Graco HORIZON Operation manual

308–607
Rev. B
Supersedes A
First
choice when
quality counts.
INSTRUCTIONS-PARTS
LIST
INSTRUCTIONS
This
manual contains important
warnings and information.
READ AND KEEP FOR REFERENCE.
Fluid
Management Systems
GRACO INC. P.O. BOX 1441
MINNEAPOLIS, MN
55440–1441
COPYRIGHT
1997, GRACO INC.
Graco
Inc. is registered to I.S. EN ISO 9001

2
308–607
Table
of Contents
Terms 2.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Symbols 3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Warning 3
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pre-installation
Checklist
4.
. . . . . . . . . . . . . . . . . . . . .
Installation
Checklist
6.
. . . . . . . . . . . . . . . . . . . . . . . . .
Hardware Installation 8.
. . . . . . . . . . . . . . . . . . . . . . . . .
Flush
the System
8.
. . . . . . . . . . . . . . . . . . . . . . . . . .
Install
Solenoids and Meters
8.
. . . . . . . . . . . . . . . .
Set
Control Module Addresses
8.
. . . . . . . . . . . . . .
To
Change from 120 V
AC to 240 V
AC 9.
. . . . . . . .
Mount
the Control Module and Keypad Bracket
10
Cable Routing and Connection 11.
. . . . . . . . . . . . . . .
Connect
the AC Electrical Power
11.
. . . . . . . . . . .
Route
the Solenoid and Meter Cables
12.
. . . . . . .
Connect
the Solenoid and Meter Cables
12.
. . . . .
Connect
the Control Modules to the CAN
13.
. . . .
Connect
the Keypad Cable
14.
. . . . . . . . . . . . . . . .
Connect
the Printer or Computer Cable
14.
. . . . . .
Visually
Check the Wire Connections
14.
. . . . . . . .
System
Setup
15.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Startup 15
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Modify
or New
17.
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Clear
Setup
18.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Print
Setup
19.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Update Tables 20.
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostics 21
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time
and Date
24.
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Operator
Access
24.
. . . . . . . . . . . . . . . . . . . . . . . . .
Save
Setup
25.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control
Modules
25.
. . . . . . . . . . . . . . . . . . . . . . . . . .
Fluids 26
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dispense
Areas
27.
. . . . . . . . . . . . . . . . . . . . . . . . . .
Connection
Assignments
28.
. . . . . . . . . . . . . . . . . .
Meter
Calibration
29.
. . . . . . . . . . . . . . . . . . . . . . . . .
Inventory 30
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Report
Options
31.
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Run
Options
31.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System T
ime Outs
31.
. . . . . . . . . . . . . . . . . . . . . . . .
Run Mode 32.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Dispensing 32
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Review
Jobs
36.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting 38
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Maintenance 39
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Shutdown
Procedure
39.
. . . . . . . . . . . . . . . . . . . . . .
Power
Failure
39.
. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Control
Module is Not User Repairable
39.
. . . . . .
To
Clean The Keypad
39.
. . . . . . . . . . . . . . . . . . . . .
To
Install New Software
39.
. . . . . . . . . . . . . . . . . . .
To
Replace the Complete Pulse Meter
40.
. . . . . . .
To
Replace the Electronic Pulse Module
40.
. . . . .
To
Replace the Metering Unit
40.
. . . . . . . . . . . . . . .
To
Clean the Solenoid V
alve 41.
. . . . . . . . . . . . . . .
Horizon
System Components
42.
. . . . . . . . . . . . . . . .
Control
Modules
42.
. . . . . . . . . . . . . . . . . . . . . . . . . .
Keypads 44
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Keypad
W
all-mount Bracket
45.
. . . . . . . . . . . . . . . .
Fluid
Solenoid V
alves 46.
. . . . . . . . . . . . . . . . . . . . .
Air
Solenoid V
alves 46.
. . . . . . . . . . . . . . . . . . . . . . .
Pulse
Meters
47.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
System
Cables
48.
. . . . . . . . . . . . . . . . . . . . . . . . . . .
Pressure
Relief Kit
50.
. . . . . . . . . . . . . . . . . . . . . . . .
Fluid
Check V
alve 50.
. . . . . . . . . . . . . . . . . . . . . . . .
40
Column Thermal Printer
50.
. . . . . . . . . . . . . . . .
Appendix
Horizon
Software Features
52.
. . . . . . . . . . . . . . . . . . .
System Configuration 53.
. . . . . . . . . . . . . . . . . . . . . . .
Installation
Considerations
53.
. . . . . . . . . . . . . . . . .
Steps
For Configuring A System
53.
. . . . . . . . . . . .
System
Design Suggestions
53.
. . . . . . . . . . . . . . .
System
Configuration Examples
54.
. . . . . . . . . . . .
Horizon
Forms #1–6
(Guide to Initial Setup)
56.
System
Dynamics And Design Factors
67.
. . . . . . .
Pressure
Relief Kit
67.
. . . . . . . . . . . . . . . . . . . . . . . .
Dispense
Fluid During System Failure
67.
. . . . . . .
Avoiding
Pulsation
69.
. . . . . . . . . . . . . . . . . . . . . . . .
Selecting
a Supply Pump
69.
. . . . . . . . . . . . . . . . . .
Technical
Data
70.
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Graco
W
arranty and Limitation of Liability 72.
. . . .
Graco
Phone Number
72.
. . . . . . . . . . . . . . . . . . . . . . .
Terms
CAN:
Controller Area Network; network that
interconnects the control modules in the system.
Dispense Point:
The combined designation of the
dispense area and fluid number
.
Fluid Zone:
The groups of reels that share a pulse
meter.
Keypad:
Hand-held device with display screen and
keys that communicates with the control module it is
connected to.
Master Control Module:
In addition to the functions of
a
Slave Control Module
, it controls activity over the
CAN
, has additional memory
, provides printer or
computer interface, and continuously tracks the time
and date.
Non-volatile Memory:
Data is retained when the
power is shut of
f.
Simultaneous Dispensing:
The ability for more than
one hose reel in the Horizon system to be dispensing
fluid at the same time. The Horizon allows up to 12
dispenses to take place at a time.
Slave Control Module:
Drives air and fluid solenoids
and counts pulses of the meters that are connected
to it.

