manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. GE
  6. •
  7. Relay
  8. •
  9. GE SAM201 User manual

GE SAM201 User manual

GEK
-
90666
D
INSTRUCTIONS
Static
Timing
Relays
SAM
201
SAM
202
SAM
203
SAM
204
SAM
205
SAM
206
SAM
207
Static
RANGE
TU
2
SECONDS
MULTIPLIER
Timing
Relay
l
2
*
$
f
3
20
40
SO
0
01
01
10
B
>
p
TWIG
|
p
|
TA
MTtHQS
»
*
PA
ijffl
Static
Timing
Relay
RATINGS
«
NA
AS
/
UO
/
U
5
.
'
Z
»
'
250
VOC
RANGE
MULTIPLIER
0
010
!
10
MODEL
SAM
20
CALA
TU
SECONDS
1
2
«
S
10
2
C
-
4
e
?
0
r
nr
r
r
r
r
,
q
i
±
r
~
i
i
i
i
J
1
J
J
INSTRUCTION
BOOK
CEIW
06
G
*
PARTS
BULLETIN
GEM
065
METER
AND
CONTROL
IN
.
M
*
-
.
£
*
GE
Protection
and
Control
205
Great
Valley
Parkway
Malvern
,
PA
19355
-
1337
Courtesy of NationalSwitchgear.com
GEK
-
90666
CONTENTS
Page
3
Description
Application
Specifications
DC
control
voltage
Settings
Accuracy
Overshoot
Ride
-
Thru
Time
Environmental
3
5
5
5
5
5
5
5
Ratings
Burden
Contacts
Target
6
6
6
6
6
Settings
Displays
Functional
Description
Construction
Receiving
,
Handling
and
Storage
Acceptance
Tests
General
Visual
Test
Equipment
General
Testing
Consideration
Tests
7
7
8
8
8
8
8
9
9
9
Timing
test
Target
test
Procedure
Surge
ground
Electrical
tests
Settings
Periodic
checks
and
routine
maintenance
Servicing
Renewal
parts
Trouble
shooting
Timer
Board
Functional
Description
Problems
and
Solutions
List
of
Figures
10
10
Installation
10
10
11
11
11
11
12
14
15
16
17
Cover
photos
(
8043819
,
820
,
820
)
These
instructions
do
not
purport
to
cover
all
details
or
variations
in
equipment
nor
to
provide
for
every
possible
contingency
to
be
met
in
connection
with
installation
,
operation
or
maintenance
.
Should
further
information
be
desired
or
should
particular
problems
arise
which
are
not
covered
sufficiently
for
the
purchaser
’
s
purposes
,
the
matter
should
be
referred
to
the
General
Electric
Company
.
To
the
extent
required
the
products
described
herein
meet
applicable
ANSI
,
IEEE
and
NEMA
standards
,
but
no
such
assurance
is
given
with
respect
to
local
codes
and
ordinances
because
they
vary
greatly
.
-
2
-
Courtesy of NationalSwitchgear.com
GEK
-
90666
STATIC
TIMING
RELAYS
TYPE
SAM
201
,
202
,
203
,
204
,
205
,
206
&
207
DESCRIPTION
The
SAM
200
relays
provide
accurate
and
repeatable
timing
functions
that
produce
a
contact
closure
after
a
selected
time
delay
has
expired
.
The
time
-
delay
settings
are
made
using
toggle
switches
mounted
on
the
front
plate
of
the
relay
,
as
explained
in
the
SETTINGS
section
.
The
total
time
delay
consists
of
the
set
time
delay
added
to
tne
o
operating
time
of
the
output
relay
,
typically
2
-
6
millisecon
significant
at
the
low
end
of
the
time
-
aelay
setting
range
.
iperating
time
of
the
output
relay
.
The
as
as
shown
in
Figure
39
,
will
only
be
Table
I
summarizes
the
models
available
.
Table
I
Timing
Trip
Functions
Targets
Case
Model
Size
TA
&
TB
201
SI
TU
NONE
SI
TU
202
TU
2
&
TU
3
TA
&
TB
203
SI
TU
2
&
TU
3
NONE
204
SI
TU
T
1
&
T
2
205
SI
TU
2
&
TU
3
T
1
,
T
2
&
T
3
NONE
206
SI
TU
207
S
2
External
connection
diagrams
for
the
above
models
are
shown
in
Figures
1
through
7
.
APPLICATION
The
SAM
200
relays
are
applied
wherever
accurate
and
repeatable
timing
functions
are
required
.
The
basic
timing
function
is
the
same
for
all
models
or
the
SAM
200
family
,
but
each
model
is
different
based
on
the
number
of
timing
functions
present
,
the
presence
or
absence
of
targets
,
and
the
contact
arrangement
.
This
differentiation
makes
certain
models
more
suited
for
specific
applications
.
Table
II
on
the
next
page
lists
the
models
and
their
recommended
applications
.
-
3
-
Courtesy of NationalSwitchgear.com
GEK
-
90666
TABLE
II
SAM
201
General
purpose
General
purpose
2
zone
step
distance
schemes
for
line
protection
using
zone
-
packaged
distance
relays
SAM
202
SAM
203
General
purpose
3
zone
step
distance
schemes
for
line
protection
SAM
204
3
zone
step
distance
schemes
for
line
protection
using
zone
-
packaged
distance
relays
SAM
205
2
zone
step
distance
schemes
for
line
protection
using
phase
-
packaged
distance
relays
3
zone
step
distance
schemes
for
line
protection
using
phase
-
packaged
distance
relays
SAM
206
SAM
207
General
purpose
The
application
category
"
general
purpose
"
in
Table
II
includes
use
of
the
appropriate
SAM
200
relay
for
the
timing
function
associated
with
local
breaker
-
failure
backup
schemes
.
The
term
"
phase
-
packaged
"
refers
to
component
distance
relays
where
the
measuring
units
for
all
required
zones
associated
with
one
phase
or
phase
-
pair
are
included
in
one
relay
case
.
An
example
of
a
phase
-
packaged
distance
relay
is
the
GCY
51
A
.
The
term
"
zone
-
packaged
"
refers
to
component
distance
relays
where
the
measuring
units
for
all
3
phases
or
phase
-
pairs
associated
with
one
zone
are
included
in
one
relay
case
.
An
example
of
a
zone
-
packaged
distance
relay
is
the
CEY
52
A
.
Fi
gure
40
shows
the
SAM
202
relay
used
in
a
breaker
-
failure
scheme
.
Figure
41
shows
a
SAM
202
used
in
a
2
zone
step
distance
scheme
with
CEY
and
CEB
distance
relays
.
Figure
42
shows
a
SAM
204
used
in
a
3
zone
step
