GEZE GC 341 User manual

: <80 %(non-condensing)
MANUFACTURER'S STATEMENT
DETECTION AREA
ENGLISH
5922880 JAN 2015
NI-0034-1
Model
Cover color
Mounting height
Detection area
Detection method
Depth angle
adjustment
Power supply (*2)
Power consumption
Operation indicator
Test input
: GC 341
: Black
: 2.0 (6'7") to 3.5 m (11'6")
: See DETECTION AREA
: Active infrared reflection (*1)
: -6 to +6 °
: 12 to 24 VAC ±10 % (50 / 60 Hz)
12 to 30 VDC ±10 %
: < 1W (< 2 VA at AC)
: See Operation indicator table
: Opto coupler
Voltage 5 to 30 VDC
Current 6 mA Max. (30 VDC)
Safety output : Opto coupler (NPN)
Voltage 5 to 50 VDC
Current 100 mA Max.
Dark current 600 nA Max.
(Resistance load)
The specifications herein are subject to change without prior notice due to improvements.
NOTE
MANUFACTURER'S STATEMENT
WARNING Do not wash, disassemble, rebuild or repair the sensor, otherwise
it may cause electric shock or breakdown of the equipment.
Danger of electric shock
WARNING
CAUTION
NOTE
Disregard of the warning symbol can cause improper operation which may cause death
or serious injury.
Special attention is required to the section of this symbol.
Disregard of the caution symbol can cause improper operation which may cause injury of a
person or damage the object.
NOTE
Read this operation manual carefully before use to ensure proper operation of this product.
Failure to read this operation manual may cause improper operation and may result in serious injury or death of
a person.The meanings of the symbols are as follows.
1. This product is a non-contact switch intended for operator cover mount or wall mount for use on an
automatic sliding door. Do not use for any other applications.
2. When setting the sensor's detection area, make sure that there is no traffic around the installation site.
3. Before turning the power ON, check the wiring to prevent damage or malfunction of equipment connected to
the product.
4. Only use the product as specified in the operation manual provided.
5. Be sure to install and adjust the sensor in accordance with the local laws and standards of the country in which
the product is installed.
6. Before leaving the installation site make sure that the product is operating properly and instruct the building
owner/operator on proper operation of the door and the product.
7.The product settings can only be changed by an installer or service engineer. When changed, the
changed settings and the date shall be registered in the maintenance logbook accompanying the door.
The actual detection area may become smaller depending on the ambient light, the color / material of
the object or the floor as well as the entry speed of the object.
The sensor may not be activated when the entering speed of the object or a person is slower than
50 mm / s or faster than 1500 mm / s
NOTE
Operation indicator table
CAUTION
Risk of getting caught
Make sure to affix the mounting template as described in the above chart,
otherwise it can be dangerous since there may be no detection area around
the threshold. Install the sensor as low as possible on the operator cover.
WARNING
Danger of electric shock
Do not use the sensor without the cover.
When using the cable knockout, install the sensor indoors or use the rain cover
