GE GCY51F Series User manual

I
N
ST
RU
C
T
ION
S
MHO
Distance
Relay
Type
GCY51F
GEK-26437B
Supersedes
GEK-2643Th
GENERALS
ELECTRIC

DESCRIPTION
APPLICATION
.
RATINGS
ONE
SECOND
RATINGS
AND
H
2
OFFSET
H
1
AND
N
2
TAP LOCATIONS
12GCY51F1A
12GCY5IF2A
CONTACTS
TARGET/SEAL-IN
UNIT
BURDENS
12GCY51F1A
CURRENT
CIRCUITS
POTENTIAL
CIRCUITS
H
1
UNIT
M
2
UNIT
12GCYS1F2A
CURRENT
CIRCUITS
POTENTIAL
CIRCUITS
H
1
UNIT
M
2
Unit
CALCULATION
OF
SETTINGS
OPERATING
PRINCIPLES
H
1
UNIT
H
2
UNIT
CHARACTERISTICS
H
1
UNIT
IMPEDANCE
CHARACTERISTIC
UNDERREACH
MEMORY
ACTION
TRANSIENT
OVERREACH
...
OPERATING
TIME
UNIT
IMPEDANCE
CHARACTERISTIC
UNDERREACH
MEMORY
ACTION
TRANSIENT
OVERRREACH
OPERATING
TIME
CONSTRUCTION
CASE
GENERAL
ELECTRICAL
TESTS
DRAWOUT
RELAYS
GENERAL
POWER
REQUIREMENTS
GENERAL
RECEIVING,
HANDLiNG
AND
STORAGE
PERIODIC
CHECKS
AND
ROUTINE
MAINTENANCE
CONTACT
CLEANING
MECHANICAL
INSPECTION
SERVICING
CONTROL
SPRING
ADJUSTMENT
CLUTCH
CHECKS
CLUTCH-ELECTRICAL
TESTS
BASIC
MINIMUM
REACH
TESTS
ANGLE
OF
MAXIMUM
TORQUE
REACH
TAP CHECK
M
1
-M
2
OFFSETS
TESTS
TARGET/SEAL-IN
INSTALLATION
PROCEDURE
LOCATION
MOUNTING
CONNECTIONS
RENEWAL
PARTS
GE
K-254
37
CONTENTS
PAGE
4
4
5
5
6
6
6
6
7
7
7
7
7
7
7
8
8
8
8
8
8
9
10
10
11
11
11
11
12
12
12
12
13
13
13
13
13
13
13
13
14
14
14
14
15
15
15
15
16
16
16
17
17
17
18
18
18
18
18
18
19
2

GEK-26437
MHO
DISTANCE
RELAY
TYPE
GCY5IF
DESCRIPTION
The
GCY51F
is
a
single—phase
inho
relay
consisting
of
two
units
and
associated
auxiliaries
mounted
in
the
large
(La)
double-ended
case.
The
lower
unit
is
an
M
1
unit
which
is
designed
for
first
zone
application.
The
upper
unit
is
an
M
2
unit
which
is
designed
for
second
zone
applications
only.
The
second
zone
is
offset
in
the
forward
direction
to
provide
a
figure
8”
characteristic
suitable
for
ling,
heavily
loaded
lines.
GEK-26437
covers
a
5
ampere,
60
hertz
model (Form
1A)
and
a
1
ampere,
50
hertz
model (Form
2A).
The
impedance
ranges
and
offsets
are
shown
in
Table
I.
Since
the
one
ampere
relay
has
five
times
the
impedance
range
of the
five
ampere
relay,
the
application
and
calculation
of
setting
discussion
is
applicable
to
the
one
ampere
relay
by
multiplying
the
impedances
by
five.
The
internal
connections
diagram
is
as
shown
in
Figure
13.
APPLICATION
The
GCY51F
relay
is
used
for
phase
fault
protection
of
a
transmission
line.
It
has
a
distinctive
figure
eight’
characteristic
which
is
obtained
by
using
two
separate
mho
units
per
phase
of the
line.
The
first
zone
mho
unit,
M
1
,
has
a
characteristic
which
passes
through
the
origin
of
the
R-X
diagram
as
in
the
usual
application.
The
characteristic
of
the
second
zone
mho
unit,
M
2
,
s
offset
in
the
forward
direction
by
an
adjustable
amount which
allows
overlapping
of
the
two
characteristics.
See
the
R-X
plot
o
the
character
istics
in
Fig.
11.
The
‘figure
eight’
characteristic
is
applied
where
a
relay
with
a
long
forward
reach
setting
is
required
and
at
the
same
time
it
is
necessary
to
accoirmiodate
heavy
line
loadings
or
nhinor
system
swings
without
caus
ing
relay
operation.
The
M
1
first
zone
unit
may
be
used
alone to provide
instantaneous
tripping
for
a
portion
of
the
protected
line.
The
N
2
second
zone
unit
is
used
with
a
timer
to provide
time-delay
back-up
tripping
for
the balance
of
the
protected
line
and
a
portion
of the
next
line
section.
The
trip
contacts
of
both
units
connected
in
parallel
will
provide
the
overreaching
tripping
characteristic
needed
for
directional
comparison
or
trans
ferred
tripping
pilot—relaying
schemes.
Typical
external
connections are
shown
in
Figs.
l6A
and
B
for
the
scheme
of
protection
described.
This
shows
the
need
for
auxiliaries
such
as
a
timer
and
a
tripping
rectifier
for
circuit
isolation
in
addition
to
the
auxiliaries
needed
for
whatever
type
of
pilot-relaying
scheme
is
selected.
If
the
GCYS1F
is
used
in
a
pilot-relaying
scheme
with
the
line
side
potential
and
high speed
reclosing,
it
is
recorrieended
that
overcurrent
fault
detectors
be
used
to
supervise
the
trip
circuits.
When
setting
the
relay
units,
it
is
reconnended
that
the
offset
setting
on
the
M
2
unit
not
exceed
80
per
cent
of
tho
forward
reach
setting
of
the
Ml
unit.
This
will
insure
at
least
a
20
percent
overlap
of
the
two
characteristics
based
on
the
reach
setting
of
the
N
1
unit.
When
selecting
a
basic
minimum
ohmic
reach
tap
to
protect
a
line,
it
is
desirable
to
select
the
highest
one
that
will
accoriiriodate
the
desired
setting.
For
example,
if
a
5
ohm
setting
is desired
on
the
M
1
unit,
the tap
selected
should
be
3
ohms
minimum
rather
than
the
0.75
or
1.5
ohm
tap.
This
will
insure
the
highest
possible
torque
level
in
the
relay.
Refer
to
the
sec
tion
on
CALCULATION
OF
SETTINGS
for
a
worked
example
of
determining
the
required
settings
for
a
typical
application.
Refer
to
the
section
on
CHARACTERISTICS
for
the
relay
unit
operating
time
curves,
Fig.
8
and
Fig.
10
and
the
relay
reach
vs.
fault
current
curves
in Fig.
7
and
Fig.
9.
In
the
normal
transmission
line
application
the
N
1
first
zone
unit
reverse
offset
is
set
at
zero.
Thus,
this
unit
will
operate
for
faults
only
in
the
protected
line
section
and
not
operate
for
bus
faults
behind
the
relay
location.
However,
when
the
protected
line
ends
in
a
transformer
and
the
relay
is
connected
to
CT’s
and
PT’s
on
the
line
side
of
the
transformer,
the
M
1
first
zone
reverse
of,set
may
be
set at
0.5
ohm
so as
to
reach
backwards
part
way
into
the
impedance
of
the
transformer
bank.
Thus,
the
relay
will
remain
picked
up
even
for
a
zero
voltage
line
fault
right
at
the
transformer terminals
independent of
first
zone
memory
action.
The;e
instructions
do
not
purport
to cover
all
details
or
variations
in
equipment
nor
to
provide
for
ever.;
possbie
contingency
to
be
met
in
connectIon
with
installation,
operation
or
maintenance.
Should
further
information
be
desired
or
should
particular
problems
arise
which
are
not
covered
sufficicntly
for
the
purchaser’s
purposes,
the
matter
should
be
reterz-ed
to
the
General
Electric
Company.
To
the
extent
required
the
products described herein
meet
applicable
ANSI,
IEEE
and
NEMA
standards;
but
no
such
assurance
is
given
with
respect
to
local
codes
and
ordinances
because
they
vary
greatly.
3

