
V 1.3 Feb 19
It is VITAL that personnel responsible for the installation and use
of the VWCM-4000 Crack Meters READ and UNDERSTAND the
manual, prior to working with the equipment.
**********
As stated before, it is vital to check all the equipment in the shipment soon after
taking delivery and in good time before installation is to be carried out. Check that
all components that are detailed on the shipping documents are included.
5.0 INSTALLATION
This section of the manual is intended for all users of VWCM-4000 Crack Meters
manufactured by Geosense® and is intended to provide guidance with respect to
their installation.
It must be remembered that no two installations will be the same and it is inevitable
that some ‘fine tuning’ of the following procedures will be required to suit specific site
conditions.
5.1 Getting started - Preparation for Installation
Prior to installation of a VWCM-4000 Crack Meters it is essential to establish and
confirm details of the installation to be carried out. Some of the main considerations
are listed below :-
1. Intended location and subsequent Protection
2. Expected Movement of the Crack or Joint (see setting range)
3. Anchoring Method
4. Cable routing and marking
The end of the cables connected to VWCM-4000 Crack Meters is marked with the
unique serial number of the sensor to which it is attached.
All instrument cables should be marked with unique identification (e.g. colour codes).
Markings should be repeated at regular intervals along the cable where multiple
cables are to be grouped together, so that in the event of cable damage, there may
be a chance that the identification could be exposed and the cables re-joined
correctly. Multiple cable marks are particularly important close to the end of the
cable. The spacing of markings can vary according to specific site requirements but
a guide of 5m to 10m separation is commonly applied (marking materials available on
request from Geosense).
Cable routing must be carefully considered so as to ensure that it is not vulnerable
from intentional or accidental damage. Vibrating Wire signals can be affected by
electrical interference (EMI), so cable routing should AVOID close proximity to
possible sources.
10