GEA HG22e Series User manual

D
GB
F
E
1
96188-09.2013-DGbFEI
engineering for a better world GEA Refrigeration Technologies
Bock Compressor HG22e
Assembly instructions
HG22e/125-4 HG22e/125-4 S HGX22e/125-4 HGX22e/125-4 S
HG22e/160-4 HG22e/160-4 S HGX22e/160-4 HGX22e/160-4 S
HG22e/190-4 HG22e/190-4 S HGX22e/190-4 HGX22e/190-4 S
1
2
3
4
5
6
7
8
9
10
1 1
12
13

2
D
GB
F
E
96188-09.2013-DGbFEI
1 Safety 4
1.1 Identicationofsafetyinstructions
1.2 Qualicationsrequiredofpersonnel
1.3 Generalsafetyinstructions
1.4 Intendeduse
2 Product description 6
2.1 Shortdescription
2.2 Nameplate
2.3 Typekey
3 Areas of application 8
3.1 Refrigerants
3.2 Oilcharge
3.3 Limitsofapplication
4Compressor assembly 10
4.1 Settingup
4.2 Pipeconnections
4.3 Pipes
4.4 Layingsuctionandpressurelines
4.5 Operatingtheshut-offvalves
4.6 Operatingmodeofthelockableserviceconnections
5 Electrical connection 13
5.1 Informationforcontactorandmotorcontactorselection
5.2 Connectionofthedrivingmotor
5.3 Circuitdiagramfordirectstart230 V ∆/ 400 V Y
5.4 Startunloader
5.5 ElectronictriggerunitMP10
5.6 ConnectionoftheelectronictriggerunitMP10
5.7 FunctionaltestoftheelectronictriggerunitMP10
6 Commissioning 18
6.1 Preparationsforstart-up
6.2 Pressurestrengthtest
6.3 Leaktest
6.4 Evacuation
6.5 Refrigerantcharge
6.6 Start-up
6.7 Avoidingslugging
6.8 Connectionofoillevelregulator
7 Maintenance 20
7.1 Preparation
7.2 Worktobecarriedout
7.3 Sparepartsrecommendation
7.4 Accessories
7.5 Extractfromthelubricantstable
7.6 Decommissioning
8 Technical data 22
9 Dimensions and connections 23
10 Declaration of conformity and installation 24
11 Service 25
About these instructions
Readtheseinstructionsbeforeassemblyandbeforeusingthecompressor.Thiswillavoidmisunder-
standings andpreventdamage.Improperassemblyanduseofthecompressorcanresultinserious
orfatalinjury.
Observethesafetyinstructionscontainedintheseinstructions.
Theseinstructionsmustbepassedontotheendcustomeralongwiththeunitinwhichthecompres-
sorisinstalled.
GEABockGmbH
72636Frickenhausen
GEABockGmbH
Benzstraße7
72636Frickenhausen
Germany
Telephone+49702294540
Fax +4970229454137
www.bock.de
Manufacturer
Contact

D
GB
F
E
3
96188-09.2013-DGbFEI
Contents Page
1 Safety 4
1.1 Identicationofsafetyinstructions
1.2 Qualicationsrequiredofpersonnel
1.3 Generalsafetyinstructions
1.4 Intendeduse
2 Product description 6
2.1 Shortdescription
2.2 Nameplate
2.3 Typekey
3 Areas of application 8
3.1 Refrigerants
3.2 Oilcharge
3.3 Limitsofapplication
4Compressor assembly 10
4.1 Settingup
4.2 Pipeconnections
4.3 Pipes
4.4 Layingsuctionandpressurelines
4.5 Operatingtheshut-offvalves
4.6 Operatingmodeofthelockableserviceconnections
5 Electrical connection 13
5.1 Informationforcontactorandmotorcontactorselection
5.2 Connectionofthedrivingmotor
5.3 Circuitdiagramfordirectstart230 V ∆/ 400 V Y
5.4 Startunloader
5.5 ElectronictriggerunitMP10
5.6 ConnectionoftheelectronictriggerunitMP10
5.7 FunctionaltestoftheelectronictriggerunitMP10
6 Commissioning 18
6.1 Preparationsforstart-up
6.2 Pressurestrengthtest
6.3 Leaktest
6.4 Evacuation
6.5 Refrigerantcharge
6.6 Start-up
6.7 Avoidingslugging
6.8 Connectionofoillevelregulator
7 Maintenance 20
7.1 Preparation
7.2 Worktobecarriedout
7.3 Sparepartsrecommendation
7.4 Accessories
7.5 Extractfromthelubricantstable
7.6 Decommissioning
8 Technical data 22
9 Dimensions and connections 23
10 Declaration of conformity and installation 24
11 Service 25

