GEA Bock FK50 Series User manual

GEA Bock FK50
Assembly instructions
09704-10.2019-Gb
Translation of the original instructions
FK50/460 N FK50/555 N FK50/660 N FK50/775 N FK50/830 N FK50/980 N
FK50/460 K FK50/555 K FK50/660 K FK50/775 K FK50/830 K FK50/980 K
FKX50/460 N FKX50/555 N FKX50/660 N FKX50/775 N FKX50/830 N FKX50/980 N
FKX50/460 K FKX50/555 K FKX50/660 K FKX50/775 K FKX50/830 K FKX50/980 K

2
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
About these instructions
Read these instructions before assembly and before using the compressor. This will avoid
misunderstandings and prevent damage. Improper assembly and use of the compressor can lead to
serious or fatal injury.
Observe the safety instructions contained in these instructions.
These instructions must be passed onto the end customer along with the unit in which the
compressor is installed.
GEA Bock GmbH
72636 Frickenhausen
GEA Bock GmbH
Benzstraße 7
72636 Frickenhausen
Germany
Telephone +49 7022 9454 0
Fax +49 7022 9454 137
www.gea.com
Manufacturer
Contact

3
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
Contents Page
1 Safety 4
1.1 Identicationofsafetyinstructions
1.2 Qualicationsrequiredofpersonnel
1.3 General safety instructions
1.4 Intended use
2 Product description 6
2.1 Brief description
2.2 Name plate
2.3 Type key
3 Areas of application 8
3.1 Refrigerants
3.2 Oil charge
3.3 Limits of application
4Compressor assembly 9
4.1 Setting up
4.2 Maximum permissible inclination
4.3 V-belt drive
4.4 Main bearing load
4.5 Electromagnetic clutch assembly
4.6 Pipe connections
4.7 Pipes
4.8 Operating the shut-off valves
4.9 Operating mode of the lockable service connections
4.10Suctionpipelter
5 Commissioning 13
5.1 Preparations for start-up
5.2 Pressure strength test
5.3 Leak test
5.4 Evacuation
5.5 Refrigerant charge
5.6 Oil level check
5.7 Shaft seal
5.8 Avoidingliquidshocks
6 Maintenance 16
6.1 Preparation
6.2 Work to be carried out
6.3 Shaft seal, emptying the oil reservoir
6.4 Recommended spare parts
6.5 Integrated decompression valves
6.6 Extract from the lubricants table
6.7 Decommissioning
7 Accessories 18
7.1 Capacity regulator
7.2 Thermi protection thermostat
8 Technical Data 19
9 Dimensions and Connections 20
10 Installationcerticate 22
11 Service 23

4
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
1|Safety
1.2 Qualicationsrequiredofpersonnel
DANGER Indicates a dangerous situation which, if not avoided,
will cause immediate fatal or serious injury.
WARNING Indicates a dangerous situation which, if not avoided,
may cause fatal or serious injury.
CAUTION Indicates a dangerous situation which, if not avoided,
may cause fairly severe or minor injury.
ATTENTION Indicates a situation which, if not avoided,
may cause property damage.
INFO Important information or tips on simplifying work.
WARNING Inadequatelyqualied personnelposes therisk ofaccidents,the
consequencebeingseriousorfatalinjury.Workoncompressors
isthereforereservedforpersonnelwhichisqualiedtoworkon
pressurized refrigerant systems:
• For example, a refrigeration technician, refrigeration mechatronic
engineer. As well as professions with comparable training, which
enables personnel to assemble, install, maintain and repair
refrigeration and air-conditioning systems. Personnel must be capable
of assessing the work to be carried out and recognising any potential
dangers.
1.1 Identicationofsafetyinstructions:

5
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
1|Safety
These assembly instructions describe the standard version of the FK50 manufactured by GEA. The
compressor is intended for use in refrigeration systems in compliance with the limits of application.
Onlytherefrigerantspeciedintheseinstructionsmaybeused.
Any other use of the compressor is prohibited!
The GEA refrigerating compressor named in the title is intended for installation in a machine (within
the EU according to the EU Directives 2006/42/EC Machinery Directive and 2014/68/EU Pressure
EquipmentDirective).
Commissioning is permissible only if the compressor has been installed in accordance with these
assembly instructions and the entire system into which it is integrated has been inspected and
approved in accordance with legal regulations.
1.4 Intended use
1.3 General safety instructions
WARNING Risk of accidents.
Refrigerating compressors are pressurised machines and as such
call for heightened caution and care in handling.
The maximum permissible overpressure must not be exceeded,
even for testing purposes.
Risk of burns!
- Depending on the operating conditions, surface temperatures of
over 60°C on the discharge side or below 0°C on the suction side
can be reached.
- Avoid contact with refrigerant necessarily.
Contact with refrigerant can cause severe burns and skin
damage.

6
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
2|Product description
Two different designs are available for various ranges of application:
> for air-conditioning the K Design
> for air-conditioning or normal cooling the N Design
The differences lie mainly in the valve plate tooling which is adapted to each applica-
tion range where operational safety and efficiency are concerned.
Compact six cylinder compressor in W design.
Six capacity ranges.
Lightweight aluminum design.
Lubricating oil pump with oil pressure relief valve independent of rotational direction.
Variable arrangement of the shut-off valves.
Fig. 1
2.1 Brief description
Fig. 2
Valve plate
Cylinder cover
Shaft end
Shaft seal
Suction shut-off valve
Suction line valve
Oil pump
Dimension and connection values can be found in Chapter 9
Eyebolt
Leak oil trapping
device with oil
reservoir
Name plate
Eyebolt
Oil sight glass
Oil sightglass
Discharge shut-off valve
Leak oil drain hose

7
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
2|Product description
/
FK 05 775 NX
1 Type designation
2 Displacement at 1450 rpm
3 LP: Max. permissible operating pressure
(g)Lowpressureside
HP: Max. permissible operating pressure
(g)Highpressureside
4 Machine number
5 Factory-lledoiltype
Fig. 3
2.2 Name plate (example)
2.3 Type key (example)
¹)K - specially for air-conditioning
N - specially for air-conditioning or normal cooling
²)X- Esteroilcharging(HFCrefrigerant,e.g.R134a,R407C)
Designs ¹)
Swept volume
Size
Ester oil charging ²)
Series
1
2
3
4
5
BB12345A029
19/28bar
Observe the limits of application
diagrams!
}
FKX50/775N
67,4
GEA Bock GmbH
72636 Frickenhausen, Germany

8
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
3|Areas of application
Thecompressorsarefactory-lledwiththefollowingoiltype:
- for R134a, R404A/R507, R407C FUCHS Reniso Triton SE 55
- for R22 FUCHS Reniso SP 46
Compressorswithesteroilcharge(FUCHSRenisoTritonSE55)aremarkedwithanXinthetype
designation (e.g. FKX50/775N).
3.1 Refrigerants
• HFKW / HFC: R134a, R404A/R507, R407C
• (H)FCKW/(H)CFC: R22
3.2 Oil charge
3.3 Limits of application
ATTENTION Compressor operation is possible within the operating limits.
These can be found in GEA Bock compressor selection tool (VAP)
under vap.gea.com. Observe the information given there.
- Max. permissible discharge end temperature: 140°C
- Max. permissible ambient temperature: 100°C
-Max.permissibleswitchingfrequency:12x/h
-A minimum running time of 2 min. at equilibrium (continuous
operation) must be achieved.
Avoid continuous operation near the threshold. Should the com-
pressor happen to be used near the thresholds, we recommend the
use of a thermal protection thermostat (Accessories, Chap. 7).
For operation with capacity regulator:
- Continuous operation, when the capacity regulator is activated,
is not permissible and can cause damage to the compressor.
- The suction gas superheat temperature may need to be reduced
or set individually when operating near to the threshold.
- When the capacity regulator is activated, the gas velocity in the
systemcannotundercertaincircumstancesensurethatsuf-
cient oil is transported back to the compressor.
When operating in the vacuum range, there is a danger of air en-
tering on the suction side. This can cause chemical reactions, a
pressure rise in the condenser and an elevated compressed-gas
temperature. Prevent the ingress of air at all costs!
INFO For recharging, we recommend the above oil types. Alternatives are:
see lubricants table, Chapter 6.6.

