VOLTAGE RELAY PNM-32 INSTRUCTION MANUAL
Zakład Mechaniki i Elektroniki
ZAMEL sp.j.
J.W. Dzida, K. Łodzińska
ul. Zielona 27, 43-200 Pszczyna, Poland
Tel. +48 (32) 210 46 65, Fax +48 (32) 210 80 04
www.zamelcet.com, e-mail: [email protected]
CONNECTION
APPERANCE
MAIN RESET
MOUNTING
DIMENSIONS
PRODUCT FAMILY
The PNM-32 is a member of the PNM
product family.
1. Disconnect power supply by the pha-
se fuse, the circuit-breaker or the
switch- disconnector combined to the
proper circuit.
2. Check if there is no voltage on con-
nection cables by means of a spe-
cial measure equipment.
3. Install the PNM-32 on the TH-35 DIN
rail in the switchboard.
4. Connect the cables with the terminals
in accordance with the installing dia-
gram.
5. Switch on the power supply from the
mains.
WARRANTY CARD
INNER DIAGRAM
In order to cancel the circuit data and set de-
fault values it is necessary, in the main win-
dow, to press and hold simultaneously ( and
) keys for 3 seconds;
All display elds will be lighted;
The main window will be entered after a
while.
FUNCTIONING
After power supply switching on it is necessary to set maximum and minimum voltage, hy-
steresis, phase unbalance and the relay ON-time and OFF-time. If not, the following default
values will be set = 235 V, = 225 V, = 1 V, = 2 s, = 2 s, = 10 V. If all
phase voltages are greater or equal to 170 V, automatic phase sequence checking will start.
In case of incorrect phase sequence the output relay will be switched OFF ( ), the symbol
will be displayed: , and a message with info which phases are to be changed over in or-
der to set a correct phase sequence will be displayed too. If the phase sequence is correct,
the device will start displaying measured voltages in three-second cycles (see the gure)
and voltages controlling.
It is possible to toggle
between the phases by
pressing the cursors
which causes breaking
cyclic phase voltages
display (every 3 s) and
holding the set phase
display for 20 seconds.
If the voltages are in-
cluded within the set range ( , ), after time the relay will be ON ( ). Any voltage
threshold exceeding for the given phase will be signalled by displaying the following sym-
bol: for the minimum threshold and the symbol for the max voltage , and start
counting the time , and then will switch OFF the output relay ( ). If, during displaying
e.g. the L3 phase voltage, the L1 or L2 phase voltage falls below the voltage threshold ,
or exceeds the min , threshold, the device will toggle the phase value displayed actually
to the phase with the incorrect voltage value and will remain in this state until the wrong va-
lue disappears or the relay is OFF. Układ wykrywa również asymetrię napięcia. The device
is capable of detecting voltage unbalance. If the potential difference between the phases is
greater than , the display will show , and after time the relay will be OFF ( ).
L2
L1
L3
KLAW. LCD
μC
ZAS.
A/C
A/C
A/C
N
FEATURES
TECHNICAL DATA
DESCRIPTION
PNM-32
Power terminals: L1, L2, L3, N
Rated voltage: 230/400 V AC
Rated voltage tolerance: -15 ÷ +10 %
Rated frequency: 50 / 60 Hz
Rated current: 2 W / 14 VA
Measured voltage indicator: wyświetlacz LCD
Relay state and soft network indicator: wyświetlacz LCD
Voltage unbalance / phase sequence indicator: wyświetlacz LCD
Voltage threshold settings: klawiatura
Umin adjustment range: 170 ÷ 225 V
Umax adjustment range: 235 ÷ 290 V
Voltage hysteresis adjustment range: 1 ÷ 4 V
Unbalance level adjustment range: 10 ÷ 60 V
OFF-time toff:2 ÷ 15 s keyboard
ON-time ton:2 ÷ 15 s keyboard
Time setting accuracy: max ±1 s / 24 h at temp. 25 °C
Voltage measurement accuracy (50 Hz sinus): ±1,5 %*
Output relay parameters: 1NO/NC - 16 A / 250 V AC1 4000 VA
Number of terminal clamps: 12
Section of connecting cables: 0,2 ÷ 2,50 mm2
Ambient temperature range: -20 ÷ +60 oC
Operating position: freely
Mounting: rail TH 35 (PN-EN 60715)
Protection degree: IP20 (PN-EN 60529)
Protection level: II
