manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. GE
  6. •
  7. Relay
  8. •
  9. GE CEX57D User manual

GE CEX57D User manual

GEK
-
49778
D
INSTRUCTIONS
ANGLE
-
IMPEDANCE
RELAY
TYPES
:
CEX
57
D
CEX
57
E
CEX
57
F
GE
Power
Management
205
Great
Valley
Parkway
Malvern
,
PA
19355
Telephone
:
(
610
)
251
-
7000
www
.
ge
.
com
/
edc
/
pm
Courtesy of NationalSwitchgear.com
GEK
-
49778
CONTENTS
PAGE
DESCRIPTION
APPLICATION
CEX
57
D
AND
CEX
57
F
CEX
57
E
RATINGS
CONTACTS
OPERATING
PRINCIPLES
CHARACTERISTICS
ANGLE
-
IMPEDANCE
UNIT
UPPER
UNIT
LOWER
UNIT
TAPPED
AUTOTRANSFORMER
BURDENS
CURRENT
CIRCUIT
POTENTIAL
CIRCUIT
CALCULATION
OF
SETTINGS
rflNCTRlirTTON
RECEIVING
,
HANDLING
AND
STORAGE
ACCEPTANCE
TESTS
VISUAL
INSPECTION
MECHANICAL
INSPECTION
ELECTRICAL
TESTS
ELECTRICAL
TESTS
-
AUXILIARY
UNIT
(
CEX
57
F
ONLY
)
INSTALLATION
PROCEDURE
LOCATION
MOUNTING
CONNECTIONS
VISUAL
INSPECTION
MECHANICAL
INSPECTION
INSPECTION
ANGLE
-
IMPEDANCE
TESTS
PERIODIC
CHECKS
AND
ROUTINE
MAINTENANCE
CONTACT
CLEANING
SERVICING
CONTROL
SPRING
ADjuSTMENT
*
.
*
.
!
!
!
.
.
ANGLE
OF
MAXIMUM
TORQUE
ADJUSTMENT
BASIC
REACH
OHMS
CORE
ADJUSTMENT
RENEWAL
PARTS
3
3
3
4
4
4
4
6
6
6
7
7
8
8
8
9
10
11
12
12
12
12
OHM
UNIT
13
14
14
14
14
14
14
14
14
15
15
16
16
16
17
18
18
(
COVER
PHOTO
8042958
)
2
Courtesy of NationalSwitchgear.com
GEK
-
49778
ANGLE
-
IMPEDANCE
RELAY
TYPES
:
CEX
57
D
CEX
57
E
CEX
57
F
DESCRIPTION
Type
CEX
57
relays
are
high
speed
induction
cup
-
type
devices
with
ohm
unit
characteristics
that
can
be
set
parallel
to
the
impedance
of
a
transmission
line
.
The
relays
are
designed
for
use
with
other
protective
devices
in
blinder
applications
to
restrict
the
tripping
area
of
the
tripping
units
used
in
a
protective
relay
scheme
.
Or
,
they
may
be
used
in
applications
where
tripping
is
required
during
an
out
-
of
-
step
condition
.
instruction
book
.
These
applications
are
discussed
in
the
APPLICATION
section
of
this
Type
CEX
57
relays
each
contain
two
cup
-
type
units
,
and
they
are
mounted
in
an
M
2
size
case
.
The
CEX
57
F
relay
also
contains
an
auxiliary
telephone
-
type
unit
.
Internal
connections
for
the
relays
are
shown
in
Figures
9
,
10
and
11
;
typical
external
connections
are
shown
in
Figure
5
.
Outline
and
panel
drilling
dimensions
are
shown
in
Figure
14
.
APPLICATION
The
CEX
57
relays
were
designed
specifically
for
use
in
blinder
applications
,
or
in
applications
to
initiate
tripping
during
an
out
-
of
-
step
condition
.
Three
models
of
the
relay
are
available
:
CEX
57
D
,
CEX
57
E
and
CEX
57
F
.
Typical
applications
for
each
of
these
relays
are
as
follows
:
CEX
57
D
AND
CEX
57
F
The
CEX
57
D
and
CEX
57
F
relays
are
used
in
blinder
applications
to
restrict
the
area
of
the
tripping
functions
used
in
a
transmission
line
protective
relaying
scheme
(
see
Figure
4
)
.
Either
three
CEX
57
D
or
three
CEX
57
F
relays
are
required
.
Basically
,
tripping
will
be
permitted
only
when
the
fault
impedance
plots
within
the
reach
of
the
mho
tripping
function
AND
both
of
the
ohm
units
.
Since
the
right
hand
ohm
unit
will
operate
only
for
faults
to
the
left
of
it
,
both
units
can
operate
simultaneously
only
for
faults
that
plot
between
them
.
The
tripping
function
(
mho
)
will
provide
correct
directional
action
,
and
limit
the
reach
in
the
forward
direction
.
The
contacts
of
the
CEX
57
D
ohm
units
are
brought
out
separately
,
and
are
externally
connected
in
series
with
the
contacts
of
the
corresponding
mho
tripping
function
to
provide
supervision
(
see
Figure
5
C
)
.
The
contacts
of
the
CEX
57
F
relay
are
These
instructions
do
not
purport
to
cover
all
details
or
variations
in
equipment
nor
to
provide
for
every
possible
contingency
to
be
met
in
connection
with
installation
,
operation
or
maintenance
.
Should
further
information
be
desired
or
should
particular
problems
arise
which
are
not
covered
sufficiently
for
the
matter
should
be
referred
to
the
General
Electric
Company
.
the
purchaser
'
s
purposes
.
To
the
extent
reguired
the
products
described
herein
meet
applicable
ANSI
,
but
no
such
assurance
is
given
with
respect
to
local
codes
and
ordinances
because
they
vary
greatly
.
IEEE
and
NEMA
standards
;
3
Courtesy of NationalSwitchgear.com
GEK
-
49778
internally
connected
in
series
,
and
are
used
to
operate
the
internal
mounted
auxiliary
telephone
relay
.
The
contacts
of
this
auxiliary
relay
are
then
used
to
supervise
the
corresponding
mho
tripping
function
(
see
Figure
5
B
)
.
CEX
57
E
The
Type
CEX
57
E
relay
was
designed
specifically
for
use
with
Type
GSY
or
NAA
relays
,
which
provide
the
additional
functions
required
to
implement
an
out
-
of
-
step
tripping
scheme
.
Only
one
CEX
57
E
relay
is
required
in
these
applications
.
The
CEX
-
NAA
combination
is
primarily
for
application
to
transmission
lines
,
combination
is
primarily
for
application
to
generators
.
Specific
details
on
the
operation
of
either
of
these
schemes
can
be
found
in
the
appropriate
NAA
or
GSY
relay
instruction
books
.
For
further
information
,
and
exact
model
numbers
of
these
relays
,
contact
the
nearest
General
Electric
District
Sales
Office
.
The
CEX
-
GSY
RATINGS
The
Type
CEX
57
relays
covered
by
these
instructions
are
rated
120
volts
,
five
amperes
,
for
either
50
or
60
hertz
.
They
have
three
basic
minimum
ohmic
reaches
that
are
set
by
a
double
set