9
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
4|Compressor assembly
4.1 Setting up
4.2 Maximum permissible inclination
Amax. 30°,
max. 2 minutes
amax. 15°,
continuous
operation
Fig. 4
Transportandsuspensionunitonbotheyebolts(Fig.4).
Fittings(e.g.pipeholders,additionalunitsetc.)onthecompressorarepermissibleonly
following consultation with GEA.
Setuponanevensurfaceorframewithsufcientload-bearingcapacity.Use all 4 fastening
points.
Correct setup of the compressor and mounting of the belt drive are decisive for running comfort,
operating safety and the service life of the compressor.
AA
aa
AA
aa
Fig. 5
INFO Newcompressorsarefactory-lledwithinertgas.Leavethisser-
vice charge in the compressor for as long as possible and prevent
the ingress of air.
Check the compressor for transport damage before starting any
work.
ATTENTION Poor lubrication can damage the compressor. Respect the stated
values.
WARNING Movecompressorsonlywithhoiststhathaveadequateload-bear-
ing capacity.

10
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
4|Compressor assembly
During operation with capacity controllers (Accessories, Chap. 7), the changing load can cause
increased running noises and belt drive vibrations.
4.3 V-belt drive
4.5 Electromagnetic clutch assembly
The following description applies for an electromagnetic clutch secured to a shaft.
To absorb the magnetic eld of the electromagnetic clutch, the front bearing ange has
asnugt148h8(seeFig.7).
Toconnectthemagneticeld,loosenthe4cheeseheadscrewsM8onthebearingange
(seeFig.7).
Slidethemagneticeldtoasnugtandre-attachusingthefourcheeseheadscrewsM8
(Fig.8).Screwtorque=37Nm.
Further assembly of the electromagnetic clutch according to the clutch manufacturer.
Fig. 7
Bearingange,front
Magneticeld
Fig. 8
148 h8
4.4 Main bearing load
To prevent the belt drive overloading the compressor main bearing,
ensure that:
The engagement force applied by the belt tension (centre of
shafttaper,seeFig.10)mustnotexceedFmax per.=2750N.
If the force engagement point shifts to the right (see Fig.6,
smallpoint),theforceFmax per. reduces as per the following
formula:
Fmax per.= 245 kNmm
(90 mm + L1[mm])
Fmax= 2750 N
Mbmax= 245kNmm
L
1
(mm)
Fig. 6
ATTENTION Inappropriately designed belt drives, especially belt knocking
or excessive tensioning forces can cause compressor damage!
Make sure that the drive belt is designed correctly, e.g. by using
tensionersandselectingthebeltproleandthebeltlength.

11
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
4|Compressor assembly
4.7 Pipes
Pipes and system components must be clean and dry inside and free of scale, swarf and layers of
rust and phosphate. Only use air-tight parts.
Lay pipes correctly. Suitable vibration compensators must be provided to prevent pipes being
cracked and broken by severe vibrations.
Ensure a proper oil return.
Keep pressure losses to an absolute minimum.
The discharge and suction line valves have stepped internal
diameters, enabling the use of pipes with standard millimetre and
inch dimensions. The depth of pipe insertion will depend on the
dimension.
The connection diameters of the shut-off valves are designed for
maximum compressor output. Therequiredpipecross-section
must be matched to the capacity. The same applies for
non-return valves.
Fig. 9: Stepped
internal diameters
4.6 Pipe connections
4.8 Operating the shut-off valves
Before opening or closing the shut-off valve, release the valve spindle seal by approx. ¼ of a turn
counter-clockwise.
After activating the shut-off valve, re-tighten the adjustable valve spindle seal clockwise.
Fig. 10 Fig. 11
Therequiredtighteningtorquefortheangeconnectionis60Nm.
Valve spindle seal
Release
Tighten
ATTENTION Overheating can damage the valve.
Therefore, remove the pipe supports from the valve before
soldering.
Solder only using inert gas to inhibit oxidation products (scale).

12
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
4|Compressor assembly
4.9 Operating mode of the lockable service connections
Fig. 12
Fig. 13
Opening the shut-off valve
Spindle 1: turn to the left (counter-
clockwise)asfarasitwillgo.
—> Shut-off valve fully opened /
service connection 2 closed.
Opening the service connection (2):
Spindle 1: 1/2- 1 rotation to the right
—> Service connection 2 opened /
shut-off valve opened.
Connection 3 is provided for safety devices
and is not lockable.
1
1
3
3
2
2
Afteractivatingthespindle,generallytthespindleprotectioncapagainandtightenwith14-16Nm.
This serves as a second sealing feature during operation.
For systems with long pipes and higher degree of contamination, a lter on the suction-side is
recommended.Thelterhastobebereneweddependingonthedegreeofcontamination(reduced
pressureloss).
4.10Suctionpipelter

13
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
5|Commissioning
5.1 Preparations for start-up
5.4 Evacuation
First evacuate the system and then includethe compressor in the evacuation process.
Relieve the compressor pressure.
Open the suction and discharge line valves.
Evacuate the suction and discharge pressure sides using the vacuum pump.
At the end of the evacuation process, the vacuum should be < 1.5 mbar when the pump is switched off.
Repeattheprocessasoftenasisrequired.
The compressor has undergone trials in the factory and all functions have been tested. There are
therefore no special running-in instructions.
Check the compressor for transport damage!
5.3 Leak test
Carry out the leak test on the refrigerating plant in accordance with EN 378-2 or a corresponding
safety standard, while always observing the maximum permissible overpressure for the compressor.
DANGER Risk of bursting!
The compressor must only be pressurised using nitrogen (N2).
Never pressurise with oxygen or other gases!
The maximum permissible overpressure of the compressor must
not be exceeded at any time during the testing process (see name
plate data)! Do not mix any refrigerant with the nitrogen as this
could cause the ignition limit to shift into the critical range.
5.2 Pressure strength test
The compressor has been tested in the factory for pressure integrity. If however the entire system is
to be subjected to a pressure integrity test, this should be carried out in accordance with EN 378-2
or a corresponding safety standard without the inclusion of the compressor.
INFO To protect the compressor against inadmissible operating condi-
tions, high-pressure and low-pressure pressostats are mandatory
on the installation side.

14
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
5|Commissioning
Make sure that the suction and discharge line valves are open.
Withthecompressorswitchedoff,addtheliquidrefrigerantdirectlytothecondenserorreceiver,
breaking the vacuum.
If the refrigerant needs topping up after starting the compressor, it can be topped up in vapour
formonthesuctionside,or,takingsuitableprecautions,alsoinliquidformattheinlettothe
evaporator.
After starting, check the compressor's oil level.
Drive motor in operating condition "High idle".
Compressor run time min. 10 minutes.
The system should have reached operating points.
Checkoillevel.Astheinstallationlocationofthecompressorcandifferinpractice(inclinations),
it is recommended that the oil level is checked in both sightglasses. The oil level must be visible
in at least one sightglass.
5.5 Refrigerant charge
5.6 Oil level check
5.7 Shaft seal
CAUTION Wear personal protective clothing such as goggles and protective
gloves!
ATTENTION Avoidoverllingthesystemwithrefrigerant!
To avoid shifts in concentration, zeotropic refrigerant blends
mustalwaysbeaddedtotherefrigeratingplantinliquidform.
Donotpourliquidrefrigerantthroughthesuctionlinevalveonthe
compressor.
It is not permissible to mix additives with the oil and refrigerant.
ATTENTION After a compressor is replaced, the oil level must be checked again.
If the level is too high, oil must be drained off (risk of oil impact,
reduced performance of the air-conditioning system).
ATTENTION Failure to observe the following instructions can cause loss of
refrigerant and damage to the shaft seal!
INFO The shaft seal seals and lubricates with oil. An oil leakage of
0.05 ml per operating hour is therefore normal. This applies
particularly during the run-in phase (200 - 300 h).
Totrapandcollectleakedoil,theFK50isttedwithaninte-
grated leak oil trapping device with oil reservoir (P.6, Fig. 1).

