the
upper
unit
and
P
2
for
the
lower
unit
)
can
be
used
to
adjust
the
angle
of
maximum
torque
to
be
between
30
and
35
degrees
.
Angle
of
maximum
torque
can
be
set
between
25
and
30
degrees
using
these
same
two
potentiometers
,
jumpers
should
be
added
or
not
will
vary
from
relay
to
relay
,
and
will
have
to
be
determined
by
test
of
the
relay
actually
being
adjusted
.
Whether
the
CHARACTERISTICS
ANGLE
-
IMPEDANCE
UNIT
The
angle
-
impedance
unit
characteristic
is
a
straight
line
when
plotted
on
an
R
-
X
diagram
.
The
shortest
distance
from
the
characteristic
to
the
origin
is
the
minimum
relay
reach
.
The
minimum
relay
reach
is
determined
by
two
sets
of
taps
.
The
two
tap
plugs
in
the
current
circuits
set
the
basic
minimum
reach
(
TB
)
.
The
tap
plugs
in
the
restraint
circuit
increase
the
basic
reach
as
the
restraint
taps
(
TR
)
are
reduced
from
100
percent
.
The
reach
at
angle
of
maximum
torque
is
equal
,
therefore
,
to
:
TB
x
100
ZM
=
-
TR
ZM
=
minimum
reach
TB
=
minimum
basic
reach
TR
=
restraint
tap
where
:
UPPER
UNIT
The
angle
of
maximum
torque
is
the
angle
that
the
reach
,
Z
^
,
described
above
,
leads
the
"
R
"
axis
(
Figure
4
)
.
This
angle
is
adjustable
from
5
to
35
degrees
lead
.
The
reach
of
the
angle
-
impedance
unit
at
any
angle
is
given
by
the
following
equation
:
tB
x
100
TR
x
cos
(
0
-
0
)
cos
(
0
-
0
)
ZM
Z
=
6
Courtesy of NationalSwitchgear.com
GEK
-
49778
0
=
angle
I
/
\
g
leads
V
/\
g
0
=
angle
of
maximum
torque
See
Table
II
for
values
of
Tg
for
the
various
angles
of
maximum
torque
.
where
:
LOWER
UNIT
This
unit
is
identical
to
the
upper
unit
except
it
is
polarized
to
have
maximum
torque
180
degrees
from
the
upper
unit
.
Therefore
,
the
equation
is
:
ZM
Z
=
cos
(
0
-
9
+
180
)
The
value
Tg
is
given
in
Table
II
for
various
angles
of
maximum
torque
.
The
value
of
TB
is
equal
to
the
tap
value
when
the
maximum
torque
angle
is
set
for
five
degrees
.
If
only
the
upper
potentiometer
(
PI
for
the
upper
unit
,
or
P
2
for
the
lower
unit
)
is
adjusted
,
the
value
of
TR
will
be
as
shown
in
Table
II
.
The
value
of
Tg
can
be
adjusted
by
using
the
lower
potentiometer
(
P
3
for
the
upper
unit
,
or
P
4
for
the
lower
unit
)
;
however
,
it
may
not
be
possible
to
make
Tg
equal
to
the
tap
value
at
all
angles
of
maximum
torque
settings
.
TABLE
II
BASIC
REACH
OHMS
(
TB
)
ANGLE
OF
MAXIMUM
TORQUE
STUDS
13
-
14
STUDS
15
-
16
0.5
OHM
TAP
1.5
OHM
TAP
3.0
OHM
TAP
50
Jumper
1.43
-
1.58
2.85
-
3.15
0.48
-
0.53
10
°
Jumper
0.41
-
0.47
1.22
-
1.40
2.43
-
2.79
15
°
Jumper
1.14
-
1.26
0.38
-
0.42
2.28
-
2.52
20
°
Jumper
0.34
-
0.38
1.02
-
1.13
2.04
-
2.25
25
°
Jumper
0.94
-
1.07
1.89
-
2.13
0.32
-
0.36
30
°
Open
0.31
-
0.37
0.92
-
1.11
1.83
-
2.22
350
Open
0.35
-
0.40
1.05
-
1.20
2.10
-
2.40
TAPPED
AUTOTRANSFORMER
The
reach
in
ohms
of
the
angle
-
impedance
may
be
adjusted
by
two
taps
on
the
autotransformer
.
