  9. GJD Emerald 3000 MK3 User manual

GJD Emerald 3000 MK3 User manual

The GJD Emerald is a dual area security lighting controller
which enables external areas to be accurately monitored.
It automatically switches up to 3000 Watts of resistive
lighting at night for a pre-set period and can be manually
overridden when required. The controller incorporates an
audible warning tone and features six detector indicators
which illuminate when activated by detection day and night.
OPERATING INSTRUCTIONS
When a detector is activated day or night the relevant
detector indicator ickers and will remain on for the length
of the timer setting. During darkness the lighting will be
switched on automatically while the detector is receiving
activation signals, and will automatically turn off after the
pre-set timer period.
The ‘Zone 1’ and ‘Zone 2’ green indicator have to be
selected for automatically controlled lighting on detection
during darkness.
ZONE 1
ZONE 1
ZONE 1
Green indicator is ‘on’. This mode
must be selected for automatic
lighting during darkness.
Indicator ‘off’. Lighting and tone
are switch off for this zone.
Green indicator ashing. A
detector has activated the
lighting.
Manually selecting this yellow
indicator will turn the lighting
‘on’. Turning the indicator ‘off’ will
return to automatic mode.
Indicator ‘off’.
Yellow indicator ashing. A
detection has automatically
activated the lighting.
Red indicator ‘on’. Audible
warning tone selected. Zone 1
and/or Zone 2 indicator to be
selected to function.
Indicator ‘off’ Audible warning
tone is switched off.
ADJUSTMENT TO FACTORY SETTINGS
When connecting the unit to the electrical supply or when
the supply is interrupted, the indicators will ash for one
minute whilst the system settles. Pressing any button
during this time will start normal operation.
Internal adjustments panel
The factory settings are shown.
AUX - Auxiliary Output (50mA maximum)
OFF - Internal sounder and auxiliary output disabled
STD -Internal sounder and auxiliary output active and will
emit a warning tone on each detection when the tone
button is selected.
10-30 Seconds - The auxiliary output time after last
detection. The internal sounder is as the STD
LIGHT ON TIME IN MINUTES
1 to 24 minutes - The length of the time after last detection
during darkness. The red detector indicators will stay on for
this time after the last detection day and night.
Pulse Count / Walk Test - Select the symbol to assist in
location/alignment of the detector beams during daylight
installations. When the detector beams are activated the
external lights will stay on for a period of 6 seconds.
1,2 or 3 - After completing the ‘walk test’ function, set
the pulse count to the required level. The pulse count is
the number of detector beams that have to be crossed to
trigger the system.
1. will give fast response
2. gives better immunity with good response
3. gives highest immunity to false activation in poor
environments but is less responsive.
OFF
STD
10
20
30 1
3
5
10
24
1 2
3
AUX
TIME SECS
LIGHT ON
TIME MINS
PULSE
COUNT
Emerald 3000 MK3
GJD010 Lighting Controller
Detect.Illuminate.Dete
r
1. Link both lighting areas together ( except in walk test) connect ‘LINK” to “-”.
2. Remote triggering of lights for the timer period. Pulse Count ‘1’ must be selected.
3. Activate zone lighting for alarm period when linked to an intruder alarm panel.
All diodes: IN4148, IN4002 etc.
CAUTION: To be installed by qualied personnel only:
DUAL CABLE
CLAMPING
SINGLE CABLE
CLAMPING
CABLE
CABLE CABLE
LOAD
ZONE 1
MAINS
SUPPLY
LOAD
ZONE
SLEEVED EARTH CABLES
BROWN
PLUG TYPE FUSE
normally
open
contact
OPTIONAL
TRIGGER LIGHTS IN
ALARM CONDITION
LOAD 1
1500VA MAX
LIVE
230V~
LOAD 2
1500VA MAX
N
N
N
13A
13A
3
GJD
BASE 2
12VDC
CONNECTIONS
Z 1
Z 2
+12VDC
100mA
Max
BLUE
YELLOW
RED
BLACK
BLUE
YELLOW
RED
BLACK
OPTIONAL
BUTTON
2
ZONE 2 ZONE 1
1 2 3 1 2 3
ZONE 1
GJD DETECTORS
ZONE 2
GJD DETECTORS
+
A
S
+
A
S
+
A
S
+
A
S
+
A
S
+
A
S
OPTIONAL PIEZO SOUNDER
OR
RELAY +DIODE
12VDC / 50MA MAX +
GJD EMERALD MK3 1AUX
Z 1
+
A 1
A 2
A 3
S 1
LINK
Z 2
A 1
A 2
A 3
S 2
RED/S
BLACK/S
BLUE
BLUE
BLUE
YELLOW/S
BLUE
BLUE
BLUE
YELLOW/S
BROWN
BROWN
BLUE
BLUE
BLUE
EXCHANGING EMERALD 3000 WITH AND EMERALD
MK3
If it becomes necessary to exchange an original
Emerald 3000 (DX10) lighting controller with an
Emerald MK3 lighting controller then the following
connection changes need to be applied.
230 Volt A.C Connections
Emerald 3000 (DX10) EMERALD MK3
LIVE LIVE
LIGHT A LOAD 1
LIGHT B LOAD 2
NEUTRAL N
12 Volt D.C Connections
S1 S1 ZONE1
S2 S1 ZONE1
S3 S1 ZONE1
S4 S2 ZONE2
S5 S2 ZONE2
S6 S2 ZONE2
AA A1,A2, OR A3 ZONE1
AB A1, A2 OR A3 ZONE2
→ - AUX
SPECIFICATIONS
SUPPLY 230 Vac 50Hz via ELCB/MCB -
unit fused at 13A
12VDC@ 100mA GJD Opal XL (6mA) or Elite
Detectors (10mA) Optional
external 12VDC piezo sounder
up to 50mA
LOAD: Each expansion unit switches
two channels each up to
1500W of resistive load or
1000 Watts of inductive load.
The inductive load may require
a ‘snubber’ (suppressor) to
manage the lamp discharge
current.
INDICATION: Six 24 hour detector indicators
which pulse during detection
and are steady after detection
for the duration of the light on
timer setting.
AUDIBLE Internal warning tone which
sounds on detection day and
night, and is button selectable.
It has a steady tone for zone
one and pulsed tone for zone
two.
CONTROL Controls up to 12 x GJD
detectors. Switches two
independent areas of lighting
with manual override when
required.
OPTIONS Ability to link both lighting
areas together.
Ability to have a time auxiliary
output.
Ability to active lighting when
linked to an intruder alarm
panel.
DIMENSIONS 146(W) x 86(H) x 56(D) mm
MOUNTING Indoor use only. Mount in a
clean dry location on a secure
at surface.
TEMPERATURE -10 to +55 Centigrade
CERTIFICATIONS
Self contained - Class 2 independently mounted control
Unit 2, Birch Business Park, Whittle Lane, Heywood, Greater Manchester, OL10 2SX, UK
w: www.gjd.co.uk t: +44 (0) 1706 363 998 f: +44 (0) 1706 363 991
ENGINEER NOTES