15
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
5|Commissioning
The compressor shaft is sealed to outside using a shaft seal. The sealing element rotates with the
shaft.
The following is especially important to ensuring fault-free operation:
The complete refrigerant circuit must be correctly executed and clean inside.
Heavy shocks and vibrations to the shaft as well as continuous cyclic operation are to be
avoided.
Thesealingsurfacescansticktogetherduringprolongeddowntimes(e.g.winter).Therefore,run
the system every 4 weeks for 10 minutes.
5.8 Avoidingliquidshocks
Topreventliquidshocks:
The complete refrigeration plant must be correctly designed and executed.
The capacities of all components must be compatible (particularly evaporator and expansion
valve).
Suction gas superheating at the evaporator output should be at least 7 – 10 K (check setting
oftheexpansionvalve).
Thesystemmustreachastateofequilibrium.
Particularlyincriticalsystems(e.g.severalevaporatorpoints),suitablemeasures,e.g.
useofliquidtraps,solenoidvalveintheliquidline,etc.arerecommended.
ATTENTION Slugging can damage the compressor and cause refrigerant to leak.

16
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
6.1 Preparation
6.2 Work to be carried out
6|Maintenance
Oil change: In principle, an oil change is not mandatory if the system is correctly manufactured
and operated. However, based on decades of experience we recommend that the following oil
change/service work is carried out:
- Firstoilchangeduringtherstmaintenanceofthevehicle.
- Then after every 5,000 operating hours, though no more than 3 years, clean the oil strainer
at the same time. If necessary, also empty the oil reservoir at the shaft seal.
Annual checks: Oil level, tightness of the compressor, running noise, pressures, temperatures,
function of auxiliary devices such as checking the capacity control.
WARNING Before starting any work on the compressor:
Switch off the compressor and secure it to prevent a restart.
Relieve compressor of system pressure.
Preventairfrominltratingthesystem!
After maintenance has been performed:
Connect safety switch.
Evacuate compressor.
Release switch lock.
As changing the shaft seal involves opening the refrigerant
circuit, this is recommended only if the seal is losing
refrigerant. Replacing the shaft seal is described in the spare
part kit concerned.
Emptying the oil reservoir: The oil reservoir can be emptied
very simple without having to dismantle the clutch and/or
belt drive. It is recommended that this is done at the same
time as the air-conditioning maintenance and motor service.
To proceed, detach the oil hose from the bracket, remove the
sealing plug and drain the oil into a collecting vessel. After
emptying, reseal the oil hose and clamp it into the bracket.
Dispose of the used oil in accordance with national
regulations.
6.3 Shaft seal, emptying the oil reservoir
Fig. 14

17
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
6.7 Decommissioning
Close the shut-off valve on the compressor. Drain the refrigerant (it must not be discharged directly
into the environment) and dispose of it according to the regulations. When the compressor is
depressurised, undo the fastening screws of the shut-off valves. Remove the compressor using an
appropriate hoist. Dispose of the oil inside in accordance with the valid national regulations.
6|Maintenance
6.6 Extract from the lubricants table
The oil type charged as standard in the factory is marked on the name plate. This oil type should be
used as a preference. Alternatives are stated in the extract from our lubricants table below.
Refrigerants GEA standard oil types Recommended alternatives
HFC
(e.g. R134a, R407,
R404A)
Fuchs Reniso Triton SE 55
(seealsochap.6.3)
Fuchs SEZ 32/68/80
Esso/Mobil EAL Arctic 46
HCFC(e.g.R22) Fuchs Reniso SP 46
(seealsochap.6.3)
BP Energol LPT 46
Sunoco Suniso 3.5GS
Texaco Capella WF 46
FK50 / ... 460 N, 555 N 660 N, 775 N,
830 N, 980 N
460 K, 555 K
660 K, 775 K
830 K, 980 K
Designation Art. No. Art. No. Art. No.
Set of gaskets 80231 80089
Valve plate kit 80243 80244 08926
Set of shaft seals 80023
Oil SP 46, 1 litre 02279
Oil SE 55, 1 litre 02282
The valves are fundamentally maintenance-free.
However, constant leakage can occur after repeated blowing off due to abnormal operating conditions.
This leads to reduced performance and increases the compressed gas temperature. In this case check
the valves and replace as necessary.
6.5 Integrated decompression valves
Only use genuine GEA spare parts!
6.4 Recommended spare parts

18
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
7|Accessories
7.1 Capacity regulation
FK50 / ... ... N ... K
Designation Item No. Item No.
Special accessory 12 V 08703 08708
Special accessory 24 V 08704 08709
Foradescription,seetechnicalinformation"Capacityregulation"(ItemNo.09900)
Ifthecapacityregulatorisfactory-tted,itisintegratedintoanextra,dedicatedcylindercover.For
retrots,itissuppliedwiththecylindercover.Theregulatorclosesonecylinderbankatatime(capacity
regulationapprox.33%).Tworetrotkitsarerequiredforacapacityregulationofapprox.66%.
A screw-in option is provided for the sensor element on the hot gas side of the compressor
housing(seeChap.9).Connectthethermalprotectionthermostatinserieswiththecontrolline.
Technical Data:
Switching voltage max. : 24 V DC
Switching current max. : 2.5 A at 24 V DC
Switch-off temperature : 145 °C ± 5 K
Switch-on temperature : approx. 115 °C
7.2 Thermal protection thermostat (Item No. 07595)
ATTENTION Capacity-regulated operation alters the gas speeds and pressure
ratios of the refrigerating plant: Adjust the suction line routing and
dimensioningaccordingly,donotsetthecontrolintervalstoocloseand
do not let the system switch more than 12 times per hour (refriger-
atingplantmusthavereachedastateofequilibrium).Continuous
operation in the control stage is not recommended as the gas
velocity in the plant system under certain circumstances does not
guaranteesufcientoilreturntothecompressorwithactivated
capacity regulator for a compressor speed below 1200 - 1500 rpm.
We recommend switching to unregulated operation (100% capacity)
for at least 5 minutes per capacity-regulated operating hour. An
assuredoilreturncanalsoberealisedbya100%capacityrequire-
ment after each compressor restart as otherwise the compressor
can also be shut down in the regulated operating time by the
thermostat.
Electrical actuation of the solenoid valve: Normally open, (cor-
responds to 100 % compressor capacity).
Cylinder covers for capacity regulation are marked with the
designation "CR" (Capacity Regulator).

19
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
8|Technical data
Type
No. of cylinders
Displace-
ment
cm3
Swept
volume
(1450 rpm)
m3/h
Weight
kg
Discharge
line
DV
mm / inch
Suction
line
SV
mm / inch
Oil
charge
Ltr.
Inertia
moment
of the
driving
unit
[kgm2]
Lubrication Oil pump
FK50/460
6
459 40,1 44,0 28 / 1 1/835 / 1 3/8
2,5
0,0047
Forced
lubrication
Rotation
direction
independent
FK50/555 556 48,3 43,0 28 / 1 1/835 / 1 3/8
FK50/660 662 57,6 42,0 35 / 1 3/82 x 35 / 1 3/8
FK50/775 776 67,6 41,0 35 / 1 3/82 x 35 / 1 3/8
FK50/830 831 72,3 43,0 35 / 1 3/82 x 35 / 1 3/80,0056
FK50/980 976 84,9 41,0 35 / 1 3/82 x 35 / 1 3/8
Connections *
The technical data for the different designs K and N are identical.
The compressor type data therefore do not mention these additions.
* K design: closed with cardboard disc.