distance
scheme
with
CEY
and
CEB
distance
relays
.
Figure
43
shows
a
SAM
206
used
in
a
3
zone
step
distance
scheme
with
GCY
51
distance
relays
.
-
4
-
Courtesy of NationalSwitchgear.com
GEK
-
90666
SPECIFICATIONS
DC
Control
Voltage
Nominal
48
,
110
,
125
,
220
,
250
Minimum
37
Volts
Maximum
280
Volts
Settings
Timin
ft
ange
Multiplier
:
0.01
Recommended
Timing
Range
:
0.03
to
0.99
seconds
in
0.01
second
steps
Repeatability
:
±
1.5
%
Range
Multiplier
:
0.1
Recommended
Timing
Range
Repeatability
:
±
0.75
%
Range
Multiplier
:
1.0
Recommended
Timing
Range
Repeatability
:
±
0.25
%
:
0.10
to
9.90
seconds
in
0.10
second
steps
:
1.0
to
99.0
seconds
in
1.00
second
steps
Accuracy
±
3
msec
.
or
±
3
%
of
selected
setting
,
whichever
is
greater
.
Overshoot
(
Overtravel
)
5
msec
.
(
Relative
to
the
actual
measured
time
.
)
Ride
-
Thru
Time
Ride
-
Thru
time
is
defined
as
the
ability
of
the
SAM
Relay
to
operate
properly
when
it
is
energized
by
an
initiating
pulse
of
250
>
xsec
followed
by
an
off
time
of
3
msec
.
after
which
a
continuous
signal
is
applied
until
the
relay
operates
.
3
msec
.
Reset
Time
When
the
relay
is
timing
out
,
but
not
picked
up
,
the
reset
time
is
9
mSec
.
When
the
relay
has
timed
out
,
and
is
picked
up
,
the
reset
time
is
3
mSec
.
Environmental
Operating
-
20
°
C
to
+
65
°
C
95
%
relative
humidity
(
noncondensing
)
Storage
-
40
°
C
to
+
75
°
C
95
%
relative
humidity
(
noncondensing
)
Surge
ANSI
C
37.90
(
SWC
and
Fast
Transient
)
GERFI
IEC
255
-
5
-
Courtesy of NationalSwitchgear.com
GEK
-
90666
RATINGS
Burden
Table
III
Power
Su
ipply
B
DC
WATTS
urden
Model
125
250
48
201
,
202
&
205
1.1
3.0
6.3
203
2.3
6.3
13.5
204
&
206
1.8
4.7
9.8
207
2.4
6.5
13.9
Contact
ratings
Make
and
carry
30
amps
for
1
second
.
Trip
rated
per
ANSI
C
37.90
.
Break
50
VA
resistive
,
25
VA
inductive
(
L
/
R
=
40
msec
.
)
at
125
/
250
VDC
.
Target
ratings
The
operate
level
of
a
target
unit
is
150
ma
,
with
less
than
2.0
volt
drop
at
30
amps
.
30
Amps
for
1
sec
.
,
5
Amps
continuous
,
both
with
diode
bridge
.
SETTINGS
The
following
settings
,
which
must
be
set
in
each
application
,
are
made
from
the
front
of
the
relay
without
the
need
for
pulling
boards
or
removing
the
nameplate
.
It
is
only
necessary
to
remove
the
front
cover
from
the
relay
.
"
TU
"
or
"
TU
2
"
&
"
TU
3
"
Seconds
An
eight
-
position
toggle
switch
(
es
)
,
in
conjunction
with
the
Range
Multiplier
switch
,
is
used
to
select
the
desired
output
delay
setting
.
The
setting
is
equal
to
the
sum
of
tne
switch
segments
that
are
set
in
the
UP
position
.
Refer
to
the
Specification
section
,
under
Settings
,
for
the
recommended
timing
ranges
.
Note
:
a
default
setting
of
1
will
be
selected
if
all
of
the
switch
segments
are
set
in
the
DOWN
position
.
Range
Multiplier
A
three
-
position
slide
switch
,
in
conjunction
with
the
"
TU
"
or
"
TU
2
"
&
"
TU
3
"
Seconds
toggle
switches
,
is
used
to
select
the
desired
multiplication
factor
.
Positioning
the
switch
to
its
extreme
left
position
,
the
multiplication
factor
of
0.01
is
selected
.
With
the
switch
positioned
to
its
mid
position
,
the
0.1
multiplication
factor
is
selected
.
Finally
,
the
multiplication
factor
of
1.0
is
selected
when
the
switch
is
m
its
extreme
right
position
.
-
6
-
Courtesy of NationalSwitchgear.com
GEK
-
90666
DISPLAYS
Trip
Targets
The
trip
indicators
are
electro
-
mechanical
devices
and
depending
on
the
relay
model
they
TA
&
TB
"
,
'
T
1
&
T
2
"
or
'
Tl
,
T
2
&
T
3
"
.
They
will
operate
when
the
current
flowing
through
their
coils
is
over
150
ma
.
When
activated
,
they
will
indicate
a
red
block
through
windows
located
on
the
relay
'
s
nameplate
.
The
targets
are
reset
by
pushing
up
on
the
reset
rod
,
which
is
located
on
the
bottom
left
hand
corner
of
the
front
cover
.
Table
I
is
a
list
of
the
relay
models
that
shows
which
are
equipped
with
targets
and
identifies
the
targets
that
are
provided
in
those
models
.
are
labeled
FUNCTIONAL
DESCRIPTION
The
SAM
relay
provides
the
following
basic
functions
:
regulation
,
timing
,
output
and
display
.
A
generic
block
diagram
for
the
SAM
relays
is
found
in
Figure
8
and
the
internal
-
connection
diagrams
for
each
of
the
models
can
be
found
in
Figures
9
thru
15
.
Regulation
The
input
power
is
regulated
by
a
series
-
pass
Darlington
transistor
pair
that
provides
the
6
and
12
VDC
supplies
that
are
required
by
the
various
circuits
on
the
timer
board
.
Timing
The
timing
circuits
are
driven
by
an
oscillator
circuit
that
is
tuned
to
2
kHz
.
The
oscillator
circuit
clocks
binary
counters
whose
outputs
become
the
clock
signals
for
BCD
counters
.
At
the
end
of
the
desired
timing
interval
,
the
BCD
counters
provide
the
input
signal
for
the
output
driver
circuits
through
the
JK
Flip
-
Flop
and
Multivibrator
circuits
.
Output
Each
driver
circuit
is
capable
of
energizing
one
output
relay
.
The
coil
of
the
output
relay
is
connected
in
series
with
the
power
source
and
tne
collector
of
the
drive
transistor
.
The
output
relay
contacts
consist
of
normally
open
(
NO
)
contacts
,
and
in
some
models
normally
closed
(
NC
)
contacts
.
These
contacts
will
change
state