(Separately available) otherwise electric shock or breakdown of
the sensor may occur.
Before starting the procedure, make sure that the power is turned OFF.
When passing the cable through the hole, do not tear the shield
otherwise it may cause electric shock or breakdown of the sensor.
1.Plug the connector.
2.Supply power to the sensor. Adjust the detection area and set the DIP-switches.
(See ADJUSTMENTS 3. DIP-switch settings)
Place the housing cover.
If wiring is to be exposed, break the knockout.
H : Height from the floor to the bottom of the operator cover
Y : Distance between the bottom of the operator cover and the sensor
X : Distance between the door and the mounting surface
WARNING
Danger of electric shock
NOTE Make sure to connect the cable correctly to the door controller before turning the power ON.
When turning the power ON or after adjusting the settings, do not enter the detection area for more
than 10 seconds in order to enable the presence detection.
Do not touch the DIP-switches before turning the power ON, otherwise an error occurs.
After changing the DIP-switch settings, make sure to push the function switch for 2 seconds.
INSTALLATION
The following conditions are not suitable for sensor installation.
-Fog or exhaust emission around the door
-Wet floor
-Vibrating operator cover or mounting surface
-Moving objects, steel plate, emergency lights or illumination in the detection area or in vicinity
-Highly reflecting floor or highly reflecting objects around the door
- Make sure that the operator cover has been earthed.
NOTE
X
H
Y
Sensor
Door
Operator cover
Floor
SPECIFICATIONS
1. Affix the mounting template at the desired mounting position.
2. Drill two mounting holes of ø3.4 mm (ø1/8”).
3. To pass the cable through the operator cover, drill a wiring hole of ø8 mm (ø5/16”).
4. Remove the mounting template.
5. Remove the housing cover. Fix the sensor to the mounting surface with the two mounting screws.
1
2
3
4
Mounting height : 2.2 m(7'3")
Angle adjustment : +6 °
Sensitivity : Middle
: IR spots
: Detection area
: IR spots
(can be turned off)
1000 ms 1000 ms
Installation mode
Operating mode
Adjustment confirmation required
Signal saturation
Sensor failure / sensitivity too low
1st row detection
2nd row detection
Status
Green
Red & Green Blinking
Slow Green Blinking
Fast Green Blinking
Yellow
Red
Operation indicator color
Red Blinking
1
2
3
GC 341 as safety sensor in main closing edge (SIS)
Test conditions required by EN 16005 and DIN 18650
Floor :Grey paper
Detection object : EN 16005 and DIN 18650 CA reference body
Sensitivity : Middle
Speed of detection object : 50 mm / s
To comply with EN 16005 and DIN 18650, make sure that the detection area is within the values of the chart below.
Detection area
The chart shows the values at depth angle +6 °
Emitting area
A
X
E
G*
2.20 (7'3")2.00 (6'7")
0.25 (10")
1.12 (3'8")
2.65 (8'8")
3.00 (9'10")
0.34 (1'1")
1.53 (5')
3.60 (11'10")
0.23 (9")
1.02 (3'4")
2.41 (7'11")
The values above are those of the Detection area when tested referring to the test conditions of
EN 16005 and DIN 18650. (The area is as shown in Emitting area above.)