Overvoltage category: II
Pollution degree: 2
Dimensions: double-modular (35 mm) 90x35x66 mm
Weight: 0,12 kg
Reference standards: PN-EN 60730-1; PN-EN 60730-2-1;
PN-EN 61000-4-2,3,4,5,6,11
* The PNM-32 device is not tted with the True RMS converter and therefore only 50 Hz sinusoidal voltages can be measured correctly;
if there are signicant harmonic distortions, the measurement result error may be serious.
● Three-phase load protection against
voltage swing and unbalance, and
incorrect phase sequence,
● Measured voltage state indicator,
● Relay state indicator,
● The device supplying with any phase,
● Minimum (170 ÷ 225 V) and maximum
(235 ÷ 290 V) voltage setting,
● OFF-time delay adjustment,
● Voltage control for each phase,
● Correct phase sequence control,
● Voltage unbalance control,
● Relay output - single changeover
contact, maximum load 16 A,
● Mounted on TH 35 rail.
The PNM-32 voltage relay is designed
for the three-phase system voltage con-
trol and load protection. It is possible
to set minimum and maximum voltage,
hysteresis, voltage unbalance and ON
/ OFF delay. The device is capable of
detecting voltage unbalance and phase
sequence. The LCD display and keybo-
ard enable easy parameters visualization
and programming.
The device is designed for
three-phase installation and
must be installed in accor-
dance with standards valid
in a particular country. The
device should be connec-
ted according to the details
included in this operating manual. Installa-
tion, connection and control should be car-
ried out by a qualied electrician staff, who
act in accordance with the service manual
and the device functions. Disassembling of
the device is equal with a loss of guarantee
and can cause electric shock. Before in-
stallation make sure the connection cables
are not under voltage. The cruciform head
screwdriver 3,5 mm should be used to in-
stal the device. Improper transport, storage,
and use of the device inuence its wrong
functioning. It is not advisable to instal the
device in the following cases: if any device
part is missing or the device is damaged or
deformed. In case of improper functioning
of the device contact the producer.
CAUTION
Values (voltage, time)
Information eld
Relay mode
Relay output terminals
(12, 11, 14)
Power / measure terminals
(L1, L2, L3)
Power terminal (N)
Display
Control buttons
VER. 001_14.09.2009
The symbol means selective
collecting of electrical and electronical
equipment. It is forbidden to put
the used equipment together
with other waste
Device version:
10 – single phase
31 – three-phase
32 – three-phase, LCD
Device type
There is 24 months guarantee on the product
Salesman stamp and signature, date of sale
1. ZMIE ZAMEL SP. J. assures 24 months guarantee for the product.
2. The manufacturer’s guarantee does not cover any of the following actions:
a) mechanical damage during transport, loading / unloading or under other circumstances,
b) damage caused by incorrect product mounting or misuse,
c) damage caused by unauthorised modications made by the PURCHASER or any third parties to the product or any other devices
needed for the product functioning,
d) damage caused by Act of God or any other incidents independent of the manufacturer.
3. The PURCHASER shall lay any claims in writing to the dealer or ZMIE ZAMEL SP. J.
4. ZMIE ZAMEL SP. J. is liable for processing any claim according to current Polish legislation.
5. ZMIE ZAMEL SP. J. shall process the claim at its own discretion: product repair, replacement or money return.
6. The manufacturer’s guarantee is valid in the Republic of Poland.
7. The PURCHASER’s statutory rights in any applicable legislation whether against the retailer arising from the purchase contract or
otherwise are not affected by this warranty.
DESCRIPTION
MAIN MENU
MAXIMUM AND MINIMUM THRESHOLD SETTING
VOLTAGE HYSTERESIS SETTING
ON-TIME AND OFF-TIME SETTING
UNBALANCE LEVEL SETTING