when
the
output
relay
is
energized
.
The
operating
time
of
the
output
relay
,
which
must
be
considered
when
selecting
the
desired
setting
of
the
SAM
relay
,
will
vary
depending
on
the
voltage
that
is
applied
to
the
relay
.
Figure
39
shows
typical
operating
time
of
tne
output
relay
with
respect
to
the
applied
voltage
.
Display
Some
of
the
SAM
models
provide
targets
that
are
connected
in
series
with
the
normally
open
contacts
of
the
output
relay
.
The
targets
will
be
energized
when
trip
current
flows
through
their
coils
.
-
7
-
Courtesy of NationalSwitchgear.com
GEK
-
90666
CONSTRUCTION
The
components
of
the
relay
are
mounted
on
a
cradle
assembly
that
can
easily
be
removed
from
the
relay
case
,
refer
to
Figures
32
thru
35
.
The
cradle
is
locked
in
the
case
by
latches
at
the
top
and
bottom
.
The
electrical
connections
between
the
case
blocks
and
the
cradle
blocks
are
completed
through
removable
connection
plug
(
s
)
,
as
shown
in
Figure
27
,
to
permit
testing
the
relay
in
its
case
.
The
cover
is
attached
to
the
front
of
the
case
and
includes
two
interlocking
arms
that
prevent
the
cover
from
being
replaced
until
the
connection
plug
(
s
)
has
been
inserted
.
The
case
is
suitable
for
semi
-
flush
mounting
on
panels
.
Hardware
is
available
for
all
panel
thicknesses
up
to
two
inches
.
A
panel
thickness
of
1
/
8
inch
will
be
assumed
unless
otherwise
specified
on
the
order
.
Outline
and
panel
drilling
dimensions
for
the
SAM
201
through
SAM
206
are
shown
in
Figure
16
and
for
the
SAM
207
they
are
shown
in
Figure
17
.
The
printed
-
circuit
board
(
s
)
are
mounted
behind
the
nameplate
and
can
be
accessed
by
removing
the
four
screws
securing
the
nameplate
.
The
boards
are
mounted
horizontally
in
guides
.
Each
board
is
labeled
to
correspond
to
a
given
location
.
Use
GE
part
number
0286
A
2847
rl
card
puller
or
other
suitable
means
to
remove
the
circuit
boards
.
If
you
do
not
have
a
card
puller
,
be
careful
not
to
damage
or
bend
any
components
when
removing
the
boards
.
A
card
puller
can
be
obtained
by
contacting
the
factory
.
The
output
relays
are
mounted
in
sockets
on
a
board
fixed
to
the
back
of
the
cradle
.
If
a
relay
requires
replacement
,
unclip
the
retaining
wire
and
pull
the
relay
out
of
the
socket
.
The
target
assembly
,
when
provided
,
is
mounted
on
the
bottom
plate
of
the
relay
cradle
.
RECEIVING
,
HANDLING
and
STORAGE
These
relays
,
when
not
included
as
part
of
a
control
panel
,
will
be
shipped
in
cartons
designed
to
protect
them
against
damage
.
Immediately
upon
receipt
of
a
relay
examine
it
for
any
damage
sustained
in
transit
.
If
damage
resulting
from
handling
is
evident
,
file
a
damage
claim
at
once
with
the
transportation
company
and
promptly
notify
the
nearest
General
Electric
Sales
Office
.
If
the
relays
are
not
to
be
installed
immediately
,
they
should
be
stored
in
their
original
cartons
in
a
place
that
is
free
from
moisture
,
dust
and
metallic
chips
.
ACCEPTANCE
TESTS
General
The
relay
should
be
examined
and
tested
upon
delivery
to
make
sure
that
no
damage
has
been
sustained
in
shipment
and
that
the
relay
is
functioning
correctly
.
Visual
Remove
the
relay
from
its
case
and
check
for
signs
of
physical
damage
such
as
broken
or
cracked
parts
.
-
8
-
Courtesy of NationalSwitchgear.com
GEK
-
90666
CAUTION
Every
circuit
in
the
drawout
case
has
an
auxiliary
brush
.
It
is
especially
important
on
circuits
with
shorting
bars
that
the
auxiliary
brush
be
bent
high
enough
to
engage
the
connecting
plug
or
test
plug
before
the
main
brushes
do
.
This
will
prevent
the
secondary
circuits
from
being
open
-
circuited
during
insertion
of
the
connection
plug
.
A
drawout
case
relay
may
be
tested
without
removing
it
from
the
panel
,
by
using
a
12
XLA
13
A
test
plug
.
This
plug
makes
connection
to
the
relay
only
and
does
not
disturb
any
shorting
bars
in
the
case
.
The
12
XLA
12
A
test
plug
may
also
be
used
.
Although
this
plug
allows
greater
flexibility
,
it
requires
shorting
jumpers
since
connections
are
made
to
both
the
relay
and
the
external
circuits
.
Test
Equipment
DC
voltage
source
rated
at
48
V
with
less
than
5
%
ripple
Universal
Counter
with
two
independent
channels
Limiting
resistors
for
timing
and
target
tests
,
300
H
/
10
W
SPST
switch
,
for
applying
and
removing
power
to
the
relay
Snubber
circuit
to
minimize
noise
due
to
the
closure
of
the
DC
source
switch
.
Resistor
,
220
O
/
2
W
and
a
capacitor
,
3.3
Mfd
/
450
VDC
.
Note
:
Observe
the
polarity
markings
,
if
an
electrolytic
capacitor
is
used
in
the
test
circuit
.
1
.
2
.
3
.
4
.
5
.
General
Testing
Considerations
CAUTION
In
the
event
that
the
relay
is
tested
with
high
voltage
,
280
VDC
,
and
in
a
temperature
environment
of
greater
than
40
°
C
,
care
must
be
taken
so
that
the
relay
is
not
left
energized
for
a
period
exceeding
five
times
its
maximum
time
setting
.
Failure
to
observe
this
caution
will
damage
the
relay
.
The
relay
can
be
tested
by
using
one
or
two
simple
tests
.
These
tests
are
the
Timing
test
,
and
for
those
models
that
are
equipped
with
targets
,
the
Target
test
.
The
timing
test
procedures
are
similar
for
all
relay
models