of
taps
on
each
unit
.
The
taps
are
0.5
,
1.5
or
3.0
ohms
(
phase
-
to
-
nuetral
)
when
the
maximum
torque
angle
is
set
for
five
degrees
lead
(
current
leads
voltage
)
.
The
reach
of
the
unit
can
be
increased
from
minimum
ohms
(
100
percent
tap
)
to
ten
time
the
minimum
ohms
(
ten
percent
tap
)
by
means
of
taps
in
the
potential
circuit
.
The
relay
can
be
set
for
an
ohmic
reach
between
0.5
ohms
and
30
ohms
.
TABLE
I
TAP
RANGE
IN
RANGE
IN
AMPERES
ONE
SECOND
CURRENT
RATING
CONTINUOUS
CURRENT
RATING
USED
OHMS
0.5 0.5
-
5
8.2
-
40
100
amperes
100
amperes
5
amperes
1.5
1.5
-
15
5.0
-
40
5
amperes
3.0
3.0
-
30
3.5
-
40
100
amperes
5
amperes
CONTACTS
The
contacts
of
the
Type
CEX
57
relay
will
close
and
carry
30
amperes
DC
momentarily
.
However
,
the
circuit
breaker
trip
circuit
must
be
opened
by
an
auxiliary
switch
contact
or
other
suitable
means
,
since
the
relay
contacts
have
no
interrupting
rating
.
OPERATING
PRINCIPLES
The
units
in
the
Type
CEX
57
relay
are
four
-
pole
induction
cylinder
units
(
see
Figure
2
)
,
with
schematic
connections
as
shown
in
Figure
6
.
impedance
at
an
angle
.
The
two
front
coils
and
the
two
back
coils
are
energized
with
These
units
measure
4
Courtesy of NationalSwitchgear.com
GEK
-
49778
delta
currents
to
produce
polarizing
flux
.
The
same
delta
current
flows
through
the
operating
coil
to
produce
an
operating
flux
.
The
phase
-
to
-
phase
voltage
is
applied
to
the
restraint
coil
to
produce
a
restraint
flux
.
The
torque
produced
by
the
unit
results
from
the
interaction
of
the
fluxes
.
The
torque
,
therefore
,
is
as
shown
below
:
TR
Torque
=
I
x
I
x
Tg
-
I
x
E
x
x
cos
(
0
-
9
)
100
I
=
delta
current
(
I
/
\
-
Ig
)
TB
=
basic
reach
tap
E
=
phase
-
phase
voltage
(
E
/
\
B
)
TR
=
restraint
tap
in
percent
0
=
angle
between
(
1
^
-
Ig
)
and
E
^
B
0
=
maximum
torque
angle
of
the
relay
At
the
relay
balance
point
,
the
torque
is
zero
.
where
:
TR
0
=
I
x
I
x
TB
-
I
x
E
x
X
cos
(
0
-
0
)
100
TR
x
cos
(
0
-
0
)
=
I
X
I
x
TB
=
I
x
E
x
100
TR
x
cos
(
0
-
0
)
=
I
x
TB
=
E
x
-
cos
(
0
-
0
)
=
-
5
-
x
100
100
I
TR
The
phase
-
to
-
phase
voltage
(
E
)
divided
by
the
delta
current
is
equal
to
the
phase
-
to
-
neutral
ohms
(
Z
)
.
Therefore
:
Z
cos
(
0
-
0
)
=
^
x
100
TR
For
example
,
if
the
basic
reach
taps
(
TB
)
are
set
for
1.5
ohms
,
and
the
restraint
tap
(
TR
)
is
set
for
50
percent
,
then
the
relay
reach
(
Z
)
will
be
:
x
100
=
3
ohms
(
phase
-
to
-
neutral
)
1.5
Z
cos
(
0
-
9
)
=
50
The
equation
,
TB
Z
cos
(
0
-
9
)
=
x
100
TR
is
the
equation
for
a
straight
line
when
plotted
on
an
R
-
X
diagram
(
Figure
3
)
.
The
equation
also
gives
a
straight
line
if
Z
and
0
are
plotted
on
polar
paper
(
Figure
4
)
.
5
Courtesy of NationalSwitchgear.com
GEK
-
49778
By
selecting
values
for
TB
and
TR
,
the
characteristic
can
be
adjusted
to
be
at
any
distance
from
0.5
to
30
ohms
from
the
origin
.
This
30
ohm
limitation
is
based
on
TR
never
being
less
than
ten
percent
,
its
minimum
recommended
value
.
The
angle
of
maximum
torque
(
0
)
can
be
adjusted
to
be
any
angle
between
5
degrees
lead
and
35
degrees
lead
for
the
top
unit
.
The
bottom
is
identical
to
the
top
unit
,
except
its
polarity
is
reversed
so
that
the
maximum
torque
angle
is
adjustable
from
5
plus
180
,
or
185
degrees
,
to
35
plus
180
,
or
215
degrees
.
The
upper
potentiometer
on
each
unit
(
PI
for
the
upper
unit
and
P
2
for
the
lower
unit
)
is
used
to
set
the
angle
of
maximum
torque
.
With
the
potentiometer
set
for
zero
ohms
,
the
angle
of
maximum
torque
will
be
between
25
and
30
degrees
(
current
leads
voltage
)
.
If
a
jumper
is
added
to
connect
stud
13
to
stud
14
,
and
a
second
jumper
to
connect
stud
15
to
stud
16
,
then
the
angle
of
maximum
torque
can
be
adjusted
to
be
between
5
degrees
and
25
degrees
by
using
the
PI
potentiometer
for
the
upper
unit
,
and
the
P
2
potentiometer
for
the
lower
unit
.
If
jumpers
are
not
added
,
then
these
same
two
potentiometers
(
PI
for
the
upper
unit
and
P
2
for
the
lower
unit
)
can
be
used
to
adjust
the
angle
of
maximum
torque
to
be
between
30
and
35
degrees
.
Angle
of
maximum
torque
can
be
set
between
25
and
30
degrees
using
these
same
two
potentiometers
,
jumpers
should
be
added
or
not
will
vary
from
relay
to
relay
,
and
will
have
to
be
determined
by
test
of
the
relay
actually
being
adjusted
.
Whether
the
CHARACTERISTICS
ANGLE
-
IMPEDANCE
UNIT
The
angle
-
impedance
unit
characteristic
is
a
straight
line
when
plotted
on
an
R
-
X
diagram
.
The
shortest
distance
from
the
characteristic
to
the
origin
is
the
minimum
relay
reach
.
The
minimum
relay
reach
is
determined
by
two
sets
of
taps
.
The
two
tap
plugs
in
the
current
circuits
set
the
basic
minimum
reach
(
TB
)
.
The
tap
plugs
in
the
restraint
circuit
increase
the
basic
reach
as
the
restraint
taps
(
TR
)
are
reduced
from
100
percent
.
The
reach
at
angle
of
maximum
torque
is
equal
,
therefore
,
to
:
TB
x
100
ZM
=
-
TR
ZM
=
minimum
reach
TB
=
minimum
basic
reach
TR
=
restraint
tap
where
:
UPPER
UNIT
The
angle
of
maximum
torque
is
the
angle
that
the
reach
,
Z
^
,
described
above
,
leads
the
"
R
"
axis
(
Figure
4
)
.
This
angle
is
adjustable
from
5
to
35
degrees
lead
.
The
reach
of
the
angle
-
impedance
unit
at
any
angle
is
given
by
the
following
equation
:
tB
x
100
TR
x
cos
(
0
-
0
)
cos
(
0
-
0
)
ZM
Z
=
6
Courtesy of NationalSwitchgear.com
GEK
-
49778
0
=