20
09704-10.2019-DGbFPtITr
D
GB
F
PT
I
TR
9|Dimensions and connections
145
305
ca.335
112,5
255
4x
13
135
112,5
ca.370 (375)
X
L
C/E
A
A1
M
G
SV
Zusätzliches SV bei FK(X)50/660-980
Additional SV on FK(X)50/660-980
356
108,4
133,4 190 82
ca.
430
ca.
165
ca.
115
4xM10x21 LK
210
Y
SV1
D
H
K
F
X
B
B1
DV
Y
Lecköl-Ablass Schlauch
Leak oil drain hose
M
12
x28
2
40
50
54
66
74
100
90
98
110
148 h8
8xM8
130
6xM8
72
A5x9 DIN6888
1:5
1.0851-13918.0 0e
Fahrzeugverdichter / Vehicle Compressor
( ) K Ausführung
( ) K version
Massenschwerpunkt
Centre of gravity
Maße in mm
Dimensions in mm
Änderungen vorbehalten
Subject to change without notice
Typ / type
Teile-Nr. / part-no.
Typ / type
Teile-Nr. / part-no.
Typ / type
Teile-Nr. / part-no.
Typ / type
Teile-Nr. / part-no.
FK(X)50/460 N
13863 (13871) * FK(X)50/460 K 13864 (13872) *
FK(X)50/830 N
13916 (13923)
FK(X)50/460 TK
14347 (14351) *
FK(X)50/555 N
13865 (13873) * FK(X)50/555 K 13866 (13874) *
FK(X)50/980 N
13918 (13925)
FK(X)50/555 TK
14348 (14352) *
FK(X)50/660 N
13867 (13875)
FK(X)50/660 K
13868 (13876)
FK(X)50/830 K
13917 (13924)
FK(X)50/660 TK
14349 (14353)*
FK(X)50/775 N
13869 (13877)
FK(X)50/775 K
13870 (13878)
FK(X)50/980 K
13919 (13926)
FK(X)50/775 TK
14350 (14354)*
* Keine Serie / No series
Anschlüsse /
Connections
FK(X)50/460+555
FK(X)50/660-980
SV
Saugabsperrventil, Rohr
(L)*
mm / Zoll
mm / inch
35 - 1 3/8"
2x35 - 1 3/8"
Suction line valve, tube
(L)*
SV1
Opt. Anschlußmöglichkeit Saugabsperrventil
-
-
Opt. connection suction line valve
DV
Druckabsperrventil, Rohr
(L)*
mm / Zoll
mm / inch
28 - 1 1/8" 35 - 1 3/8"
Discharge line valve, tube
(L)*
A
Anschluß Saugseite, nicht absperrbar
Zoll / inch
1/8“ NPTF
Connection suction side, not lockable
A1
Anschluß Saugseite, absperrbar
Zoll / inch
7/16“ UNF
Connection suction side, lockable
B
Anschluß Druckseite, nicht absperrbar
Zoll / inch
1/8“ NPTF
Connection discharge side, not lockable
B1
Anschluß Druckseite, absperrbar
Zoll / inch
7/16“ UNF
Connection discharge side, lockable
C
Anschluß Öldrucksicherheitsschalter OIL
Zoll / inch
1/8“ NPTF
Connection oil pressure safety switch OIL
D
Anschluß Öldrucksicherheitsschalter LP
Zoll / inch
1/8“ NPTF
Connection oil pressure safety switch LP
E
Anschluß Öldruckmanometer
Zoll / inch
1/8“ NPTF
Connection oil pressure gauge
F
Ölablaß
mm
1/4“ NPTF
Oil drain
G
Opt. Anschlußmöglichkeit Ölsumpfheizung 1)
-
-
Opt. connection oil sump heater 1)
H
Stopfen Ölfüllung
mm
1/4“ NPTF
Oil charge plug
KSchauglas
Zoll / inch
2 x 1 1/8 “ – 18 UNEF
Sight glass
L
Anschluß Wärmeschutzthermostat
Zoll / inch
1/8“ NPTF
Connection thermal protection thermostat
M
Ölsieb
mm
M22x1,5
Oil filter
(L)* = Lötanschluß
(L)* = Brazing connection
1) = Nur ab Werk möglich
1) = Only possible ex factory
F
E
D
C
A
F
E
D
C
4
1
A
B
5
6
7
8
1
2
3
4
5
6
7
8
Zeichn.-Nr. / Drawing no. :
B
3
2
157148
Dok-ID:
Der Lieferant muss sicherstellen, dass die Ware
in einwandfreiem Zustand angeliefert wird
(Korrosionsschutz, Verpackung für sicheren
Transport).
The supplier has to ensure the delivery of parts
in proper conditions (corrosion prevention,
packaging for safe transportation).
Weitergabe sowie Vervielfältigung dieses Dokuments,
Verwertung und Mitteilung seines Inhalts sind ver-
boten, soweit nicht ausdrücklich gestattet. Zuwider-
handlungen verpflichten zu Schadenersatz. Alle
Rechte für den Fall der Patent-, Gebrauchsmuster-
oder Geschmacksmustereintragung vorbehalten.
The reproduction, distribution and utilization of this
document as well as the communication of its
contents to others without express authorization is
prohibited. Offenders will be held liable for the
payment of damages. All rights reserved in the event
of the grant of a patent, utility
model or design.
Ersatz für / replacement for:
Allgemeintoleranzen / General tolerances
DIN ISO 2768-mK
Ra Rz
22.03.12
Layh
Maß
/
Dimension
Passung / Clearance
h8
147,937
148,000
148
0,000
-0,063
Baumustergeprüft / Type examination:
-
-
K.-Auftrag / C.-Task:
Projektleiter / Project leader:
120
400
±0.5
0.5
6
GEA Bock GmbH - Benzstraße 7 - 72636 Frickenhausen - Germany - www.bock.de
-
-
-
Unbemaßte Radien / Undimensioned radii:
-
Bearb. / Edited
Datum / Date
Änd.-Nr. / Mod-No.
Werkstoff (Zeile 2+3 alternativ) /
Material (Line 2+3 alternative):
Ausgangsteil, Rohteil /
Base part, Raw part:
-
-
Geprüft / Appr.
Name
Datum / Date
22.03.12
22.03.12
Werkstückkanten /
Workpiece edges
DIN ISO 13715
Erstellt / Drawn
Geprüft / Verified
Büttner
Gneiting
1/3
Oberflächenbehandlung, Härte / Treatment of surface, Hardness:
-
Blatt /
Page:
400
Benennung / Description:
±0.8
1000
30
6
-
±0.3
120
30
±0.2
Zeichnungs-Nr. /
Drawing-No.
Oberflächenangaben /
Indication of surface texture
DIN EN ISO 1302
Zust. / Rev.
Gußtoleranzen / General casting tolerances:
Gewicht / Weight: (kg)
±0.1
Maßstab /
Scale:
%
C - FK50/980 N
Rz 25
Rz 160
25
0,05
Rz 1,6
0,3
0,7
1,6
2
Rz 16
6,3
Rz 63
Rz 6,3
Rz 12,5
Status:
-
-
Frei (CAD)
Nein / No
13918
.0
10.08.12
23.05.13
15.01.14
25.03.15
02.12.15
Gneiting
Grass
Gneiting
Egeler_Ch
Grass
0a | Ansicht Sickenrichtung hinzugefügt (Bl.2)
0b | Betrifft Blatt 2
0c | Pos. 570 und Pos. 590 vertauscht (Blatt 3)
0d | Betrifft Blatt 2+3
0e | Betrifft Blatt 3
8351
8527, 8640
8869
9339
9638, 9654
Schaich
Layh
Layh
Layh
Schaich
K - FK50/980 N
-
0851
1.
Kunde / Customer:
-
s
t u
w
x y z
Freigabe / Approved
über / above
bis / up to
Teile-Nr. /
Part-No.
Layh
Shaft end
Leak oil drain hose
Fig. 15
Fig. 16
Dimensions in ()=KDesign
145
305
ca.335
112,5
255
4x
13
135
112,5
ca.370 (375)
X
L