*: When installed at higher than 3.0 m(9'10"), EN 16005 and DIN 18650 requirements are fulfilled only
within the area width "G" of 3.6 m(11'10").
[m(feet,inch)]
A
E
F
G
0
1.0
(3′3")
1.0(3′3")
1.0
(3′3")
2.0
(6′7")
2.0
(6′7")
2nd row
BC
D
A
B
C
D
E
F
2.20 (7'3")
0.25 (10")
0.39 (1'3")
0.65 (2'2")
1.33 (4'4")
2.70 (8'10")
0.31 (1')
3.00 (9'10")
0.34 (1'1")
0.48(1'7")
0.80 (2'7")
0.53 (1'9")
0.89 (2'11")
1.63 (5'4") 1.81 (5'11")
2.50 (8'2")
0.28 (11")
0.44 (1'5")
0.74 (2'5")
1.51(4'11")
2.00 (6'7")
0.23 (9")
0.35 (1'2")
0.59 (1'11")
1.21 (3'12")
2.05 (6'9") 2.51 (8'3") 2.79 (9'2")2.32 (7'7")1.86 (6'1")
G 2.78 (9'1") 3.40 (11'2") 3.79 (12'5")
3.50 (11'6")
0.39 (1'3")
0.61 (2')
1.03(3'5")
2.11 (6'11")
3.25 (10'8")
4.42 (14'6")3.15 (10'4")2.52(8'3")
[m(feet,inch)]
NOTE Make sure not to mount the sensor lower than the bottom of operator cover.
X
Mounting
surface
GC 341
COMPLIED STANDARDS
AND EXTRACT FROM EC DECLARATION OF CONFORMITY
Output hold time
Response time
Operating temperature
Relative air humidity
IP rate
Category
Weight
Accessories
Performance level
: <500 ms
: <300 ms
: -20 to +55 °C (-4 to 131 °F)
: IP54
:
2 (EN ISO13849-1 : 2008)
:
d (EN ISO13849-1 : 2008)
: 250 g (8.8 oz )
: 1 Operation manual
2 Mounting screws
1 Mounting template
1 Area adjustment tool
1 Cable 3 m (9'10")
( 8×0.22 mm² AWG24 ) (*3)
Noise level : <70 dBA
ESPE
1st row
:
Type 2
Maximum mounting distance (Y)
X2.00 (6' 7") 2.30 (7' 7") 2.50 (8' 2") 2.80 (9' 2")
0No limit
0.05 (2") 0.13 (5") 0.13 (5") 0.14 (6")
0.10 (4") 0.11 (4") 0.12 (5") 0.12 (5") 0.12 (5")
0.15 (6") 0.10 (4”) 0.10 (4”) 0.11 (4") 0.11 (4")
0.20 (8") -0.09 (4”) 0.10 (4”) 0.10 (4”)
0.25 (10") 0.09 (4”)
0.30 (12") - -
H
0.13 (5")
-
--
- 0.09 (4")
[m (feet,inch)]
3.00 (9'10") 3.50 (11'6")
0.14
(6")
0.12
(5")
0.11
(4")
0.10
(4")
0.09
(4")
-
0
0
0
0
0
0
Original instructions
(The mounting height is "H + Y".)
(When setting the detection area close to the door, mount the sensor according to the chart below.)
COM
1 AIR
2 Test
100 mA
+
1
2
21
1
2
01
o r
BN
WH
BU
PK
BK
RD
SIS1
GND
24V
SIS1
GND
24V
TST
1
2
11
1
2
10
GND
24V
SIS2
GND
24V
TST
SIS2
1
2
12 to 24 VAC±10 % / 12 to 30 VDC±10 %
BN
WH
Opto coupler(NPN) / Voltage: 5 to 50 VDC
BU(-)
PK(+)
Opto coupler / Voltage: 5 to 30 VDC
BK(-)
RD(+)
EN 12978:2003 +A1:2009
EN ISO 13849-1:2008 EN ISO 13849-2:2012
EN 16005:2012
EMC Directive 2004/108/EC
EN 61496-3:2001 clause 4. 3. 5 and 5. 4. 7. 3
EN 61000-6-2:2005 EN 61000-6-3:2007 +A1:2011
DIN18650-1:2010
Machinery Directive 2006/42/EC
*2 : The sensor has to be connected to a door system which has a SELV circuit.
*1 : Active infrared reflection has a presence detection function.
*3 : Overcurrent protection with less than 2 A.
38(1 1/2")
61(2 3/8")
267(10 1/2")
125(4 15/16")
36(1 7/16") 43(1 11/16")
7.5(5/16")
OUTER DIMENSIONS AND PART NAMES
(1) Connector
(2) Mounting holes
(3) Operation indicator
(4) Width adjustment screws
(5) Depth angle adjustment screw
(6) Function switch
(7) DIP-switches
(8) Detection window
(9) Area adjustment tool
[mm (inch)]
(9)
(1)
(4) (5) (7)(6)
(8)
(3)
(2)
GC 341 as safety sensor in secondary closing edge (SIO)
COM
1 AIR
2 Test
100 mA
+
o r
BN
SIO1
SIO1
GND
24V
TST10
2
13
1
SIO2
1
2
-UB
+UB
SIO2
GND
24V
TST10
2
14
1
WH
RD
BK
PK
BU
Set-up YellowBlinking

