1
11
1
XXXXXX
P
Type: P9625
Type: P9625Type: P9625
Type: P9625
Definite Time (DT)
Definite Time (DT)Definite Time (DT)
Definite Time (DT) Overcurrent
Overcurrent Overcurrent
Overcurrent Relay
Relay Relay
Relay
True R.M.S. measurements
Individual Trip Level adjustment for each phase
Adjustable Delay setting
Test and Reset button for simulating and clearing of fault condition
Red L D indication of which phase has been triggered
Red L D indication of actual tripped condition
Green L D indication for Auxiliary power supply presence
Microprocessor based (self checking) with non-volatile memory
Terminals suitable for 2 x 2.5mm
2
wires (complete with protective cover)
•G N RAL OV RVI W
The P9625 (from the P9600 series family of IDMT/DT relays) is a micro rocessor based relay
designed to monitor and detect Overcurrents in 3- hase a lications. Ty ically the P9625 is
wired in conjunction with external current transformers (1 er hase) of the feeder to be
rotected.
The adjustments and indicators are laid out such to hel the user during set-u and fault
finding. The adjustment for the L
LL
L1 (R)
1 (R) 1 (R)
1 (R) for exam le has its corres onding red LED ositioned
above it so it is clear as to which hase this LED relates to. Adjustment and LED o eration is
ex lained further on the next age.
The adjustment for the Delay
Delay Delay
Delay is a global adjustment that is connected with any one hase that
exceeds the set threshold and delays the relay from energising.
A Test mode is rovided (also accessible with the tam er roof trans arent cover closed) to
confirm the correct o eration of the internal relay. The relay will energise when the “T ST”
button is ressed and de-energise when the “R S T” button is ressed.
•OP RATION
When an Overcurrent occurs in one of the hases and the level of
current exceeds the tri threshold, the corres onding red LED above
the adjustment illuminates. The time out then commences and the
relay energises after the delay has run. The red “Tri ”
“Tri ”“Tri ”
“Tri ” LED will then
flash indicating a tri ed condition.
If the fault current has been removed, ressing the “R S T” button
will return the relay back to normal o eration. The red LED’s will then
extinguish.
In the event of an Overcurrent condition, the basic sequence of
events is shown below.
•PR S NTATION
1. “Phase” tri adjustment* 5. “Trip” red LED indication
2. “Phase” tri level exceeded red LED indication 6. “T ST” button
3. “Power supply” green LED indication 7. “R S T” button
4. “Delay” adjustment*
* accessible only when the front cover is o en
START
OVERCURRENT
occurs
Corres onding
LED illuminates
Time out
commences
Timeout
com lete?
N
Y
TRIP!
Dims:
W x H. 96 x 96mm (front)
W x H. 89.5 x 89.5mm (main body)
L. 107mm

Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. ngland
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 mail: [email protected] Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk
.
P9625-2-A
2
22
2
XXXXXX
P
•S TTING & OP RATION
Setting of the P9625 is carried out using the 4 otentiometers located behind the
trans arent cover.
1. Delay
The adjustment for “Delay” defines the delay eriod
between exceeding a tri threshold on any of the hases
and the relay energising.
The delay can be set from 50mS to 1.0s.
2. Trip threshold
Individual adjustments for the tri threshold allow
the user to set each hase inde endently of each other.
When the threshold is exceeded on any hase due to
an Overcurrent condition, the corres onding red LED
above the adjustment illuminates indicating activity.
When tri ing finally occurs, the red “Tri ”
“Tri ”“Tri ”
“Tri ” LED will
then flash.
In res onse to an Overcurrent condition (on any hase):
Status Phase L D* Trip
Normal
Phase triggered
Tri ed
In res onse to Test and Reset button o eration:
Button press Phase L D* Trip
* Can be L1(R), L2 (S) or L3(T)
Key:
LED off
LED on
LED flashing
•INSTALLATION
•B FOR INSTALLATION, ISOLAT TH SUPPLY. THIS PRODUCT IS
D SIGN D TO CONN CT TO S V RAL TYP S OF CIRCUITS.
NSUR ALL AR ISOLAT D
•Remove the P9625 from the ackaging.
•Lift the raised art of the side cli in order to remove from the housing. Carry
this out on each side.
•Insert the P9625 into the anel cut-out and fit the side cli s back on to the
housing.
•Slide the cli s towards the front of the unit until they come in to contact with
the reverse of the anel. The unit is now secured in lace.
•Connect wires to the rear terminals as required.
•The P9625 is now ready for owering and setting.
The front window of the P9625 is supplied with a clear protective film which can be
removed as and when necessary.
•NORMAL OP RATION
•A ly ower to the unit and the green “Power supply” LED will illuminate.
•T ST MOD
•Press and hold the button and the relay will energise after the delay
eriod. All red LED’s will illuminate.
•Release the button, the relay will remain energised and all red LED’s lit.
•Press the button to de-energise the relay. All red LED’s will extinguish.
Testing should be carried out on a regular basis to check the integrity of the
P9625.
D N T use this product to provide a means of isolating circuits in
order to work on when placed in the “TEST”
“TEST”“TEST”
“TEST” mode. This should only be
done by means of operating isolators, circuit breakers or other
methods of removing power in this application.
Installation work must be carried
out by qualified personnel.