308–607 3
Symbols
Warning Symbol
WARNING
This
symbol alerts you to the possibility of serious
injury or death if you do not follow the instructions.
Caution Symbol
CAUTION
This
symbol alerts you to the possibility of damage to
or destruction of equipment if you do not follow the
instructions.
WARNING
FIRE, EXPLOSION, AND ELECTRIC SHOCK HAZARD
Improper
grounding, poor air ventilation, open flames, or sparks can cause a hazardous condition and
result in fire or explosion and serious injury
.
The Horizon System must only be installed and serviced by a qualified electrician.
Ground the equipment. See
Connect AC Electrical Power to the Control Module
, page 1
1.
Do not install the equipment in a hazardous area.
Extinguish all the open flames or pilot lights in the dispense area.
Keep the dispense area free of debris, including solvent, rags, and gasoline.
Do not smoke in the dispense area.
If there is any static sparking while using the equipment,
stop dispensing immediately
. Identify
and correct the problem.
Keep liquids away from the electrical components.
Disconnect electrical power at the main switch before servicing the equipment.
INSTRUCTIONS
EQUIPMENT MISUSE HAZARD
Equipment
misuse can cause the equipment to rupture, malfunction, or start unexpectedly and result
in serious injury
.
This equipment is for professional use only
.
Read all instruction manuals, tags, and labels before operating the equipment.
Use the equipment only for its intended purpose. If you are uncertain about usage, call your Graco
distributor.
Do not alter or modify this equipment. Use only genuine Graco parts and accessories.
Check the equipment daily
. Repair or replace worn or damaged parts immediately
.
Do not exceed the maximum working pressure of the lowest rated system component. See the in
-
struction manuals of the individual system components for their maximum working pressures.
Do not stop or deflect fluid leaks with your hand, body
, glove, or rag.
Follow the
Shutdown Procedure
on page 39 whenever you stop dispensing; or clean, check, or
service the equipment.
Use fluids or solvents that are compatible with the equipment wetted parts. See the
T
echnical Data
section of all the equipment manuals. Read the fluid and solvent manufacturer
’
s warnings.
Comply with all applicable local, state and national fire, electrical and other safety regulations.

4 308–607
Pre-installation
Checklist
CAUTION
Accurately
and thoroughly document the Control Module port connections and dispense areas. If the Software
Map does not exactly match the way the cables are connected, the system will not operate properly
. Errors that
could occur include: inability to turn on a fluid at a given dispense area; the wrong fluid or dispense point is acti
-
vated; or a fluid dispense point is properly activated, but the wrong meter is monitored so the dispense job will not
shut of
f properly
.
This process is not difficult, but it is detailed and precise. Follow all steps and document them according to this
manual to ensure a successful installation.
Follow these steps before beginning to install the Horizon system.
n
Pre-installation Steps
Reference
1.
Locate the Floor Plan, System Map (diagram of component locations), and all
other documentation used to specify the system prior to ordering it.
If this information cannot be located, recreate it from the packing slip that
came with the system.
Packing slip and
Appendix, pages
51–69
2. V
erify that all the parts on the Floor Plan match the parts shipped to you. Floor Plan, purchase
order
, and packing
slip
3. V
erify that all Horizon system components are marked in their proper loca
-
tions on the Floor Plan. Floor Plan
4.
Assign a name and number to all the control modules in the system. Record
the control module numbers on the Floor Plan.
D
The Master Control Module (which the Administrative Keypad and printer
or computer connect to) is always assigned number 1.
D
Additional Slave Control Modules are numbered in sequence as 2, 3, etc.
D
The control modules do not have to be in numerical order along the
network cable.
Floor Plan
5.
Assign a name and number to each dispense area. Record the names and
numbers on the Floor Plan.
D
The dispense area usually consists of banks of hose reels, but may also
consist of oil bars or individual hoses.
D
The names should make sense to the shop personnel who will use the
system. For example:
Fast Lube, Service Bay 3, etc
.
Floor Plan
6.
Within each dispense area, verify that the Floor Plan shows the fluid that
each reel or hose should dispense.
Floor Plan

