Genius GE-R4 User manual

GE-R4
MANUAL
1 2 3 4
Installation / User’s Guide
ATTENTION ELECTRICIAN
SEE WIRING DETAILS ON PAGES A-3
ADDITIONAL INFORMATION IN SECTION B
WIRING DIAGRAM
INDEX / WARRANTY
INSTALLATION
www.monitrol.com

WARNINGS AND PRECAUTIONS
Although the manufacturer has made every effort to ensure the accuracy of the information
contained herein, this document is subject to change without notice due to ongoing product
development.
WARNINGS AND PRECAUTIONS
Equipment, blown fuses and/or tripped breakers may prove harmful to the contents of the
building. Therefore it is strongly recommended to install backup devices. Spare equipment should
also be available at the owner’s site. Equipment manufactured by the manufacturer is protected
against normal line surges. High surges caused by thunder storms or power supply equipment
may damage this equipment. For added security against line voltage surges it is recommended
that surge and noise suppression devices be installed at the electrical distribution panel. These
devices are available from most electrical supply distributors.
RECOMMENDATIONS
The manufacturer recommends that all installation procedures described herein be performed by a
qualified electrician or installation technician. Further more the manufacturer recommends to test
all the functions, including the backup devices, after installation, after changes to the installation
and every month after that.
Fuse verification and replacement, as well as the proper setting of control values shall be the
responsibility of the owner of this equipment.
www.monitrol.com

GE-R4 WIRING DIAGRAM
GE-R4 Section A-3
Wiring Diagram
WIRING DIAGRAM GE-R4
WIRING DIAGRAM
Yanick Alain
GE-R4
13/04/07
DRAW
CONFIGURATION
WIR
/DIAGIC/GE-R4
FILE
REV
0
1265 A
GE-R4
32
L1 L2/N OUTPUT
COIL
SIGNAL
1
POWER
INPUT
STAGE 1
L1 L2/N OUTPUT
COIL
SIGNAL
3
POWER
INPUT
STAGE 3
L1 L2/N OUTPUT
COIL
SIGNAL
4
POWER
INPUT
STAGE 4
L1 L2/N OUTPUT
COIL
SIGNAL
2
POWER
INPUT
STAGE 2 NEUTRAL
FOR COILS
L2
L1
L2
L1
L2
L1
L2
L1
N
MASTER CONTROLLER
OUT 1
L1
OUT 2
L1
OUT 3
L1
OUT 4
L1
32 32 32
www.monitrol.com

GE-R4 WIRING DIAGRAM
GE-R4
Section A-4
GE-R4
Electrician’s notes
wiring tips and hints (see guide for details)
HIGH VOLTAGE WIRE INSTALLED ACCORDING TO LOCAL WIRING CODE.
THE CURRENT SHALL NOT EXCEED 25A, 3HP AT EACH OUTPUT (OUT).
MAXIMUM 2 WIRES OF SAME SIZE PER BLACK TERMINAL, NO BIGGER
THAN AWG #12, NO SMALLER THAN AWG #22.
1
2
3
www.monitrol.com

GE-R4 INSTALLATION
GE-R4
Section B-5
This section will inform the electrician on proper wiring and installation procedures for
the GE-R4.
The manufacturer recommends that the following installation instructions be followed to
as closely as possible, and that all work be performed by a certified electrician. Failure to
do so may void the warranty.
Description
The GE-R4 is designed to drive four stages of up to 25A under the control of a master
control system resulting in a clean air environment for your livestock.
It provides you with automated control over its four stages via the use of the master
control or alternatively by manual switch.
It will also keep you constantly informed of its four stages via LED indications. As the
LED will be lighted when the output is activated.
Unpacking
Unpack the GE-R4 and inspect contents for damage. Should the contents appear to be
damaged, contact your local distributor to return the material.
The package should contain the following standard items:
1 GE-R4 module
4 Bracket / 4 screws
1 Spare fuse
1 Installation / User’s Guide
Mounting Hardware Required
This is the list of the mounting hardware needed, which is not included with the product:
4 screws (to hang the unit onto the wall)
Screwdrivers
Soldering iron kit or approved sealed connectors
www.monitrol.com

