Safety warning
Any installation and operation on inverter must be performed by qualified electricians, in compli-
ance with standards, wiring rules or requirements of local grid authorities or companies (like AS
4777 and AS/NZS 3000 in Australia).
Prohibit inserting and pulling the AC and DC terminals when the inverter is running.
Before any wiring connection or electrical operation on inverter, all DC and AC power must
be disconnected from inverter for at least 5 minutes to make sure inverter is totally isolated
to avoid electric shock.
The temperature of inverter surface might exceed 60℃ during operation, so please make
sure it has cooled down before touching it, and make sure the inverter is out of reach of
children.
Do not open the inverter's cover or change any components without manufacturer's autho-
rization, otherwise the warranty commitment for the inverter will be invalid.
Usage and operation of the inverter must follow instructions in this user manual, otherwise
the protection design might be impared and warranty commitment for the inverter will be
invalid.
Appropriate methods must be adopted to protect inverter from static damage. Any damage
caused by static is not warranted by manufacturer.
Battery negative(BAT-) on inveter side is not grounded as default design.
Connecting BAT- to EARTH are strictly forbidden.
The inverter, with built-in RCMU, will exclude possibility of DC residual current to 6mA, thus
in the system an external RCD (type A) can be used(≥30mA).
In Australia, the inverter internal switching does not maintain neutral integrity, which must
be addressed by external connection arrangements like in the Off-Grid System Connection
Diagram in page 17.
In Australia, output of back-up side in switchbox should be labeled "Main Switch UPS
Supply", the output of normal load side in switch box should be labeled "Main Switch Invert-
er Supply".
LED Indicators
Battery Terminal
Wi-Fi Module
DRED & Remote Shutdown
Smart Meter
Communication Cable
BMS Communication Cable
Back-Up Port
On-Grid Port
To Smart Meter
To Battery
HYBIRD LED INDICATORS
INDICATOR
SYSTEM
BACK-UP
BATTERY
GRID
ENERGY
COM
WiFi
FAULT
STATUS
ON = System is ready
BLINK = System is starting up
OFF = System is not operating
ON = Back-up is ready / power available
OFF =
Back-up is off / on power available
ON = Battery is charging
BLINK 1 = Battery is discharging
BLINK 2 = Battery is low / soc is low
OFF =
Battery is disconnected / not active
ON = Grid is active and connected
BLINK = Grid is active but not connected
OFF = Grid is not active
ON =
Consuming energy from grid / buying
BLINK 1 =
Supplying energy to grid / zeroing
BLINK 2 =
Supplying energy to grid / selling
OFF =
Grid not connected or system not operating
ON = BMS and meter communication ok
OFF =
BMS and meter communication fail
ON = WiFi connected / active
BLINK 1 = WiFi system resetting
BLINK 2 = WiFi not connect to router
BLINK 4 = WiFi server problem
OFF = WiFi not active
ON = Fault has occurred
BLINK4 = CT wiring fault
OFF = No fault
EXPLANATION
SYSTEM BACK-UP BATTERY GRID ENERGY COM WiFi FAULT
BLINK 1 = Meter communication ok,
BMS communication fail
BLINK 2 = BMS communication ok,
meter communication fail
BLINK1 = Overload of back-up
Output / reduce load
OFF