After changing the DIP-switch settings, make sure to push the function
switch for 2 seconds.
2
1
ADJUSTMENTS
Red
Area depth angle adjustment
Area width adjustment
Depth angle adjustment screw
for the area
Use the area adjustment tool (A) as shown above
to change the area depth angle.
Depth angle
adjustment screw
DIP-switch settings
When adjusting the 1st row close to the door,
see Table 2 DIP-switch16 for the easier adjustment.
1. Always keep the detection window clean. If dirty, wipe the window with a damp cloth. Do not use any cleaner / solvent.
2. Do not wash the sensor with water.
3. Do not disassemble, rebuild or repair the sensor yourself, otherwise an electric shock may occur.
4. When the operation indicator blinks green, contact your installer or service engineer.
5. Only the service engineer is allowed to change the settings.
6. Do not paint the detection window.
WARNING
1. When turning the power ON, always walk-test the detection area to ensure the proper operation.
2. Do not place any objects that move or emit light in the detection area. (e.g. plant, illumination, etc.)
Make sure that the detection area does not overlap with the door/operator cover, and there is no highly
reflecting object near the detection area otherwise ghosting/signal saturation may occur.
NOTE
NOTE
NOTE
3
INFORM BUILDING OWNER / OPERATOR OF THE FOLLOWING ITEMS
Width adjustment screws
Narrow
Wide
turned off
turned off
To adjust the detection area width, use the
adjustment screws as shown below.
push 2 seconds
*After changing the DIP-switch settings, make sure to push the function switch for 2 seconds.
Wrong wiring or connection failure. Check the wires and connector.
Door operation Operation
indicator Possible cause Possible countermeasures
None Wrong power supply voltage. Set to the stated voltage.
Wrong wiring or connection failure.
Door opens or
doesn´t react
in case of side
screen safety,
when no one is
in the detection
area
(ghosting).
Unstable
Check the wires and connector.
Door does not
open or doesn´t
react in case of
side screen
safety, when a
person enters
the detection
area.
Unstable Wrong detection area positioning. Check ADJUSTMENTS 1, 2.
Sensitivity is too low. Set the sensitivity higher.(*)
Short presence timer. Set the presence timer longer.(*)
Proper
Dirty detection window. Wipe the detection window with a damp cloth.
Do not use any cleaner or solvent.
TROUBLESHOOTING
Waterdrops on the detection window.
The detection area overlaps with
that of another sensor.
Check Table 2 DIP-switch 5, 6.(*)
Objects that move or
emit light in the detection area.
Remove the objects.
Sensitivity is too high. Set the sensitivity lower.(*)
Contact your installer or service engineer.
Sensor failure.
Wrong wiring or connection failure. Check the wires and connector.
Fast
Green
Blinking
Signal saturation.
Dirty detection window. Wipe the detection window with a damp cloth.
Do not use any cleaner or solvent.
Sensitivity is too low. Set the sensitivity higher.(*)
The detection area overlaps with
the door/operator cover.
Adjust the detection area to "Deep" (Outside).
Door remains
open or react
always without
sensor detection
in case of side
screen safety.
Sudden change in the detection area. Check Table 2 DIP-switch 1 to 4.(*)
If the problem still persists, hard-reset the
sensor.(Turn the power OFF and ON again)
Slow
Green
Blinking
Remove highly reflecting objects from the
detection area. Or lower the sensitivity.(*)
Or change the area depth angle.
Setting error.Red &
Green
Blinking
Proper
Wrong setting of DIP-switches. Check Table 2 DIP-switch 7, 8.(*)
After changing the DIP-switch settings, make sure
to push the function switch for 2 seconds.
Installation mode is set to "ON". Set DIP-switch 16 to "OFF".(*)
Yellow
Table 2
To enable the presence detection, do not
enter the detection area for 10 seconds
after setting the timer.
When using more than one sensor close
to each other, set the frequency different
for each sensor.
To comply with EN 16005 and DIN 18650,
the self-monitoring has to be enabled
(position OFF).
Set DIP-switch 16 to "ON"to adjust the 1st
row. During the installation mode only the
1st row remains active and the operation
indicator shows yellow. After setting the
row set DIP-switch 16 "OFF".
Presence timer
Frequency
Test input
High Low
High Low
Safety output
Self monitoring
Installation mode
7
88
Enable
14
Disable
14
OFF
16
ON
16
7
Function
DIP-switch
1
DIP-switch
2
DIP-switch
7
DIP-switch
8
DIP-switch
14
DIP-switch
16
Set the sensitivity according to the