;
the
target
test
procedures
are
similar
for
all
relay
models
that
include
targets
.
All
tests
should
be
made
with
the
relay
in
its
case
and
in
a
reasonably
level
position
.
Tests
For
the
following
tests
refer
to
Figures
18
thru
26
for
test
connections
,
and
to
Figure
29
,
30
and
31
for
front
views
of
several
relay
models
.
-
9
-
Courtesy of NationalSwitchgear.com
GEK
-
90666
Timing
Test
1
.
Connect
the
SAM
relay
to
be
tested
as
per
the
appropriate
timing
test
connections
diagram
,
Figures
18
thru
22
.
2
.
Set
the
"
TU
"
or
"
TU
2
"
&
"
TU
3
"
SECONDS
switch
segment
labeled
"
2
"
to
the
UP
position
.
All
other
switch
segments
must
be
set
to
the
DOWN
position
.
3
.
Set
the
RANGE
MULTIPLIER
switch
to
"
1.0
"
.
4
.
Set
the
DC
Power
supply
to
48
volts
.
5
.
Apply
the
48
VDC
to
the
relay
by
closing
switch
"
SI
"
.
Note
:
in
order
for
the
timing
circuits
to
function
correctly
,
the
DC
voltage
must
be
suddenly
applied
to
the
relay
.
6
.
Check
that
the
output
relay
has
picked
up
between
1.94
and
2.06
seconds
,
as
indicated
by
the
universal
counter
(
s
)
.
Target
Test
1
.
Connect
the
SAM
relay
to
be
tested
as
per
the
appropriate
target
test
connections
diagram
Figures
23
thru
26
.
2
.
Set
all
of
the
"
TU
"
or
"
TU
2
"
&
"
TU
3
"
SECONDS
switch
segments
to
the
DOWN
position
.
3
.
Set
the
RANGE
MULTIPLIER
switch
to
"
1.0
"
.
4
.
Set
the
DC
Power
supply
to
48
volts
.
5
.
Apply
the
48
VDC
to
the
relay
by
closing
switch
"
SI
"
.
6
.
Check
that
the
correct
target
has
picked
up
.
End
Of
Acceptance
Testing
INSTALLATION
PROCEDURE
The
relay
should
be
installed
in
a
clean
,
dry
location
,
free
from
dust
and
excessive
vibration
.
It
should
be
mounted
on
a
vertical
surface
.
The
outline
and
panel
-
drilling
dimensions
are
shown
in
Figures
16
and
17
.
Surge
ground
The
case
stud
should
be
permanently
connected
to
ground
by
a
conductor
not
less
than
AWG
No
.
12
copper
wire
or
equivalent
.
This
connection
is
made
to
ground
the
relay
case
and
the
surge
suppression
networks
in
the
relay
.
The
surge
ground
lead
should
be
as
short
as
possible
,
preferably
10
inches
or
less
,
to
provide
maximum
protection
from
surges
.
Figures
37
and
38
show
the
rear
view
of
an
SI
and
an
S
2
case
,
respectively
,
illustrating
the
position
of
the
case
grounding
stud
.
-
10
-
Courtesy of NationalSwitchgear.com
GEK
-
90666
Electrical
tests
The
test
given
in
the
Acceptance
Section
can
be
used
as
a
guide
in
the
establishment
of
your
procedure
.
Settings
Set
the
timing
circuit
(
s
)
for
the
operating
time
required
by
the
particular
application
.
The
setting
is
equal
to
the
sum
of
the
"
TU
"
,
"
TU
2
"
or
"
TU
3
"
SECONDS
switch
segments
that
are
set
in
the
UP
position
,
multiplied
by
the
setting
of
the
Range
Multiplier
switch
.
The
recommended
timing
ranges
are
listed
in
the
Specification
section
of
this
manual
,
under
Settings
.
Time
PERIODIC
CHECKS
and
ROUTINE
MAINTENANCE
Considering
the
vital
role
of
protective
relays
in
the
operation
of
a
power
system
,
it
is
important
that
a
periodic
test
program
be
followed
.
It
is
recognized
that
the
interval
between
periodic
checks
will
vary
depending
upon
environment
,
type
of
relay
,
and
the
users
'
experience
with
periodic
testing
.
Until
the
users
have
accumulated
enough
experience
to
select
the
test
interval
best
suited
to
their
individual
requirements
,
it
is
suggested
that
the
points
listed
under
Acceptance
Tests
be
checked
at
an
interval
of
from
one
to
two
years
.
The
procedure
outlined
under
Acceptance
Tests
can
be
followed
.
SERVICING
CAUTION
REMOVE
ALL
power
from
relay
before
removing
or
inserting
any
of
the
printed
-
circuit
boards
or
output
relays
.
Failure
to
observe
this
caution
may
result
in
damage
to
and
/
or
misoperation
of
the
relay
.
There
are
two
basic
approaches
that
may
be
followed
in
servicing
the
SAM
relay
.
One
approach
is
field
service
,
where
an
attempt
is
made
to
replace
defective
components
at
the
relay
location
.
Generally
,
this
will
take
the
most
time
and
require
the
highest
degree
of
skill
ana
understanding
.
It
can
also
be
expected
to
result
in
the
longest
system
-
outage
time
.
The
preferred
approach
is
board
replacement
,
where
a
determination
is
made
as
to
which
printed
-
circuit
board
has
failed
and
that
board
is
replaced
with
a
spare
board
.
The
system
can
quickly
returned
to
service
.
Considerable
time
is
saved
and
there
is
much
less
pressure
to
make
a
decision
about
what
to
do
with
the
defective
part
.
This
approach
typically
yields
the
shortest
down
time
.
It
is
recommended
that
a
complete
set
of
spare
printed
-
circuit
board
be
kept
at
the
main
maintenance
center
.
For
those
who
wish
to
repair
at
the
component
level
,
drawings
are
available
from
the
factory
.
When
requesting
drawings
,
the
following
information
must
be
supplied
to
the
factory
.
The
assembly
number
of
the
p
/
c
board
.
This
is
found
on
the
component
side
of
the
printed
-
circuit
board
.
It
is
an
eight
-
digit
number
with
a
letter
inserted
between
the
fourth
and
fifth
digit
and
suffixed
with
a
group
identification
,
e
.
g
.
0215
B
5865
G
001
or
Gl
.
then
be
-
11
-
Courtesy of NationalSwitchgear.com