4
D
GB
F
E
96188-09.2013-DGbFEI
1|Safety
1.2 Qualicationsrequiredofpersonnel
1.3 General safety instructions
WARNING! Inadequately qualied personnel poses the risk of accidents, the
consequence being serious or fatal injury. Work on compressors
mustthereforeonlybeperformedbypersonnelwiththequalica-
tions listed below:
•For example, a refrigeration technician, refrigeration mechatron-
icsengineer.Aswellasprofessionswithcomparabletraining,which
enablepersonneltoassemble,install,maintainandrepairrefrigeration
andair-conditioningsystems.Personnelmustbecapableofassessing
theworktobecarriedoutandrecognisinganypotentialdangers.
WARNING! •Refrigerating compressors are pressurised machines and
thereforerequireparticularcautionandcareinhandling.
•Risk of burns! Depending on the operating conditions, surface
temperatures of over 60 °C on the pressure side or below 0 °C on
the suction side can be reached.
•The maximum permissible overpressure must not be exceeded,
even for testing purposes.
1.1 Identicationofsafetyinstructions:
DANGER! Indicatesadangeroussituationwhich,ifnot
avoided,willcauseimmediatefatalorseriousinjury.
WARNING!
Indicatesadangeroussituationwhich,ifnot
avoided,maycausefatalorseriousinjury.
CAUTION!
Indicatesadangeroussituationwhich,ifnot
avoided,maycausefairlysevereorminorinjury.
ATTENTION! Indicatesasituationwhich,ifnot
avoided,maycausepropertydamage.
INFO! Importantinformationortipsonsimplifyingwork.

D
GB
F
E
5
96188-09.2013-DGbFEI
1|Safety
TheseassemblyinstructionsdescribethestandardversionoftheHG22emanufacturedbyBock.The
compressorisintendedforuseinrefrigerationsystemsincompliancewiththelimitsofapplication.
Onlytherefrigerantspeciedintheseinstructionsmaybeused.
Any other use of the compressor is prohibited!
TheBockrefrigeratingcompressornamedinthetitleisintendedforinstallinginamachine(within
theEUaccordingtotheEUDirectives2006/42/ECMachineryDirective,97/23/ECPressureEquipment
Directiveand2006/95/EC–LowVoltageDirective).
Commissioningisonlypermissibleifthecompressorhasbeeninstalledinaccordance withthese
assembly instructions and the entire system into which it is integrated has been inspected and
approvedinaccordancewithlegalregulations.
1.4 Intended use
WARNING! The compressor may not be used in potentially
explosive environments!

6
D
GB
F
E
96188-09.2013-DGbFEI
1
2
3
4
5
6
7
8
9
10
1 1
12
13
2|Product description
• Semi-hermetictwo-cylinderreciprocatingcompressorwithoilpumplubrication.
• Suctiongascooleddrivemotor.
2.1 Short description
Nameplate
Fig.1
Fig.2
Oilsightglass
Cylindercover
Oilpump
Terminalbox
Suction
shut-offvalve
Drivesection
Motorsection
DimensionandconnectionvaluescanbefoundinChapter9
Transporteyelet
Valveplate
Discharge
shut-offvalve