mounting height.
Setting
21 212121
Low Middle High S-High
Sensitivity
Comment
2.0 to 3.0 m 2.0 to 3.0 m 2.5 to 3.2 m 3.0 to 3.5 m
ShallowDeep
1.0
(3′3") 1.0
(3′3")
00
[m(feet,inch)]
Front view
[m(feet,inch)]
0
0
3.0
(9′10")
2.0
(6′7")
-1.0
(-3′3")
4 9
112
~
~
:Wide
:Narrow
Please adjust
by using the tool (B)
123 10 11 12
456 789
123 10 11 12
3.5
(11′6")
DIP-switch
3
DIP-switch
4
43 434343
30 s 60 s 180 s 600 s
DIP-switch
5
DIP-switch
6
65 656565
Setting1 Setting2 Setting3 Setting4
DIP-switch
5
DIP-switch
7
2.0(6′7")
3.0(9′10")
3.5(11′6")
1.0
(3′3")
2.0
(6′7") 1.0
(3′3") 2.0
(6′7")
Area depth adjustment with INFRARED FINDER (separately available)
Detection area
Detection area
1. Set the DIP-switch 16 "Installation mode" to ON and confirm by pushing the function switch for 2 seconds
2. Turn the depth angle adjustment screw to the right (deep) to place the detection area away from the door.
3. Place the INFRARED FINDER on the floor until it detects the infrared curtain.
4. Slide the INFRARED FINDER as close as possible towards the door
5. Turn the depth angle adjustment screw to the left (shallow) until the INFRARED FINDER lights up.
6. Set the DIP-switch 16 to OFF and confirm by pushing the function switch for 2 seconds.
Adjust the detection area to "Deep" (Outside).
Or install in a place keeping the waterdrops off.
Or wipe the detection window with a damp cloth.
Use the rain-cover. (Separately available)
Proper
The detection area overlaps with
the door/operator cover.
Do not use any cleaner or solvent.
When setting the detection area width, make sure to turn
the adjustment screws until it clicks.
resp. can only be turned off as a group.
123 10 11 12
GEZE GmbH
Tel. : 0049 7152 203-0
Fax. : 0049 7152 203-310
www.geze.com Material number 160278-00
Reinhold-Vöster-Stra e 21-29
D-71229 Leonberg
ß
Germany
EN 16005 DIN 18650
Shallow Deep
After changing the DIP-switch settings, make sure to push the function
switch for 2 seconds.
2
1
ADJUSTMENTS
Red
Area depth angle adjustment
Area width adjustment
Depth angle adjustment screw
for the area
Use the area adjustment tool (A) as shown above
to change the area depth angle.
Depth angle
adjustment screw
DIP-switch settings
When adjusting the 1st row close to the door,
see Table 2 DIP-switch16 for the easier adjustment.
1. Always keep the detection window clean. If dirty, wipe the window with a damp cloth. Do not use any cleaner / solvent.
2. Do not wash the sensor with water.
3. Do not disassemble, rebuild or repair the sensor yourself, otherwise an electric shock may occur.
4. When the operation indicator blinks green, contact your installer or service engineer.
5. Only the service engineer is allowed to change the settings.
6. Do not paint the detection window.
WARNING
1. When turning the power ON, always walk-test the detection area to ensure the proper operation.
2. Do not place any objects that move or emit light in the detection area. (e.g. plant, illumination, etc.)
Make sure that the detection area does not overlap with the door/operator cover, and there is no highly
reflecting object near the detection area otherwise ghosting/signal saturation may occur.
NOTE
NOTE
NOTE
3
INFORM BUILDING OWNER / OPERATOR OF THE FOLLOWING ITEMS
Width adjustment screws
Narrow
Wide
turned off
turned off
To adjust the detection area width, use the
adjustment screws as shown below.
push 2 seconds
*After changing the DIP-switch settings, make sure to push the function switch for 2 seconds.
Wrong wiring or connection failure. Check the wires and connector.
Door operation Operation
indicator Possible cause Possible countermeasures
None Wrong power supply voltage. Set to the stated voltage.
Wrong wiring or connection failure.
Door opens or
doesn´t react
in case of side
screen safety,
when no one is
in the detection
area
(ghosting).
Unstable
Check the wires and connector.
Door does not
open or doesn´t
react in case of
side screen
safety, when a
person enters
the detection
area.
Unstable Wrong detection area positioning. Check ADJUSTMENTS 1, 2.
Sensitivity is too low. Set the sensitivity higher.(*)
Short presence timer. Set the presence timer longer.(*)
Proper
Dirty detection window. Wipe the detection window with a damp cloth.
Do not use any cleaner or solvent.
TROUBLESHOOTING
Waterdrops on the detection window.
The detection area overlaps with
that of another sensor.
Check Table 2 DIP-switch 5, 6.(*)
Objects that move or
emit light in the detection area.
Remove the objects.
Sensitivity is too high. Set the sensitivity lower.(*)