GEK-26a37
RATINGS
-
c-stance
relays
are
rated
as
follows
DE
SECOND
RATINGS
The
one
second
ratings
of
the
current
circuits
of
the
12GCY51F(-)A
relays
are
listed
below.
K
=
12
t
rating
chart.
TABLE
I
equation
12GCY51F1A
J
BASIC MIN.
OHMIT
ANGLE
MAX.
OFFSET
RANGE
ANGLE
OF
UNIT
4
REACH
0-N__—
RANGE
jJRQUE
0—N
OFFSET
Ml
.75/1.5/3.0
0.75-30
60-75°
Lag
0/0.5
Ohm
255°
Lag
M
2
1/2/3
1.0
—3.0
60-75°
Lag
0—4
Ohms
750
Lag
—
—__________
(1.0
Ohm
steps)
TABLE
II
12SF
Y51F2J\
______
____________
_____
________
___________
_______________
r
UASIC
MIS.
OFFSEF
RANGE
ANGLE
OF
UNIT
REACH
0-N 0-N
OFFSET
3.75/7.5/15
3.75-150 60-75°
Lag
0/2.5
Ohms
255°
Lag
N
2
5/10/15
5.0
—150
60—75°
Faq
0—20
Ohms
75°
Faq
L
___L”_steps)
__
__
Thcsc
rridys
are
factory
adjusted
br
the
basic
minimum
reach
dt
the
75
deqree
lag,
angle
ot
maximum
rJr’JIC
1-1
though
the
units
can
he
adjusted
to
a
60
degree
lag,
angle
of
maximum
torque,
a
reduction
of
the
ciii
urn
reash
can
be
expected.
self’,
at
600
lag
3
reduction
in
reach.
jri
:.
at
GO°
lag
2O
reduction
in
reach.
Other
magnitudes
of
current
can
be
applied
for
various
periods
of
time
by
applying
the
following
t=
The
and
II.
Constant.
(See
one
second
Applied
current
(rms).
Time
(Seconds).
basic
minimum
reach
range,
angles
of
maximum
torque,
offset
range
and
angle
are
listed
in
Tables
I
OHMIC
0—14
H
AN
C
L
ANGLE
MAX.
TORQUL
4

GEK-26437
The
basic
minimum
reach
can
hr
extended
up
to
the
maximum
ohmic
0—H
reach
by
reducing
the
uri’c
restraint
transformer.
This
can
be
accomplished
by
applying
the following
equation.
Transf.
setting
()
1P
---)_X
ba
4
’
“nium
rech
tap.
Z
—N
Z
0-N
=
desired
reach
Basic
iciminmum
reach
tap
=
select
the
highest
reach
tap
below
the
Z
0-N
setting
desired.
M
1
and
N
2
_Offset
The
M
1
unit
has
a
reverse
offset,
where
the
forward
reach
of
the
unit
is
maintained
and
the
insertirn
of
an
offset
increases
the
diameter
of
the
characteristic
so
that
it
extends
in
a
reverse
direction,
providing
an
offset
equal
to
the
offset
tap
selected
(+)
10
percent.
The
M
2
unit
has
a
forward
offset,
where
the
diameter
of
the
units
characteristic
is
moved
forward
along
the
unit’s
angle
of
maximum
torque,
equal
to
the
offset
tap
(+)
10
percent.
and
M
2
Tap
Locations
12PCY51F1A
The
N
1
unit
reach taps
are
located
on
two
tap
plates
and
block
located
to
the
right
of
the
Ml
unit
(lower
unit).
The
basic
minimum
reach
taps are
marked
on
the
plate.
The
taps
are
selected
by
two
insulated
tap
screws
and
should
be
set
identically
for
a
particular
reach
setting.
The
M
1
offset
tap
is
located
at
the
rear
of
the
relay
behind
the
M2
unit
(upper
unit).
The
offset
is
a
fixed
value
and
is
selected
by
a
link
in
an
‘In”
or
Out’
consideration.
The
N
1
unit
restraint
transformer
is
located
on
the
left
side
of
the
relay
front
view.
It
has
taps
in
one
percent
dnd
10
percent
steps
which
are
selected
with
two
insulated
tap
plugs
and
movable
jumper
leads.
The
N
2
unit
reach
taps are
located
behind
the
relay
on
a
Bakelite
tap
block,
using
links
to
obtain
the
basic
minimum
reach.
Both
sets
of
links
must
be
set
identically
for
any
basic
reach
desired.
Table
HI
indicates
the
connections
for
the
basic
minimum
reach
setting.
TABLE
III
RELAY
BASIC
MINIMUM A”
“B”
MODEL
REACH
0-N
LINKS
LINKS
1
Ohm
1
0
GCY51F1A
2
Ohms
0
2
3Ohms
1
2
5Ohms
5
0
GCY51F2A
10
Ohms
0
10
l5Ohms
5
j
10
The
M
2
unit
offset
is
located
at
the
front
of the
relay
just
above
the
N
2
unit.
The
offset
taps
are
marked
--0,
1, 2, 3,
4
ohms
and
are
selected
by
a
sliding
lead
and
captured
screw.
The
N
2
restraint
transformer
is
located
on
the
right
side
of
the
relay
front
view.
It
consists
of
a
ta
block
with
taps
ranging
in
one
percent
steps
and
in
ten
percent
steps.
The
tans
arr
selected
with
two
insu
lated
tap
pluqs
and
movable
jumper
leads.
12GCYB1F2A
The
location
of
units
and
components
of
the
12GCY51F2A
is
the
same
as
in
the
12GCY51Fi
relay,
except
that
it
is
used
with
one
ampere
current transformers,
with
th
Dhmic
range
equai
to
five
times
the
12GCYS1F1A
relay.