C/E
A
A1
M
G
SV
Zusätzliches SV bei FK(X)50/660-980
Additional SV on FK(X)50/660-980
356
108,4
133,4 190 82
ca.
430
ca.
165
ca.
115
4xM10x21 LK
210
Y
SV1
D
H
K
F
X
B
B1
DV
Y
Lecköl-Ablass Schlauch
Leak oil drain hose
M
12
x28
2
40
50
54
66
74
100
90
98
110
148 h8
8xM8
130
6xM8
72
A5x9 DIN6888
1:5
1.0851-13918.0 0e
Fahrzeugverdichter / Vehicle Compressor
( ) K Ausführung
( ) K version
Massenschwerpunkt
Centre of gravity
Maße in mm
Dimensions in mm
Änderungen vorbehalten
Subject to change without notice
Typ / type
Teile-Nr. / part-no.
Typ / type
Teile-Nr. / part-no.
Typ / type
Teile-Nr. / part-no.
Typ / type
Teile-Nr. / part-no.
FK(X)50/460 N
13863 (13871) * FK(X)50/460 K 13864 (13872) *
FK(X)50/830 N
13916 (13923)
FK(X)50/460 TK
14347 (14351) *
FK(X)50/555 N
13865 (13873) * FK(X)50/555 K 13866 (13874) *
FK(X)50/980 N
13918 (13925)
FK(X)50/555 TK
14348 (14352) *
FK(X)50/660 N
13867 (13875)
FK(X)50/660 K
13868 (13876)
FK(X)50/830 K
13917 (13924)
FK(X)50/660 TK
14349 (14353)*
FK(X)50/775 N
13869 (13877)
FK(X)50/775 K
13870 (13878)
FK(X)50/980 K
13919 (13926)
FK(X)50/775 TK
14350 (14354)*
* Keine Serie / No series
Anschlüsse /
Connections
FK(X)50/460+555
FK(X)50/660-980
SV
Saugabsperrventil, Rohr
(L)*
mm / Zoll
mm / inch
35 - 1 3/8"
2x35 - 1 3/8"
Suction line valve, tube
(L)*
SV1
Opt. Anschlußmöglichkeit Saugabsperrventil
-
-
Opt. connection suction line valve
DV
Druckabsperrventil, Rohr
(L)*
mm / Zoll
mm / inch
28 - 1 1/8" 35 - 1 3/8"
Discharge line valve, tube
(L)*
A
Anschluß Saugseite, nicht absperrbar
Zoll / inch
1/8“ NPTF
Connection suction side, not lockable
A1
Anschluß Saugseite, absperrbar
Zoll / inch
7/16“ UNF
Connection suction side, lockable
B
Anschluß Druckseite, nicht absperrbar
Zoll / inch
1/8“ NPTF
Connection discharge side, not lockable
B1
Anschluß Druckseite, absperrbar
Zoll / inch
7/16“ UNF
Connection discharge side, lockable
C
Anschluß Öldrucksicherheitsschalter OIL
Zoll / inch
1/8“ NPTF
Connection oil pressure safety switch OIL
D
Anschluß Öldrucksicherheitsschalter LP
Zoll / inch
1/8“ NPTF
Connection oil pressure safety switch LP
E
Anschluß Öldruckmanometer
Zoll / inch
1/8“ NPTF
Connection oil pressure gauge
F
Ölablaß
mm
1/4“ NPTF
Oil drain
G
Opt. Anschlußmöglichkeit Ölsumpfheizung 1)
-
-
Opt. connection oil sump heater 1)
H
Stopfen Ölfüllung
mm
1/4“ NPTF
Oil charge plug
KSchauglas
Zoll / inch
2 x 1 1/8 “ – 18 UNEF
Sight glass
L
Anschluß Wärmeschutzthermostat
Zoll / inch
1/8“ NPTF
Connection thermal protection thermostat
M
Ölsieb
mm
M22x1,5
Oil filter
(L)* = Lötanschluß
(L)* = Brazing connection
1) = Nur ab Werk möglich
1) = Only possible ex factory
F
E
D
C
A
F
E
D
C
4
1
A
B
5
6
7
8
1
2
3
4
5
6
7
8
Zeichn.-Nr. / Drawing no. :
B
3
2
157148
Dok-ID:
Der Lieferant muss sicherstellen, dass die Ware
in einwandfreiem Zustand angeliefert wird
(Korrosionsschutz, Verpackung für sicheren
Transport).
The supplier has to ensure the delivery of parts
in proper conditions (corrosion prevention,
packaging for safe transportation).
Weitergabe sowie Vervielfältigung dieses Dokuments,
Verwertung und Mitteilung seines Inhalts sind ver-
boten, soweit nicht ausdrücklich gestattet. Zuwider-
handlungen verpflichten zu Schadenersatz. Alle
Rechte für den Fall der Patent-, Gebrauchsmuster-
oder Geschmacksmustereintragung vorbehalten.
The reproduction, distribution and utilization of this
document as well as the communication of its
contents to others without express authorization is
prohibited. Offenders will be held liable for the
payment of damages. All rights reserved in the event
of the grant of a patent, utility
model or design.
Ersatz für / replacement for:
Allgemeintoleranzen / General tolerances
DIN ISO 2768-mK
Ra Rz
22.03.12
Layh
Maß
/
Dimension
Passung / Clearance
h8
147,937
148,000
148
0,000
-0,063
Baumustergeprüft / Type examination:
-
-
K.-Auftrag / C.-Task:
Projektleiter / Project leader:
120
400
±0.5
0.5
6
GEA Bock GmbH - Benzstraße 7 - 72636 Frickenhausen - Germany - www.bock.de
-
-
-
Unbemaßte Radien / Undimensioned radii:
-
Bearb. / Edited
Datum / Date
Änd.-Nr. / Mod-No.
Werkstoff (Zeile 2+3 alternativ) /
Material (Line 2+3 alternative):
Ausgangsteil, Rohteil /
Base part, Raw part:
-
-
Geprüft / Appr.
Name
Datum / Date
22.03.12
22.03.12
Werkstückkanten /
Workpiece edges
DIN ISO 13715
Erstellt / Drawn
Geprüft / Verified
Büttner
Gneiting
1/3
Oberflächenbehandlung, Härte / Treatment of surface, Hardness:
-
Blatt /
Page:
400
Benennung / Description:
±0.8
1000
30
6
-
±0.3
120
30
±0.2
Zeichnungs-Nr. /
Drawing-No.
Oberflächenangaben /
Indication of surface texture
DIN EN ISO 1302
Zust. / Rev.
Gußtoleranzen / General casting tolerances:
Gewicht / Weight: (kg)
±0.1
Maßstab /
Scale:
%
C - FK50/980 N
Rz 25
Rz 160
25
0,05
Rz 1,6
0,3
0,7
1,6
2
Rz 16
6,3
Rz 63
Rz 6,3
Rz 12,5
Status:
-
-
Frei (CAD)
Nein / No
13918
.0
10.08.12
23.05.13
15.01.14
25.03.15
02.12.15
Gneiting
Grass
Gneiting
Egeler_Ch
Grass
0a | Ansicht Sickenrichtung hinzugefügt (Bl.2)
0b | Betrifft Blatt 2
0c | Pos. 570 und Pos. 590 vertauscht (Blatt 3)
0d | Betrifft Blatt 2+3
0e | Betrifft Blatt 3
8351
8527, 8640
8869
9339
9638, 9654
Schaich
Layh
Layh
Layh
Schaich
K - FK50/980 N
-
0851
1.
Kunde / Customer:
-
s
t u
w
x y z
Freigabe / Approved
über / above
bis / up to
Teile-Nr. /
Part-No.
Layh
Centre of gravity
115
165
210
130
72
DV B
X
Ventilausführung K-Version
valve version K-version
B1
D
F
SV1
4xM10x21
H
K
Y
357
108,5
133,5
405
190
432 +2
304
BDV B1
X
Ventilausführung N-Version
valve version N-version
6xM8
A5x9 DIN6888
8xM8
1:5
x28
98
2
110
40