TIME DIAGRAMS AND MESSAGES
Description of displayed elds and messages
- relay state
- unbalance
, , - phase designator
, - change phase sequence
- wrong phase sequence, - Warning! Voltage measured greater than 300 V
Button description
• exit from the edition mode or menu;
• exit from the edition mode or menu;
• the main menu or submenu access (setting adjustment);
• for the main window - displayed phases changeover;
• the main menu navigation, parameter change in a submenu.
Press OK to enter menu from the main window;
menu scrolling by means of the cursors .
Function Description
MAX THRESHOLD SETTING
MIN THRESHOLD SETTING
VOLTAGE HYSTERESIS SETTING
ON-TIME SETTING
OFF-TIME SETTING
UNBALANCE LEVEL SETTING
PNM - 32
- maximum threshold setting, enter by pressing OK;
With cursors select maximum threshold value, setting range:
235÷290 V;
After pressing OK button, changes are saved and the main menu is entered,
where, with the left and right cursors it is possible to enter another menu
item or exit the menu by means of
or ;
- minimum threshold setting, enter by pressing OK;
With cursors select minimum threshold value, setting range: 170÷225 V;
After pressing OK button, changes are saved and the main menu is entered,
where, with the cursors it is possible to enter another menu item or exit
the menu by means of
or
.
It is possible to exit any submenu window at any moment, without setting
saving by means of pressing the keys or .
If you do not exit a submenu (and thus enter the main menu) during 15 seconds
after pressing any key, the measurement result display window will be entered
automatically without changes saved.
- voltage hysteresis setting;
With cursors select hysteresis value, setting range: 1÷4 V;
After pressing OK button, changes are saved and the main menu is entered,
where, with the cursors it is possible to enter another menu item or exit
the menu by means of
or
.
It is possible to exit any submenu window at any moment, without setting
saving by means of pressing the keys or .
If you do not exit a submenu (and thus enter the main menu) during 15 seconds
after pressing any key, the measurement result display window will be entered
automatically without changes saved.
Caution! Main menu access causes immediate relay switch OFF!
- relay ON-time setting, enter by pressing OK;
With cursors select time in seconds, setting range: 2÷15 s;
After pressing OK button, changes are saved and the main menu is entered,
where, with the cursors it is possible to enter another menu item or exit
the menu by means of
or ;
- relay OFF-time setting, enter by pressing OK;
With cursors select time in seconds, setting range: 2÷15 s;
After pressing OK button, changes are saved and the main menu is entered,
where, with the cursors it is possible to enter another menu item or exit
the menu by means of
or
.
It is possible to exit any submenu window at any moment, without setting
saving by means of pressing the keys or .
If you do not exit a submenu (and thus enter the main menu) during 15 seconds
after pressing any key, the measurement result display window will be entered
automatically without changes saved.
- unbalance level setting, enter by pressing OK;
With cursors select unbalance level value, setting range: 10÷60 V;
After pressing OK button, changes are saved and the main menu is entered,
where, with the cursors it is possible to enter another menu item or exit
the menu by means of
or
.
It is possible to exit any submenu window at any moment, without setting
saving by means of pressing the keys or .
If you do not exit a submenu (and thus enter the main menu) during 15 seconds
after pressing any key, the measurement result display window will be entered
automatically without changes saved.
t
11-14
toff
t
Umax
Umin
t
t
L2
L3
Umax
Umin
L1
Umax
Umin
Greater than
Umax
OK Less then
Umin
Incorrect phase
sequence
ton toff ton
Phase
unbalance
OK OK
Unbalance
toff
Hysteresis
Hysteresis
OK
ton