308–607 5
Pre-installation
Checklist
nPre-installation
Steps
Reference
7.
Repeat the following steps for each control module:
a.
For each solenoid attached to the control module, assign one port num
-
ber
, from 1 to 6. Record the port number and whether it is an air or fluid
solenoid on the Floor Plan.
NOTE:
Air and fluid solenoids can be inter
-
mixed on the Horizon ports.
b.
For each meter attached to the control module, assign one port number
,
from 7 to 12. Record the port number on the Floor Plan.
NOTE:
More
than one dispense point (reel, oil bar
, hose, etc.) can share a meter
.
CAUTION:
Record all the information carefully as it must be accu
-
rately entered during software setup.
Floor Plan
8.
Record the system data from the Floor Plan to the corresponding Pre-instal
-
lation Forms. The completed forms will ease system setup by placing the
information in the order the software will request the input. T
o ease software
setup, keep the items in numerical order
.
Pre-installation Forms
Form #1:
User Name, PIN Number
, and Access Level
Form #2:
Control Module and Fluid: Names and Numbers
Form #3:
Dispense Area Names and Numbers
Form #4:
Connection Assignments
Form #5:
Meter Calibration Chart
Form #6:
W
arranty Registration and Checkout Form
Floor Plan and Forms
1–6; see examples of
forms on pages 56–66
9.
Make sure the following tools are available for the system installation:
D
Drill, drill bit, and anchors to mount the control modules and keypad
brackets on the walls or beams
D
Wire cutter
D
Wire stripper (wire gauge ranges between 18 and 22 A
WG)
D
Small, slotted screwdriver
D
VOM (volt-ohmmeter) or multimeter to check cable continuity
, input
voltage, etc.
10. Y
ou are now ready to install the system. See the
Installation Checklist
on
page 6.

6 308–607
Installation
Checklist
After
completing the
Pre-installation Checklist
on page 4, use the following installation checklist to guide you
through the steps of the system installation.
Hardware Installation
Installation
Steps
Reference
1.
Flush all fluid lines to remove the debris and avoid clogs in the meters.
2.
Install the solenoids and meters in the fluid and air systems. Floor plan, Appendix
(pages 67–69), and
solenoid and meter
manuals
3.
Set the control module addresses with the DIP switches and label each
control module.
Floor plan and
page 8
4.
If the electrical input is 240 V
AC, rewire the transformer
.
Page 9
5.
Mount each control module and keypad bracket in its assigned location.
Floor plan and
page 10
Cable Routing and Connection
Installation
Steps
Reference
6.
Route and connect the AC power to each control module.
Do not turn on
the power yet!
Floor plan and
page 1
1
7.
Route the solenoid and meter cables to their assigned control module.
Floor plan
8.
Connect each solenoid and meter cable to the proper connector/port in the
assigned control module.
CAUTION:
Observe
the proper polarity of meter connections or the meter
will be damaged.
Floor
plan and
page 12
9.
Route the CAN network cable between the control modules. Connect the
cable to the proper control module connectors. Remove the terminating
resistor from the connectors of the control modules that are in the middle of
the network chain.
Floor plan and
page 13
10.
Route and connect the keypad cables between the keypads and the control
modules.
Floor plan and
page 14
11.
Route and connect the printer or computer cable between the Master Control
Module and the printer or computer
.
Page 14
12. V
isually check that all wiring is connected correctly
. Compare the wiring to the
diagrams in this manual.
Pages 1
1–14

308–607 7
Installation
Checklist
System Startup
Installation
Steps
Reference
13. T
urn on the printer or computer
.
14. T
urn on the AC power to each control module. All the keypads should briefly
display a revision screen and then the HOME screen. The printer should print
“WELCOME T
O HORIZON...” If the HOME screen is not displayed and/or
there is no print-out, see T
roubleshooting, page 38.
Page 15
15.
Using the Administrative Keypad, which is connected to the Master Control
Module, access the Setup screens. The Password is 1
11
1 for a new system
installation.
Page 15
16.
If your system has one control module only
,
disable the CAN network.
Page 16
17.
Select CLEAR SETUP to intialize the system. Be sure to enter a new pass
-
word for setup access before exiting Setup.
Page 18
18.
Using the administrative keypad, connected to the Master Control Module,
complete the System Setup. Use the six forms that were filled out in the
Pre-installation Procedure
(refer to step 8, page 5) to enter the System
Map information into the Setup screens.
Pre-installation Forms
and Appendix, pages
56–65, or page 17,
Step 6
Test the System
Installation
Steps
Reference
19.
Request a dispense job for each fluid to each location. If any problems occur
,
see
Diagnostics
, page 21, and
Troubleshooting
, page 38.
Pages 32 – 35
20.
Select SETUP
PRINT SETUP
ALL MEMOR
Y to print a record of all the
data entered during Setup. Send a copy of this record and all other required
documents as instructed in Pre-installation Form 6,
W
arranty Registration &
Checkout Form
.
Pages 19 and 66
System Installation Complete