50
54
66
74
100
90
M12
148 h8
Y
Lecköl-Ablass Schlauch
Leak oil drain hose
Maßstab /
-
F
E
D
C
A
F
E
D
C
41
A
B
5
6
7
8
1
2
34
5
6
78
Zeichn.-Nr. / Drawing-no. :
B
3
-
233512
±0.1
über / above
Freigabe / Approved
zyxw
Der Lieferant muss sicherstellen, dass die Ware
in einwandfreiem Zustand angeliefert wird
(Korrosionsschutz, Verpackung für sicheren
Layh
Allgemeintoleranzen / General tolerances
Drawing-No.
bis / up to
Dok-ID:
uts
-
0f | Dichtungssatz + Druckschriften zu einem Satz zusammengefasst
1.
Kunde / Customer:
packaging for safe transportation).
model or design.
in proper conditions (corrosion prevention,
22.03.12
2
Ersatz für / replacement for:
The supplier has to ensure the delivery of parts
Transport).
prohibited. Offenders will be held liable for the Dimension Passung / Clearance
Unbemaßte Radien / Undimensioned radii:
Baumustergeprüft / Type examination:
-
K.-Auftrag / C.-Task:
Projektleiter / Project leader:
120
400
±0.5
0.5
6
Oberflächenbehandlung, Härte / Treatment of surface, Hardness:
GEA Bock GmbH - Benzstraße 7 -72636 Frickenhausen - Germany - www.bock.de
Base part, Raw part:
-
-
-
Bearb. / EditedDatum / Date
payment of damages. All rights reserved in the event Änd.-Nr. / Mod-No.
Werkstoff (Zeile 2+3 alternativ) /
DIN ISO 2768-mK-E
-
-
Geprüft / Appr.
Name
-
Datum / Date
Material (Line 2+3 alternative):
Ausgangsteil, Rohteil /
Workpiece edges
DIN ISO 13715
Erstellt / Drawn 22.03.12
Geprüft / Verified Büttner
1/4
Gneiting
22.03.12
Werkstückkanten /
Page:
400 Benennung / Description:
±0.8
1000
306
-
±0.3
12030
-
Blatt /
±0.2
of the grant of a patent, utility /
DIN EN ISO 1302
Zust. / Rev.
Gußtoleranzen / General casting tolerances:
Gewicht / Weight: (kg)
Zeichnungs-Nr. /
Indication of surface texture
%
S. Büttner
C - FK50/980 N
Rz 25
Rz 160 Rz 1,6
Rz 16
Rz 63 Rz 6,3
Rz 12,5
01.04.19
Status:
Nein / No
Scale:
in Bearbeitung (CAD)
-
13918 .0
01.04.19
01.04.19
01.04.19
01.04.19
S. Büttner
Part-No.
02.05.19
02.05.19
S. Büttner
S. Büttner
S. Büttner
S. Büttner
S. Büttner
M. Schaich
0f | Blindflansch 04269 + 04715 auf 51752 vereinheitlicht
M. Schaich
0f | Unterlagscheiben an Bodenplatte entfernt, Optionale Anbauten (Blatt 4) hinzu
8566
0f | Schraube, Scheibe, Federring am Wellenende entfernt
0f | Schraubenanzugsdrehmoment ergänzt
10164
10597
10567
0851
10447,10463
10619
0f | Entfall von Lötstutzen und zugehörigen Anbauteilen bei K-Version
M. Schaich
M. Schaich
0f | Zylinderstift für Zylinderbuchse aus VDGH entfernt und im Endprodukt aufgenommen
M. Schaich
M. Schaich
-
10468
K - FK50/980 N
M. Schaich
Weitergabe sowie Vervielfältigung dieses Dokuments,
Verwertung und Mitteilung seines Inhalts sind ver-
boten, soweit nicht ausdrücklich gestattet. Zuwider-
handlungen verpflichten zu Schadenersatz. Alle
Rechte für den Fall der Patent-, Gebrauchsmuster-
oder Geschmacksmustereintragung vorbehalten.
The reproduction, distribution and utilization of this
document as well as the communication of its
contents to others without express authorization is
Maß
Oberflächenangaben /
Teile-Nr. /
Layh
M
G
L
C/E
A
A1
SV
X
112,5
255
145
4x 13
112,5
331 (334)
+2
372 (380) +2
1.0851-13918.0 0f
Fahrzeugverdichter / Vehicle Compressor
Typ / type Teile-Nr. / part-no. Typ / type Teile-Nr. / part-no.
FK(X)50/660 N 13867 (13875) * FK(X)50/660 K 13868 (13876)
FK(X)50/775 N 13869 (13877) * FK(X)50/775 K 13870 (13878)
FK(X)50/830 N 13916 (13923) FK(X)50/830 K 13917 (13924)
FK(X)50/980 N 13918 (13925) * FK(X)50/980 K 13919 (13926)
* Keine Serie / No series
Anschlüsse /
Connections FK(X)50/
660-980 N FK(X)50/
660-980 K
SV Saugabsperrventil, Rohr (L)* mm - Zoll /
mm - inch 2x35 - 1 3/8" mit Pappscheibe
verschlossen /
closed with
cardboard disc
Suction line valve, tube (L)*
DV Druckabsperrventil, Rohr (L)* mm - Zoll /
mm - inch 35 - 1 3/8"
Discharge line valve, tube (L)*
AAnschluss Saugseite, nicht absperrbar Zoll / inch 1/8“ NPTF
Connection suction side, not lockable
A1 Anschluss Saugseite, absperrbar Zoll / inch 7/16“ UNF
Connection suction side, lockable
BAnschluss Druckseite, nicht absperrbar Zoll / inch 1/8“ NPTF
Connection discharge side, not lockable
B1 Anschluss Druckseite, absperrbar Zoll / inch 7/16“ UNF
Connection discharge side, lockable
CAnschluss Öldrucksicherheitsschalter OIL Zoll / inch 1/8“ NPTF
Connection oil pressure safety switch OIL
DAnschluss Öldrucksicherheitsschalter LP Zoll / inch 1/8“ NPTF
Connection oil pressure safety switch LP
EAnschluss Öldruckmanometer Zoll / inch 1/8“ NPTF
Connection oil pressure gauge
FÖlablass Zoll / inch 1/4“ NPTF
Oil drain
GOpt. Anschlussmöglichkeit Ölsumpfheizung 1) --
Opt. connection oil sump heater 1)
HStopfen Ölfüllung Zoll / inch 1/4“ NPTF
Oil charge plug
KSchauglas Zoll / inch 2 x 1 1/8 “ – 18 UNEF
Sight glass
LAnschluss Wärmeschutzthermostat Zoll / inch 1/8“ NPTF
Connection thermal protection thermostat
MÖlsieb mm M22x1,5
Oil filter
SV1 Opt. Anschlussmöglichkeit Saugabsperrventil --
Opt. connection suction line valve
(L)* = Lötanschluss / brazing connection
1) = Nur ab Werk möglich / ony possible ex factory
( ) K Ausführung
( ) K version Massenschwerpunkt
Centre of gravity Änderungen vorbehalten
Subject to change without notice Maße in mm
Dimensions in mm
115
165
210
130
72
DV B
X
Ventilausführung K-Version
valve version K-version
B1
D
F
SV1
4xM10x21
H
K
Y
357
108,5
133,5
405
190
432 +2
304
BDV B1
X
Ventilausführung N-Version
valve version N-version
6xM8
A5x9 DIN6888
8xM8
1:5
x28
98
2
110
40
50
54
66
74
100
90
M12
148 h8
Y
Lecköl-Ablass Schlauch
Leak oil drain hose