angle
I
/
\
g
leads
V
/\
g
0
=
angle
of
maximum
torque
See
Table
II
for
values
of
Tg
for
the
various
angles
of
maximum
torque
.
where
:
LOWER
UNIT
This
unit
is
identical
to
the
upper
unit
except
it
is
polarized
to
have
maximum
torque
180
degrees
from
the
upper
unit
.
Therefore
,
the
equation
is
:
ZM
Z
=
cos
(
0
-
9
+
180
)
The
value
Tg
is
given
in
Table
II
for
various
angles
of
maximum
torque
.
The
value
of
TB
is
equal
to
the
tap
value
when
the
maximum
torque
angle
is
set
for
five
degrees
.
If
only
the
upper
potentiometer
(
PI
for
the
upper
unit
,
or
P
2
for
the
lower
unit
)
is
adjusted
,
the
value
of
TR
will
be
as
shown
in
Table
II
.
The
value
of
Tg
can
be
adjusted
by
using
the
lower
potentiometer
(
P
3
for
the
upper
unit
,
or
P
4
for
the
lower
unit
)
;
however
,
it
may
not
be
possible
to
make
Tg
equal
to
the
tap
value
at
all
angles
of
maximum
torque
settings
.
TABLE
II
BASIC
REACH
OHMS
(
TB
)
ANGLE
OF
MAXIMUM
TORQUE
STUDS
13
-
14
STUDS
15
-
16
0.5
OHM
TAP
1.5
OHM
TAP
3.0
OHM
TAP
50
Jumper
1.43
-
1.58
2.85
-
3.15
0.48
-
0.53
10
°
Jumper
0.41
-
0.47
1.22
-
1.40
2.43
-
2.79
15
°
Jumper
1.14
-
1.26
0.38
-
0.42
2.28
-
2.52
20
°
Jumper
0.34
-
0.38
1.02
-
1.13
2.04
-
2.25
25
°
Jumper
0.94
-
1.07
1.89
-
2.13
0.32
-
0.36
30
°
Open
0.31
-
0.37
0.92
-
1.11
1.83
-
2.22
350
Open
0.35
-
0.40
1.05
-
1.20
2.10
-
2.40
TAPPED
AUTOTRANSFORMER
The
reach
in
ohms
of
the
angle
-
impedance
may
be
adjusted
by
two
taps
on
the
autotransformer
.
The
tap
block
and
the
tap
plugs
are
located
on
the
right
side
of
the
relay
.
The
two
tap
leads
marked
#
1
control
the
upper
unit
,
and
the
two
tap
leads
marked
#
2
control
the
lower
unit
.
The
upper
#
1
and
#
2
tap
leads
should
be
connected
to
a
tap
in
the
upper
half
of
the
block
(
zero
to
ten
percent
)
.
The
lower
#
1
and
#
2
tap
leads
should
be
connected
to
a
tap
in
the
lower
half
of
the
block
(
10
to
90
percent
)
.
The
restraint
tap
setting
,
TR
,
is
the
sum
of
the
two
tap
values
into
which
the
#
1
or
#
2
leads
7
Courtesy of NationalSwitchgear.com
GEK
-
49778
are
connected
.
For
example
,
if
the
upper
#
1
lead
is
put
in
the
5
tap
,
and
the
lower
#
1
lead
is
put
in
the
60
tap
,
then
the
#
1
tap
setting
,
TR
is
5
plus
60
,
or
65
.
TR
should
not
be
set
for
less
than
ten
percent
.
BURDENS
CURRENT
CIRCUIT
The
current
burden
imposed
by
each
current
circuit
at
five
amperes
is
listed
in
Table
III
.
TABLE
III
BASIC
OHM
TAP
AMPS
HERTZ
R
X
PF
WATTS
VA
5
60
0.5
0.10
0.09
0.72
2.41
3.35
5
60
1.5
0.12
0.10
0.77
3.06
3.95
5
60
3.0
0.16
4.11
5.13
0.12
0.80
5
50
0.5
0.09
2.14
0.08
0.74
2.89
5
50
1.5
0.11
0.08
0.80
2.75
3.45
5
50
3.0
0.14
0.10
0.81
3.59
4.41
POTENTIAL
CIRCUIT
The
maximum
potential
burden
imposed
by
the
two
units
in
the
relay
is
shown
in
Table
IV
.
*
TABLE
IV
VOLTS
HERTZ
R
X
PF
WATTS
VA
120
60
386
536
0.59
12.74
21.8
120
50
497
-
523
0.69
13.74
20.0
The
potential
burden
is
maximum
when
the
restraint
taps
,
TR
,
are
set
for
100
and
the
angle
of
maximum
torque
is
near
25
degrees
lead
.
At
any
tap
setting
,
TR
,
the
potential
burden
for
each
unit
will
be
as
follows
:
Watts
+
jVars
=
(
A
+
jB
)
x
*
Indicates
Revision
8
Courtesy of NationalSwitchgear.com
GEK
-
49778
where
:
A
=
watts
,
when
TR
=
100
B
=
vars
,
when
TR
=
100
See
Table
V
for
values
of
A
and
B
.
TABLE
V
MAXIMUM
TORQUE
ANGLE
(
LEAD
)
JUMPERS
13
-
14
AND
15
-
16
WATTS
WATTS
(
A
)(
B
)
VOLTS
HERTZ
120
5
°
60
ON
-
2.70
-
3.50
-
6.50
5.20
120
10
°
60
ON
5.70
120
60
25
°
ON
6.30
120
60
300
OFF
8.20
6.20
120
60
350
OFF
6.40
7.55
120
50
50
ON
5.15
-
2.30
-
3.33
-
7.20
10
O
120
50
5.90
ON
120
50
25
°
ON
6.95
120
50
30
°
OFF
6.60
4.83
120
50
35
°
OFF
6.30
4.00
The
total
potential
burden
will
be
the
sum
of
the
burden
from
each
unit
.
Normally
both
units
will
be
set
for
the
same
reach
and
maximum
torque
angle
,
so
it
will
only
be
necessary
to
calculate
the
burden
for
one
unit
.
This
value
will
be
the
burden
on
each
of
the
two
potential
devices
.
The
burden
measured
on
any
unit
may
vary
plus
or
minus
ten
percent
from
the
instruction
book
values
,
due
to
allowable
tolerances
on
capacitors
and
coils
.
CALCULATION
OF
SETTINGS
The
exact
settings
to
be
made
on
the
ohm
units
in
Type
CEX
57
relays
will
depend
on
the
particular
application
.
When
used
in
blinder
applications
,
the
primary
objective
is
to
restrict
the
tripping
area
of
the
tripping
units
to
avoid
operation
on
load
impedance
.
Thus
,
the
reach
setting
should
be
made
so
that
operation
is
prevented
during
maximum
load
flow
or
stable
power
swing
conditions
.
The
angle
setting
should
be
made
so
that
the
ohm
units
will
plot
parallel
to
the
protected
line
.
When
out
-
of
-
step
tripping
during
power
swings
is
required
,
tripping
during
stable
swings
can
be
prevented
,
and
the
breaker
duty
minimized
,
by
permitting
tripping
only
after
a
favorable
angle
is
reached
.
Thus
,
the
reach
settings
to
be
made
will
be
Indicates
Revision
9
Courtesy of NationalSwitchgear.com
GEK
-
49778
Specific
details
for
dependent
on
particular
system
conditions
and
configuration
.
determining
the
settings
for
transmission
line
or
generator
applications
can
be
found
in
the
appropriate
instruction
book
for
Type
NAA
or
GSY
relays
,
ac
mentioned
earlier
.
Once
the
desired
reach
and
angle
has
been
determined
,
it
is
only
necessary
to
calculate
and
set
the
restraint
taps
to
meet
the
desired
reach
.
The
restraint