GEK
-
90666
The
revision
number
.
This
is
also
found
on
the
printed
-
circuit
board
,
e
.
g
.
REV
.
l
.
The
acceptance
tests
should
be
performed
after
a
printed
-
circuit
board
has
been
repaired
or
replaced
.
Whenever
the
nameplate
is
removed
from
the
relay
,
care
must
be
taken
when
replacing
it
so
that
it
does
not
interfere
with
the
mechanical
operation
of
any
switches
that
protrude
through
the
nameplate
.
RENEWAL
PARTS
It
is
recommended
that
sufficient
quantities
of
renewal
parts
be
carried
in
stock
to
enable
the
prompt
replacement
of
any
that
are
broken
or
damaged
.
When
ordering
renewal
parts
address
the
nearest
Sales
Office
of
the
General
Electric
Company
.
Specify
the
quantity
required
,
the
name
of
the
part
wanted
,
the
part
number
if
known
,
and
the
complete
model
number
of
the
relay
for
which
the
part
is
required
.
The
table
below
lists
the
part
numbers
for
the
most
common
replacement
parts
.
It
is
recommended
that
renewal
parts
only
be
obtained
from
the
General
Electric
Company
.
Should
a
printed
-
circuit
card
become
inoperative
,
it
is
recommended
that
the
card
be
replaced
with
a
spare
.
Model
SAM
Function
Part
number
Timer
Board
201
0184
B
8750
G
-
1
202
205
203
Timer
Board
0184
B
8750
G
-
5
204
Timer
Board
0184
B
8750
G
-
2
206
Timer
Board
0184
B
8750
G
-
3
Timer
Board
207
0184
B
8750
G
-
4
201
Backplane
Backplane
Backplane
Backplane
Backplane
Backplane
Backplane
0188
B
9755
G
-
1
202
0184
B
9755
G
-
2
203
0184
B
9755
G
-
3
204
0184
B
9755
G
-
4
205
0184
B
9755
G
-
5
206
0184
B
9755
G
-
6
207
0184
B
9756
G
-
1
-
12
-
Courtesy of NationalSwitchgear.com
GEK
-
90666
Model
SAM
Part
number
Function
Output
relay
(
s
)
0246
A
9826
P
-
5
201
202
203
204
205
206
207
Target
(
s
)
0188
B
9764
G
-
1
201
203
205
206
Lower
Cradle
Block
0184
B
8624
G
-
4
201
202
0184
B
8624
G
-
5
Lower
Cradle
Block
203
Lower
Cradle
Block
Lower
Cradle
Block
0184
B
8624
G
-
6
0184
B
8624
G
-
7
204
205
0184
B
8624
G
-
8
Lower
Cradle
Block
206
0184
B
8624
G
-
9
0184
B
8624
G
-
12
Lower
Cradle
Block
Upper
Cradle
Block
207
207
06418058
G
-
646
Lower
Case
Block
201
202
06418058
G
-
45
Lower
Case
Block
203
206
06418058
G
-
144
Lower
Case
Block
204
06418058
G
-
617
Lower
Case
Block
205
06418058
G
-
158
06418058
G
-
158
Lower
Case
Block
Upper
Case
Block
207
207
0128
B
2305
G
-
5
Cover
201
203
205
206
0128
B
2305
G
-
2
Cover
202
204
006229807
G
-
7
Cover
207
-
13
-
Courtesy of NationalSwitchgear.com
GEK
-
90666
TROUBLE
SHOOTING
WARNING
THE
POWER
SUPPLY
IN
THIS
RELAY
IS
NOT
ISOLATED
FROM
THE
INCOMING
POWER
.
ALL
TRANSISTOR
HEAT
SINKS
ARE
AT
THE
INCOMING
POTENTIAL
.
FURTHER
,
THE
COMMON
OF
THE
REGULATED
DC
IS
AT
THE
SAME
POTENTIAL
AS
THE
MOST
-
NEGATIVE
POWER
TERMINAL
AND
SHOULD
NOT
BE
CONNECTED
TO
GROUND
.
MAKE
SURE
THAT
TEST
INSTRUMENTS
CONNECTED
TO
MONITOR
THE
SIGNALS
WITHIN
THE
RELAY
ARE
SUITABLY
ISOLATED
FROM
GROUND
AND
OBSERVE
PROPER
TECHNIQUES
TO
AVOID
A
SHOCK
HAZARD
.
The
following
equipment
will
be
required
for
trouble
shooting
the
relay
.
A
48
VDC
power
supply
,
capable
of
supplying
at
least
60
ma
of
current
,
to
energize
the
relay
.
A
counter
with
two
independent
channels
that
can
be
triggered
on
positive
edges
.
A
frequency
counter
,
to
measure
the
clock
frequency
.
A
storage
scope
to
measure
the
various
timing
signals
.
A
multi
meter
,
and
finally
a
card
extender
board
,
GE
part
number
0215
B
8031
G
1
,
which
is
required
to
perform
the
tests
indicated
in
the
trouble
-
shooting
guide
.
CAUTION
REMOVE
ALL
power
from
relay
before
removing
or
inserting
any
of
the
printed
-
circuit
boards
or
output
relays
.
Failure
to
observe
this
caution
may
result
in
damage
to
and
/
or
misoperation
of
the
relay
.
The
trouble
-
shooting
diagram
,
Figure
28
,
will
be
extremely
useful
in
identifying
defective
circuits
in
the
relay
.
In
addition
to
the
trouble
shooting
diagram
,
a
functional
description
of
the
timer
board
and
a
list
of
possible
problems
/
solutions
have
been
provided
in
this
section
.
Additionally
,
several
views
of
the
relay
have
been
provided
,
Figures
29
thru
38
.
These
figures
will
assist
in
identifying
,
as
well
as
locating
,
components
in
the
relay
.
The
trouble
-
shooting
diagram
,
Figure
28
,
illustrate
voltages
and
waveforms
to
be
found
at
selected
points
in
the
relay
.
The
points
are
the
pin
numbers
of
the
various
components
found
in
the
relay
and
timer
board
,
as
well
as
the
connector
pin
numbers
on
the
extender
board
.
The
failure
of
the
signal
to
meet
the
values
and
levels
shown
on
the
diagram
indicates
a
failure
in
that
portion
of
the
circuit
.
All
signals
should
be
measured
with
high
-
input
-
impedance
instruments
to
avoid
loading
the
circuits
.
Remember
the
regulated
DC
is
not
isolated
.
A
logic
low
is
a
signal
with
an
amplitude
of
between
zero
and
20
%
of
the
regulated
DC
voltage
;
nominally
this
is
0
to
2.4
volts
for
tne
12
volt
supply
and
0
to
1.2
volts
for
the
6
volt
supply
.
A
logic
high
is
defined
as
a
signal
whose
amplitude
is
between
80
%
and
100
%
of
the
regulated
DC
voltage
;
nominally
this
is
9.6
to
12
volts
for
the
12
volt
supply
and
4.8
to
6.0
volts
for
the