Maßstab /
-
F
E
D
C
A
F
E
D
C
41
A
B
5
6
7
8
1
2
34
5
6
78
Zeichn.-Nr. / Drawing-no. :
B
3
-
233512
±0.1
über / above
Freigabe / Approved
zyxw
Der Lieferant muss sicherstellen, dass die Ware
in einwandfreiem Zustand angeliefert wird
(Korrosionsschutz, Verpackung für sicheren
Layh
Allgemeintoleranzen / General tolerances
Drawing-No.
bis / up to
Dok-ID:
uts
-
0f | Dichtungssatz + Druckschriften zu einem Satz zusammengefasst
1.
Kunde / Customer:
packaging for safe transportation).
model or design.
in proper conditions (corrosion prevention,
22.03.12
2
Ersatz für / replacement for:
The supplier has to ensure the delivery of parts
Transport).
prohibited. Offenders will be held liable for the Dimension Passung / Clearance
Unbemaßte Radien / Undimensioned radii:
Baumustergeprüft / Type examination:
-
K.-Auftrag / C.-Task:
Projektleiter / Project leader:
120
400
±0.5
0.5
6
Oberflächenbehandlung, Härte / Treatment of surface, Hardness:
GEA Bock GmbH - Benzstraße 7 - 72636 Frickenhausen - Germany - www.bock.de
Base part, Raw part:
-
-
-
Bearb. / EditedDatum / Date
payment of damages. All rights reserved in the event Änd.-Nr. / Mod-No.
Werkstoff (Zeile 2+3 alternativ) /
DIN ISO 2768-mK-E
-
-
Geprüft / Appr.
Name
-
Datum / Date
Material (Line 2+3 alternative):
Ausgangsteil, Rohteil /
Workpiece edges
DIN ISO 13715
Erstellt / Drawn 22.03.12
Geprüft / Verified Büttner
1/4
Gneiting
22.03.12
Werkstückkanten /
Page:
400 Benennung / Description:
±0.8
1000
306
-
±0.3
12030
-
Blatt /
±0.2
of the grant of a patent, utility /
DIN EN ISO 1302
Zust. / Rev.
Gußtoleranzen / General casting tolerances:
Gewicht / Weight: (kg)
Zeichnungs-Nr. /
Indication of surface texture
%
S. Büttner
C - FK50/980 N
Rz 25
Rz 160 Rz 1,6
Rz 16
Rz 63 Rz 6,3
Rz 12,5
01.04.19
Status:
Nein / No
Scale:
in Bearbeitung (CAD)
-
13918 .0
01.04.19
01.04.19
01.04.19
01.04.19
S. Büttner
Part-No.
02.05.19
02.05.19
S. Büttner
S. Büttner
S. Büttner
S. Büttner
S. Büttner
M. Schaich
0f | Blindflansch 04269 + 04715 auf 51752 vereinheitlicht
M. Schaich
0f | Unterlagscheiben an Bodenplatte entfernt, Optionale Anbauten (Blatt 4) hinzu
8566
0f | Schraube, Scheibe, Federring am Wellenende entfernt
0f | Schraubenanzugsdrehmoment ergänzt
10164
10597
10567
0851
10447,10463
10619
0f | Entfall von Lötstutzen und zugehörigen Anbauteilen bei K-Version
M. Schaich
M. Schaich
0f | Zylinderstift für Zylinderbuchse aus VDGH entfernt und im Endprodukt aufgenommen
M. Schaich
M. Schaich
-
10468
K - FK50/980 N
M. Schaich
Weitergabe sowie Vervielfältigung dieses Dokuments,
Verwertung und Mitteilung seines Inhalts sind ver-
boten, soweit nicht ausdrücklich gestattet. Zuwider-
handlungen verpflichten zu Schadenersatz. Alle
Rechte für den Fall der Patent-, Gebrauchsmuster-
oder Geschmacksmustereintragung vorbehalten.
The reproduction, distribution and utilization of this
document as well as the communication of its
contents to others without express authorization is
Maß
Oberflächenangaben /
Teile-Nr. /
Layh
M
G
L
C/E
A
A1
SV
X
112,5
255
145
4x 13
112,5
331 (334) +2
372 (380) +2
1.0851-13918.0 0f
Fahrzeugverdichter / Vehicle Compressor
Typ / type Teile-Nr. / part-no. Typ / type Teile-Nr. / part-no.
FK(X)50/660 N 13867 (13875) * FK(X)50/660 K 13868 (13876)
FK(X)50/775 N 13869 (13877) * FK(X)50/775 K 13870 (13878)
FK(X)50/830 N 13916 (13923) FK(X)50/830 K 13917 (13924)
FK(X)50/980 N 13918 (13925) * FK(X)50/980 K 13919 (13926)
* Keine Serie / No series
Anschlüsse /
Connections FK(X)50/
660-980 N FK(X)50/
660-980 K
SV Saugabsperrventil, Rohr (L)* mm - Zoll /
mm - inch 2x35 - 1 3/8" mit Pappscheibe
verschlossen /
closed with
cardboard disc
Suction line valve, tube (L)*
DV Druckabsperrventil, Rohr (L)* mm - Zoll /
mm - inch 35 - 1 3/8"
Discharge line valve, tube (L)*
AAnschluss Saugseite, nicht absperrbar Zoll / inch 1/8“ NPTF
Connection suction side, not lockable
A1 Anschluss Saugseite, absperrbar Zoll / inch 7/16“ UNF
Connection suction side, lockable
BAnschluss Druckseite, nicht absperrbar Zoll / inch 1/8“ NPTF
Connection discharge side, not lockable
B1 Anschluss Druckseite, absperrbar Zoll / inch 7/16“ UNF
Connection discharge side, lockable
CAnschluss Öldrucksicherheitsschalter OIL Zoll / inch 1/8“ NPTF
Connection oil pressure safety switch OIL
DAnschluss Öldrucksicherheitsschalter LP Zoll / inch 1/8“ NPTF
Connection oil pressure safety switch LP
EAnschluss Öldruckmanometer Zoll / inch 1/8“ NPTF
Connection oil pressure gauge
FÖlablass Zoll / inch 1/4“ NPTF
Oil drain
GOpt. Anschlussmöglichkeit Ölsumpfheizung 1) --
Opt. connection oil sump heater 1)
HStopfen Ölfüllung Zoll / inch 1/4“ NPTF
Oil charge plug
KSchauglas Zoll / inch 2 x 1 1/8 “ – 18 UNEF
Sight glass
LAnschluss Wärmeschutzthermostat Zoll / inch 1/8“ NPTF
Connection thermal protection thermostat
MÖlsieb mm M22x1,5
Oil filter
SV1 Opt. Anschlussmöglichkeit Saugabsperrventil --
Opt. connection suction line valve
(L)* = Lötanschluss / brazing connection
1) = Nur ab Werk möglich / ony possible ex factory
( ) K Ausführung
( ) K version Massenschwerpunkt
Centre of gravity Änderungen vorbehalten
Subject to change without notice Maße in mm
Dimensions in mm
115
165
210
130
72
DV B
X
Ventilausführung K-Version
valve version K-version
B1
D
F
SV1
4xM10x21
H
K
Y
357
108,5
133,5
405
190
432 +2
304
BDV B1
X
Ventilausführung N-Version
valve version N-version
6xM8
A5x9 DIN6888
8xM8
1:5
x28
98
2
110
40
50
54
66
74
100
90
M12
148 h8
Y
Lecköl-Ablass Schlauch
Leak oil drain hose
Maßstab /
-
F
E
D
C
A
F
E
D
C
41
A
B
5
6
7
8
1
2
34
5
6
78
Zeichn.-Nr. / Drawing-no. :