tap
setting
can
be
calculated
as
follows
:
T
=
(
Ml
(
TB
)
ZM
T
=
restraint
tap
setting
in
percent
Tg
=
basic
reach
tap
ZM
=
desired
reach
in
secondary
ohms
at
the
selected
torque
angle
For
example
,
refer
to
Figure
3
and
4
and
assume
ZM
should
be
set
to
reach
five
ohms
at
the
torque
angle
shown
.
Base
reach
taps
of
0.5
,
1.5
and
3.0
ohms
are
available
.
Always
select
the
highest
base
reach
tap
that
will
provide
the
desired
reach
setting
.
For
this
example
,
use
the
3.0
ohm
tap
.
Therefore
,
where
:
T
=
(
100
)
(
3.0
)
=
60
percent
5
Set
the
restraint
taps
for
both
ohm
units
to
60
percent
.
CONSTRUCTION
The
Type
CEX
57
relays
are
assembled
in
a
medium
size
,
double
end
(
M
2
)
drawout
case
,
having
studs
at
both
ends
in
the
rear
for
external
connections
.
The
electrical
connections
between
the
relay
units
and
the
case
studs
are
made
through
stationary
molded
inner
and
outer
blocks
,
between
which
nests
a
removable
connection
plug
,
which
completes
the
circuit
.
The
outer
blocks
attached
to
the
case
have
studs
for
the
external
connections
,
and
the
inner
blocks
have
terminals
for
the
internal
connections
.
Every
circuit
in
the
drawout
case
has
an
auxiliary
brush
,
as
shown
in
Figure
8
,
to
provide
adequate
overlap
when
the
connecting
plug
is
withdrawn
or
inserted
.
Some
circuits
are
equipped
with
shorting
bars
(
see
internal
connections
)
and
on
those
circuits
,
it
is
especially
important
that
the
auxiliary
brush
make
contact
as
indicated
in
Figure
8
with
adequate
pressure
to
prevent
the
opening
of
important
interlocking
circuits
.
The
relay
mechanism
is
mounted
in
a
steel
framework
called
the
cradle
and
is
a
complete
unit
with
all
leads
terminated
at
the
inner
block
.
This
cradle
is
held
firmly
in
the
case
with
a
latch
at
both
top
and
bottom
and
by
a
guide
pin
at
the
back
of
the
case
.
The
connecting
plug
,
besides
making
the
electrical
connections
between
the
respective
blocks
of
the
cradle
and
case
,
also
locks
the
latch
in
place
.
The
cover
,
which
is
drawn
to
the
case
by
thumbscrews
,
holds
the
connecting
plugs
in
place
.
The
target
reset
mechanism
is
a
part
of
the
cover
assembly
.
10
Courtesy of NationalSwitchgear.com
GEK
-
49778
The
relay
case
is
suitable
for
either
a
semi
-
flush
or
surface
mounting
on
all
panels
up
to
two
inches
thick
and
appropriate
hardware
is
available
.
However
,
panel
thickness
must
be
indicated
on
the
relay
order
to
insure
that
proper
hardware
will
be
included
.
A
separate
testing
plug
can
be
inserted
in
place
of
the
connecting
plug
to
test
the
relay
in
place
on
the
panel
either
from
its
own
source
of
current
and
voltage
,
or
from
other
sources
.
Or
,
the
relay
can
be
drawn
out
and
replaced
by
another
relay
which
has
already
been
tested
in
the
laboratory
.
Figure
1
shows
the
relay
removed
from
its
case
with
all
major
components
identified
.
Symbols
used
to
identify
circuit
components
are
the
same
as
those
which
appear
on
the
internal
connection
diagrams
in
Figures
9
,
10
and
11
.
The
relays
include
two
angle
-
impedance
units
mounted
on
the
front
of
the
cradle
and
a
tapped
autotransformer
.
The
Type
CEX
57
F
also
has
an
auxiliary
unit
(
telephone
-
type
)
mounted
at
the
top
.
The
angle
-
impedance
unit
assembly
includes
the
four
pole
unit
,
two
potentiometers
,
one
capacitor
and
two
tap
blocks
for
setting
basic
reach
.
The
upper
potentiometer
(
PI
for
the
top
unit
or
P
2
for
the
lower
unit
)
is
used
to
set
the
angle
of
maximum
torque
.
The
lower
potentiometer
(
P
3
for
the
top
unit
or
P
4
for
the
lower
unit
)
is
used
to
set
basic
reach
to
tap
value
.
The
operating
coil
consists
of
two
current
coils
,
and
both
coils
have
three
taps
.
These
taps
come
to
the
two
tap
blocks
mounted
on
the
left
side
of
the
unit
.
These
taps
determine
the
basic
reach
of
the
unit
,
and
both
tap
plugs
are
normally
set
for
the
same
tap
value
.
See
Table
II
for
data
on
how
the
basic
reach
ohms
vary
as
the
angle
of
maximum
torque
is
changed
.
RECEIVING
,
HANDLING
AND
STORAGE
These
relays
,
when
not
included
as
part
of
a
control
panel
will
be
shipped
in
cartons
designed
to
protect
them
against
damage
.
Immediately
upon
receipt
of
a
relay
,
examine
it
for
any
damage
sustained
in
transit
.
If
damage
resulting
from
rough
handling
is
evident
,
file
a
damage
claim
at
once
with
the
transportation
company
and
promptly
notify
the
nearest
General
Electric
Apparatus
Sales
Office
.
Reasonable
care
should
be
exercised
in
unpacking
the
relay
in
order
that
none
of
the
parts
are
damaged
or
the
adjustments
disturbed
.
If
the
relays
are
not
to
be
installed
immediately
,
they
should
be
stored
in
their
original
cartons
in
a
place
that
is
free
from
moisture
,
dust
and
metallic
chips
.
Foreign
matter
collected
on
the
outside
of
the
case
may
find
its
way
inside
when
the
cover
is
removed
,
and
cause
trouble
in
the
operation
of
the
relay
.
11
Courtesy of NationalSwitchgear.com
GEK
-
49778
ACCEPTANCE
TESTS
Immediately
upon
receipt
of
the
relay
,
an
inspection
and
acceptance
test
should
be
made
to
insure
that
no
damage
has
been
sustained
in
shipment
,
and
that
the
relay
calibrations
have
not
been
disturbed
,
readjustment
is
necessary
,
refer
to
SERVICING
.
If
examination
or
test
indicates
that
VISUAL
INSPECTION
Check
the
nameplate
stamping
to
insure
that
the
model
number
and
rating
of
the
relay
agree
with
the