D
GB
F
E
7
96188-09.2013-DGbFEI
2|Product description
2.2 Name plate(example)
1 Typedesignation 6 Voltage,circuit,frequency
2 Machinenumber 7 Nominalrotationspeed
3 maximumoperatingcurrent 8 Displacement
4 Startingcurrent(rotorblocked) 9 Voltage,circuit,frequency
5 ND(LP):max.admissibleoperating 10 Nominalrotationspeed
pressure(g)Lowpressureside 11 Displacement
HD(HP):
max.admissibleoperating
12 Oiltypelledatthefactory
pressur
e(g)Highpressureside 13 Terminalboxprotectiontype
Observe the limits of application Electrical accessories can change
diagrams! the IP protection class!
50 Hz
}
60 Hz
}
/
HG 22 e 190-4 SX
2.3 Typekey (example)
¹)HG-HermeticGas-cooled(suctiongas-cooled)forthenormal-/airconditioningapplications
²)X
- Esteroilcharge(HFCrefrigerant,e.g.R134a,R404A/R507,R407C)
³)S - Morepowerfulmotor,e.g.forair-conditioningapplications
Motorvariant³)
Numberofpoles
Sweptvolume
e-series
Numbersofcylinders
Size
Oilcharge²)
Series¹)
Typschild (Beispiel)
1
2
3
4
513
12
7
11
6
10
8
9
1 Typbezeichnung
2 Maschinennummer
3 maximaler Betriebsstrom
4 Anlaufstrom (Rotor blockiert)
5 ND (LP): max. zulässiger Stillstandsdruck
Saugseite
HD (HP): max. zulässiger Betriebsdruck
Hochdruckseite
Einsatzgrenzendiagramme beachten!
50 Hz
60 Hz
6 Spannung, Schaltung, Frequenz
7 Nenndrehzahl
8 Hubvolumen
9 Spannung, Schaltung, Frequenz
10 Nenndrehzahl
11 Hubvolumen
12 Werkseitig eingefüllte Ölsorte
13 Schutzart Klemmenkasten
HGX22e/190-4
SE 55
AS35830A001
13,8/8,0A
69A 40A
66
GEA Bock GmbH
72636 Frickenhausen, Germany
Fig.3

8
D
GB
F
E
96188-09.2013-DGbFEI
3|Areas of application
ATTENTION! Compressor operation is possible within the operating limits
shown in the diagrams. Please note the signicance
of the shaded areas. Thresholds should not be selected as design
or continuous operation points.
- Max. permissible discharge end temperature 140 °C
-Max.permissibleswitchingfrequency8x/h.
- A minimum running time of 3 min. steady-state condition
(continuous operation) must be achieved.
For operation with additional cooling:
- Use only oils that are highly thermally stable.
- Avoid continuous operation near the limits.
Foroperationwithfrequencyconverter:
- The maximum current and power consumption must not be
exceeded. Inthecaseofoperationabovethemainsfrequency,
the application limit can therefore be limited.
When operating in the vacuum range, there is a danger of air
enteringonthesuctionside.Thiscancausechemicalreactions,
a pressure rise in the condenser and an elevated compressed-gas
temperature. Prevent the ingress of air at all costs!
Thecompressorsarelledatthefactorywiththefollowingoiltype:
-forR134a,R404A/R507,R407C FUCHSRenisoTritonSE55
-forR22 FUCHSRenisoSP46
Compressorswithesteroilcharge(FUCHSRenisoTritonSE55)aremarkedwithanXinthetype
designation(e.g.HGX22e/190-4).
3.1 Refrigerants
• HFKW/HFC: R134a,R404A/R507,R407C
• (H)FCKW/(H)CFC: R22
3.2 Oil charge
3.3 Limits of application
INFO! Forrefilling,werecommendtheaboveoiltypes.
Alternatives: seelubricantstable,Chapter7.5.
The oil level must be in the
visible part of the sight
glass; damage to the com-
pressor is possible if over-
filled or underfilled!
max.oillevel
min.oillevel
ATTENTION!
Fig.4