Broyce Control Ltd., Pool Street, Wolverhampton, West Midlands WV2 4HN. ngland
Tel: +44 (0) 1902 773746 Fax: +44 (0) 1902 420639 mail: [email protected] Web: www.broycecontrol.com
The information provided in this literature is believed to be accurate (subject to change without prior notice); however, use of such information shall be entirely at the user’s own risk
.
P9625-2-A
3
33
3
XXXXXX
P
Housing:
Flame retardant Lexan
Protection: IP55 / IP20 (rear)
Weight: ≈ 590g
Mounting: Panel mounting. Cut-out = 91 x 91mm (± 0.5mm)
Max. anel thickness: 12mm
Terminal conductor size: 0.05 - 2.5mm
2
(30 - 12AWG)
Recommended tightening
torque: 10in lb (1Nm)
Wire stri ing length: 0.24 – 0.30in (6 – 7.5mm)
A rovals: Conforms to IEC. CE and and RoHS Com liant.
EMC: Immunity: EN/IEC 61000-6-2
Emissions: EN/IEC 61000-6-4
Generic: IEC 60255-26 (EMC), IEC 255-3, IEC
60255-151
( ) Bold digits in brackets refer to terminal numbers on the rear of the unit.
Options:
The P9600 range also includes individual Overcurrent or Earth fault relays
available with either IDT or IDMT tri ing characteristics. Please refer to se arate
data sheets.
•T CHNICAL SP CIFICATION
Su ly voltage Un (1, 2): 115VAC ±15%
230VAC ±15%
(Voltage should be specified at time of ordering)
Rated frequency: 50/60Hz
Isolation: Over voltage cat. III
Rated im ulse
withstand voltage: 4kV (1.2 / 50µS) IEC 60664
Power consum tion: 3W max.
Rated current in ut In: 5A (directly connected)
Rated frequency: 50Hz
Burden: <0.4VA @ In
Overload: 4 x In (continuous)
External CT’s
(9, 10, 11, 12, 13, 14): Class P recommended. (with 5A secondary)
Overcurrent settings:
Tri threshold: 2.0 – 6.0A (40 – 120%)
Time Delay: 0.05 – 1.0s
Pick u value: +2% of tri setting
Accuracy:
Protection thresholds: ± 5%
Res onse time: ± 5% (with a minimum of 50mS)
Re eat accuracy: ± 0.5% @ constant conditions
Ambient tem erature: -10 to +60°C
Relative humidity: +95% (non-condensing)
Out ut:
(RL1 - 3, 4, 5): 1 x SPDT relay
Out ut rating: AC1 250V 8A (2000VA)
AC15 250V 5A (1250VA)
DC1 25V 8A (200W)
Electrical life: ≥ 150,000 o s at rated load
Dielectric voltage: 2kV AC (rms) IEC 60947-1
Rated im ulse
withstand voltage: 4kV (1.2 / 50µS) IEC 60664
Max. DC Load Breaking Ca acity Electrical Endurance
•CONN CTION DIAGRAM
L1
L2
L3
N
A1
A2
RL1
Aux.
911
10
12
13
14
15
16
1
3
2
4
5
6
7
8
I
L1
I
L2
I
L3
•DIM NSIONS
96
96
10
95
89.5
96
12
80
Front view Side view
All dimensions are in mm.
Other Broyce Control Relay manuals

Broyce Control
Broyce Control P9660 User manual

Broyce Control
Broyce Control P9690 User manual

Broyce Control
Broyce Control P50EFR User manual

Broyce Control
Broyce Control ELR01PN User manual

Broyce Control
Broyce Control P9620 User manual

Broyce Control
Broyce Control P9650 User manual

Broyce Control
Broyce Control P50ELR Series User manual

Broyce Control
Broyce Control P9600 Series User manual

Broyce Control
Broyce Control ELRV-30 User manual

Broyce Control
Broyce Control ELRV-30 User manual