requisition
.
Remove
the
relay
from
its
case
and
check
that
there
are
no
broken
or
cracked
molded
parts
or
other
signs
of
physical
damage
,
and
that
all
screws
are
tight
.
MECHANICAL
INSPECTION
There
should
be
no
noticeable
friction
in
the
rotating
structure
of
the
units
.
Make
sure
the
control
springs
are
not
deformed
,
and
that
spring
convolutions
do
not
touch
each
other
.
1
.
2
.
With
the
relay
well
-
leveled
in
its
upright
position
,
the
left
contacts
of
both
units
must
be
open
.
The
moving
contacts
of
the
units
should
rest
against
the
right
contact
.
Check
the
location
of
the
contact
brushes
on
the
cradle
and
case
blocks
against
the
internal
connection
diagram
for
the
relay
.
The
rotating
shaft
end
play
should
be
0.005
inch
to
0.010
inch
.
The
contact
gap
should
be
0.018
inch
to
0.020
inch
.
The
contact
wipe
should
be
0.003
inch
to
0.006
inch
.
3
.
4
.
5
.
6
.
7
.
ELECTRICAL
CHECKS
-
OHM
UNIT
All
tests
should
be
made
with
the
relay
in
its
case
.
Before
any
electrical
checks
are
made
on
the
units
,
the
relay
should
be
connected
as
shown
in
Figure
12
B
,
and
allowed
to
warm
up
for
approximately
15
minutes
with
the
potential
circuit
alone
energized
at
rated
voltage
,
and
the
restraint
taps
set
at
100
percent
.
The
units
were
warmed
up
prior
to
factory
adjustment
,
and
if
they
are
rechecked
when
cold
,
they
will
have
a
tendency
to
underreach
by
three
or
four
percent
.
Accurately
calibrated
meters
are
,
of
course
,
essential
.
Check
the
factory
setting
and
calibration
by
means
of
the
tests
described
in
the
following
sections
.
The
units
were
carefully
adjusted
at
the
factory
,
and
these
settings
should
not
be
disturbed
unless
the
following
checks
indicate
conclusively
that
the
settings
have
been
disturbed
.
If
readjustments
are
necessary
,
refer
to
the
section
on
SERVICING
for
recommended
procedures
.
12
Courtesy of NationalSwitchgear.com
GEK
-
49778
Test
connections
for
checking
correct
unit
operation
.
Jumper
studs
13
to
14
and
15
to
16
.
Control
Spring
Adjustment
:
Be
sure
that
the
relay
is
level
in
its
upright
position
.
Leave
the
relay
connected
as
shown
in
Figure
12
B
,
and
leave
the
restraint
taps
in
the
100
percent
position
.
Put
the
basic
reach
taps
in
the
1.5
ohm
taps
.
With
the
voltage
set
for
zero
,
the
current
required
to
close
the
left
contact
should
be
as
shown
below
:
CEX
57
D
CEX
57
E
CEX
57
F
Amperes
to
Close
Left
Contact
1.2
-
1.5
0.85
-
1.00
1.2
-
1.5
Clutch
Adjustment
:
Remove
jumpers
from
studs
13
-
14
and
15
-
16
.
With
the
connections
shown
in
Figure
12
B
,
set
the
phase
angle
to
185
degrees
(
I
leads
V
)
for
the
top
unit
,
or
5
degrees
(
I
leads
V
)
for
the
lower
unit
.
Put
restraint
taps
in
100
percent
,
basic
reach
taps
in
the
3.0
ohm
taps
,
and
set
for
rated
voltage
.
Increase
the
current
until
the
clutch
just
slips
.
The
current
should
be
between
22
and
30
amps
.
The
clutch
slip
can
be
detected
by
observing
the
nut
at
the
top
of
the
rotating
shaft
assembly
.
This
nut
will
turn
when
the
clutch
slips
,
but
the
moving
contact
will
remain
in
contact
with
the
left
stationary
contact
.
Ohmic
Reach
Connect
the
relay
per
Figure
12
B
.
Set
the
phase
angle
to
maximum
torque
(
I
leads
V
by
five
degrees
if
factory
adjusted
)
.
With
restraint
taps
on
100
percent
,
basic
reach
taps
on
1.5
ohms
,
and
V
=
30
volts
,
determine
current
to
just
close
the
left
contact
of
the
upper
unit
.
The
current
should
be
between
9.7
and
10.3
amperes
.
f
or
the
lower
unit
,
repeat
as
above
,
except
set
the
phase
angle
to
185
degrees
(
I
leads
V
)
.
Note
that
the
mho
units
see
a
phase
-
to
-
phase
fault
of
twice
the
basic
minimum
reach
for
the
test
conditions
.
Angle
of
Maximum
Torque
:
To
check
the
angle
of
maximum
torque
,
again
use
the
connections
of
Figure
12
B
.
Set
the
phase
shifter
to
maximum
torque
angle
,
plus
30
degrees
.
The
current
to
close
the
left
contact
should
be
82
to
91
percent
of
the
value
determined
in
"
Ohmic
Reach
"
above
.
Repeat
the
above
check
with
the
phase
angle
set
for
maximum
torque
angle
,
minus
30
degrees
.
The
current
to
close
the
left
contact
should
also
be
82
to
91
percent
of
the
value
determined
in
"
Ohmic
Reach
.
"
ELECTRICAL
CHECKS
-
AUXILIARY
UNIT
(
CEX
57
F
ONLY
)
Select
the
proper
tap
for
the
DC
voltage
to
be
used
on
the
relay
.
13
Courtesy of NationalSwitchgear.com
GEK
-
49778
Apply
75
percent
of
rated
DC
voltage
to
studs
1
and
11
,
with
plus
DC
on
stud
11
.
Close
the
left
contact
of
both
induction
cylinder
units
.
The
auxiliary
relay
should
pick
up
.
INSTALLATION
PROCEDURE
LOCATION
The
relay
should
be
installed
in
a
location
that
is
clean
,
dry
,
free
from
dust
,
and
well
lighted
to
facilitate
inspection
and
testing
.
MOUNTING
The
relay
should
be
mounted
on
a
vertical
surface
.
The
outline
and
panel
drilling
dimensions
are
shown
in
Figure
14
.
CONNECTIONS
The
internal
connections
diagrams
for
the
relays
are
shown
in
Figures
9
,
10
and
An
elementary
diagram
of
typical
external
connections
is
shown
in
Figure
5
.
VISUAL
INSPECTION
11
.
Remove
the
relay
from
its
case
and
check
that
there
are
no
broken
or
cracked
component
parts
,
and
that
all
screws
are
tight
.
MECHANICAL
INSPECTION
Recheck
the
seven
adjustments
detailed
in
the
MECHANICAL
INSPECTION
section
of
ACCEPTANCE
TESTS
.
INSPECTION
Before
placing
a
relay
into
service
,
the
following
mechanical