GEK-26437
Contacts
The
contacts
of
these
distance relays
when
closed
due
to
a
fault,
will
momentarily
carry
30
amperes
up
jltS
d-c.
However,
the
circuit
breaker
trip
circuit
must
be
opened
by an
auxiliary
switch
or
by
some
other
suitable
means
since
the
relay contacts
do
not
have
an
interrupting
rating.
Target/Seal-in
Unit
The
relays
have
a
0.6/2.0
ampere
d-c
tap
rating.
The
electrical
parameters
are
listed
in
Table
IV.
TABLE
IV
TARGET
SEAL-IN
UNIT
0.6
AMP
TAP
2.0
AMP
TAP
Minimum
Operating 0.6
amps
2.0
amps
Carry
Continuously
1.5
mps
3.5
amps
Carry
30
Amps
for
0.5
secs.
4
secs.
Carry
10
Amps
for
4
secs.
30
secs
0-C
Resistance
0.6
ohms
0.13
ohms
60
Cycle
Impedance
6
ohms
0.53
ohms
BURDENS
Current
Circuits
The
maximum
current
burden
Imposed
on
each
GCY51F(-)A
relays
is
shown
in
Table
V.
AMPS
HERTZ
R
X
P.F.
W.
5
60
0.3
0.05
0.98
7.5
7.6
This
data
is
for
the
3.0
ohm
basic
reach
tap
of
the
M
1
and
M
2
units.
The
burden
with
the
M
1
unit
in
the
1.5
or
0.75
ohm
tap
or
with
the
M
2
unit
in
the
2
or
1
ohm
tap
will
be
slightly
lower.
Potential
Circuits
The
maximum
potential
burden
imposed
on
each
potential
transformer
at
120
volts,
60
hertz
Table
VI
for
restraint
transformer
settings
at
100
percent.
TABLE
VI
is
shown
in
CIRCUIT
I
R
JX
P.F.
WATTS
V.A.
M
1
Restraint
3200
JO
1.0
4.5 4.5
N
1
Polarizing
1300
-J680
0.89
8.7 9.8
M
2
Restraint
1150
+J]370
0.64
5.2
8.1
M
2
Polarizing
1440
-J217
0.99
9.7
9.8
The
potential
burdens
at
restraint
from
toe
following
formula.
transformer
settings
of
less
than
100
percent
can
he
calculated
,
Unit
VA
(a
+
Jb)rMl
tap
setting()1
2
+
(C
+
Jd)
[input
tap
setting
(j_J
1
2GCY51 F1A
current
transformer
at
five
amperes
for
a
set
of
three
TABLE
V
6

GEK-26437
TI
2
Unit
VA
=
(e
+
if)
rM2
tap
setting
()
1
2
+
Jh)
Linput
tap
setting
(%)J
The
terms
(a
+
Jb),
(C
+
Jd)
etc.
represent
the
burdens
of
the
Mi
and
M
7
potential
circuits
expressed
in
watts
and
vars
with
the
restraint
taps
in
100
percent.
Table
VII
gives
the
values
for
these
tenlis.
TABLE
VII
1
CIRCUIT
TERM
(WATTS
+
J
VARS)
(WATTS
+
3
VARS)
TI
1
Restraint
a
+
Jb
4.5
+
JQ
Mi
Polarizing
c
+
Jd
8.7
-
34.5
M
2
Restraint
e
+
if
5.2
+
J6.2
M
2
Polarizing
y
+
Jh
9.7
—
31.5
Total
burden
can
be
obtained
by
adding
the
M
1
and
M
2
watts
and
vars
for
each
unit
as
determined
by
the
above
Table
VII and
converting
the
total
to
volt-amperes.
1
2GCY51
F2A
Current
Circuits
The
maximum
current
burden
imposed
on
each
current
transformer
at
one
ampere
for
a
set
of
three
relays
is
listed
in
Table
VIII.
The
data
is
for
a
relay
set
at
the
maximum
reach
taps.
TABLE
VIII
AMPS
HERTZ
R
X
P.F.
WATTS
V.A.
1
50
11.90
16.40
0.587
11.90
20.27
Potential
Circuits
CIRCUIT
R
ix
P.F.
WATTS
V.A.
VARS
TI
1
Restraint
19.60
32279
3.652 3.12
4.78
3.62
M
1
Polarizing
14.53
-3817
0.872 7.53
8.63
—4.21
TI
2
Restraint
11.65
31866
0.53
3.46
6.52
5.52
TI
2
Polarizing
15.42
-J769
0.89 7.34 8.25
-3.26
The
potential
burdens
at
restraint
transformer
settings
of
less
than
100
percent
can
be
calculated
from
the
following
equations.
M
1
Unit
VA
=
(a
+
Jb)EM1
tap
setting
()
1
2
+
(C
+
3d)
[input
tap
setting
(%)]
TI
2
Unit
VA
(e
+
Jf)r2
tap
setting
2
+
+
Jh)
Linput
tap
setting
(‘)J
The
terms
(a
+
313)
to
(g
+
JH)
represent
the
burdens
of
the
Ml
and
TI
2
potential
circuits
expressed
in
watts
and
vars
with the
restraint
taps
in
100
percent.
Table
X
lists
the
values
of
these
terms.
The
input
tap
settings
in
the
above
equations are
100
percent.
7
TABLE
IX

GEK-26437
TABLE
X
CIRCUIT
TERM
WATTS
+
J
VARS
WATTS
+
J
VARS
-
H
1
Restraint
a
+
Jb
3.12
+
J3.62
M
1
Polarizing
C
(+) Jd
7.53
-
J4.2l
H
2
Restraint
e
+
Jf
3.46
+
J5.52
H
2
Polarizing
g
(±)
Jh
7.34
-
J3.76
The
total
burden
can
be
obtained
by
adding
the
H
1
and
N
2
watts
and
vars
for
each
unit
as
listed
In
Table
X
and
converting
to
volt—amperes as
indicated
in
the
equations
for
transformer
settings
less
than
100
percent.
The
maximum
burden
imposed
on
the
potential
transformer
by
the
offset
transactor
in
addition
to
the
unit’s
burden
in
Table
IX
is
shown
In
XI.
TABLE
XI
R
JX
P.F.
WATTS
V.A.
VARS
7.66
11.59
0.66 7.66
11.60
8.72
If
offset
is
used
the
volt-amperes
of the
offset
transactor
must
be
added
to
the
M
1
and
N
2
units
volt
amperes
to
determine
the
maximum
volt
amperes
of
the
relay’s
potential
circuit
with
offset.
CALCULATION
OF
SETTINGS
The
following
is
a
typical
worked
example
of
how
to
determine
the
reach
and
offset
tap
settings
for
the
relay
to
provide
the
proper
line
protection.
Assume
a
230kV
line
100
miles
long
with
a
positive
sequence
primary
impedance
of
Z(pri)
=
8O
With
a
CT
ratio
of
1200/5
and
a
PT
ratio
of
2000/1
the
secondary
impedance
becomes
CT
Ratio
Z(sec)
=
Z(pri)
X
PT
Ratio
Z(sec)
ohms
Set
the
M
1
first
zone
unit
to
90
percent
of
the
protected
line
section
taking
into
account
the
dif
ference
between
the
line
angle
0
=
85
degrees
and
the
H
1
angle
of
maximum
torque
9
=
75
degrees
by
the
func
tion
of
cos
(0—9).
The
N
1
reach
at
its
angle
of
maximum
torque
should
be
-
0.90
x
9.6
—
8.64
—
—
—
8.77
ohms
Using
the
three
ohm
basic
minimum
reach
tap,
the
N
1
tap
setting
will
be
TAP
(M
1
)
=
—-
=
34
Assume
that
we
are
using
a
relay
where
the
N
2
unit
has
a
0-4
ohm
forward
offset
range.
It
is
obvious
that
with
a
full
four
ohm
offset,
the
overlap
with
the
H
1
unit
reach
set
at
8.83
will
be
ample.
Set
the
M,
rit
to
reach
approximately
150
percent
of
the
protected
line
section
with
zero
infeed
at
the
remote
bus
again
taking
into
account the
difference
in
line
ano
1
e
with
maximum
torque
angle.
The
M
2
reach
at
its
angle
c
airnur
torque
will
then
be
Reach
(N
)
1.5(9.6)
14.62
/75°
2
cus
10°
8