D
GB
F
E
9
96188-09.2013-DGbFEI
Evaporationtemperature(°C)
Condensingtemperature(°C)
Suctiongassuperheat(K)
Suctiongastemperature(°C)
3|Areas of application
Design for other
areasonrequest
R134a
R407C
R404A/R507
R22
Fig.5
Fig.6
Fig.7
Fig.8
Unlimitedapplicationrange
Supplementarycoolingor
reducedsuctiongastemperature
Supplementarycoolingand
reducedsuctiongastemperature
MotorversionS
(morepowerfulmotor)
1) LP=Lowpressure
HP=Highpressure
Max. permissible operating
pressure (LP/HP)1): 19/28 bar

10
D
GB
F
E
96188-09.2013-DGbFEI
?
4|Compressor assembly
4.1 Setting up
Setuponanevensurfaceorframewithsufcientload-
bearingcapacity.
Singlecompressorpreferablyonvibrationdamper.
Duplexandparallelcircuitsalwaysrigid.
Usetransporteyelet.
Donotliftmanually!
Useliftinggear!
Provideadequateclearanceformaintenancework.
Ensureadequatecompressorventilation.
Donotuseinacorrosive,dusty,dampatmosphereora
combustibleenvironment.
Fig.9
Fig.10
Fig.11
Fig.12
4.2 Pipe connections
The pipe connectionshavegraduatedinsidediameterssothatpipeswith
standartmillimetreandinchdimensionscanbeused.
Theconnectiondiametersoftheshut-offvalvesareratedformaximum
compressoroutput.Theactualrequiredpipecrosssectionmustbe
matched to the output. The same applies for non-return valves.
Fig.13:graduated
internaldiameter
F
E
D
C
B
A
1
2
3
4
F
E
D
C
4
3
2
1
A
B
Tol.-Ang. DIN ISO 2768-mK
Ra Rz
Maß
Passung
Freigabe
Alternativbezug:
Baumustergeprüft
Teil inaktiv
Lieferantenzeichnung
-
-
K.-Auftrag:
PL:
Zeichnung ungültig
Entwicklungsstand
Teil keine Serie
120
400
±0.5
über 0.5
bis 6
Benzstraße 7 - 72636 Frickenhausen - Germany - www.bock.de
-
-
Unbemaßte Radien:
-
Diese Zeichnung ist unser Eigentum!
Sie darf ohne unsere Genehmigung weder nach-
gebildet, vervielfältigt, oder Dritten Personen zu-
gänglich gemacht werden. Der Nachbau nach
dieser Zeichnung, oder an Hand der nach dieser
Zeichnung hergestellten Gegenstände durch den
Abnehmer oder Dritte ist nicht gestattet.
Wir behalten uns alle Rechte, gemäß DIN ISO 16016
an dieser Zeichnung vor.
Bearb.
Datum
Änderungs-Nr.
Werkstoff:
Ausgangsteil, bzw. Rohteil:
--
Gepr.
Name
Datum
19.04.
Werkstückkanten
DIN ISO 13715
Ersatz für:
Ersetzt durch:
Erstellt
2010
Geprüft
-
Kurz
Zone
1/x
Oberflächenbehandlung / Härte:
-
Blatt:
Änderungsbeschreibung
400
Benennung:
±0.8
1000
30
6
-
±0.3
120
30
±0.2
Zeichn.-Nr. Teile-Nr.
Oberflächenangaben ISO 1302
x.xxxx-xxxxx.x
Zust.
Gußtoleranzen:
Gewicht: (kg)
±0.1
Maßstab:
1:1
Wasserwaage
für Indesign
Der Lieferant muß sicherstellen, dass die Ware in
einwandfreiem Zustand angeliefert wird (Korrosions-
schutz, Verpackung für sicheren Transport).
Rz 25
Rz 160
s
25
z
y
x
w
u
t
0,05
Rz 1,6
0,3
0,7
1,6
2
Rz 16
6,3
Rz 63
Rz 6,3
Rz 12,5
F:\user\kurz\3D Sachen\3D Teile\Zeichnungen\Wasserwaage
INFO! Newcompressorsarefactory-lledwithinertgas(3barnitrogen).
Leave this service charge in the compressor for as long as possible
and prevent the ingress of air.
Check the compressor for transport damage before starting any
work.
ATTENTION! Do not solder as long as the compressor is under pressure.
Superheating can damage the valve. Remove the pipe supports
therefore from the valve for soldering and accordingly cool
the valve body during and after soldering.
Only solder using inert gas to inhibit oxidation products (scale).