adjustments
should
be
checked
:
ANGLE
-
IMPEDANCE
UNIT
There
should
be
no
noticeble
friction
in
the
rotating
structure
of
the
unit
.
The
unit
'
s
moving
contacts
should
just
return
to
the
right
contact
when
the
relay
is
de
-
energized
and
in
the
vertical
position
.
There
should
be
approximately
0.005
to
0.010
inch
end
play
in
the
shaft
of
the
rotating
structure
.
The
lower
jewel
screw
bearing
should
be
screwed
firmly
into
place
,
and
the
top
pivot
locked
in
place
by
its
set
screw
.
If
the
jewel
should
become
cracked
or
dirty
,
the
screw
assembly
can
be
removed
from
the
bottom
of
the
unit
and
examined
.
When
replacing
a
jewel
,
have
the
top
pivot
engaged
in
the
shaft
while
screwing
in
the
jewel
screw
.
14
Courtesy of NationalSwitchgear.com
GEK
-
49778
All
nuts
and
screws
should
be
tight
,
particularly
on
the
tap
plugs
.
The
felt
gasket
on
the
cover
should
be
securely
cemented
in
place
in
order
to
keep
out
dust
.
Determine
the
impedance
and
phase
angle
seen
by
the
relays
.
Once
the
impedance
and
phase
angle
is
determined
,
the
tap
value
at
which
the
relay
will
just
operate
can
be
calculated
.
It
is
then
only
necessary
to
reduce
the
tap
setting
of
the
relay
until
the
units
operate
,
and
see
how
close
the
actual
tap
value
found
checks
with
the
calculated
value
.
The
calculated
value
should
take
into
account
the
shorter
reach
of
the
unit
at
low
currents
.
This
effect
is
shown
in
Figure
14
.
A
procedure
to
check
most
of
the
possible
open
circuits
in
the
AC
portion
of
the
relay
is
as
follows
:
(
a
)
Open
the
potential
circuit
by
removing
one
of
the
#
1
and
one
of
the
#
2
tap
plugs
.
Place
current
taps
in
the
1.5
ohm
taps
.
With
current
greater
than
two
amps
flowing
in
the
current
coils
,
the
left
contact
of
the
unit
should
close
.
(
b
)
(
c
)
Replace
the
#
1
and
#
2
restraint
tap
plugs
.
With
120
volts
on
the
relay
,
one
unit
should
close
its
right
contact
,
while
the
other
unit
should
have
increased
torque
closing
the
left
contact
.
Which
unit
has
its
left
contact
closed
,
and
which
has
its
right
closed
,
is
determined
by
the
direction
of
the
current
in
the
current
circuit
,
relative
to
the
voltage
on
the
potential
circuit
.
PERIODIC
CHECKS
AND
ROUTINE
MAINTENANCE
In
view
of
the
vital
role
of
protective
relays
in
the
operation
of
a
power
system
,
The
interval
between
it
is
important
that
a
periodic
test
program
be
followed
,
periodic
checks
will
vary
depending
upon
environment
,
type
of
relay
and
the
user
'
s
experience
with
periodic
testing
.
Until
the
user
has
accumulated
enough
experience
to
select
the
test
interval
best
suited
to
his
individual
requirements
,
it
is
suggested
that
the
points
listed
under
ACCEPTANCE
TESTS
be
checked
at
an
interval
of
from
one
to
two
years
.
CONTACT
CLEANING
A
flexible
burnishing
tool
should
be
used
for
cleaning
relay
contacts
.
This
is
a
flexible
strip
of
metal
with
an
etched
-
roughened
surface
,
which
in
effect
resembles
a
superfine
file
.
The
polishing
action
of
this
file
is
so
delicate
that
no
scratches
are
left
on
the
contacts
,
yet
it
cleans
off
any
corrosion
thoroughly
and
rapidly
,
flexibility
of
the
tool
insures
the
cleaning
of
the
actual
points
of
contact
.
Relay
contacts
should
never
be
cleaned
with
knives
,
files
,
or
abrasive
paper
or
cloth
.
The
15
Courtesy of NationalSwitchgear.com
GEK
-
49778
SERVICING
If
the
unit
calibrations
are
found
to
be
out
of
limits
during
installation
or
periodic
tests
,
they
should
be
recalibrated
as
outlined
in
the
following
paragraphs
.
The
calibrations
should
be
made
in
the
laboratory
.
The
circuit
components
listed
below
,
normally
considered
as
factory
adjustments
,
are
used
in
recalibrating
the
units
.
The
parts
may
be
physically
located
on
Figures
1
and
2
.
Their
location
in
the
relay
circuit
is
shown
on
the
internal
connection
diagrams
,
Figures
10
,
11
and
12
.
PI
:
Angle
of
maximum
torque
adjustment
on
upper
unit
P
2
:
Angle
of
maximum
torque
adjustment
on
lower
unit
P
3
Ohmic
reach
of
top
unit
P
4
:
Ohmic
reach
of
bottom
unit
Before
making
pickup
or
phase
angle
adjustments
on
the
units
,
they
should
be
allowed
to
heat
up
for
approximately
15
minutes
,
energized
with
rated
voltage
alone
,
and
the
restraint
tap
leads
set
for
100
percent
.
It
is
also
important
that
the
relay
is
mounted
in
an
upright
position
so
that
the
units
are
level
.
NOTE
:
CONTROL
SPRING
ADTUSTMENT
Make
connections
to
the
relay
as
shown
in
Figure
12
B
:
Set
voltage
to
zero
volts
Put
basic
reach
taps
in
1.5
ohm
taps
Set
current
to
1.0
ampere
.
Insert
the
blade
of
a
thin
screwdriver
into
one
of
the
slots
in
the
edge
of
the
spring
adjusting
ring
(
see
Figure
2
)
and
turn
the
ring
until
the
left
contact
of
the
unit
just
closes
.
Turning
the
ring
to
the
right
will
increase
the
current
required
to
close
the
left
contact
.
When
the
left
contact
just
closes
at
1.0
ampere
,
reduce
the
current
to
zero
,
and
check
that
the
right
contact
is
closed
.
ANGLE
OF
MAXIMUM
TORQUE
ADTUSTMENT
The
angle
of
maximum
torque
is
primarily
controlled
by
the
adjustment
of
the
upper
rheostat
on
each
unit
(
PI
for
the
upper
unit
,
or
P
2
for
the
lower
unit
)
,
and
by
whether
a
jumper
is
applied
across
studs
13
-
14
and
15
-
16
.
The
lower
rheostat
on
each
unit
(
P
3
for
the
upper
unit
,
or
P
4
for
the
lower
unit
)
,
has
a
secondary
effect
on
the
angle
of
maximum
torque
.