8
308–607
Hardware
Installation
CAUTION
It
is important to follow the floor plan or note any
deviations as the software addresses will be setup
according to what the floor plan shows. If addresses
and physical connections do not match, the system
will not operate properly
.
1. Flush the System
Flush
the fluid and air lines thoroughly to remove any
particles that could clog the meters.
2. Install Solenoids and Meters
WARNING
A
Pressure Relief Kit is required in the
Horizon system to reduce the risk of
serious injury
, caused by splashing fluid
in the eyes or on the skin resulting from component
rupture from over-pressurization. See Fig. 18,
page 67. See page 50 to order the kit.
Install the fluid system with the meters and solenoids in
their designated locations. Install pressure relief kits,
check valves, ball valves, fluid filters and other acces
-
sories that are shown in the floor plan. Refer to Appen
-
dix, pages 67 to 69.
3. Set Control Module Addresses and
Label the Boxes
Each
control module is numbered. The Master Control
Module is always number 1. The Standard Control
Modules can have an address number from 2 to 40.
Set the control module addresses with the DIP
switches as shown in the chart on page 9. Refer to
the Detail drawing of the DIP switches in Fig. 1. See
page 43 for the location of the DIP switches in the
control module.
Label the control module boxes with their designated
number.
NOTE:
The Slave Control Modules are shipped with their
address set to 0.
The addresses are binary numbers.
It is imperative that each control module has a
unique address, set by the DIP switches. Each
packet of information sent through the network
contains the unique address of the control module
the information is intended for
. If the DIP switches
are not set to the correct address, the control
module will not receive its information. If two control
modules have the same address, both of them will
receive the information and try to act on it, resulting
in system errors and incorrectly dispensed jobs.
DIP switch 7
is used to tell the control module
whether a basic keypad or enhanced or administra
-
tive keypad is connected to it. The OFF position
indicates a basic keypad is connected. The ON
position indicates an enhanced or administrative
keypad is connected.
DIP switch 8 should be in the ON position for
normal system operation. The OFF position turns
on all six solenoid drivers in the control module.
This option can be used when there is a system
failure and fluids need to be dispensed. The moni
-
toring and controlling of dispensed fluids is disabled
when the switch is in the OFF position.
Fig. 1
Basic
Keypad
Connected
Automatic
Operation
Control
Control Module
Addresses

308–607
9
Hardware
Installation
3. Set Control Module Addresses and
Label the Boxes (continued)
DIP
Switch
No.
1 2 3 4 5 6 Address
Setting OFF OFF OFF OFF OFF OFF
0*
Setting
ON OFF OFF OFF OFF OFF 1
OFF ON OFF OFF OFF OFF 2
ON ON OFF OFF OFF OFF 3
OFF OFF ON OFF OFF OFF 4
ON OFF ON OFF OFF OFF 5
OFF ON ON OFF OFF OFF 6
ON ON ON OFF OFF OFF 7
OFF OFF OFF ON OFF OFF 8
ON OFF OFF ON OFF OFF 9
OFF ON OFF ON OFF OFF 10
ON ON OFF ON OFF OFF 11
OFF OFF ON ON OFF OFF 12
ON OFF ON ON OFF OFF 13
OFF ON ON ON OFF OFF 14
ON ON ON ON OFF OFF 15
OFF OFF OFF OFF ON OFF 16
ON OFF OFF OFF ON OFF 17
OFF ON OFF OFF ON OFF 18
ON ON OFF OFF ON OFF 19
OFF OFF ON OFF ON OFF 20
ON OFF ON OFF ON OFF 21
OFF ON ON OFF ON OFF 22
ON ON ON OFF ON OFF 23
OFF OFF OFF ON ON OFF 24
ON OFF OFF ON ON OFF 25
OFF ON OFF ON ON OFF 26
ON ON OFF ON ON OFF 27
OFF OFF ON ON ON OFF 28
ON OFF ON ON ON OFF 29
OFF ON ON ON ON OFF 30
ON ON ON ON ON OFF 31
OFF OFF OFF OFF OFF ON 32
ON OFF OFF OFF OFF ON 33
OFF ON OFF OFF OFF ON 34
ON ON OFF OFF OFF ON 35
OFF OFF ON OFF OFF ON 36
ON OFF ON OFF OFF ON 37
OFF ON ON OFF OFF ON 38
ON ON ON OFF OFF ON 39
OFF OFF OFF ON OFF ON 40
* Slave
Control Modules are shipped with their address set
to 0.
4. To Change from 120 VAC to 240 VAC
WARNING
FIRE,
EXPLOSION, AND ELECTRIC
SHOCK HAZARD
T
o reduce the risk of fire, explosion, and
electric shock all wiring must be done by
a qualified electrician.
a.
Power should not be connected at this point of
installation if the procedure is being followed
properly
. Make sure there is no power to the
control module(s).
b.
See Fig. 2 wire connections for 120 V
AC. Cut
the white wire connecting transformer termi
-
nals 2 to 6 at the terminal 2 connector
.
c.
Cut the black wire connecting transformer
terminals 1 to 5 at the terminal 1 connector
.
d.
Switch the connectors on terminals 2 and 6.
See Fig. 2 wire connections for 240 V
AC.
e.
Strip 0.25 in. (6.4 mm) of insulation from the
wires connected to terminals 2 and 5. Connect
the wires together with a wire nut.
Fig. 2
06652
120 V
AC Connection
240 V
AC Connection
transformer
wire
nut
06897
transformer
Wire
Connector Color
1 black
2 white
5 black
6 white
Wire
Connector Color
1 black
2 white
5 black
6 white