D
GB
F
E
11
96188-09.2013-DGbFEI
4.4 Laying suction and pressure lines
INFO! Proper layout of the suction and pressure lines directly after the
compressor is integral to the smooth running and vibration behaviour
of the system.
ATTENTION! Improperly installed pipes cancause cracks and tears whichcan
resultinalossofrefrigerant,
A rule of thumb:
Alwayslaytherstpipesectionstartingfromtheshut-offvalvedownwards and
parallel to the drive shaft.
4|Compressor assembly
4.3 Pipes
Pipesandsystemcomponentsmustbecleananddryinsideandfreeofscale,swarfandlayersof
rustandphosphate.Onlyuseair-tightparts.
Lay pipes correctly. Suitable vibration compensators must be provided to prevent pipes being
crackedandbrokenbyseverevibrations.
Ensureaproperoilreturn.
Keeppressurelossestoanabsoluteminimum.
Fig.14
As short as
possible
Rigid
fixed point

12
D
GB
F
E
96188-09.2013-DGbFEI
4|Compressor assembly
Pipeconnection
Pipeconnection
4.6 Operatingmodeofthelockableserviceconnections
Fig.17
Opening the shut-off valve:
Spindle:turntotheleft(counter-clockwise)asfarasitwillgo.
—>Shut-offvalvecompletelyopened/serviceconnectionclosed.
Fig.18
Opening the service connection
Spindle:Turn½-1turntotherightclockwise.
—>Serviceconnectionopened/shut-offvalveopened.
Serviceconnec-
tionclosed
Connection
blocked
Spindle
Serviceconnec-
tionopened
Spindle Connection
open
Compressor
Compressor
Valve spindle seal
Release
Tighten
Beforeopeningorclosingtheshut-offvalve,releasethevalvespindlesealbyapprox.¼ofaturn
counter-clockwise.
Afteractivatingtheshut-offvalve,re-tightentheadjustablevalvespindlesealclockwise.
Fig.15 Fig.16
4.5 Operating the shut-off valves

D
GB
F
E
13
96188-09.2013-DGbFEI
5|Electrical connection
5 Electrical connection
DANGER! Highvoltage!Riskofelectricshock!Onlycarryoutworkwhenthe
electrical system is disconnected from the power supply!
INFO! Connectthecompressormotorinaccordancewiththecircuitdiagram
(seeinsideofterminalbox).
Use suitable cable entry point of the correct protection type
(see name plate) for routing cables into the terminal box.
Insert the strain reliefs and prevent chafe marks on the cables.
Comparethevoltageandfrequencyvalueswiththedataforthemains
powersupply.Only connect the motor if these values are the same.
5.1 Information for contactor and motor contactor selection
Allprotectionequipment,switchingandmonitoringdevicesmustcomplywiththelocalsafetyregula-
tionsandestablishedspecications(e.g.VDE)andregulationsaswellasthemanufacturer’sspecica-
tions.Motorprotectionswitchisrequired!Motorcontactors,feedlines,fusesandmotorprotection
switchesmustberatedaccordingtothemaximumoperatingcurrent(seenameplate).
Usethefollowingoverloadprotectiondevice:
Acurrent-dependenttime-delayedoverloadprotectiondeviceformonitoringofallthreephases,not
sethigherthantheratedcurrentofthemachine,whichmustrespondat1.2timesthesetcurrent
within2hoursandmustnothaverespondedat1.05timesthesetcurrentwithin2hours,oranother
comparabledevice.
5.2 Connection of the driving motor
Thecompressorisdesignedwithamotorforstar-deltacircuits.
Designationonthenameplate Stickerontheterminalbox
∆/ Y
Star-delta start-up is only possible on 230 V voltage supply. Example:
230 V ∆
Direct start Star-delta start
400 V Y
Direct start only
Elektrischer Anschluss
Electrical connection
Raccordement électrique ∆/ Y
96027-11.06-DGbF
∆
Niedere Spannung
Low voltage
Bas voltage
Y
Hohe Spannung
High voltage
Haut voltage
L3
L1 L2
L3
L1 L2
Elektrischer Anschluss
Electrical connection
Raccordement électrique ∆/ Y
96027-11.06-DGbF
∆
Niedere Spannung
Low voltage
Bas voltage
Y
Hohe Spannung
High voltage
Haut voltage
L3
L1 L2
L3
L1 L2
L1 L2 L3
L1 L2 L3
INFO! The connection examples shown refer to the standard
version.Inthecaseofspecialvoltages,theinstructionsafxedtothe
terminal box apply.