GEK-26437
The
approximit.e
diaiieter
of
the
M
cheracteristic
will
then
he
this
redch
minus
the
four
ohms
offset
at
75
degrees
or
Z
(M
2
)
=
14.6?
-
4.0
10.E?
Again
using
the
three
ohm
basic
minimum
reach the
M
2
tap
setting
will
be
TAP
(M
2
)
10.62
=
281
This
calculation
of
the
setting
of M
2
is
not
n
exact
solution
but
may
be
close
enough
for
all
prac
tical
purposes
since
it
is
the
setting
on
overreaching
second
zone
characteristic.
The
smaller
the
angular
difference
between
the
line
and
the
relay
angle
of
maximum
torque,
the
smaller
the
error
in
the
reach.
Conversely
time
larger
the
amount
of
forward
offset
that
is
used
for
M
2
,
provided
there
is
an
angular
dif
ference,
the
greater
the
error.
To
check
the
calculitions
it
is
always
best
to
use
an
R-X
diagram
and
plot
the
line
and
the
relay
characteristics
to
scale
to
check
the
application.
This
has
been
done
in
Fig.
4
for
the
sample
calculations
just
described.
The
various
characteristics
and
points
shown
are
as
follows:
OA
protected
line
DC
=
90
percent
of
protected
line
08
=
150
percent
of
protected
line
OF
=
reach
at
75
degrees
E
=
center
of
M
1
characteristic
00
M
2
forward
offset
at
75
degrees
OH
=
M
2
reach
or
diameter
at
75
degrees
0
=
center
of
M
2
characteristic
The
optimum
settings
to
provide
the
narrowest
combined
relay
characteristic
would
be
to
have
equal
diameters
for
M
1
and
M
with the
overlap
kept
to
the
minimum
reconmmended
20
percent.
This
may
not
always
be
practical
or
feasibie
and
a
judicious
compromise
may
be
advisable
to
take
full
advantage
of
other
fea
tures
such
as
the
first
zone
backup
feature.
ihenever
the
reverse
offset
of
the
M
1
first
zone
unit
is
used, the
forward
reach
setting
of
the
M
1
unit
is
undisturbed.
This
offset
is
used in
a
situation
as
described
under
APPLICATION.
Since
the
offset
voltage supplied
by
the
tra9sactor
is
inserted
in
the
M
1
polarizing
circuit
only,
the
forward
reach
of
the
unit
into
t’ie
protected
line
remains unchanged.
The
tap
setting
used
on
the
target
and
seal-in
unit
is
determined
by
the
current
drawn
by
the
trip
coil.
The
0.6
ampere
tap
is
used
with
trip
coils
which
operate
on
currents
ranging
from
0.6
amperes
to
2.0
amperes
at
the
minimum
control
voltage
while
the 2.0
amperes
tap
should
be
used
when
trip
currents
are
greater
than
2.0
amperes.
It
is
not
good
practice
to
use
the
0.6
ampere
tap
when
the
trip
current
is
greater
than
2.0
amperes
since
the 0.6
ohm
resistance
of
the
O.
ampere
tap
will
cause
an
unnecessarily
high
voltage
drop
which
will
reduce
the
voltage
of
the
circuit
breaker
trip
coil.
If
the
tripping current
should
exceed
30
amperes,
it
is
recommended
that
an
auxiliary
tripping
relay
be
used.
OPERATING
PRINCIPLES
The
eho
units
of
the
GCYB1
relay
are
all
of the
four
pole
induction
cylinder
construction
in
which
torque
is
produced
by
the
interaction
between
a
oolarizinq
flux
and
fluxes
proportional
to
the
restraining
or
operating
quantities.
The
method
of
obtaining
the
mho
characteristic
for
the
N
1
unit
differs
from
that
used
for
th’
N
2
.
Both
schemes
are
described
below.
N
1
Unit
The
schematic
connections
of
the
M
1
unit
are
shnwn
in
Fig.
3.
The
two
side
poles,
enerqized
by
phase—
to-phase
voltage,
produce
the
polarizing
flux.
The
flux
froim
the
front
and
rear
poles,
energized
by
the
difference
between
-the
secondary
vol
taqe
of
transactor
TR-l and
a
percentage
of
the
same
phase-to-phase
voltage,
interacts
with
the
polarizing
flux
to produce
torque.
The
torque
equation
can
be
written
as
follows:
9

GEK-26437
Torcue
KE
(IZT1
-
TE)
cos
p
(1)
where
E
=
phase—to-phase
voltage
(F
12
)
I
delta current
(‘11
-
12)
ZT
1
=
transfer
impedance
of
transactor
TR-l
(design
constant)
p
=
angle
between
E
and
(1Z
11
-
E)
K
=
design
constant
T
=
auto-transformer
tap
setting
That
this
equation
(1)
defines
a
mho
characteristic
can
be
shown
graphically
by
means
of
Fig.
5.
The
vector
IZT1
at
an
angle
9
determines
the
basic
minimum
reach
of
the
unit
for
a
particular
tap
setting
of the
transactor
TR-l
primary.
Assuming
finite
values
of
E
and (IZT1
-
TE),
the
balance
point,
torque
=
0,
will
occur
where
cos
P
=
0,
that
is
where
the angle
P
is
90
degrees.
The
locus
of
the
terminus
of
vector
TE
(point
A
in Fig.
5)
which
will
cause the
angle
p
to
always
be
90
degrees
is
a
circle
passing
through
the
origin
and
with
the
vector
IZT1
as
a
diameter.
Considering
further
the
diagram
in
Fig.
4,
we
note
that
the
angle
P
is
less
than
90
degrees
for
an
internal
fault
(point
C)
and
the
net
torque
will
be
in
the
closing
direction
(cos
p
is
positive);
and
that
the
angle
p
is
greater
than
90
degrees
for
an
external
fault
(point
0)
and
the
net
torque
will
be
in
the
.pning
direction
(cos
P
is
negative).
M
2
Unit
The
schematic
connections
of the
M
2
unit
are
shown
in Fig.
3.
The
two
side
poles,
energized
by
phase—
to-phase
voltage,
produce
the
polarizing
flux.
The
flux
in
the
front
pole,
which
is
energized
by
a
percent
age
of
the
same
phase—to-phase
voltage,
interacts
with
the
polarizing
flux
to
produce
restraint
torque.
The
flux
in
the
rear
poTe, which
is energized
by
the
two
line
currents
associated
with
the
same
phase-to—phase
voltage,
interacts
with
the
polarizing
flux
to
produce
operating torque.
The
torque
at
the
balance
point
of the
unit
can
therefore
be
expressed
by
the
following
equation:
Torque
0
=
El
cos
(0
-
9)
-
KE
2
(2)
where:
E
=
phase-to—phase
voltage
(F
12
)
I
=
delta
current
(11—12)
9
angle
of
maximum
torque
of
the
unit
0
=
power
factor
angle
of
fault
impedance
K
=
design
constant.
To
prove
that
equation
(2)
defines
a
mho
characteristic
divide
both
sides
by
F
2
and
transpose.
The
equation
reduces
to:
3-cos
(0
-
0)
=
K
or:
Y
cos
(0
-
9)
=
K
(3)
Thus,
the
unit
will
pick
up
at
a
constant
component
of
admittance
at
a
fixed
angle
depending
on
the
angle
of
maximum
torque.
Hence
the
name
mho
unit.
CHARACTERISTICS
‘
mit
pedance
Characteristic
Th
impedance
characteristic
of the
unit
is
shown
in
Fig.
5
for
the
0.75
ohm
basic
minimun
reach
settinG
at
a
maxiMum
torque
angle of
-75
degrees.
This
characteristic
is
obtained
with
the
terminal
voltage
o
tne
relay
supplied
directly
to
the
restraint
circ.,t
of
the
M
1
unit,
that
is
with
the
M
1
taps
on
the
ajtc-transforrer
tao
block
set
at
100
percent.
This
circular
impedance
characteristic
can
be
enlarged,
tmit
i
unit
redh
increased,
by up
to
10/1
by
reducing
the
percentage
of the
terminal
voltage
supolied
Er
the