10
308–607
Hardware
Installation
5. Mount the Control Module and Keypad
Bracket
Control Module
D
The control module(s) should be mounted near the
hose reels. Control modules can be mounted on the
wall or at ceiling level.
D
Locate the control module(s) as directed in the floor
plan, being sure to follow the cable length and other
configuration requirements.
D
The mounting surface must be able to support the
weight of the control module, 14 lbs. (6.3 kg). Use
wall anchors if necessary
.
D
See Fig. 3 for the mounting hole layout.
6
in. (152.4 mm)
8.75 in. (222.3 mm)
Fig.
3
06799
Keypad Bracket
See Fig. 4 for the mounting hole layout.
3.44
in. (87.4 mm)
3.66 in. (93.0 mm)
1.97 in. (50.0 mm)
1.77 in. (45.0 mm)
0.62 in. (15.7 mm)
Fig.
4

308–607 1
1
Cable
Routing and Connection
6. Connect the AC Electrical Power to the
Control Module
WARNING
FIRE,
EXPLOSION, AND ELECTRIC
SHOCK HAZARD
T
o reduce the risk of fire, explosion, and
electric shock:
D
All wiring must be done by a qualified electri
-
cian.
D
Ground the Horizon system by connecting the
electrical power cable to a true earth ground.
Wire the control module(s) into the facility’
s electrical
system. It is recommended that the system be wired to
a separate circuit breaker
. This will help prevent acci
-
dental shutdown of the system and make it easier to
power of
f the system when necessary
. The system is
designed to remain powered-up continuously during
normal operation.
T
o ease system maintenance, install a switch for
turning of
f the power at each control module. Locate
the switches near each control module, but out of
reach from the floor to prevent accidental shutof
f of
power to the control module.
Connect the power cable to the control module as
shown in Fig. 5.
Fig. 5
green
AC
AC
power supply
, 120 V
AC or 240 VAC; 240 V
AC operation
requires modification of transformer connections inside control
module. See page 9.
Leave green ground wire 2 inches (50.8 mm) longer than the
two AC wires.
T
o chassis ground
T
o transformer
Strip 0.25 in. (6.4 mm) of insulation from wires, insert wires into
terminal block, and tighten screws to hold wire.

12
308–607
Cable
Routing and Connection
7. Route the Solenoid and Meter Cables
to their Assigned Control Module
8. Connect the Solenoid and Meter
Cables
a. Connect
the solenoid cables as shown in Fig.
6. The cables connect at the solenoid end with
wire nuts.
b.
Connect the Ready Light as shown in Fig. 6.
c.
Connect the pulse meter cables. The cables
connect at the pulse meter end with wire nuts.
D
Connect an oil meter as shown in Fig. 7.
D
Connect an anti-freeze meter as shown in
Fig. 8. Be sure to install the RC Filter
.Fig. 6 06577
P8
or P9
Solenoid Connection
Use
bulk Cable P/N 1
13–557 (500 ft. [152.5 m]) or 1
13–558
(1000 ft. [305 m)]); 50 ft. (15.3 m) maximum length
Ready Light Kit 238–996
NOTE:
If existing Ready Light is used, the bulb and lens must
be replaced with bulb P/N 1
13–859 and lens 1
13–857
Fluid Solenoid P/N 218–588 (includes Ready Light), 215–487
or 512–927; Air Solenoid P/N 215–407 or 512–926
NOTE: See Fig. 9, page 13, for connector locations.
Fig. 7 06579
J5
P5
Pulse Meter P/N 238–618 Connection
ground
signal
+12V
black
white
red
Connector
J5 in this drawing; can be J5, J6, or J7
Use bulk Cable P/N 1
13–555 (500 ft. [152.5 m]) or
1
13–556 (1000 ft. [305 m)]); 50 ft. (15.3 m) maxi
-
mum length
Pulse Meter P/N 238–618
ground
signal
signal
ground
+12V
shield
+12V
shield
black
white
red
Circuit Board
Fig.
8
06580
Pulse Meter P/N 215–474 Connection
P5
shield
black
red
Connector
J5 in this drawing; can be J5, J6, or J7
RC Filter P/N 1
13–837; included with meter
Pulse Meter P/N 215–474
NC=No Connection
N/C N/C
black
red
ground
signal
N/C
ground
signal