14
D
GB
F
E
96188-09.2013-DGbFEI
5.3 Circuit diagramm for direct start 230 V ∆/ 400 V Y
Fig.19 Compressorterminalbox
R1 ColdconductorPTCsensormotorwinding
R2 Thermalprotectionthermostat(PTCsensor)
F1 Loadcircuitsafetyswitches
F2 Controlpowercircuitfuse
F3 Safetychain(high/lowpressuremonitoring)
B1 Releaseswitch(thermostat/pressostat)
Q1 Mainswitch

D
GB
F
E
15
96188-09.2013-DGbFEI
S1 Controlvoltageswitch
M1 Compressormotor
K1 Compressorcontactor
MP10 ElectronictriggerunitMP10
E Oilsumpheater
X3 Terminalstripinterminalbox
XSS Terminalstripintheexternalswitchcabinet
A1 AlarmMotorprotection
A2 OverheatingR1,R2
A3 Alarmhighpressure
XSS Terminalstripintheexternal
switchcabinet

16
D
GB
F
E
96188-09.2013-DGbFEI
5|Electrical connection
PTC1 PTC2
Terminalbox
Fig.20
ATTENTION!
Terminals 1 - 6 on the trigger
unit MP 10 and terminals PTC
1 and PTC 2 on the compres-
sor terminal board must not
come into contact with mains
voltage. This would destroy the
trigger unit and PTC sensors.
The supply voltage at L1-N
(+/- for DC 24 V version) must
be identical to the voltage at
terminals11,12,14and43.
5.5 Electronic trigger unit MP 10
The compressor motor is tted with cold conductor temperature sensors (PTC) connected to the
electronictriggerunitMP10intheterminalbox.ReadinesstooperateissignalledbytheH3LED
(green)afterthepowersupplyisapplied.Inthecaseofexcesstemperatureinthemotorwinding,the
unitswitchesoffthecompressorandtheH1LEDlightsred.
Thehotgassideofthecompressorcanalsobeprotectedagainstovertemperatureusingathermal
protectionthermostat(accessory).TheH2LED(red)isprovidedfortheprotectionfunction.
The unit trips when an overload or inadmissible operating conditions occur. Find and remedy
the cause.
5.6 Connection of the trigger unit MP10
INFO! Connect the trigger unit MP10 in accordance with the circuit dia-
gram. Protect the trigger unit with a delayed-action fuse (F) of max.
4A.Inordertoguaranteetheprotectionfunction,installthetrigger
unitastherstelementinthecontrolpowercircuit.
Temperaturemonitoringconnections:
Motorwinding: Terminals1-2
Thermalprotectionthermostat: Terminals3-4
Restartprevention: Terminals5-6
5.4 Start unloader
ToavoidcurrentpeaksduringthestartingphasewerecommendusingtheBock-ESSsoftstarting
device(ElectronicSoftStart).Referto"Accessories"forfurtherinformation.
INFO!
Theunithasarestartpreventiondevice.Afteryouhaverectiedthe
fault,interruptthemainsvoltage.Thisunlockstherestartprevention
device and the LEDs H1 and H2 go out.