Contact your installer or service engineer.
Sensor failure.
Wrong wiring or connection failure. Check the wires and connector.
Fast
Green
Blinking
Signal saturation.
Dirty detection window. Wipe the detection window with a damp cloth.
Do not use any cleaner or solvent.
Sensitivity is too low. Set the sensitivity higher.(*)
The detection area overlaps with
the door/operator cover.
Adjust the detection area to "Deep" (Outside).
Door remains
open or react
always without
sensor detection
in case of side
screen safety.
Sudden change in the detection area. Check Table 2 DIP-switch 1 to 4.(*)
If the problem still persists, hard-reset the
sensor.(Turn the power OFF and ON again)
Slow
Green
Blinking
Remove highly reflecting objects from the
detection area. Or lower the sensitivity.(*)
Or change the area depth angle.
Setting error.Red &
Green
Blinking
Proper
Wrong setting of DIP-switches. Check Table 2 DIP-switch 7, 8.(*)
After changing the DIP-switch settings, make sure
to push the function switch for 2 seconds.
Installation mode is set to "ON". Set DIP-switch 16 to "OFF".(*)
Yellow
Table 2
To enable the presence detection, do not
enter the detection area for 10 seconds
after setting the timer.
When using more than one sensor close
to each other, set the frequency different
for each sensor.
To comply with EN 16005 and DIN 18650,
the self-monitoring has to be enabled
(position OFF).
Set DIP-switch 16 to "ON"to adjust the 1st
row. During the installation mode only the
1st row remains active and the operation
indicator shows yellow. After setting the
row set DIP-switch 16 "OFF".
Presence timer
Frequency
Test input
High Low
High Low
Safety output
Self monitoring
Installation mode
7
88
Enable
14
Disable
14
OFF
16
ON
16
7
Function
DIP-switch
1
DIP-switch
2
DIP-switch
7
DIP-switch
8
DIP-switch
14
DIP-switch
16
Set the sensitivity according to the
mounting height.
Setting
21 212121
Low Middle High S-High
Sensitivity
Comment
2.0 to 3.0 m 2.0 to 3.0 m 2.5 to 3.2 m 3.0 to 3.5 m
ShallowDeep
1.0
(3′3") 1.0
(3′3")
00
[m(feet,inch)]
Front view
[m(feet,inch)]
0
0
3.0
(9′10")
2.0
(6′7")
-1.0
(-3′3")
4 9
112
~
~
:Wide
:Narrow
Please adjust
by using the tool (B)
123 10 11 12
456 789
123 10 11 12
3.5
(11′6")
DIP-switch
3
DIP-switch
4
43 434343
30 s 60 s 180 s 600 s
DIP-switch
5
DIP-switch
6
65 656565
Setting1 Setting2 Setting3 Setting4
DIP-switch
5
DIP-switch
7
2.0(6′7")
3.0(9′10")
3.5(11′6")
1.0
(3′3")
2.0
(6′7") 1.0
(3′3") 2.0
(6′7")
Area depth adjustment with INFRARED FINDER (separately available)
Detection area
Detection area
1. Set the DIP-switch 16 "Installation mode" to ON and confirm by pushing the function switch for 2 seconds
2. Turn the depth angle adjustment screw to the right (deep) to place the detection area away from the door.
3. Place the INFRARED FINDER on the floor until it detects the infrared curtain.
4. Slide the INFRARED FINDER as close as possible towards the door
5. Turn the depth angle adjustment screw to the left (shallow) until the INFRARED FINDER lights up.
6. Set the DIP-switch 16 to OFF and confirm by pushing the function switch for 2 seconds.
Adjust the detection area to "Deep" (Outside).
Or install in a place keeping the waterdrops off.
Or wipe the detection window with a damp cloth.
Use the rain-cover. (Separately available)
Proper
The detection area overlaps with
the door/operator cover.
Do not use any cleaner or solvent.
When setting the detection area width, make sure to turn
the adjustment screws until it clicks.
resp. can only be turned off as a group.
123 10 11 12
GEZE GmbH
Tel. : 0049 7152 203-0
Fax. : 0049 7152 203-310
www.geze.com Material number 160278-00
Reinhold-Vöster-Stra e 21-29
D-71229 Leonberg
ß
Germany
EN 16005 DIN 18650
Shallow Deep

5923130 JAN 2015
NI-0034-1
Other GEZE Accessories manuals
Popular Accessories manuals by other brands

ooma
ooma Water Sensor quick start guide

STEINEL
STEINEL IR 180 UP easy manual

LINKUP
LINKUP LP400 Operator's manual

QUEST ELITE
QUEST ELITE Snowdon Full item instructions and extended details

ekwb
ekwb EK-FC980 GTX Classy Backplate Installation and mounting manuals

Nobile
Nobile 9109011009 Mounting and operation instructions

Stobag
Stobag TP7100 manual

GSi
GSi 2 Series Installation and operation manual

Hubbell
Hubbell Direct Drive Electric Cable Reels MMD32 Installation and maintenance instructions

Konifera
Konifera BW92001 Installation and operating instructions

PCB Piezotronics
PCB Piezotronics 353B52 Installation and operating manual

SENSTAR
SENSTAR FiberPatrol FP1150 Series Product guide