The
tap
block
and
the
tap
plugs
are
located
on
the
right
side
of
the
relay
.
The
two
tap
leads
marked
#
1
control
the
upper
unit
,
and
the
two
tap
leads
marked
#
2
control
the
lower
unit
.
The
upper
#
1
and
#
2
tap
leads
should
be
connected
to
a
tap
in
the
upper
half
of
the
block
(
zero
to
ten
percent
)
.
The
lower
#
1
and
#
2
tap
leads
should
be
connected
to
a
tap
in
the
lower
half
of
the
block
(
10
to
90
percent
)
.
The
restraint
tap
setting
,
TR
,
is
the
sum
of
the
two
tap
values
into
which
the
#
1
or
#
2
leads
7
Courtesy of NationalSwitchgear.com
GEK
-
49778
are
connected
.
For
example
,
if
the
upper
#
1
lead
is
put
in
the
5
tap
,
and
the
lower
#
1
lead
is
put
in
the
60
tap
,
then
the
#
1
tap
setting
,
TR
is
5
plus
60
,
or
65
.
TR
should
not
be
set
for
less
than
ten
percent
.
BURDENS
CURRENT
CIRCUIT
The
current
burden
imposed
by
each
current
circuit
at
five
amperes
is
listed
in
Table
III
.
TABLE
III
BASIC
OHM
TAP
AMPS
HERTZ
R
X
PF
WATTS
VA
5
60
0.5
0.10
0.09
0.72
2.41
3.35
5
60
1.5
0.12
0.10
0.77
3.06
3.95
5
60
3.0
0.16
4.11
5.13
0.12
0.80
5
50
0.5
0.09
2.14
0.08
0.74
2.89
5
50
1.5
0.11
0.08
0.80
2.75
3.45
5
50
3.0
0.14
0.10
0.81
3.59
4.41
POTENTIAL
CIRCUIT
The
maximum
potential
burden
imposed
by
the
two
units
in
the
relay
is
shown
in
Table
IV
.
*
TABLE
IV
VOLTS
HERTZ
R
X
PF
WATTS
VA
120
60
386
536
0.59
12.74
21.8
120
50
497
-
523
0.69
13.74
20.0
The
potential
burden
is
maximum
when
the
restraint
taps
,
TR
,
are
set
for
100
and
the
angle
of
maximum
torque
is
near
25
degrees
lead
.
At
any
tap
setting
,
TR
,
the
potential
burden
for
each
unit
will
be
as
follows
:
Watts
+
jVars
=
(
A
+
jB
)
x
*
Indicates
Revision
8
Courtesy of NationalSwitchgear.com
GEK
-
49778
where
:
A
=
watts
,
when
TR
=
100
B
=
vars
,
when
TR
=
100
See
Table
V
for
values
of
A
and
B
.
TABLE
V
MAXIMUM
TORQUE
ANGLE
(
LEAD
)
JUMPERS
13
-
14
AND
15
-
16
WATTS
WATTS
(
A
)(
B
)
VOLTS
HERTZ
120
5
°
60
ON
-
2.70
-
3.50
-
6.50
5.20
120
10
°
60
ON
5.70
120
60
25
°
ON
6.30
120
60
300
OFF
8.20
6.20
120
60
350
OFF
6.40
7.55
120
50
50
ON
5.15
-
2.30
-
3.33
-
7.20
10
O
120
50
5.90
ON
120
50
25
°
ON
6.95
120
50
30
°
OFF
6.60
4.83
120
50
35
°
OFF
6.30
4.00
The
total
potential
burden
will
be
the
sum
of
the
burden
from
each
unit
.
Normally
both
units
will
be
set
for
the
same
reach
and
maximum
torque
angle
,
so
it
will
only
be
necessary
to
calculate
the
burden
for
one
unit
.
This
value
will
be
the
burden
on
each
of
the
two
potential
devices
.
The
burden
measured
on
any
unit
may
vary
plus
or
minus
ten
percent
from
the
instruction
book
values
,
due
to
allowable
tolerances
on
capacitors
and
coils
.