308–607
13
Cable
Routing and Connection
9. Connect the Control Modules to the
CAN (Controller Area Network)
WARNING
FIRE,
EXPLOSION, AND ELECTRIC
SHOCK HAZARD
T
o reduce the risk of fire, explosion, and
electric shock all wiring must be done by
a qualified electrician.
The cables are connected at each control module by
stripping the wires and connecting the wires as shown
in Fig. 10. Refer to Fig. 9 for the placement of the
control module connectors.
Each control module ships with a terminating resistor
on the connector for the CAN network. When the cable
is connected to the control module, the resistor must
be removed from the control modules located in the
middle of the network chain, leaving only the resistors
at each end of the network. The end resistors are
necessary for the control modules to be able to com
-
municate properly with each other across the network.
Connect the control module(s) in the middle of the
network chain as shown in Fig. 10, with the termi
-
nating resistor removed.
Connect the control modules at the end
of the
network chain as shown in Fig. 10, with the termi
-
nating resistor in place.
Fig. 9 06581
Control Module Connectors
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
1
2
3
4
5
6
123456
Fig. 10 06578
black
clear
shield
black black
clear clear
shield shield shieldshieldshield
P4 P4 P4 P4
End
of Chain
Middle of Chain
(resistor removed)
Middle of Chain
(resistor removed)
End of Chain
Controller
Area Network
(4 control modules shown)
Use
Bulk Cable P/N 1
13–559 (500 ft. [152.5 m]) or 1
13–560 (1000 ft. [305 m)])
NOTE:
No distance requirement between control modules provided the overall length of the network cables does not exceed 2000 ft. (610 m).

14
308–607
Cable
Routing and Connection
10.Connect the Keypad Cable
Route
and connect the keypad cables between the
keypads and control module connectors. If using the
Administrative or Enhanced Keypad, be sure to con
-
nect the cable to the top keypad connector
. The bottom
connector is for the bar code reader
.
11.Connect the Printer or Computer Cable
Route
and connect the printer or computer cable
between the printer or computer and the control mod
-
ule connectors. See
Connecting T
o Printer P/N
113–774
, below
, for further printer information.
12.Visually Check the Wire Connections
NOTE:
The Horizon hardware installation is now
complete. The
Checklist
Steps 1 to 12, page 6,
should be checked of
f.
Connecting to Printer P/N 1
13–774
252423222120191817161514
13 12 11 10 9 8 7 6 5 4 132
25 24 23 22 21 20 19 18 17 16 15 14
13121110987654132 54132
9876
87654132654132
Printer P/N 1
13–774
25
Pin D–Sub Male Pin Connector
(Jumper 6 to 20)
Control Module
9
Pin D–Sub Male Pin Connector
ON
OFF
Standard DIP Switch Settings for Printer 113–774
Printer
serial port
Printer cable with connector
, P/N 191–395 (25 ft. [7.6 m])
or 191–396 (50 ft. [15.3 m)])
Fig.
1
1
green
white
red
ground
receive
transmit
ground
receive
transmit
shield

308–607 15
System Setup – Startup
CAUTION
The
addresses in the software must match the
physical connections to the control modules or the
system will not operate properly
.
Instructions Screens
Startup Screen
This
screen is displayed for four seconds after the
system is turned on, then the
Mode Selection
screen
(or Home screen) appears.
ST
ARTUP Screen
HORIZON
REV X.XX
GRACO INC
COPYRIGHT XXXX
1. Mode Selection (HOME)
NOTE:
This is the HOME screen. It is the destination
any time the HOME button on the keypad is pressed.
a.
Cursor is initially on RUN.
b.
Move the cursor to SETUP by pressing the
"
or #
key
.
NOTE: The SETUP option can only be modified on
the administrator keypad.
c.
Press ENTER on the keypad.
HOME Screen
_ _ _ _ _ _ _ _ _ _
"
HOME
A
_ _ _ _ _ _ _ _ _ _
RUN SETUP
INVNT
2. Enter Password
NOTE:
The password is determined by what is entered
during setup. The first time the system is started, the
Password is 1
111.
a.
Cursor is in the P
ASSWORD field.
b. T
ype the password.
c.
Press ENTER on the keypad.
P
ASSWORD Screen
ENTER P
ASSWORD
SETUP MENU
XXXX