Other Zamel Relay manuals

Zamel EXTA PBM-03 User manual

Zamel

Zamel EXTA PBM-03 User manual

Zamel PCM-07/U User manual

Zamel

Zamel PCM-07/U User manual

Zamel Exta PBM-07 User manual

Zamel

Zamel Exta PBM-07 User manual

Zamel EXTA PCM-11 User manual

Zamel

Zamel EXTA PCM-11 User manual

Zamel EXTA PBM-02 User manual

Zamel

Zamel EXTA PBM-02 User manual

Zamel exta PB Series User manual

Zamel

Zamel exta PB Series User manual

Zamel exta PCM-01 User manual

Zamel

Zamel exta PCM-01 User manual

Zamel Exta PCM-02/U User manual

Zamel

Zamel Exta PCM-02/U User manual

Zamel PNM-10 User manual

Zamel

Zamel PNM-10 User manual

Zamel PCM-02/24V User manual

Zamel

Zamel PCM-02/24V User manual

Zamel exta PNM-10 User manual

Zamel

Zamel exta PNM-10 User manual

Zamel exta PCM-09 User manual

Zamel

Zamel exta PCM-09 User manual

Zamel EXT10000084 User manual

Zamel

Zamel EXT10000084 User manual

Zamel exta PBM-07 User manual

Zamel

Zamel exta PBM-07 User manual

Zamel exta PPM - 05 User manual

Zamel

Zamel exta PPM - 05 User manual

Zamel EXTA PBP-01 User manual

Zamel

Zamel EXTA PBP-01 User manual

Zamel PCM-04/24V User manual

Zamel

Zamel PCM-04/24V User manual

Zamel PCM-08 User manual

Zamel

Zamel PCM-08 User manual

Zamel Exta PBM-03 User manual

Zamel

Zamel Exta PBM-03 User manual

Zamel EXTA PCP-06 User manual

Zamel

Zamel EXTA PCP-06 User manual

Zamel EXTA PCP-04 User manual

Zamel

Zamel EXTA PCP-04 User manual

Zamel Exta PBM-04/U User manual

Zamel

Zamel Exta PBM-04/U User manual

Zamel PBM-01 User manual

Zamel

Zamel PBM-01 User manual

Popular Relay manuals by other brands

Pilz PNOZ X3.2 operating instructions

Pilz

Pilz PNOZ X3.2 operating instructions

Basler BE1-59NC instruction manual

Basler

Basler BE1-59NC instruction manual

CD Automation Revo Sx user manual

CD Automation

CD Automation Revo Sx user manual

LEGRAND LEXIC 0047 43 manual

LEGRAND

LEGRAND LEXIC 0047 43 manual

Thytronic NA20 manual

Thytronic

Thytronic NA20 manual

nodon DRB-1-1-00 user guide

nodon

nodon DRB-1-1-00 user guide

Ei Electronics RadioLINK Relay Module Ei428 instruction manual

Ei Electronics

Ei Electronics RadioLINK Relay Module Ei428 instruction manual

Stahl ISPAC 9172 11 00 Series operating instructions

Stahl

Stahl ISPAC 9172 11 00 Series operating instructions

Siemens SIRIUS 3TK2840 operating instructions

Siemens

Siemens SIRIUS 3TK2840 operating instructions

Omron G7SA datasheet

Omron

Omron G7SA datasheet

ABB SPAD 330 C manual

ABB

ABB SPAD 330 C manual

Omron K8DT-AW Series manual

Omron

Omron K8DT-AW Series manual

Elko CRM-82TO quick start guide

Elko

Elko CRM-82TO quick start guide

Entes DG-10 quick start guide

Entes

Entes DG-10 quick start guide

GE ICR51A instructions

GE

GE ICR51A instructions

Zander Aachen SR3E operating instructions

Zander Aachen

Zander Aachen SR3E operating instructions

Omega Engineering DPA1004 user guide

Omega Engineering

Omega Engineering DPA1004 user guide

F&F BIS-413M manual

F&F

F&F BIS-413M manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.