D
GB
F
E
17
96188-09.2013-DGbFEI
5|Electrical connection
ThecompressorandthetriggerunitMP10areoperationalwhentheH3LED(green)lights.
5.7 Function test of the trigger unit MP 10
Pos Procedure LED H1 LED H2 LED H3
red red green
1•Interrupt power supply (L1 or S1) OFF OFF OFF
•Releasethemotortemperaturesensorconnection(1or2)
•Releasethehotgastemperaturesensor(ifinstalled)(3or4)
2•Restore the power supply (L1 or S1) ON
•Functioncheckofmotortemperaturesensor:operational ON
•Functioncheckofhotgastemperaturesensor:operational ON
3•Interrupt power supply again (L1 or S1) OFF OFF OFF
•Reconnectterminals1or2and/or3or4
4•Restore the power supply (L1 or S1): OFF OFF ON
•MP10isoperationalagain
Beforestart-up,troubleshootingormakingchangestothecontrolpowercircuit,checkthefunctionality
ofthetriggerunit:

18
D
GB
F
E
96188-09.2013-DGbFEI
6|Commissioning
6.1 Preparations for start-up
6.4 Evacuation
Firstevacuatethesystemandthenincludethe compressor in the evacuation process.
Relievethecompressorpressure.
Openthesuctionandpressurelineshut-offvalves.
Evacuatethesuctionanddischargepressuresidesusingthevacuumpump.
Attheendoftheevacuationprocess,thevacuumshouldbe<1.5mbarwhenthepumpisswitchedoff.
Repeatthisprocessasoftenasisrequired.
ATTENTION! Do not start the compressor if it is under vacuum. Do not apply
any voltage - even for test purposes (must only be operated with
refrigerant).
Under vacuum, the spark-over and creepage current distances of the
terminalboardconnectionboltsshorten;thiscanresultinwindingand
terminalboarddamage.
INFO! In order to protect the compressor against inadmissible operating
conditions,high-pressureandlow-pressurepressostatscontrolsare
mandatory on the installation side.
Thecompressorhasundergonetrialsinthefactoryandallfunctionshavebeentested.Thereare
thereforenospecialrunning-ininstructions.
Checkthecompressorfortransportdamage!
6.2 Pressure strength test
DANGER! Bursting! The compressor must only be pressurised using nitrogen
(N2). Never pressurise with oxygen or other gases!
The maximum permissible overpressure of the compressor must not
be exceeded at any time during the testing process (see name plate
data)! Do not mix any refrigerant with the nitrogen as this could
cause the ignition limit to shift into the critical range.
Thecompressorhasbeenfactory-testedforpressureresistance.Thefollowingmustbeobservedif
theentireplantissubjectedtoanadditionalpressurestrengthtest:
TesttherefrigerationcircuitaccordingtoEN378-2oracorrespondingsafetystandard.
6.3 Leaktest
DANGER! Bursting!
Do not mix any refrigerant with the nitrogen (N2) as this could cause
the ignition limit to shift into the critical range.
CarryouttheleaktestoftherefrigeratingsysteminaccordancewithEN378-2oracorresponding
safetystandardwithout including the compressor.