16 308–607
System
Setup – Startup
Instructions
3. Type of Setup
a. SETUP
screen appears.
b.
Cursor is on ENABLE CAN.
c.
Move the cursor by pressing the
"or #
key
.
d.
Press ENTER on the keypad when the cursor
is at the desired selection.
D
ENABLE CAN is the default selection. It
indicates that the systems has more than
one control module. T
o change to DIS
-
ABLE CAN, which must be done for a
system with only one control module,
follow step 4 below
.
D
MODIFY SETUP to modify a current setup.
Follow step 5, page 17.
D
NEW SETUP to enter a completely new
setup. Follow step 6, page 17.
D
CLEAR SETUP to clear particular setup
options. Choose CLEAR SETUP if this is
the initial setup of a new system. Follow
step 7, page 18.
D
PRINT SETUP to print out selected infor
-
mation about the control module. If this is
the initial setup of a new system, print out
ALL MEMOR
Y after the system is com
-
pletely installed, for future reference. Fol
-
low step 8, page 19.
DUPDA
TE T
ABLES to send information from
one control module to all connected control
modules. If the Master Control Module was
setup of
f-line, use this feature to send
information to all control modules after
they are connected.
D
DIAGNOSTICS to help troubleshoot the
system.
Screens
SETUP Screens
_ _ _ _ _ _ _ _ _ _
"
SETUP
A
_ _ _ _ _ _ _ _ _ _
ENABLE CAN
MODIFY SETUP
NEW SETUP
#
_ _ _ _ _ _ _ _ _ _
"
SETUP
A
_ _ _ _ _ _ _ _ _ _
CLEAR SETUP
"
PRINT SETUP
UPDA
TE T
ABLES #
_ _ _ _ _ _ _ _ _ _
"
SETUP
A
_ _ _ _ _ _ _ _ _ _
PRINT SETUP
"
UPDA
TE T
ABLES
DIAGNOSTICS
4. Enable/Disable CAN Option
NOTE:
See page 2 for CAN definition.
a.
With the cursor at ENABLE CAN, press
ENTER on the keypad.
b.
The CAN COMMUNICA
TIONS screen will ap
-
pear
, with the cursor at ENABLE CAN.
c.
Press the
#or " key
to toggle between
ENABLE and DISABLE CAN. Change to DIS
-
ABLE CAN if the system has only one control
module.
d.
Press ENTER on the keypad when the cursor
is at the desired option.
e.
The controller will return to the SETUP OP
-
TIONS screen to allow another option to be
selected and modified until HOME is pressed.
_ _ _ _ _ _ _ _ _ _
"
SETUP
A
_ _ _ _ _ _ _ _ _ _
ENABLE CAN
MODIFY SETUP
NEW SETUP
#
CAN Screen
CAN COMMUNICA
TIONS:
ENABLE CAN
"#
PRESS ENTER KEY T
O
CHANGE

308–607 17
System
Setup – Modify or New
Instructions Screens
5. Modify Setup Options
a. With
the cursor at MODIFY SETUP
, press
ENTER on the keypad.
b.
The SETUP OPTIONS screen will appear
.
Only Master Control Module will have TIME
AND DA
TE on the screen.
c.
Scroll to the option that needs to be modified
by pressing the
#or " key.
d. Press
ENTER on the keypad when the cursor
is at the desired option.
e.
Follow the instructions for modifying the se
-
lected option on pages 24 to NO
TAG.
f.
Everytime a setup option is modified and
saved, the controller will return to the SETUP
OPTIONS screen to allow another option to be
selected and modified until HOME is pressed.
NOTE:
The options that can be defined in
MODIFY SETUP include:
DT
ime and date*
D
Operator pass
-
words
D
Control modules
DFluids
D
Dispense areas
D
Assign connec
-
tions
D
Meter calibration
DInventory
D
Report options
D
Run options
D
System time outs
* On Master Control Module only
.
_ _ _ _ _ _ _ _ _ _
"
SETUP
A
_ _ _ _ _ _ _ _ _ _
ENABLE CAN
MODIFY SETUP
NEW SETUP
#
MODIFY SETUP Screen
SETUP OPTIONS:
TIME AND DA
TE
OPERAT
OR P
ASSWORDS
CONTROL MODULES
#
6. New Setup Options
NOTE:
If you are installing a new system, use CLEAR
SETUP!
ALL MEMOR
Y to prepare the system for
setup. See page 18.
a.
With the cursor at NEW SETUP
, press ENTER
on the keypad.
b.
Follow the instructions for modifying the op
-
tions on pages 24 to NO
TAG.
c.
Everytime a setup option is modified and
saved, the controller will go directly to the first
screen of the next setup subroutine.
NOTE:
The options that can be defined in NEW
SETUP include:
DT
ime and date*
D
Operator pass
-
words
D
Control modules
DFluids
D
Dispense areas
D
Assign connec
-
tions
D
Meter calibration
DInventory
D
Report options
D
Run options
D
System time outs
* On Master Control Module only
.
_ _ _ _ _ _ _ _ _ _
"
SETUP
A
_ _ _ _ _ _ _ _ _ _
ENABLE CAN
MODIFY SETUP
NEW SETUP
#

18 308–607
System
Setup – Clear Setup
Instructions Screens
7. Clear Setup Options
CAUTION
Clearing
the OPERA
T
OR P
ASSWORDS or ALL
MEMOR
Y will delete all passwords, including the
password the system is supplied with, which allows
Setup access. Before exiting SETUP
, enter a new
password for Setup access. See page 24.
a.
Move the cursor to CLEAR SETUP using the
#
key.
b.
Press ENTER on the keypad.
c.
The CLEAR OPTIONS screen will appear, with
the cursor at ALL MEMOR
Y.
d.
Scroll to the option that needs to be modified
by pressing the
#or " key.
e. Press
ENTER on the keypad when the cursor
is at the desired option.
f.
The CLEAR verification screen will appear with
the cursor on
NO
. If ENTER is pressed with
NO selected, the screen will return to CLEAR
OPTIONS screen.
g.
Scroll to YES by pressing the
#or " key.
h. Press
ENTER on the keypad. The selected
table will be cleared and the CLEAR OPTIONS
screen will appear
.
i.
Press BACK key to return to SETUP screen.
NOTE:
The options that can be defined in
CLEAR SETUP include:
D
All memory
D
Operator pass
-
words
D
Control modules
DFluids
D
Dispense areas
D
Assign connections
D
Meter calibration
DInventory
D
Report options
D
Run options
D
System time outs
DQueues
_ _ _ _ _ _ _ _ _ _
"
SETUP
A
_ _ _ _ _ _ _ _ _ _
MODIFY SETUP
"
NEW SETUP
CLEAR SETUP
#
CLEAR OPTIONS Screen
CLEAR OPTIONS:
ALL MEMOR
Y
OPERAT
OR P
ASSWORDS
CONTROL MODULES
#
CLEAR V
erification Screen
CLEAR:" NO " #
WARNING:
YES WILL
CLEAR CURRENT
SETUP V
ALUES