bEK-26437
rstrai
ni.
circuit
by
inean
of
the
M
1
taps
on
the
autotransfornier
tap
block,
and
the
circle
can
be
further
enlarged,
providing
a
total
range
adjustment
of
up
to
40/1,
by
means
of the
basic
minimum
reach
tap
screws.
The
circle
will
always
piS;
through
the
origin
and
have
a
diameter
alonn
thp
Th
dpnr’
impedance
line
equal
i
the
ohwc
reach
of the
unit
as
expressed
by
the
following
equation.
Ohmic
Reach
(Input
Tar)
mjn
(4)
M
1
Tap
Setting
()
who
re:
Input
Tap
=
Input
Tap
Sctting
in
percent
(normally
100%).
=
Basic
minimum
phase—to—neutral
ohmic
reach
of the
unit
(as
set
by
taps).
The
angle
of
maximum
torque
of
the
unit
can
be
adjusted
down
to
60
degrees
with
negligible
effect
on
the
reach
of
the
unit.
Underreach
At
reduced
voltage
the
ohmic
value
at
which
the
M
1
unit
will
operate
may
be
somewhat
lower
than
the
calculated
value.
This
pullback
or
reduction
in
reach
is
shown
in
Fig.
7
for
the
0.75,
1.5,
and
3
ohm
basic
minimum
reach
settings.
The
unit
reach
in
percent
of
setting
is
plotted
against
the
three-ph.se
fault
current
for
three
ohmic
reach
tap
settings.
Note
that
the
fault
current
scale
changes
with
t
basic
mini
mum
reach
setting.
The
M
1
unit
will
operate
for
all
points
to
the
right
of
the
curve.
The
steady-state
curves
of
Fig.
1
were
determined
by
tests
performed
with
no
voltage
supplied
to
the
relay
before
the
fault
was
applied.
The
dynamic
curves
were
obtained
with
full
rated
voltage
of
120
volts
supplied
to
the
relay
before
the
fault
was
applied.
Memory
Action
The
dynamic
curves
of
Fig.
7
illustrate
the
effect
of
memory
action
in
the
M
1
unit
which
maintains
the
polarizing
flux
for
a
few
cycles
following
the
inception
of
the
fault.
This
memory
action is
particularly
effective
at
low
voltage
levels
where
it
enables
tie
M
1
unit
to
operate
for
low
fault
currents.
This
can
be
most
forcefully
illustrated
for
a
zero
voltage
fault
by
referring
to
Fig.
7.
A
zero
voltage
fault
must
be
right
at
the
relay
bus
and
therefore,
to
protect
for
this
fault,
it
is
imperative
that
the
relay
reach zero
percent
of
its
setting.
Fig.
7
shows
that
the
M
1
unit,
under
static
conditions,
will
not
see
a
fault
at
zero
percent
of
the
relay
setting
regardless
of
the
tap
setting.
However,
under
dynamic
conditions
when
the
memory
action
is
effective,
Fig.
7
shows
that
an M
1
unit
with
a
3
ohm
basic
minimum
reach
and
100
percent
tap
setting
will
operate
if
I
is
greater
than
1.5
amperes.
For
an
M
1
unit
with
a
15
ohm
basic
minimum
reach
and
100
percent
tap
seti’ng,
the
unit
will operate
if
130
is
greater
than
0.3
amperes.
Transient
Overreach
The
operation
of
the
M
1
unit
under
transient
conditions
at
the
inception
of
a
fault
is
important
because
the
relay
is
normally connected
so
that
the
M
1
contacts
will
trip
a
circuit
breaker
independently
of
any
other
contacts.
The
impedance
characteristic
of
Fig.
5
and
the
steady—sate
curves
of
Fig.
7
represent
steady-state
conditions.
If
the
fault
current
contains
a
d-c
transient,
the
unit
may
close
its
contacts
momentarily ever
thougr
the
impedance
being
measured
is
slightly
greater
than
the
calculated
steady-state
reach.
This
overreaching
tendency
will
be
a
maximum
when
a
fault
occurs
at
the
one
instant
in
either
half-
cycle
wich
produces
the
maximum
d-c
offset
of the
current
wave.
The
maximum
transient
overreach
of
the
M
1
unit
will
not exceed
5
percent
of
the
steady-state
reach
for line
angles
up
to
85
degrees.
Operating
Time
The
operating
tine
of
the
unit
is
determined
by
a
number
of
factors
such
as
the
basic
minimum
reach
setting
of
the
unit,
fault
current
magnitude,
ratio
of
fault
impedance
to
relay
reach,
and
magnitude
of
reld)
voltage
prior
to the
fault.
The
curves
in
Fig.
8
are
for
the
condition
of
rated
volts
prior
to
the
filt.
Time
curves
are
given
for
four
ratios
of
fault
impedance
to
relay
reach
setting.
In
all
cases,
the
M
1
taps
were
in
toe
100
percent
position
and
the
angle
of
maximum
torque
was
set
at
60
degrees
lag.
For
relass
that
were
set
for
an
angle
of
maxinum
torque
of
75
degrees
lag,
the
time
curve
would
be
approximately
3-4
percent
faster
than
that
shown
in
Figure
8.
The
130
fault
current
amperes
should
be
divided
by
five
for
the
one-ampere
rated
relays.
11

GEK—26437
M
2
Unit
Impedanse
Fh•acteristic
The
impedance
characteristic
of
the
M
2
unit
is
shown
in
Fig.
6
for
the
one
ohm
basic
minimum
reach
settin:
at
a
maximum
torque angle
of
60
derees.
As
with
the
M
1
unit,
this
circle
can
he
expanded
by
uiearis
of
tne
M
2
taps
on
the
autotransformer
tap block
providing
a
range
of
up
to
10/1,
or
by
changing the
basic
minimum
reach
of
the
unit
by
means
of
the
links
on
the
rear
of
the
M
2
subassembly
providing
a
total
range
of
up
to
30/1.
The
circle
will
always pass
through
the
origin
and
have
a
diameter
along the
60
degree
impedance
line
equal
to
the
ohmic
reach of
the
unit
as
expressed
by
the
following:
Ohmic
Reach
=
(Input
Tap)
(5)
M
2
Tap
Setting
(%)
where:
Zmin
=
basic
mm.
phase-to—neutral
ohmic
reach
of the
unit.
Input
Tap
input
tap
setting
in
percent
(normally
100%)
Underreach
The
reduction
in
reach of
the
M
2
unit
at
reduced
voltage
is
shown
in
Fig.
g
for
the
1,
2,
and
3
ohm
basic
minimum
reach
settings.
The
reach
in
percent
of
setting
is
plotted against
three-phase
fault
current
for three
ohmic
reach tap
settings.
Note
that
a
different
fault
current
scale
is
shown
for
each
basic
minimum
reach
setting.
The
M
2
unit
will
operate for
all
points
to
the
right
of
the
curve.
The
data
for
these
curves
was
taken
in
the
same
manner as
the
M
1
curves
previously
described.
Memory
Action
As
shown
by
the
dynamic
curves
of
Fig.
9
the
M
2
unit
has
a
built-in
memory
action
feature
similar
to
that
of
the
M
1
unit
previously
described.
Transient
Overreach
Since
the
M
2
unit
is
used
to
trip
the
circuit
breaker
through
the
contacts
of
a
timing
relay,
or
as
the
directional
unit
in
a
carrier-current
relaying
scheme,
it
is
not
necessary
to
control
the
transient
overreach
as
was
done
in
the
M
1
unit.
The
M
2
unit
will
have
correct
directional
action
during
transient
conditions.
Operating
Time
The
operating
time
of
the
M
2
unit
is
determined
by
the
same
factors
described
for
the
M
1
unit.
The
curves
in
Fig,
10
are
for
the
condition
of
rated
volts
prior
to
the
fault.
Since
the
transient
overreach
is
not
limited
the
M
2
unit
tends
to
be
faster
than
the
M
1
unit.
For
a
unit
that
is
calibrated
for
an
angle
of
maximum
torque of
15
degrees
lag
the
operating
times
will
be
approximately
3-4
percent
faster
than
that
shown
in
Fig.
10.
The
13
currents
must
be
divided
by
five
for
the
one
ampere
rated
relays.
The
overall
impedance
characteris!ics
of
the
12GCY51F(—)A
relay
are
shown
in
Fig.
11
which
includes
the
offset
chracteristic.
CONSTRUCT
ION
La
so
Th
Type
GCY5
relays
are
assembled
in
the
standard
large
size,
double-end
(L2)
drawout
case
havnc
studs
at
both
ends in
the
rear
for external
connections.
The
electrical
connections
between
tne
relay
units
ant;
the
case
studs
are
made
through
stationary
molded
inner
and
outer
blocks
between
which
nests
a
re
movable
connecting
plug
which
completes
the
circuits.
The
outer
blocks
attached
to
the
case
have
the
studs
fDr
tie
external connections,
and
the
inner
blocks
have
the
terminals
for
the
internal
connections.
iery
circuit
in
the
drawout
case
has
an
auxiliary
brush,
as
shown
in
Fig.
12,
to
provide
adequate
.‘nn
roe
connecting
plug
is
withdrawn
or
inserted.
Some
circuits
are
equipped
with
shortin’
bars
nterra
connc:tions
in
Fig.
13)
and
on
those
circuits,
it
is
especially
important
that
the
auxiliary
:rs
je:
:sntact
as
indicated
in
Fig.
12
with
adequate
pressure
to
prevent
the
openng
of
important
12