B
3
-
233512
±0.1
über / above
Freigabe / Approved
zyxw
Der Lieferant muss sicherstellen, dass die Ware
in einwandfreiem Zustand angeliefert wird
(Korrosionsschutz, Verpackung für sicheren
Layh
Allgemeintoleranzen / General tolerances
Drawing-No.
bis / up to
Dok-ID:
uts
-
0f | Dichtungssatz + Druckschriften zu einem Satz zusammengefasst
1.
Kunde / Customer:
packaging for safe transportation).
model or design.
in proper conditions (corrosion prevention,
22.03.12
2
Ersatz für / replacement for:
The supplier has to ensure the delivery of parts
Transport).
prohibited. Offenders will be held liable for the Dimension Passung / Clearance
Unbemaßte Radien / Undimensioned radii:
Baumustergeprüft / Type examination:
-
K.-Auftrag / C.-Task:
Projektleiter / Project leader:
120
400
±0.5
0.5
6
Oberflächenbehandlung, Härte / Treatment of surface, Hardness:
GEA Bock GmbH - Benzstraße 7 - 72636 Frickenhausen - Germany - www.bock.de
Base part, Raw part:
-
-
-
Bearb. / EditedDatum / Date
payment of damages. All rights reserved in the event Änd.-Nr. / Mod-No.
Werkstoff (Zeile 2+3 alternativ) /
DIN ISO 2768-mK-E
-
-
Geprüft / Appr.
Name
-
Datum / Date
Material (Line 2+3 alternative):
Ausgangsteil, Rohteil /
Workpiece edges
DIN ISO 13715
Erstellt / Drawn 22.03.12
Geprüft / Verified Büttner
1/4
Gneiting
22.03.12
Werkstückkanten /
Page:
400 Benennung / Description:
±0.8
1000
306
-
±0.3
12030
-
Blatt /
±0.2
of the grant of a patent, utility /
DIN EN ISO 1302
Zust. / Rev.
Gußtoleranzen / General casting tolerances:
Gewicht / Weight: (kg)
Zeichnungs-Nr. /
Indication of surface texture
%
S. Büttner
C - FK50/980 N
Rz 25
Rz 160 Rz 1,6
Rz 16
Rz 63 Rz 6,3
Rz 12,5
01.04.19
Status:
Nein / No
Scale:
in Bearbeitung (CAD)
-
13918 .0
01.04.19
01.04.19
01.04.19
01.04.19
S. Büttner
Part-No.
02.05.19
02.05.19
S. Büttner
S. Büttner
S. Büttner
S. Büttner
S. Büttner
M. Schaich
0f | Blindflansch 04269 + 04715 auf 51752 vereinheitlicht
M. Schaich
0f | Unterlagscheiben an Bodenplatte entfernt, Optionale Anbauten (Blatt 4) hinzu
8566
0f | Schraube, Scheibe, Federring am Wellenende entfernt
0f | Schraubenanzugsdrehmoment ergänzt
10164
10597
10567
0851
10447,10463
10619
0f | Entfall von Lötstutzen und zugehörigen Anbauteilen bei K-Version
M. Schaich
M. Schaich
0f | Zylinderstift für Zylinderbuchse aus VDGH entfernt und im Endprodukt aufgenommen
M. Schaich
M. Schaich
-
10468
K - FK50/980 N
M. Schaich
Weitergabe sowie Vervielfältigung dieses Dokuments,
Verwertung und Mitteilung seines Inhalts sind ver-
boten, soweit nicht ausdrücklich gestattet. Zuwider-
handlungen verpflichten zu Schadenersatz. Alle
Rechte für den Fall der Patent-, Gebrauchsmuster-
oder Geschmacksmustereintragung vorbehalten.
The reproduction, distribution and utilization of this
document as well as the communication of its
contents to others without express authorization is
Maß
Oberflächenangaben /
Teile-Nr. /
Layh
M
G
L
C/E
A
A1
SV
X
112,5
255
145
4x 13
112,5
331 (334) +2
372 (380) +2
1.0851-13918.0 0f
Fahrzeugverdichter / Vehicle Compressor
Typ / type Teile-Nr. / part-no. Typ / type Teile-Nr. / part-no.
FK(X)50/660 N 13867 (13875) * FK(X)50/660 K 13868 (13876)
FK(X)50/775 N 13869 (13877) * FK(X)50/775 K 13870 (13878)
FK(X)50/830 N 13916 (13923) FK(X)50/830 K 13917 (13924)
FK(X)50/980 N 13918 (13925) * FK(X)50/980 K 13919 (13926)
* Keine Serie / No series
Anschlüsse /
Connections FK(X)50/
660-980 N FK(X)50/
660-980 K
SV Saugabsperrventil, Rohr (L)* mm - Zoll /
mm - inch 2x35 - 1 3/8" mit Pappscheibe
verschlossen /
closed with
cardboard disc
Suction line valve, tube (L)*
DV Druckabsperrventil, Rohr (L)* mm - Zoll /
mm - inch 35 - 1 3/8"
Discharge line valve, tube (L)*
AAnschluss Saugseite, nicht absperrbar Zoll / inch 1/8“ NPTF
Connection suction side, not lockable
A1 Anschluss Saugseite, absperrbar Zoll / inch 7/16“ UNF
Connection suction side, lockable
BAnschluss Druckseite, nicht absperrbar Zoll / inch 1/8“ NPTF
Connection discharge side, not lockable
B1 Anschluss Druckseite, absperrbar Zoll / inch 7/16“ UNF
Connection discharge side, lockable
CAnschluss Öldrucksicherheitsschalter OIL Zoll / inch 1/8“ NPTF
Connection oil pressure safety switch OIL
DAnschluss Öldrucksicherheitsschalter LP Zoll / inch 1/8“ NPTF
Connection oil pressure safety switch LP
EAnschluss Öldruckmanometer Zoll / inch 1/8“ NPTF
Connection oil pressure gauge
FÖlablass Zoll / inch 1/4“ NPTF
Oil drain
GOpt. Anschlussmöglichkeit Ölsumpfheizung 1) --
Opt. connection oil sump heater 1)
HStopfen Ölfüllung Zoll / inch 1/4“ NPTF
Oil charge plug
KSchauglas Zoll / inch 2 x 1 1/8 “ – 18 UNEF
Sight glass
LAnschluss Wärmeschutzthermostat Zoll / inch 1/8“ NPTF
Connection thermal protection thermostat
MÖlsieb mm M22x1,5
Oil filter
SV1 Opt. Anschlussmöglichkeit Saugabsperrventil --
Opt. connection suction line valve
(L)* = Lötanschluss / brazing connection
1) = Nur ab Werk möglich / ony possible ex factory
( ) K Ausführung
( ) K version Massenschwerpunkt
Centre of gravity Änderungen vorbehalten
Subject to change without notice Maße in mm
Dimensions in mm
N design K design
Dimensions in mm
This manual suits for next models
24
Table of contents
Other GEA Compressor manuals

GEA
GEA InTouch HAX12P/60-4 User manual

GEA
GEA HGX22e/85-4 S CO2 User manual

GEA
GEA HGX46/250-4 S CO2T User manual

GEA
GEA HGZ7 Series User manual

GEA
GEA HG34P Series User manual

GEA
GEA HGX34P Series User manual

GEA
GEA HG34P Series User manual

GEA
GEA ATEX User manual

GEA
GEA HG22e Series User manual

GEA
GEA HG44e/475-4 S User manual