GE-R4 INSTALLATION
GE-R4
Section B-6
General installation guidelines
GE-R4 Module
- It is recommended to install the module unit in a hallway to limit the GE-R4 exposure
to noxious gases.
- In order to avoid condensation problems inside the module, it is recommended to
install the GE-R4 on an inside wall. If it is not possible, use spacers to have an air gap
between the wall and the GE-R4.
- It is required to install the GE-R4 right side up with the cable entry holes facing
down.
- The enclosure is watertight, but do not spray water or submerge the GE-R4 in water.
Cover it carefully with plastic when cleaning the room.
- The GE-R4 should be installed in easy-access location but away from damaging
elements (heat, cold, water, direct sunlight, …).
- Do not drill the face, the side, the top or the underside of the control.
- Do not install the GE-R4 module near high-voltage equipment, power supply or
transformer.
Electrical Cables
- All electrical cables must be installed according to local wiring codes.
- Use separate conduits for the low voltage cables (communication) and the high
voltage cables. There must be at least 30 cm (1 foot) between low-voltage and high-
voltage conduits.
- If a low voltage cable has to cross over a high voltage cable, make this crossing at
90°.
- It is prohibited to use overhead cables outside the building.
Electrical Power
- Protection from electrical surges should be included in the planning of each
installation.
- Every module should have a separate breaker to avoid possible problem.
www.monitrol.com

GE-R4 INSTALLATION
GE-R4 Section B-7
Mounting
- The enclosure must be mounted in a location that will allow the cover to be
completely opened right up against the wall.
- Fasten the four brackets to the four mounting holes on the back of the enclosure,
using the four screws provided with the brackets.
- Then mount the enclosure on the wall by inserting screws through the brackets’
adjustment slots, into the wall. Make sure to position the enclosure so that all wires
extends out of the bottom section of the enclosure.
- The bracket slots also serve to adjust the position of the controller.
- Once you have adjusted the controller position, tighten the four mounting screws. (see
figure 1).
FIGURE NO. 1 Mounting Position and Devices
www.monitrol.com

GE-R4 INSTALLATION
GE-R4
Section B-8
Layout Board
FIGURE NO. 2 GE-R4 Electronic module Board
L1 L2/N
STAGE 1
OUTPUT
POWER
INPUT
COIL
SIGNAL
1
L1 L2/N
STAGE 2
OUTPUT
POWER
INPUT
COIL
SIGNAL
2
NEUTRAL
FOR COILS
L1 L2/N
STAGE 3
OUTPUT
POWER
INPUT
COIL
SIGNAL
3
L1 L2/N
STAGE 4
OUTPUT
POWER
INPUT
COIL
SIGNAL
4
www.monitrol.com

GE-R4 INSTALLATION
GE-R4 Section B-9
Powering Up Procedure
Verify all Connections
Once the GE-R4 is properly mounted on the wall and all modules to the terminal block,
perform the following steps:
- Ensure the flat cable between the bottom electronic board and the faceplate electronic
board is properly connected.
- Seal all cable entry holes.
Hermetically Close the GE-R4
Close the front panel and the lower access cover.
Put the power on
Secure the front panel with a lock
Using the toggle switches
The toggle switches permit the stage to be set in one of three modes as follows:
OFF To turn the stages permanently off, set the toggle switches to the OFF
position.
ON To turn the stages continually on, set the toggles switches to the ON position.
AUTO To allow the stages to operate under the master control, set the toggles
switches to the AUTO position.
Output LED
The output LED indicates if power is present at the stage output either in auto or manual
mode.
Changing fuse
The fuse protects the relay coil from any surge or over voltage. Remove stage input
power and coil signal power before changing a fuse.
Troubleshooting
Set the toggle switches on the GE-R4 to ON.
Are the outputs operating?
If not, verify the power connections to the GE-R4, fuses and connections to the outputs
(i.e. Fans).
www.monitrol.com