CALCULATION
OF
SETTINGS
The
exact
settings
to
be
made
on
the
ohm
units
in
Type
CEX
57
relays
will
depend
on
the
particular
application
.
When
used
in
blinder
applications
,
the
primary
objective
is
to
restrict
the
tripping
area
of
the
tripping
units
to
avoid
operation
on
load
impedance
.
Thus
,
the
reach
setting
should
be
made
so
that
operation
is
prevented
during
maximum
load
flow
or
stable
power
swing
conditions
.
The
angle
setting
should
be
made
so
that
the
ohm
units
will
plot
parallel
to
the
protected
line
.
When
out
-
of
-
step
tripping
during
power
swings
is
required
,
tripping
during
stable
swings
can
be
prevented
,
and
the
breaker
duty
minimized
,
by
permitting
tripping
only
after
a
favorable
angle
is
reached
.
Thus
,
the
reach
settings
to
be
made
will
be
Indicates
Revision
9
Courtesy of NationalSwitchgear.com
GEK
-
49778
Specific
details
for
dependent
on
particular
system
conditions
and
configuration
.
determining
the
settings
for
transmission
line
or
generator
applications
can
be
found
in
the
appropriate
instruction
book
for
Type
NAA
or
GSY
relays
,
ac
mentioned
earlier
.
Once
the
desired
reach
and
angle
has
been
determined
,
it
is
only
necessary
to
calculate
and
set
the
restraint
taps
to
meet
the
desired
reach
.
The
restraint
tap
setting
can
be
calculated
as
follows
:
T
=
(
Ml
(
TB
)
ZM
T
=
restraint
tap
setting
in
percent
Tg
=
basic
reach
tap
ZM
=
desired
reach
in
secondary
ohms
at
the
selected
torque
angle
For
example
,
refer
to
Figure
3
and
4
and
assume
ZM
should
be
set
to
reach
five
ohms
at
the
torque
angle
shown
.
Base
reach
taps
of
0.5
,
1.5
and
3.0
ohms
are
available
.
Always
select
the
highest
base
reach
tap
that
will
provide
the
desired
reach
setting
.
For
this
example
,
use
the
3.0
ohm
tap
.
Therefore
,
where
:
T
=
(
100
)
(
3.0
)
=
60
percent
5
Set
the
restraint
taps
for
both
ohm
units
to
60
percent
.
CONSTRUCTION
The
Type
CEX
57
relays
are
assembled
in
a
medium
size
,
double
end
(
M
2
)
drawout
case
,
having
studs
at
both
ends
in
the
rear
for
external
connections
.
The
electrical
connections
between
the
relay
units
and
the
case
studs
are
made
through
stationary
molded
inner
and
outer
blocks
,
between
which
nests
a
removable
connection
plug
,
which
completes
the
circuit
.
The
outer
blocks
attached
to
the
case
have
studs
for
the
external
connections
,
and
the
inner
blocks
have
terminals
for
the
internal
connections
.
Every
circuit
in
the
drawout
case
has
an
auxiliary
brush
,
as
shown
in
Figure
8
,
to
provide
adequate
overlap
when
the
connecting
plug
is
withdrawn
or
inserted
.
Some
circuits
are
equipped
with
shorting
bars
(
see
internal
connections
)
and
on
those
circuits
,
it
is
especially
important
that
the
auxiliary
brush
make
contact
as
indicated
in
Figure
8
with
adequate
pressure
to
prevent
the
opening
of
important
interlocking
circuits
.
The
relay
mechanism
is
mounted
in
a
steel
framework
called
the
cradle
and
is
a
complete
unit
with
all
leads
terminated
at
the
inner
block
.
This
cradle
is
held
firmly
in
the
case
with
a
latch
at
both
top
and
bottom
and
by
a
guide
pin
at
the
back
of
the
case
.
The
connecting
plug
,
besides
making
the
electrical
connections
between
the
respective
blocks
of
the
cradle
and
case
,
also
locks
the
latch
in
place
.
The
cover
,
which
is
drawn
to
the
case
by
thumbscrews
,
holds
the
connecting
plugs
in
place
.
The
target
reset
mechanism
is
a
part
of
the
cover
assembly
.
10
Courtesy of NationalSwitchgear.com