4GMC-I Messtechnik GmbH
Power meter – powerMeter ObjectId: 2
Voltmeter – voltMeter ObjectId: 3
Energy meter – energyMeter ObjectId: 4
1) Clear the meter reading (clear).
The nvoWhTot meter reading can be set to zero with nviEnrgyClr.
The nvoRegValWhTot meter reading remains unaffected.
2) Save the meter reading (freeze).
If the nviEnergyFreeze network variable is transmitted to the meter, the meter saves its
current meter reading along with a time stamp, nvoRegValWhFr.
4.2 Units and Resolutions
Ammeter – amMeter ObjectId: 1
Current
Index Network Variable Data Type Description
Active Power
11 nvoWatTot SNVT_power_f Total active power, all 3 phases
12 nvoWat1 SNVT_power_f Active power in phase L1
13 nvoWat2 SNVT_power_f Active power in phase L2
14 nvoWat3 SNVT_power_f Active power in phase L3
Reactive Power
15 nvoVarTot SNVT_power_f Total reactive power, all 3 phases
Power Factor
16 nvoPwrFactrTot SNVT_pwr_fact Overall power factor
17 nvoPwrFactr1 SNVT_pwr_fact Power factor in phase L1
18 nvoPwrFactr2 SNVT_pwr_fact Power factor in phase L2
19 nvoPwrFactr3 SNVT_pwr_fact Power factor in phase L3
Im-
port
Configuration
Property
Data Type Description
Nv 11
... 15
cpPwrSndDelta
UCPTpwrSendDelta
(SNVT_power_f)
Send condition: delta power
(active and reactive power)
Nv 16
... 19
cpPwrFacSndDelta
UCPTpwrFactSendDelta
(SNVT_pwr_fact)
Send condition:
delta power factor
Object cpPwrMaxSndT
SCPTmaxSendTime
(SNVT_time_sec)
Send condition: maximum time until
transmission of network variables
Nv
Index
Network Variable Data Type Description
Phase Voltages
20 nvoU12 SNVT_ volt_f Phase-to-phase voltage, L1 and L2
21 nvoU23 SNVT_ volt_f Phase-to-phase voltage, L2 and L3
22 nvoU31 SNVT_ volt_f Phase-to-phase voltage, L3 and L1
23 nvoU1N SNVT_ volt_f Phase-to-neutral voltage, L1 and N
24 nvoU2N SNVT_ volt_f Phase-to-neutral voltage, L2 and N
25 nvoU3N SNVT_ volt_f Phase-to-neutral voltage, L3 and N
27 nvoUAvg SNVT_ volt_f Phase voltage mean value
26 nvoFreq SNVT_ freq_hz Fundamental voltage frequency
Im-
port
Configuration
Property
Data Type Description
Object cpVoltMaxSndT
SCPTmaxSendTime
(SNVT_time_sec)
Send condition: maximum time until
transmission of network variables
Nv 20
...26,
27
cpVoltSndDelta
UCPTvoltSendDelta
(SNVT_volt_f)
Send condition: delta voltage
Nv 26 cpFreqSndDelta
UCPTfreqSendDelta
(SNVT_freq_hz)
Send condition: delta frequency
Object cpPTConnType
UCPTconnType
(conn_type)
Voltage transformer connection type,
Object cpPTPrimary
UCPTptVoltagePrim
(SNVT_volt_f)
Nominal primary transformer voltage
Object cpPTSecondary
UCPTptVoltageSec
(SNVT_volt_f)
Nominal secondary transformer
voltage
Nv
Index
Network Variable Data Type Description
28 nviEnergyClr 1) SNVT_switch Reset nvoWhTot
30 nvoWhTot
SNVT_elec_whr_f
Total active energy, all 3 phases
31 nvoVarhTot SNVT_elec_whr_f Total reactive energy, all 3 phases
32 nvoEnergyClrTs
SNVT_time_stamp
Date and time of resetting of
nvoWhTot and nvoVarhTot
29
nviEnergyFreeze
2)
SNVT_switch Freeze active energy meter reading
36 nvoRegValWhFr
SNVT_reg_val_ts
Frozen meter reading with date and
time
38
nvoRegValWhTot
SNVT_reg_val Total active energy, all 3 phases,
cannot be reset
37
nvoRegValWhSec
SNVT_reg_val Total secondary active energy, all 3
phases, cannot be reset
39
nvoRegValVarhTot
SNVT_reg_val Total reactive energy, all 3 phases,
cannot be reset
34
nvoEnergyPwrPri UNVT_energyPower
Energy, power and fault for use with
U1601
35
nvoEnergyPwrSec UNVT_energyPower
Secondary energy, secondary power
and fault for use with U1601
40 nvoEnergyPwrVarh
UNVT_energyPower
Reactive energy, reactive power and
fault for use with U1601
33
nvoEnergyFlowHrs SNVT_time_hour
Operating hours exceeded with the
meter’s start-up threshold
Im-
port
Configuration
Property
Data Type Description
Object cpEnergyMaxSndT
SCPTmaxSendTime
(SNVT_time_sec)
Send condition: maximum time until
transmission of network variables
Object cpEnergySndDelta
UCPTenergySendDelta
(SNVT_elec_whr_f)
Send condition: delta energy
Object
cpEngyAccumMode
UCPTenergyAccumMode
(acc_mode)
Energy meter operating mode,
read-only
Object cpPulseRate UCPTpulseRate
(SNVT_count_f)
Pulse rate, S0 output 1, pulses per
kWh, with reference to secondary
energy, writeable with features V2
and V4, otherwise read-only
CT Display LON
Unit
LON
Resolution
U128x xx.xx A A 10 mA
1 x.xxx A A 1 mA
2 ... 10 xx.xx A A 10 mA
11 ... 100 xxx.x A A 100 mA
101 ... 1000 xxxx A A 1 A
1001 ... 10 000 xx.xx kA A 10 A