GLK—26437
The
relay
mechan
i
sin
is
niouritod
in
a
s
tee
framework
ca
led the
cradle
and
is
a
coinpi
ate unit
w
ti
a
1
leads
terminated
at
the
inner block.
This
cradle
is
heir
1
firmly
in
the
case
wit
1
a
latch
at
both
top
and
bottom
and
by
a
guide
pin
at
the
back
of the
case.
The
connecting nlug,
besides
maKing
tne
electrical
con
nections
between
the
respective
blocks
of the
cradle
and
case, also
locks
the
latch
in
place.
The
cover.
which
is
drawn
to
the
case
by
thumbscrews,
holds
the
connecting
plugs
in
place.
The
target
reset
mechanism
is
a
part
of
the
cover
aeinu1y.
The
relay
case
is
suitable
for
either
semi-flush
or
surface
mounting
on
all
panels
up
to
two
inches
thick
and
appropriate
nardware
is
available.
Hoae.er,
panel
thickness
must
be
indicated
on
the
relay
order
to
insure
teat
proper
hardware
will
be
included.
A
separate
testing
plug
can
be
inserted
in
place
of
the
connecting
plug
to
test
the
relay
in
place
on
the
panel
either
fro,n
its
own
source
of
current
and
voltage,
or
from
other sources.
Or
the
relay
can
be
drawn
out
and
replaced
by
another
which
has
been
tested
in
the
laboratory.
Figs.
1
and
2
shown
the
relay
removed from
its
drawout
case
with
all
major
components
identifi-.
Symbols
used
to
identify
circuit
components
are
the
same
as
those
which
appear
on
the
internal
connection
diagram
in
Fig.
13.
The
relay
includes
major
subassembly
elements:
The
lower
element
includes
the
M
1
unit
with
associated
circuit
components.
Adjustable
reactor
X
1
,
used
in
setting
angle
of
maximum
torque,
and
rheostat
R
11
,
used
in
setting
basic
minimum
reach
can
be
adjusted
from
the
front
of
the
relay.
Transactor
Tfl-l
,
with
tap
block
for
selecting
the
basic
minimum
reach
of
M
1
,
is
mounted
on
the
rear
of
the
element with
tap
screws
accessible
from
the
front.
2.
The
middle
element
includes
the
N
2
unit
with
its
associated
circuit
components.
Rheostats
R
12
for
setting
basic
minimum
reach
and
R
22
for
setting
angle of
maximum
torque
are
accessible
from
tFie
front
of
the
relay.
A
terminal
block
with
links
for
selecting
the
basic
minimum
reach
is
mounted
at
the
rear
of
the
element.
GENERAL
ELECTRICAL
TESTS
DRAWOUT
RELAYS
GENERAL
Since
all
drawout
relays
in
service
operate
in
their
cases,
it
is
recommended
tha.. they
be
tested
in
their
cases
or
an
equivalent
steel
case.
In
this
way
any
magnetic
effects
of
the
enclosure
will
be
accurately
duplicated
during
testing.
A
relay
may
be
tested
without
removing
it
from
the
panel
by
using
a
12XLA13A
test
plug.
This plug
makes
connections
only
with
the
relay
and
does
not
disturb
any
shorting
bars
in
the
case.
Of
course,
the
12XLA1?A
test
plug
may
also
be
used.
Although
this
test
plug
allows
greater
testing
flexibility,
it
also requires
shorting
jumpers
and
the
exercise
of
greater
care
since
connections
are
made
to
both
the
relay
and
the
external
circuitry.
POWER
REQUIREMENTS
GENERAL
All
alternating
current
operated devices
are
affected
by
frequency.
Since
non-sinusoidal
waveforms
can
be
analyzed
as
a
fundamental
frequency
plus
harmonics
of
the
fundamental
frequency,
it
follows
that
alternating
current
devices
(relays)
will
be
affected
by
the
applied
waveform.
Therefore,
in
order
to
properly
test
alternating
current
relays
it
is
essential
to
use
a
sine
wave
of
current
and/or
voltage.
The
purity
of
the
sine
wave
(i.e.
its
freedom
from
harmonics)
cannot
be
expressed
as
a
finite
number
for
any
particular
relay,
however,
any
relay
using
tuned
circuits,
R-L
or
RC
networks,
or
saturating
electromagnets
(such
as
time-overcurrent
relays)
wou’d
be
essentially
affected
by
non-sinusoidal
wave
forms.
Similarly,
relays requiring
d-c
control
power
should
be
tested
using d-c
and
not
full
wave
rectified
power.
Unless
the
rectified
uppiy
is
well
filtered,
many
relays
will
not
operate properly
due
to
the
dips
in
tie rectified
power. Zoner
diodes,
for
example,
can
turn
of
during
these
dips,
As
a
general
rule
the
d-c
source
should
not
contain
more
than
5
percent
ripple.
RECEIVING,
HANDLING
AND
STORAGE
most
relays,
when
miot
included
as
a
part
of
a
control
tanel
,
will
he
shipped
in
cartons
designed
to
protect
trier”
against
damage.
Irnediately
upon
receipt
of
a
relay,
examine
it
for
any
damage
substained
in
transit.
If injury
or
damage
resulting
from
rough
handling
is
evident,
file
a
damage
claim
at
once
with
t
transportation
compaly
and
promptly
notify
the
neareast
General
Electric
Apparatus
Sales
Office.
Reasonable
sare
s:cijld
be
exercised
in
unpacking
the
relay
in
order
that
none
of
the
parts
are
injured
or
the
ddjustrnentc
disturbed.

