TheUnited States EnvironmentalProtection Agency (EPA)
has issued various regulations regarding the introduc-
tion and disposal of refrigerants. Failure to follow these
regulations may harm the environment and can lead to
the imposition of substantial fines. Theseregulationsmay
vary by jurisdiction. A certified technician must perform the
installation and service of this product. Should you have any
questions please contact the local office of the EPA.
Replacement Parts
Whenreporting shortagesordamages,ororderingrepairparts,
givethecompleteproductmodelandserialnumbersasstamped
onthe product. Replacement parts for this product areavail-
able through your contractor or local distributor. For the loca-
tion of your nearest distributor consult the white business
pages,the yellow pagesectionofthe local telephone bookor
contact: CONSUMERAFFAIRS
GOODMANMANUFACTURINGCOMPANY, L.P.
7401SECURITYWAY
HOUSTON,TEXAS77040
(877)254-4729
Application Information
Heat Pump Premature Failure Notice
Running the unit without HPSK-1 kit installed on heat pump
can cause premature unit failure. A HPSK-1 kit must be
installed on all heat pump applications.
CAUTION
Thisceilingmountairhandleris available in cooling capacities
of1.5,2,and2.5nominaltonsofcooling. Electric heat models
are available in capacities of 0, 5, 6, 8 and 10 kW.
The unit is designed to be installed in a horizontal position
aboveadropped ceiling.Do NOTinstallthis unit outside the
structure. These models are designed for INDOOR USE
ONLY.
Pre-Installation Instructions
Carefullyreadallinstructionsfortheinstallation prior to install-
ingproduct. Make sure each steporprocedureis understood
and any special considerations are taken into account before
starting installation. Assemble all tools, hardware and sup-
plies needed to complete the installation. Some items may
needtobepurchased locally. Make sureeverythingneededto
install the product is on hand before starting.
Beforeattemptinganyinstallation,the following points should
beconsidered:
• Structuralstrengthofsupportingmembers
• Clearancesandprovision forservicing
• Powersupplyandwiring
• Air duct connections
• Drainfacilitiesandconnections
InstallationClearances
Place this unit as close to the space to be air conditioned as
possible.Theseunits are U.L. listed forinstallations withzero
clearancetocombustiblematerials. Ifthis unit is installed in a
removable ceiling panel, ensure adequate space is available
for servicing. Run ducts as direct as possible to supply and
return outlets. Use non-flammable weatherproof flexible con-
nectors on both supply and return connections at unit to re-
duce noise transmission.
Ducting
Duct work should be fabricated by the installing contractor in
accordance with local codes. Use industry manuals such as
such as NESCA (National Environmental Systems Contrac-
torsAssociation,1501WilsonBlvd., Arlington, Virginia 22209)
as a guide when sizing and designing the duct system.
To ensure correct system performance, the ductwork is to be
sized to accommodate 375-425 CFM per ton of cooling with
the static pressure not to exceed 0.5” W.C. Inadequate duct-
work that restricts airflow can result in improper performance
andcompressororheaterfailure
To prevent the risk of property damage, fire, carbon
monoxide poisoning, explosion, personal injury, or
death, do not connect ductwork to any heat producing
device such as a fireplace insert or stove.
WARNING
Filters
Filters are not provided with unit, and must be supplied and
installed in the return air system by the installer. A field in-
stalled filter grille is recommended for easy and convenient
access to the filters for periodic inspection and cleaning. Fil-
tersmusthaveadequatefaceareafortherated air quantity of
the unit. The minimum filter size is 20" x 20" x 1".
CondensateDrainPiping
Thecoildrainpanhasaprimaryandasecondarydrainwith3/4"
NPTfemaleconnections.Theconnectorsrequiredare3/4"NPT
male,eitherPVCormetalpipe,andshouldbehandtightened
to a torque of approximately 37 in-lbs. to prevent damage to
the drain pan connection. An insertion depth between .355 to
.485inches(3-5turns)shouldbeexpectedatthistorque.Use
thefemale(3/4NPT)threadedfitting that protrudes outside of
theenclosureforexternal connections.
1. Ensuredrainpan hole is NOT obstructed.
2. Topreventpotentialsweatinganddrippingonto finished
space, it may be necessary to insulate the condensate
drain line located inside the building. Use Armaflex® or
similarmaterial.
ASecondary CondensateDrainConnectionhasbeenprovided
for areas where the building codes require it. Pitch the drain
line1/4"per foot to provide free drainage. Insulate drainlines
located inside the building to prevent sweating. Install a con-
densatetrapto ensure properdrainage. Ifthesecondarydrain
line is required, run the line separately from the primary drain
and end it where it can be easily seen.