308–607 19
System
Setup – Print Setup
8. Print Setup Options
NOTE:
Only the information for the control module the
keypad is connected to is printed.
a.
Move the cursor to PRINT SETUP using the
#
key.
b.
Press ENTER on the keypad.
c.
The PRINT OPTIONS screen will appear
, with
the cursor at ALL MEMOR
Y.
d.
Scroll to the selection that you want to print by
pressing the
#or " key.
e. Press
ENTER on the keypad when the cursor
is at the desired option. The PRINTING screen
will appear
. Press any key to exit after DONE
appears on the screen.
f.
Press BACK key to return to SETUP screen.
NOTE:
The information that can be printed in
PRINT SETUP include:
D
All memory
D
Operator pass
-
words
D
Control modules
DFluids
D
Dispense areas
D
Assign connections
D
Meter calibration
DInventory
D
Report options
D
Run options
D
System time outs
D
Active Queue
DW
aiting Queue
D
Local Queue
D
General Information
_ _ _ _ _ _ _ _ _ _
"
SETUP
A
_ _ _ _ _ _ _ _ _ _
NEW SETUP
"
CLEAR SETUP
PRINT SETUP
#
PRINT OPTIONS Screen
PRINT OPTIONS:
ALL MEMOR
Y
OPERAT
OR P
ASSWORDS
CONTROL MODULES
#
PRINTING Screen
PRINTING...
DONE!!!
Press a key to exit.

20 308–607
System
Setup – Update T
ables
Instructions Screens
9. Update Tables Options
a. Move
the cursor to UPDA
TE T
ABLES using
the
#
key
.
b.
Press ENTER on the keypad.
c.
The UPDA
TE T
ABLES screen will appear
, with
the cursor at ALL T
ABLES.
d.
Scroll to the option that needs to be modified
by pressing the
#or " key.
e. Press
ENTER on the keypad when the cursor
is at the desired option.
f.
The UPDA
TE T
ABLE verification screen will
appear with the cursor on
NO
. If ENTER is
pressed with NO selected, the screen will re
-
turn to UPDA
TE T
ABLES screen.
g.
Scroll to YES by pressing the
#or " key.
h. Press
ENTER on the keypad. The selected
table will be cleared and the UPDA
TING
screen will appear. Press any key to return to
the UPDA
TE T
ABLES screen.
i.
Press BACK key to return to SETUP screen.
NOTE:
The options that can be defined in
UPDA
TE T
ABLES include:
D
All tables
D
Operator pass
-
words
D
Control modules
DFluids
D
Dispense areas
D
Assign connec
-
tions
D
Meter calibration
DInventory
D
Report options
D
Run options
D
System time outs
DQueues
_ _ _ _ _ _ _ _ _ _
"
SETUP
A
_ _ _ _ _ _ _ _ _ _
CLEAR SETUP
"
PRINT SETUP
UPDA
TE T
ABLES #
UPDA
TE T
ABLES Screen
UPDA
TE T
ABLES:
ALL T
ABLES
OPERAT
OR P
ASSWORDS
CONTROL MODULES
#
UPDA
TE T
ABLES V
erification Screen
UPDA
TE T
ABLE:"
NO
" #
WARNING:
UPDATE
WILL CANCEL
ACTIVE JOBS
UPDA
TING Screen
UPDATING:
PLEASE W
AIT
DONE!!!
PRESS A KEY T
O CONT
.
Table of contents
Other Graco Measuring Instrument manuals

Graco
Graco PE14 User manual

Graco
Graco 256282 User manual

Graco
Graco FLOW METERS S3000 User manual

Graco
Graco ProControl 1KE Plus Operation manual

Graco
Graco PD44 User manual

Graco
Graco PGM Parts list manual

Graco
Graco Pulse TLM Operation manual

Graco
Graco ProControl 1KE Parts list manual

Graco
Graco IM20P Datasheet

Graco
Graco PM8 Setup guide

Graco
Graco G3000 User manual

Graco
Graco PPM 3050H Operation manual

Graco
Graco LDM5 User manual

Graco
Graco SDMM8 User manual

Graco
Graco EFR Operation manual

Graco
Graco FX250 Operation manual

Graco
Graco 309455C Operation manual

Graco
Graco Dispensit 1052 Troubleshooting guide

Graco
Graco Pulse TLM User manual

Graco
Graco G3000 Operation manual