GEK-26437
relays
are
not
to
be
installed
inediate1y,
they
should
be
stored
in
their
original
cartons
in
a
place
that
is
free
from
moisture,
dust
and
metallic
chips.
Foreign
matter
collected
on
the
outside
of
the
case
may
find
its
way
inside
when
the
cover
Is
removed
and
cause
trouble
in
the
operation
of
the
relay.
PERIODIC
CHECKS
AND
ROUTINE
MAINTENANCE
In
view
of
the
vital
role
of
protective
relays
in
the
operation
of
a
power
system
it
is
important
that
a
periodic
test
program
be
followed.
It
is
recognized
that
the
interval
between
periodic
checks
rIll
vary
depending
upon
environment,
type
of
relay
and
the
users
experience
with
periodic
testing.
Until the
user
has
accumulated
enougi
experience
to
select
the
test
interval
best
suited
to
his individual
requirements
It
is
suggested
that
the
points
listed
under
INSTALLATION
PROCEDURE
be
checked
at
an
interval
of
from
one
to
two
years.
CONTACT
CLEANING
For
cleaning
relay
contacts,
a
flexible
burnishing
tool
should
be
used.
This
consists
of
a
flexible
strip
of
metal
with
an
etched-roughened
surface
resembling
in
effect
a
superfine
file.
The
polishing
action
is
so
delicate
that
no
scratches
are
left,
yet
It
will
clean
off
any
corrosion
throughly
and
rapidly.
Its
flexibility
insures
the
cleaning
of
the
actual
points
of
contact.
Do
not use
knives,
files,
abrasive
paper
or
cloth
of
any
kind
to
clean
relay
contacts.
MECHANICAL
INSPECTION
1.
It
is
reconimended
that
the
mechanical
adjustments
in
Table
XII,
be
checked.
2.
There
should
be
no
noticeable
friction
in
the
rotating
structure
of
the
units.
3.
Make
sure
control
springs
are
not
deformed
and
spring
convolutions
do
not
touch
each
other.
4.
WIth
the
relay
well
leveled
in
its
upright
position
the
contacts
of
all
units
must
be
open.
The
moving
contacts
of
the
N
1
and
N
2
units
should
rest
against
the
backstop.
5.
The
armature
and
contacts
of
the
seal-in
unit
should
move
freely
when
operated
by
hand.
There
should
be
at
least
1/32
inch
wipe
on
the
seal-in
contacts.
TABLE
XII
CHECK
POINTS
N
1
UNIT
M
2
UNIT
Cup
End
Play
0.010”
-
0.015”
0.010”
-
0.015”
Conzact
Gap
0.030”
—
0.035” 0.018”
-
0.022”
Contact
Wipe
0.003”
-
0.005”
0.003”
-
0.005”
Clutch
Gram
Pressure
45
-
60 45
-
60
Check
the
location
of
the
contact
fingers
and
brushes
on
the
cradle
and
case
blocks
against
the
internal
connections
diagram
for
the
relay
(Fig.
13).
SERVICING
The
relay
should
be
level
in
its
upright position
and
should
be
tested
in
its
case
or
an
equivalent
test
case.
Connect
the
relay
for
the
tests
connections
shown
in
Fig.
14.
CONNECT
LEAD
STUDS
A
15
-
17
-
19
B
16-18-20
C
3
D
10
Jumper
studs
4
to
5,
6
to
7
and
8
to
9.
Set
the
relay
taps
for
the
following
conditions.
12GCY51F1A
12GCV51F2A
N
1
reach
taps
1.5
ohms
7.5
ohms
N
2
reach
taps
(A
+
B
links)
0
-
2
0
-
10
Ml
offset
taps
out out
offset
taps
0
0
M
1
restraint
transf.
lOO
lO0
M
2
restraint
transf.
1OO 1O0’
14

i.j:;Jl/
12h
volts,
iI1fCr5
et
dt
Adjust
the
pnds
shi
fter
for
an
anj
1
e
sor.ti
rig
of
75
IcOrCes
1
ag
I
1
age
Preheat
the
relay
at
rated
voltage,
zero
current
‘nroximately
fifteen
minutes
before
attempting
to
perform
any
cal
ibratiori
checks
or
adjustments.
Control
Spring
Adjustment
Reduce
the
voltage
to
the
value
listed
in
Table
XIII,
increase
the
current
until
the
unit
contacts
close.
This
should
occur
between
the
values
of
rest
current
listed
in
Table
XIII.
TABLE
XIII
UNIT
i3ASIC
MINIMUM
Ø
METER
TEST
TEST
REACH
0-N
TAP
SETTING
VOL1AGE
CURRENT
1.5
ohms
750
lag 2.0
V
2.7
-
3.3A
M
1
7.5
ohms
750
lag
2.0
V
0,54
-
0.66
M
2
2.0
ohms
75°
lag
2.0
V
2.0
-
2.54
N
2
10.0
ohms
750
lag 2.0
V
0.40
-
0.54
•
Adjust
the
control spring
on
each
unit
if
necessary
to
obtain
contact
closing
between
tee
test
current
limits
in
Table
XIII.
Clutch
Checks
The
clutch
adjustments
can
be
made
using
a
special
wrench,
0246A7916 and
a
standard
3/8
inch
open
end
wrench.
The
special
wrench
is
inserted
into
the
unit
between
the
top
of
the
front
coils
and
the
contact
head.
The
wrench
should
engage
the
Bakelite
part
just
above
the
cup.
This
will
keep
the
cup
assembly
from
turning
while
adjusting
the
clutch.
With
the
special
wrench
holding the
cup
assembly
secure,
the
open
end
wrench
is
used
to
tighten
or
loosen
the
self
locking
nut
located
at
the
top
of the
cup
shaft.
Turning
this
nut
clockwise
will
tighten
the
clutch
and
increase
the
clutch
setting.
Turning
counterclockwise
will
decrease
the
clutch
setting.
To
determine
the
proper
setting
of
the
clutch,
the following
relay
settings
must
be
made.
RELAY
RESTRAINT
Ml
UNIT
M2
UNIT
OFF3ET
MODEL
LEADS
12GCY51F1A
3
ohm
taps
3
ohio
taps
0
N
unit
siort
or
J2GEY51F2A
15
ohm
taps
15
ohm
taps
0
N
2
unit
open
Clutch-Electrical
Tests
METER
CLUTCH
SLIP
CURRENT
VOLTAGE
UNIT
SETTING
12GEYS1F1A
12GCY51F2A
l
75°
Lag
120
26-45
Amp
5-9
Amp
j
N
2
750
Lag
120
35-55
Amp
7-il
Amp