For
angle
of
maximum
torque
between
5
and
25
degrees
,
a
jumper
should
be
connected
between
studs
13
-
14
,
and
a
second
jumper
between
studs
15
-
16
.
For
angle
of
maximum
torque
between
30
and
35
degrees
,
no
connections
should
be
made
to
studs
13
,
14
,
15
or
16
.
For
angle
of
maximum
torque
between
25
and
30
degrees
,
determine
whether
the
jumpers
between
studs
13
-
14
and
studs
15
-
16
should
or
should
not
be
used
.
This
will
vary
from
unit
to
unit
,
depending
upon
actual
value
of
capacitors
Cl
and
C
2
.
16
Courtesy of NationalSwitchgear.com
GEK
-
49778
The
relays
are
shipped
from
the
factory
with
the
maximum
torque
angle
set
for
five
degrees
(
I
leads
V
)
.
For
a
different
angle
of
maximum
torque
,
proceed
as
follows
:
Connect
the
relay
as
shown
in
Figure
12
B
.
Jumper
studs
13
-
14
and
studs
15
-
16
if
required
.
Put
basic
reach
taps
in
1.5
ohm
tap
.
With
restraint
taps
set
for
100
percent
,
apply
60
volts
to
relay
.
Set
current
to
15
amperes
.
Turn
the
phase
shifter
and
determine
the
two
angles
at
which
the
left
contact
just
closes
(
angle
of
zero
torque
)
.
Find
the
angle
of
maximum
torque
as
follows
:
Add
the
two
angles
found
above
Divide
the
sum
by
two
.
This
will
be
the
angle
of
maximum
torque
for
the
lower
unit
.
For
the
upper
unit
,
subtract
180
degrees
from
the
value
to
get
the
maximum
torque
angle
.
For
example
:
Assume
the
top
unit
closes
its
left
contact
at
52
degrees
and
326
degrees
.
Adding
the
two
values
52
+
326
=
378
degrees
.
Dividing
by
two
equals
189
degrees
;
subtracting
180
degrees
equals
nine
degrees
for
the
angle
of
maximum
torque
.
If
studs
13
-
14
and
studs
15
-
16
are
jumpered
,
the
upper
rheostat
on
the
unit
should
be
turned
clockwise
to
make
the
angle
of
maximum
torque
lower
;
or
counterclockwise
to
make
the
angle
of
maximum
torque
higher
.
If
studs
13
-
14
and
studs
15
-
16
are
not
jumpered
,
the
upper
rheostat
on
the
unit
should
be
turned
counterclockwise
to
make
the
angle
of
maximum
torque
lower
,
and
clockwise
'
to
make
the
angle
of
maximum
torque
higher
.
If
the
upper
rheostat
is
turned
completely
counterclockwise
,
the
rheostat
will
be
at
zero
ohms
,
and
the
angle
of
maximum
torque
will
be
approximately
the
same
whether
studs
13
-
14
and
studs
15
-
16
are
shorted
or
left
unshorted
.
This
is
the
angle
that
determines
whether
to
short
studs
13
-
14
and
studs
15
-
16
.
For
angles
of
maximum
torque
below
this
value
,
studs
13
-
14
and
studs
15
-
16
must
be
jumpered
.
For
angles
of
maximum
torque
above
this
value
,
studs
13
-
14
and
studs
15
-
16
should
not
be
shorted
.
This
value
will
be
between
26
and
30
degrees
.
1
.
2
.
3
.
4
.
5
.
6
.
a
)
b
)
7
.
8
.
9
.
BASIC
REACH
OHMS
When
the
angle
of
maximum
torque
is
set
for
the
desired
value
by
the
tests
outlined
in
ANGLE
OF
MAXIMUM
TORQUE
ADJUSTMENT
,
the
basic
reach
should
be
checked
as
follows
:
Turn
the
phase
shifter
to
set
test
circuit
to
angle
of
maximum
torque
.
1
.
17
Courtesy of NationalSwitchgear.com
GEK
-
49778
Set
the
voltage
to
the
values
given
in
Table
VI
,
and
determine
the
current
to
just
cause
the
left
contact
to
close
.
This
value
should
be
as
shown
in
Table
VI
.
2
.
CORE
ADJUSTMENT
(
IF
REQUIRED
)
The
core
adjustment
is
made
as
follows
:
Adjust
the
control
spring
until
the
moving
contact
is
not
touching
either
the
right
or
left
contact
when
the
relay
is
de
-
energized
.
Apply
rated
voltage
to
studs
3
-
4
for
15
minutes
to
allow
the
potential
circuit
to
heat
up
.
Adjust
the
core
until
the
moving
contact
remains
in
the
same
position
with
studs
3
-
4
energized
at
rated
voltage
,
or
with
studs
3
-
4
de
-
energized
.
1
.
2
.
3
.
TABLE
VI
PHASE
ANGLE
SETTING
ANGLE
OF
MAX
.
TORQUE
BOTTOM
BASIC
TOP
VOLTAGE
ON
STUDS
3
-
4
CURRENT
PICKUP
UNIT
UNIT
OHMS
5
°
185
1.43
-
1.58
1.22
-
1.40
1.14
-
1.26
1.02
-
1.13
0.95
-
1.07
0.92
-
1.11
1.05
-
1.20
5
12.7
-
14.0
14.3
-
16.4
15.9
-
17.6
17.7
-
19.6
18.7
-
21.0
18.0
-
21.7
16.7
-
19.1
40
10
°
10
190
40
150
15
195
40
20
°
20
200
40
25
°
25
205
40
300
30
210
40
350
35
215
40
There
should
be
no
current
in
the
current
circuits
(
studs
5
-
6
and
studs
7
-
8
)
when
the
core
adjustment
test
is
being
made
.
When
the
core
adjustment
test
is
completed
,
reset
the
control
spring
per
the
paragraph
on
CONTROL
SPRING
ADJUSTMENT
.
RENEWAL
PARTS
Sufficient
quantities
of
renewal
parts
should
be
kept
in
stock
for
the
prompt
replacement
of
any
that
are
worn
,
broken
or
damaged
.
When
ordering
renewal
parts
,
address
the
nearest
Sales
Office
of
the
General
Electric
Company
.
Specify
the
name
of
the
part
wanted
,
quantity
required
,
and
complete
nameplate
data
,
including
the
serial
number
,
of
the
relay
.
indicates
Revision
18
Courtesy of NationalSwitchgear.com
GEK
-
49778
TELEPHONE
RELAY
-
(
A
)
CEX
57
F
ONLY
3
»
RESTRAINT
L
.
TAP
PLUG
CURRENT
TAP
BLOCK
POTENTIOMETER
PI
CAPACITOR
Cl
UPPER
UNIT
POTENTIOMETER
P
3
CAPACITOR
C
2
LOWER
UNIT
POTENTIOMETER
P
2
POTENTIOMETER
P
4
Figure
1
(
8042959
)
Type
CEX
57
Relay
Withdrawn
from
Case
19
Courtesy of NationalSwitchgear.com
GEK
-
49778
UPPER
PIVOT
ASSEMBLY
SPRING
ADJUSTING
RING
MOVING
-
CONTACTS
UPPER
CONTROL
SPRING
NORMALLY
OPEN
STATIONARY
CONTACT
NORMALLY
CLOSED
STATIONARY
CONTACT
|
Figure
2
(
8041447
)
Four
-
Pole
Induction
Cylinder
Unit
Typifying
Construction
of
the
Units
in
Type
CEX
57
Relays
20
Courtesy of NationalSwitchgear.com