6
volt
supply
.
Commence
the
trouble
-
shooting
procedure
by
setting
all
of
the
"
TU
"
or
"
TU
2
"
&
"
TU
3
"
SECONDS
switch
segments
to
the
UP
position
.
Set
the
RANGE
MULTIPLIER
switch
to
the
0.01
setting
.
Apply
48
VDC
to
the
appropriate
input
power
terminals
of
the
relay
(
refer
to
Figures
9
thru
15
)
.
Begin
to
check
for
the
voltages
and
waveforms
indicated
in
the
trouble
-
shooting
diagram
.
-
14
-
Courtesy of NationalSwitchgear.com
GEK
-
90666
TIMER
BOARD
FUNCTIONAL
DESCRIPTION
Regulation
The
input
power
is
regulated
by
a
series
-
pass
Darlington
transistor
pair
,
Q
5
and
Q
6
.
The
base
of
Q
5
is
referenced
to
13.2
VDC
by
Z
1
(
12
VDC
)
and
D
6
&
D
7
.
Current
limit
,
which
is
set
for
24
mA
,
is
provided
by
R
39
and
Q
7
.
When
the
voltage
drop
across
R
39
,
a
24.9
n
resistor
,
exceeds
0.6
VDC
,
Q
7
turns
on
and
takes
base
current
from
Q
5
.
This
action
turns
off
Q
5
,
thus
causing
the
output
to
collapse
.
Q
8
,
R
40
and
Z
2
provide
6
VDC
for
use
by
the
driver
circuits
.
Timing
The
timing
circuit
(
s
)
,
Input
1
and
/
or
Input
2
,
are
driven
by
an
oscillator
circuit
.
The
oscillator
circuit
,
which
consists
of
three
U
4
inverters
,
three
resistors
,
R
5
,
R
6
&
R
46
and
a
capacitor
,
C
8
,
is
tuned
to
2
kHz
.
The
oscillator
clocks
the
binary
counter
,
U
3
.
The
output
of
U
3
becomes
the
clock
signal
for
U
6
,
which
is
another
binary
counter
.
Through
different
segments
of
the
range
multiplier
switch
,
SW
3
,
the
output
of
U
3
as
well
as
the
output
of
U
6
become
the
clock
signal
for
BCD
counters
U
1
and
/
or
U
8
.
Setting
SW
3
to
the
extreme
left
position
,
the
0.01
setting
,
will
program
U
3
to
divide
by
20
and
its
output
is
connected
to
BCD
counters
U
1
and
or
U
8
.
With
SW
5
set
to
the
mid
position
,
the
0.1
setting
,
U
3
is
programmed
to
divide
by
200
and
its
output
is
likewise
connected
to
U
1
and
or
U
8
.
Placing
SW
3
to
the
extreme
right
position
,
the
1.0
setting
,
will
program
U
3
to
divide
by
200
and
this
output
clocks
U
6
,
which
is
programmed
to
divide
by
10
.
The
output
of
U
6
then
becomes
the
clock
signal
for
U
1
and
/
or
U
8
.
g
the
timing
switches
,
SW
1
&
SW
2
and
SW
4
&
SW
5
,
ON
,
to
the
UP
position
,
will
program
the
BCD
counters
to
the
desired
timing
interval
.
The
timing
interval
is
equal
to
the
sum
of
the
switches
in
the
UP
position
.
If
all
the
programming
switches
are
set
OFF
,
to
the
DOWN
position
,
the
circuitry
will
give
the
BCD
counters
a
default
setting
of
1
.
The
time
interval
,
due
to
the
default
setting
,
will
be
equal
to
the
setting
of
switch
SW
3
,
which
can
be
10
,
100
or
1000
msec
.
Settin
The
output
of
the
BCD
counters
,
U
1
and
or
U
8
,
goes
low
at
the
end
of
the
desired
timing
interval
.
The
transition
from
high
to
low
is
inverted
to
create
positive
edges
that
become
the
triggering
signals
for
flip
flop
U
10
.
The
BCD
counters
will
continue
to
count
at
the
maximum
possible
setting
of
256
counts
for
as
long
as
the
power
is
applied
to
the
circuit
.
However
,
the
flip
flop
,
U
10
,
will
change
state
on
the
first
positive
-
going
edge
and
ignore
all
subsequent
positive
edges
.
The
outputs
of
U
10
are
connected
to
pins
47
and
48
,
to
monostable
multivibrator
,
U
7
,
as
well
as
to
the
driver
circuit
(
s
)
of
the
output
relay
(
s
)
.
The
multivibrator
,
U
7
,
provides
output
pulses
of
approximately
20
msec
.
These
pulses
are
also
applied
to
the
driver
circuit
(
s
)
of
the
output
relay
(
s
)
.
Output
Each
driver
circuit
consists
of
non
-
inverting
buffers
,
resistors
,
diodes
and
a
transistor
.
Buffer
(
s
)
,
U
2
,
are
connected
to
the
12
VDC
supply
rail
and
provide
the
20
msec
,
pulse
signal
(
s
)
from
the
timing
circuit
(
s
)
to
the
driver
circuit
(
s
)
.
The
continuous
signals
from
the
timing
circuits
to
the
driver
circuit
(
s
)
are
provided
by
buffer
(
s
)
,
U
5
,
which
are
connected
to
the
6
VDC
supply
rail
.
Each
driver
circuit
can
be
driven
by
either
timing
circuit
.
Input
1
or
Input
2
,
but
not
both
.
The
selection
is
made
by
choosing
the
proper
resistor
combination
from
the
following
groups
,
R
19
thru
R
22
,
R
25
thru
R
28
or
R
31
thru
R
34
.
-
15
-
Courtesy of NationalSwitchgear.com
GEK
-
90666
Each
driver
circuit
is
capable
of
energizing
one
output
relay
.
The
coil
of
the
output
relay
is
connected
in
series
with
the
power
source
and
the
collector
of
the
drive
transistor
.
Wnen
active
,
the
transistor
,
which
acts
as
a
variable
-
series
resistor
to
the
relay
,
is
biased
in
the
linear
region
.
The
voltage
across
the
emitter
resistor
remains
constant
,
regardless
of
the
applied
battery
voltage
.
Since
the
voltage
across
the
resistor
is
constant
,
the
current
flowing
through
it
is
also
constant
.
Thus
the
collector
current
is
constant
,
regardless
of
the
battery
voltage
and
therefore
,
the
relay
is
controlled
by
the
current
and
not
the
voltage
applied
.
PROBLEMS
and
SOLUTIONS
Symptoms
No
clock
signal
,
monitored
after
R
43
.
Solutions
Replace
U
4
.
Output
relav
(
s
)
picks
up
for
20
ms
then
drops
out
.
Check
6
V
supply
.
If
incorrect
,
replace
Z
2
,
Q
8
and
/
or
U
5
.
Timer
board
draws
more
than
60
ma
.
Check
Q
7
and
R
39
.
Check
that