This manual suits for next models

1

Other GJD Controllers manuals

GJD Sapphire 1500 MK3 GJD005 User manual

GJD

GJD Sapphire 1500 MK3 GJD005 User manual

GJD SAPPHIRE MK3 User manual

GJD

GJD SAPPHIRE MK3 User manual

GJD SAPPHIRE MK3 User manual

GJD

GJD SAPPHIRE MK3 User manual

GJD DYGIZONE GJD910 User manual

GJD

GJD DYGIZONE GJD910 User manual

GJD DYGIZONE GJD910 User manual

GJD

GJD DYGIZONE GJD910 User manual

GJD EMERALD MK3 User manual

GJD

GJD EMERALD MK3 User manual

Popular Controllers manuals by other brands

Panasonic MINAS-A4P Technical reference

Panasonic

Panasonic MINAS-A4P Technical reference

YASKAWA motoman NX100 manual

YASKAWA

YASKAWA motoman NX100 manual

Universal Devices ISY-26 user guide

Universal Devices

Universal Devices ISY-26 user guide

DMC TSC-25/RSA Series user guide

DMC

DMC TSC-25/RSA Series user guide

Adaptec RAID 21610SA Installation and user guide

Adaptec

Adaptec RAID 21610SA Installation and user guide

EuroLite FD-512 user manual

EuroLite

EuroLite FD-512 user manual

Citizen BD2-2880 Command reference

Citizen

Citizen BD2-2880 Command reference

Frico ERP instruction manual

Frico

Frico ERP instruction manual

Allen-Bradley PF7000A troubleshooting guide

Allen-Bradley

Allen-Bradley PF7000A troubleshooting guide

Allen-Bradley micrologix 1500 user manual

Allen-Bradley

Allen-Bradley micrologix 1500 user manual

Azbil dcp551 mark II user manual

Azbil

Azbil dcp551 mark II user manual

Siemens Stratos Outstation installation guide

Siemens

Siemens Stratos Outstation installation guide

Rodix FEEDER CUBE FC-40 Plus Series quick start guide

Rodix

Rodix FEEDER CUBE FC-40 Plus Series quick start guide

NEC N8403-018 user guide

NEC

NEC N8403-018 user guide

Herz clever&smart Room Controller WiFi Installation and operating instruction

Herz

Herz clever&smart Room Controller WiFi Installation and operating instruction

Bacharach MGS SERIES Installation and operation manual

Bacharach

Bacharach MGS SERIES Installation and operation manual

SP VirTis Wizard 2.0 Operator's manual

SP

SP VirTis Wizard 2.0 Operator's manual

Burkert 8032 manual

Burkert

Burkert 8032 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.