Other manuals for CEX57D

1

This manual suits for next models

2

Other GE Relay manuals

GE NGV21A Series User manual

GE

GE NGV21A Series User manual

GE IAC Series User manual

GE

GE IAC Series User manual

GE IAC53A User manual

GE

GE IAC53A User manual

GE Multilin 745 User manual

GE

GE Multilin 745 User manual

GE T60 User manual

GE

GE T60 User manual

GE GCX51A User manual

GE

GE GCX51A User manual

GE 750 User manual

GE

GE 750 User manual

GE D30D00HCHF8AH6AM6BP8BX7A User manual

GE

GE D30D00HCHF8AH6AM6BP8BX7A User manual

GE 12IAC8OL User manual

GE

GE 12IAC8OL User manual

GE IFC51AD User manual

GE

GE IFC51AD User manual

GE D30 series User manual

GE

GE D30 series User manual

GE SLR12A User manual

GE

GE SLR12A User manual

GE NGV29A User manual

GE

GE NGV29A User manual

GE Masoneilan 469 Series User manual

GE

GE Masoneilan 469 Series User manual

GE L60 User manual

GE

GE L60 User manual

GE Multilin 489 User manual

GE

GE Multilin 489 User manual

GE DIAC User manual

GE

GE DIAC User manual

GE T60 User manual

GE

GE T60 User manual

GE D60 User manual

GE

GE D60 User manual

GE IAV51A User manual

GE

GE IAV51A User manual

GE IAC77A User manual

GE

GE IAC77A User manual

GE JBCV51M User manual

GE

GE JBCV51M User manual

GE L30 User manual

GE

GE L30 User manual

GE IRT51 E User manual

GE

GE IRT51 E User manual

Popular Relay manuals by other brands

Pilz PNOZ X2.1VP operating manual

Pilz

Pilz PNOZ X2.1VP operating manual

ABB CM-TCN manual

ABB

ABB CM-TCN manual

Basler BE1-87T instruction manual

Basler

Basler BE1-87T instruction manual

Pilz P2HZ X4P operating manual

Pilz

Pilz P2HZ X4P operating manual

Eaton ESR5-NE-51-24VDC manual

Eaton

Eaton ESR5-NE-51-24VDC manual

ABB SA-1 Instruction leaflet

ABB

ABB SA-1 Instruction leaflet

Pilz S1EN operating instructions

Pilz

Pilz S1EN operating instructions

FANOX SIA-C user manual

FANOX

FANOX SIA-C user manual

AMX netlinx NXC-REL10 quick start guide

AMX

AMX netlinx NXC-REL10 quick start guide

ZIEHL EFR4001IP operating manual

ZIEHL

ZIEHL EFR4001IP operating manual

Muuntosahko Superintend Trafox VR-16 Short Operating Manual

Muuntosahko

Muuntosahko Superintend Trafox VR-16 Short Operating Manual

Tsubaki TSBSB Series instruction manual

Tsubaki

Tsubaki TSBSB Series instruction manual

MITSUBISHI ELECTRIC ENGINEERING DG2BK1TB Series user manual

MITSUBISHI ELECTRIC ENGINEERING

MITSUBISHI ELECTRIC ENGINEERING DG2BK1TB Series user manual

Broyce Control P9625 instructions

Broyce Control

Broyce Control P9625 instructions

ABB CM Series Operating and installation instructions

ABB

ABB CM Series Operating and installation instructions

Circutor CBS-4C-NC quick start guide

Circutor

Circutor CBS-4C-NC quick start guide

RELCO RL UN instructions

RELCO

RELCO RL UN instructions

Omron K8DT-TH manual

Omron

Omron K8DT-TH manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.