all
output
relay
coils
measure
110
Qn
±
140
n
.
Check
for
defective
chips
by
monitoring
their
temperature
.
Make
sure
that
the
external
power
supply
rises
up
to
voltage
in
less
than
3
ms
.
Check
the
clock
frequency
,
after
R
43
.
SAM
Relay
times
out
before
or
after
expected
setting
(
including
specified
timing
error
)
.
SAM
Relay
was
left
energized
continuously
at
elevated
temperatures
.
Replace
R
37
.
Replace
any
output
relay
whose
coil
resistance
is
much
less
than
specified
above
.
Replace
driver
transistor
and
resistor
associated
with
the
defective
relay
.
Q
4
&
R
30
if
K
2
is
defective
.
e
.
g
.
,
Q
3
&
R
24
if
K
1
is
defective
;
defective
and
Q
9
&
R
36
if
K
3
is
Since
the
last
edition
,
changes
have
been
made
in
RATINGS
,
Burden
,
Contact
ratings
,
and
in
Figure
41
.
-
16
-
Courtesy of NationalSwitchgear.com
GEK
-
90666
List
of
Figures
External
connection
diagram
for
the
SAM
201
External
connection
diagram
for
the
SAM
202
External
connection
diagram
for
the
SAM
203
External
connection
diagram
for
the
SAM
204
External
connection
diagram
for
the
SAM
205
External
connection
diagram
for
the
SAM
206
External
connection
diagram
for
the
SAM
207
Functional
Block
diagram
for
the
SAM
RELAYS
Internal
connections
diagram
for
the
SAM
201
Internal
connections
diagram
for
the
SAM
202
Internal
connections
diagram
for
the
SAM
203
Internal
connections
diagram
for
the
SAM
204
Internal
connections
diagram
for
the
SAM
205
Internal
connections
diagram
for
the
SAM
206
Internal
connections
diagram
for
the
SAM
207
Outline
and
mounting
dimensions
for
the
SAM
201
-
206
Outline
and
mounting
dimensions
for
the
SAM
207
Timing
Test
connections
for
SAM
201
,
202
&
205
Timing
Test
connections
for
SAM
203
Timing
Test
connections
for
SAM
204
Timing
Test
connections
for
SAM
206
Timing
Test
connections
for
SAM
207
Target
Test
connections
for
SAM
201
Target
Test
connections
for
SAM
203
Target
Test
connections
for
SAM
205
Target
Test
connections
for
SAM
206
Drawout
case
contact
assembly
Trouble
shooting
diagram
for
the
SAM
201
-
SAM
207
Front
View
of
the
SAM
203
with
the
cover
removed
Front
view
of
the
SAM
206
with
the
cover
removed
Front
view
of
the
SAM
207
with
the
cover
removed
Typical
"
SI
"
Cradle
Assembly
removed
from
Case
Typical
"
SI
"
Cradle
Assembly
with
nameplate
removed
Typical
"
SI
"
Cradle
Assembly
with
nameplate
and
circuit
boards
removed
Rear
view
of
a
typical
"
SI
"
Cradle
Assembly
View
of
a
typical
Timer
P
/
C
Board
Assembly
Rear
view
of
a
Relay
Case
(
SI
)
with
surge
ground
stud
location
Rear
view
of
a
Relay
Case
(
S
2
)
with
surge
ground
stud
location
Output
Relay
operating
time
SAM
202
used
in
breaker
-
failure
scheme
SAM
202
used
in
2
zone
step
distance
scheme
SAM
204
used
in
3
zone
step
distance
scheme
SAM
206
used
in
3
zone
step
distance
scheme
0286
A
1831
)
18
0286
A
1832
)
19
0286
A
1833
)
20
0286
A
1834
)
21
0286
A
1835
)
22
0286
A
1836
)
23
0286
A
1837
)
24
0286
A
1838
)
25
0184
B
8751
)
26
0184
B
8752
)
27
0184
B
8753
)
28
0184
B
8754
)
29
0184
B
8755
)
30
0184
B
8756
)
31
0184
B
8757
)
32
0285
A
5392
)
33
0285
A
5393
)
34
0286
A
1862
)
35
’
0286
A
1863
)
36
>
0286
A
1864
)
37
>
0286
A
1865
)
38
0286
A
1866
)
39
'
0286
A
1867
)
40
>
0286
A
1868
)
41
>
0286
A
1869
)
42
'
0286
A
1870
)
43
8025039
)
0153
D
7769
)
45
8043819
)
8043820
)
8043821
)
8043822
)
Figure
1
Figure
2
Figure
3
Figure
4
Figure
5
Figure
6
Figure
7
Figure
8
Figure
9
Figure
10
Figure
11
Figure
12
Figure
13
Figure
14
Figure
15
Figure
16
Figure
17
Figure
18
Figure
19
Figure
20
Figure
21
Figure
22
Figure
23
Figure
24
Figure
25
Figure
26
Figure
27
Figure
28
Figure
29
Figure
30
Figure
31
Figure
32
Figure
33
Figure
34
Figure
35
Figure
36
Figure
37
Figure
38
Figure
39
Figure
40
Figure
41
Figure
42
Figure
43
44
46
47
48
49
(
8043823
)
8043824
8043825
8043826
50
51
52
53
(
8043827
)
8043828
)
0286
A
1873
'
0153
D
7809
0153
D
7810
0153
D
7811
0153
D
7812
54
55
56
57
58
59
60
-
17
-
Courtesy of NationalSwitchgear.com
o
m
*
CD
O
CD
CD
CD
3
(
+
)
48
/
125
/
250
VDC
s
-
1
?
2
?
9
a
>
o
N
)
00
Initiating
Contact
ON
>
h
—
1
00
u
>
/
/
2
2
m
X
7
7
^
4
n
>
-
i
3
2
2
SAM
201
9
5
(
TU
)
TB
TA
i
n
o
00
3
3
CD
O
o
cru
)
au
)
810
6
1
8
3
88
D
D
£
3
(
-
)
oq
-
t
3
LEGEND
o
2
SAM
Timing
Relay
o
4
o
>
TA
Target
on
TB
Target
to
o
TU
Timing
Unit
Courtesy of NationalSwitchgear.com
GEK
-
90666
c
\
j
|
oo
X
o
X
cn
Z
>
a
to
OJ
|
O
o
Csj
|
oo
o
\
CXI
Z
>
a
to
OJl
o
>
>
O
CO
Q
Q
>
>
CL
Z
)
o
t
CO
lO
o
e
CXJ
c
LO
CXJ
E
ZD
LO
a
o
CXI
CO
<
c
2
LO
00
Q
E
CD
c
O
<
X
z
OO
ca
LU
+
CO
O
c
10
LLi
O
CXJ
_
E
O
Figure
2
(
0286
A
1832
)
External
-
Connection
Diagram
for
the
SAM
202
-
19
-
Courtesy of NationalSwitchgear.com
o
m
7
;
CD
O
CD
CD
CD
(
+
)
48
/
125
/
250
VDC
(
+
)
48
/
125
/
250
VDC
>
—
•
•
?
10
91
c
u
>
2
2
o
Initiating
Contacts
N
)
TB
TA
00
cr
\
>
I
—
I
00
u
>
ffl
06
64
X
2
2
2
2
Cl
SAM
203
>
-
!
3
P
?
5
CTU
2
)
CTU
3
)
?
7
o
ro
o
o
3
3
a
6
8
(
TU
3
)
°
2
(
TU
2
)
33
o
6
9
o
3
(
-
)
(
-
)
o
I
—
>
•
p
CTQ
LEGEND
P
3
2
SAM
Timing
Relay
o
’
TA
Target
3
"
c
Target
TB
on
TU
2
Timing
Unit
2
t o
TU
3
Timing
Unit
3
o
U
>
Courtesy of NationalSwitchgear.com