D
GB
F
E
19
96188-09.2013-DGbFEI
6|Commissioning
CAUTION! Wear personal protective clothing such as goggles and protective
gloves!
Makesurethatthesuctionandpressurelineshut-offvalvesareopen.
Withthecompressorswitchedoff,addtheliquidrefrigerantdirectlytothecondenserorreceiver,
breakingthevacuum.
Iftherefrigerantneedstoppingupafterstartingthecompressor,itcanbetoppedupinvapour
formonthesuctionside,or,takingsuitableprecautions,alsoinliquidformattheinlettothe
evaporator.
INFO! Avoidoverllingthesystemwithrefrigerant!
In order to prevent shifts in concentration, zeotropic refrigerant
blends (e.g. R407C) must always only be added to the refrigerating
systeminliquidform.
Do not pour liquid refrigerant through the suction line shut-off
valve on the compressor.
It is not permissible to mix additives with the oil and refrigerant.
6.5 Refrigerant charge
6.6 Start-up
WARNING! Ensure that both shut-off valves are open before starting the
compressor!
Checkthatthesafetyandprotectiondevices(pressureswitch,motorprotection,electricalcon-
tactprotectionmeasures,etc.)arefunctioningproperly.
Switchonthecompressorandletitrunforatleast10minutes.
Checktheoil level:Theoilmustbevisibleinthesightglass.
ATTENTION!Iflargerquantitiesofoilhavetobetoppedup,thereisariskofoil
impacteffects.Ifthisisthecase,checktheoilreturn!
6.7 Avoid slugging
ATTENTION! Slugging can result in damage to the compressor and cause
refrigeranttoleak.
To prevent slugging:
Thecompleterefrigerationplantmustbeproperlydesigned.
Allcomponentsmustbecompatiblyratedwitheachotherwithregardtooutput(particularlythe
evaporatorandexpansionvalves).
Suctiongassuperheatingatthecompressorinputshould be min. 7 - 10K(checkthesettingof
theexpansionvalve).
Thesystemmustreachastateofequilibrium.
Particularlyincriticalsystems(e.g.severalevaporatorpoints),measuressuchastheuseofliquid
traps,solenoidvalveintheliquidline,etc.arerecommended.
There should be no movement of refrigerant in the compressor while the system is at a
standstill.

20
D
GB
F
E
96188-09.2013-DGbFEI
7.1 Preparation
7.2 Worktobecarriedout
7|Maintenance
Inordertoguaranteeoptimumoperationalreliabilityandservicelifeofthecompressor,we recommend
carryingoutservicingandinspectionworkatregularintervals:
Oil change:
- notmandatoryforfactory-producedseriessystems.
- foreldinstallationsorwhenoperatingneartheapplicationlimit:forthersttimeafter100
to 200 operating hours, then approx. every 3 years or 10,000 - 12,000 operating hours.
Disposeofusedoilaccordingtotheregulations;observenationalregulations.
Annual checks: Oil level, leak tightness, running noises, pressures, temperatures, function of
auxiliarydevicessuchasoilsumpheater,pressureswitch.
WARNING! Beforestartinganyworkonthecompressor:
Switch off the compressor and secure it to prevent a restart.
Relieve compressor of system pressure.
Preventairfrominltratingthesystem!
After maintenance has been performed:
Connect safety switch.
Evacuate compressor.
Releaseswitch-onlock.
6.8 Connection of oil level regulator
Theconnection"O"isprovidedforinstallinganoillevelregulator.Acorrespondingadaptermustbe
obtainedfromthetrade.
6|Commissioning
OnlyusegenuineBockspareparts!
7.3 Spare parts recommendation
HG22e / ... 125-4(S) 160-4(S) 190-4(S)
Designation Ref. No. Ref. No. Ref. No.
Setofgaskets 80313
Valveplatekit 80305 80306
Oilpumpkit 08324
This manual suits for next models
9
Table of contents
Other GEA Compressor manuals

GEA
GEA HG34P Series User manual

GEA
GEA Bock FK50 Series User manual

GEA
GEA HAX2 CO2 T User manual

GEA
GEA HGX46/250-4 S CO2T User manual

GEA
GEA HGX34P Series User manual

GEA
GEA ATEX User manual

GEA
GEA HGX22e/85-4 S CO2 User manual

GEA
GEA HG44e/475-4 S User manual

GEA
GEA Bock EX-HG88e Series User manual

GEA
GEA InTouch HAX12P/60-4 User manual
Popular Compressor manuals by other brands

Becker
Becker DT 4.8 operating instructions

W4RT Electronics
W4RT Electronics One Big Punch installation manual

Dorin innovation
Dorin innovation CDS 11 operating instructions

Kasco
Kasco Teich-Aire KM Series Operation & maintenance manual

Boge
Boge S Series operating instructions

Woodstar
Woodstar cb 24of instruction manual