GEK-26437
Basic
Minimum
Reach
Tests
Set
the
following:
UNIT
12GCY51F1A
12GCY51F2A
N
1
restraint
taps
100%
100%
N
1
reach
taps 1.5
ohm
7,5
ohm
M
1
offset
tap
0
0
M
2
restraint
taps
100% 100%
M
2
reach
taps
2
ohm
10
ohm
N
2
offset
0
0
The
test
circuit
connects the
relay
for
a
phase-to—phase
fault
condition.
Therefore,
the
relay
will
reach
twice
the
basic
minmurn
0
-
N
reach
tap
setting.
TABLE
XIV
T
RELAY
UNIT
METER
SET
PICKUP
REACH
ADJUST
I
MODEL
SETTING
VOLTAGE
CURRENT
0
-
0
12GCY51F1A
M
1
75°
Lag
45V
14.7
-15.3
3
Ohms
R
11
M
2
75°
Lag
60V
14.7
-15.3
4
Ohms
R
12
12GCY51F?A
M
1
75°
Lag
45V
2.94—
3.06
15
Ohms
R
11
N
2
75°
Lag
6OV
2.94-
3.06
20
Ohms
R
12
Angle
of
Maximum
Torque
Check
pickup
currents
at
the
angles
indicated
in
Table
XV
to
deteniiine
if
the
angle of
maximum
torque
is
within
limits.
TABLE
XV
TEST
SET
PICKUP
ADJUST
RELAY
MODEL
UNIT
ANGLES
VOLTAGE
CURRENT
12GCYSIFIA
N
1
600
and
90°
45V
16.80-17.84
X
11
M
2
600
and
90°
60V
16.80-17.84
R
22
12GCYS1F2A
N
1
600
and
90°
45V
3.36-
3.57
X
11
I
N
2
600
and
900
6OV
3.36-
3.57
R
22
Reach
Tap
Check
Trie
remaining
reach
taps
on
each
unit
can
be
checked
similar
to
the
reach
test
mentioned
previously
ex
cept
use
the
value
in
Table
XVI.
TABLE
XVI
REACH
‘C
METER
PICKUP
MODEL
UNIT
VOLTAGE
TAP
SETTING
CURRENT
1?5lFlA
I
M
1
0.75
75°
Lag
30V
19.2
-20.8
N
2
3.00
75°
Lag
60V
9.6
—10.4
3.75
75°
Lag
30V
3.84-
4.16
15.00
75°
Lag
12OV
3.84—
4.16
lb

Lr’
h4/
M]-M?
Ott
ct
S[t
ite
ret
ay tnt)’
bick
to
tilu’,’
fl(fl
I
n,tenj
unici
i.rie
B;’
FI.INJAIjM
REA1O
TEST
sec,ion
eic
.‘
oFI’Mt
link
to
the
tin
ic,,
1.
on
‘
‘
urii
t
offset
tap
at
ohms
(OCYS1F1A)
,
20
ohms
(1CY51F24
1
App1
y
I
20
vol
t
1
iinpirc
rJ
e
t
t[ctc
Ise
angl
r
meter
tO
read
255
degrees
lag
Reduce
the
vol
taqe
and
current
to
that
ii
‘ted
in
Table
XVI
I
TABLE
XVII
RElAY
MODEL
OFFSET
CURRENT
l?GCY5IF1A
M
1
2550
Lag
“IN’
20V
17.0
-23.0
N
2
75°
Lag
4L
l2OV
9
-114
3E2 12OV
10.8
-Li.2A
2!l
60V
6.75-
8.254
1
60V 9—114
60V
14.7 -15.3A
I2GCY51F2A
M
1
255°
Lag
“IN”
20V
3.4
-
4.1
N
2
750
Lag
2O1
12OV
1.8
-
2.2A
15
l2OV
2.16-
2.644
lO
120V
2.7
-
3.34
5c2
l2OV
3.6
-
4.4A
0
c
60V
2.94-
3.06
TARGET/SEAL—
IN
The
target
seal-in
unit
has
an
operating coil
tapped
at
0.6
or
2.0
amperes.
The
relay
is
shipped
froo
the
factory
with
the
tap
screw
in
the
2.0
ampere
position.
The
oPerating
point
of the
seal-in
unit
can
be
checked
by
connecting
from
a
d-c
source
(+)
to
stud
11
of
the
relay
and
from
stud
1
through
an
adjustable
resistor
and
ammeter back
to
(-).
Connect
a
jumper
from
stud
13
to
stud
1
also
so
that
the
seal—in
contact
will
protect
the
unit
contact.
Then
close
the
M
contact
by
hand
and
increase
the
d—c
current
until
the
seal-in
unit
operates.
It
should
pick
up
at
tap
value
or
sliohtly
lower.
Do
not
attempt
to
interrupt
the
d-c
current
by
means
of
the
M
1
contact.
If
it
is
necessary
to
change
the tap
setting
of
the
target
seal—in
unit
from
0.6
to
2
amps,
or
vice-
versa,
observe the
following procedure.
Assuming
the
tao
is
being
changed
from
0.6
to
24,
remove one
of
the
screws
from
the
1eft-hand
contact
strip
and
insert
it
into
the
2A
position
in
the
right-hand
strip,
being
sure
that
it
is
securely
tightened.
Then
remove
the
screw
from
the
0.64
position
and
insert
it
in
the
vacant
hole
in
the
left-hand
strip.
This
procedure
insures
that
the
contact
adjustment
of
the
unit
will
not
be
disturbed
while
the tap
setting
is
being
changed.
INSTALLATION
PROCEDURE
LOCATION
The
location
of
the
relay
should
be
clean
and
dry,
free
from
dust,
excessive
heat
and
vibration,
and
should
be
well
lighted
to
facilitate
inspection
and
testing.
MOUNTING
The
relay
should
be
mounted
on
a
vertical
surface.
The
outline
and
panel
drillinc
dimensions
are
shown
in
Fig.
15.
Connections
The
electrical
connections are
made
to
the
relay
by
studs
provided
at
the
rear
of
the
case.
An
ele
mentary diagram
of
typical
external
connections
is
shown
n
Figs.
l6A
and
16B.
Reach
settings
other
than the
basic
minimum
reach
can
be
set
by
reducing the
restraint
transftriser
taD
settings.
The
reach
with
reduced
transformer
settings
can
be
deteririned
Sy
the
following
equation.
17

GEK-26437
Zreiay
transf.seJng
x2
Z
(basic
reach
p-N)
Transf.
setting
(Z)
=
Z
(desired)
x
2
Z
(basic
reach
a-N)
Knowing
the
relay
reach
as
calculated
an
electrical
test
should
be
performed
in
order
to
determine
if
the
transformer
setting
is
correct.
1.
Connect
the
relay
per
Fig.
14.
2.
Set
the
phase
angle
meter
for
75
degrees
lag.
3.
Determine
the
current
to
operate
the
unit for
the
Z
setting
0-0
of
the
relay
by
using
the following
equations.
Voltage
@
75°
lag
(+)
1%
Check
one
additional
point
to
determine
if
the
angle of
maximum
torque
is
correct
by
checking
a
pickup
30
degrees
off
the
angle
of
maximum
torque.
=
Voltage
aPPli
3
g)
@
45°
or
105°
lag
(+)
3%
Refer to
the
section
on
SERVICING
if
any
adjustments
must
be
made
to
the
relay.
Before
any
adjustments
are
made
to
the
relay
with
a
transformer
setting
other
than
100
percent,
the
basic
unit
must
be
checked
first
for
the
basic
minimum
tap
used.
RENEWAL
PARTS
It
is
recon1)erlded
that
sufficient
quantities
of
renewal
parts
be
carried
in
5tock
to
enable
the
prompt
replacement
of
any
that
are
worn,
broken, or
damaged.
When
ordering
renewal
parts,
address the
nearest
Sales
Office of
the
General
Electric
Company,
specify
quantity
required,
name
of
the
part
wanted,
and
the
complete
model
number
of
the
relay
for
which
the
part
is
required.
18

TARGET
SEAL-
iNS
R63
GE
K-264
37
M2
OFFSET—
(TR-2)
—
M2
TRANSFORMER
Ml
TRANSFORMER
Ml
UN1T
Ml
REACH
TAPS
FIG.
1
(8042842)
FRONT
VIEW
OF
THE
12
GCY
RELAY
AND
CASE
Ml
M2
R12
R22
M2
UNIT
xli
19

;i—:i4.
/
Ml
TARGET
SEAL-
IN
Ml
OFFSET
M2
REACH
TAPS
Ml
TRANSFORMER
I
Ml
UNIT
V:E
OF
THE
12
CCV
RELAY
REMOVED
FROM
CASE
20
This manual suits for next models
2
Table of contents
Other GE Relay manuals