This manual suits for next models

6

Other GE Relay manuals

GE DIAC User manual

GE

GE DIAC User manual

GE T60 User manual

GE

GE T60 User manual

GE DGP Series User manual

GE

GE DGP Series User manual

GE 735 User manual

GE

GE 735 User manual

GE G30 User manual

GE

GE G30 User manual

GE JBC51M User manual

GE

GE JBC51M User manual

GE Baker Hughes Masonelian BR200 User manual

GE

GE Baker Hughes Masonelian BR200 User manual

GE Multilin MIB User manual

GE

GE Multilin MIB User manual

GE L60 User manual

GE

GE L60 User manual

GE 750 User manual

GE

GE 750 User manual

GE CEY52B User manual

GE

GE CEY52B User manual

GE T60 User manual

GE

GE T60 User manual

GE IAC51A User manual

GE

GE IAC51A User manual

GE P642 User manual

GE

GE P642 User manual

GE IAC53A User manual

GE

GE IAC53A User manual

GE 369 Use and care manual

GE

GE 369 Use and care manual

GE HFA54 User manual

GE

GE HFA54 User manual

GE IAC Series User manual

GE

GE IAC Series User manual

GE CEY53A User manual

GE

GE CEY53A User manual

GE DFF1000 Series User manual

GE

GE DFF1000 Series User manual

GE 750 User manual

GE

GE 750 User manual

GE L60 User manual

GE

GE L60 User manual

GE IAC53A User manual

GE

GE IAC53A User manual

GE 750 User manual

GE

GE 750 User manual

Popular Relay manuals by other brands

SEB IFX4NR user manual

SEB

SEB IFX4NR user manual

Littelfuse AF0100 instruction manual

Littelfuse

Littelfuse AF0100 instruction manual

Honeywell ADEMCO 5800RL Installation and setup guide

Honeywell

Honeywell ADEMCO 5800RL Installation and setup guide

Zamel PNM-10 instruction manual

Zamel

Zamel PNM-10 instruction manual

Stelpro SBB Series Installation

Stelpro

Stelpro SBB Series Installation

BEA LO-21K user guide

BEA

BEA LO-21K user guide

Pilz PZE X4V8 operating manual

Pilz

Pilz PZE X4V8 operating manual

GEYA GRT6-S Series instruction manual

GEYA

GEYA GRT6-S Series instruction manual

LEGRAND LEXIC 26092 manual

LEGRAND

LEGRAND LEXIC 26092 manual

Omron SYSMAC-SE2 Practices Guide

Omron

Omron SYSMAC-SE2 Practices Guide

Pizzato Elettrica CS AR-08 Series manual

Pizzato Elettrica

Pizzato Elettrica CS AR-08 Series manual

ZIEHL STW20K operating manual

ZIEHL

ZIEHL STW20K operating manual

MIEPL YTC YT-520 Series product manual

MIEPL

MIEPL YTC YT-520 Series product manual

hager TX211A instruction manual

hager

hager TX211A instruction manual

ABB SPAJ 111 C user manual

ABB

ABB SPAJ 111 C user manual

ABB REL 356 quick start guide

ABB

ABB REL 356 quick start guide

Klemsan MEASTRO Quick setup manual

Klemsan

Klemsan MEASTRO Quick setup manual

Elko HRN-33 quick guide

Elko

Elko HRN-33 quick guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.