GE-R4 INSTALLATION
GE-R4
Section B-10
Specifications Module GE-R4
DESCRIPTION VALUE
Storage temperature -4°F to 131°F (-20°C to 55°C)
Operating temperature 32°F to 122°F (0°C to 50°C)
Humidity 90% maximum Non-condensing
Weight 2 lbs. (0.9Kg)
Size 11” x 17” x 5.5” (27.9 cm x 43.2 cm x 14 cm)
Norms CSA (NRTL/C)
Protection index IP 54 (dust and splashing water)
Warranty 2 years
RELAY OUTPUT
Maximum Load For Stages 1 -4 1HP @ 120VAC,
3HP @ 240VAC,
25A @ 250VAC resistive
Important Notice.
- Low-voltage and high-voltage wire must be passed through different conducts at
least 1 foot (30 cm) apart. If low-voltage and high-voltage conduits must be
crossed, the crossing must be at a 90-degree angle.
- All wiring must be made by a certified electrician and conform to local electrical
regulations.
www.monitrol.com

GE-R4 INDEX / WARRANTY
GE-R4 Section C-11
INDEX OF CONTENTS Section A
Wiring Diagram...................................................................................................................3
Electrician’s notes................................................................................................................4
INDEX OF CONTENTS Section B
Mounting Hardware Required ........................................................................................ 5
General installation guidelines........................................................................................ 6
GE-R4 Module............................................................................................................ 6
Electrical Cables ......................................................................................................... 6
Electrical Power.......................................................................................................... 6
Mounting......................................................................................................................... 7
Layout Board .................................................................................................................. 8
Powering Up Procedure.................................................................................................. 9
Verify all Connections................................................................................................ 9
Hermetically Close the GE-R4 ................................................................................... 9
Put the power on ......................................................................................................... 9
Secure the front panel with a lock............................................................................... 9
Using the toggle switches ............................................................................................... 9
Output LED..................................................................................................................... 9
Changing the fuse ........................................................................................................... 9
Troubleshooting.............................................................................................................. 9
Specifications................................................................................................................ 10
TABLE OF FIGURES Section B
FIGURE NO. 1 Mounting Position and Devices............................................................... 7
FIGURE NO. 2 GE-R4 Electronic module Board............................................................. 8
INDEX OF CONTENTS Section C
Limited Warranty...............................................................................................................12
www.monitrol.com

GE-R4 INDEX / WARRANTY
GE-R4
Section C-12
Limited Warranty
The manufactured equipment and supplied components have gone through rigorous inspection to
assure optimal quality of product and reliability. Individual controls are factory tested under load,
however the possibility of equipment failure and/or malfunction may still exist.
For service, contact your local retailer or supplier. The warranty period shall be for two years
from manufacturing date. Proof of purchase is required for warranty validation.
In all cases, the warranty shall apply only to defects in workmanship and specifically exclude any
damage caused by over-voltage, short circuit, misuse, acts of vandalism, lightning, fortuitous
events, acts of God, flood, fire, hail or any other natural disaster. Any unauthorized work,
modification or repair on this product automatically voids the warranty and disclaims the
manufacturer from all responsibility.
The manufacturer assumes only those obligations set forth herein, excluding all other
warranties or obligations. This warranty stipulates that in all cases the manufacturer shall
be liable only for the supply of replacement parts or goods and shall not be liable for any
personal injury, damages, loss of profits, interrupted operations, fines for infringement of
the law or damages to the production of the PURCHASER and the PURCHASER shall
take up the defense and hold the manufacturer faultless regarding any legal or extra legal
proceedings, notice, or claim by the customer or by a third party, and regarding any legal
and extra legal expenses and fees brought forward on by such damages.
www.monitrol.com

MAG GE-R4 VER:1.0
April 17, 2007
www.monitrol.com
Table of contents
Other Genius Controllers manuals

Genius
Genius GSM MOBILE STARTER User manual

Genius
Genius JA383 Technical manual

Genius
Genius SPRINT 382 User manual

Genius
Genius Brain 17 User manual

Genius
Genius JA277K User manual

Genius
Genius A453 Technical manual

Genius
Genius BRAIN 06 24V User manual

Genius
Genius Hub kit User manual

Genius
Genius JA487C Technical manual

Genius
Genius BRAIN 04 User manual
Popular Controllers manuals by other brands

YASKAWA
YASKAWA YASNAC 3000G Operator's manual

LINK-MI
LINK-MI LM-TV24 user manual

ARAG
ARAG 4669 Series General instruction for installation use and maintenance

Native Instruments
Native Instruments Maschine Setup guide

Mitsubishi Electric
Mitsubishi Electric FX2N-16 Hardware manual

domat
domat FC013 Protocol guide