Greyline OCF 5.0 User manual

www.greyline.com
USER'S GUIDE
Installation & Operation
Instructions
Open Channel Flow Monitor
Model OCF 5.0
Manual Series A.1.4

Note: This page has been left blank intentionally.

Page 3
OCF 5.0 Open Channel Flow Monitor
INDEX
CONNECTIONS: ...............................................................................................4
KEYPAD SYSTEM............................................................................................6
CALIBRATION MENU.....................................................................................7
RUN....................................................................................................................8
MESSAGE..........................................................................................................8
STATUS .............................................................................................................8
PASSWORD.......................................................................................................9
UNITS/MODE..................................................................................................10
CALIBRATION................................................................................................11
CHANNEL SETUP ..........................................................................................13
RELAY PARAMETERS..................................................................................14
DATA LOGGING ............................................................................................15
SPECIAL FUNCTIONS...................................................................................17
SENSOR MOUNTING METHODS................................................................19
APPLICATIONS HOTLINE............................................................................26
PRODUCT RETURN PROCEDURE..............................................................27
APPENDIX A - OPTIONS...............................................................................29
CONVERSION GUIDE ...................................................................................33
SPECIFICATIONS...........................................................................................34
IMPORTANT NOTE: This instrument is manufactured and calibrated to meet product specifications.
Please read this manual carefully before installation and operation. Any unauthorized repairs or
modifications may result in a suspension of the warranty.
Available in Adobe Acrobat pdf format

Page 4
OCF 5.0 Open Channel Flow Monitor
CONNECTIONS:
POWER INPUT: The standard model requires AC power input between 100 to 240 VAC 50/60Hz. No
adjustments are necessary for voltages within this range.
Optional DC: 9-32 VDC. Connect to + and - terminals.
Optional Thermostat and Heater modules are available rated for 115 VAC or 230 VAC.
IMPORTANT NOTE: To comply with CSA/UL electrical safety standards, AC power input and relay
connection wires must have conduit entry to the instrument enclosure. Installation requires a switch,
overcurrent fuse or circuit breaker in the building (in close proximity to the equipment) that is marked
as the disconnect switch.
Risk of electric shock. Loosen cover screw to access connections. Only qualified personnel
should access connections.
Note: Use of instrumentation over 40°C ambient requires special field wiring.
Note: User replaceable fuse is 2 Amp 250V (T2AL250V).
!

Page 5
OCF 5.0 Open Channel Flow Monitor
CONNECTIONS
HEATER OPTION
AC
LN
NO
C
NC
NO
C
NC
–
+
4-20mA/0-5V
RLY2
RLY1
AC
GROUND
NC
C
NO
NC
C
NO
NC
C
NO
NC
C
NO
RLY3 RLY4 RLY5 RLY6
EXTRA RELAYS OPTION
POWER
INPUT
GND
SENSOR
DATA LOGGER
USB A
Plug

Page 6
OCF 5.0 Open Channel Flow Monitor
KEYPAD SYSTEM
The OCF 5.0 uses a menu system. Arrows show the four directions to leave a menu box. Press a key to
move to the next item in the direction shown. Move the cursor (underline) under numerals and increase
or decrease numerals with the and keys.
To store calibration values permanently (even through power interruptions), press .

Page 7
OCF 5.0 Open Channel Flow Monitor
CALIBRATION MENU
--Password----------
Password 0000
--Data Logging-------
Log Site ID 0
Mode Flow
Set Date Sep 22/2009
Set Time 14:24:40
Interval 30sec
Log NO
}
--Units/Mode--------
Mode Flow
Linear ft
Volume USG
Time min
Temperature C
}
--Calibration-------
Min Range 1.000ft
Max Range 12.000ft
Damping 10%
LOE Time 30sec
}
--Relay Parameters--
Relay 1
Function Flow
Mode Pump
On 10000 USG/m
Off 8000 USG/m
LOE mode Off
Alternate No
}
USG/m
Tot 20130.8 USG
Relays 1 2 3 4 5 6
0.000
--Message-----------
Data log Stopped
Log Used 0%
Maximum 199.45ft /s
Sensor Good
Temperature 21C
³
--Status------------
Range 1.00ft
Tot 0.000ft
EC 100%
Relays 1 2 3 4 5 6
}
³--Special Functions-
Language English
Analog Out 4-20mA
Backlight High
Reset Totalizer NO
Restore Defaults NO
New Password 0000
}
--Simulation--------
}Test Actual
Flow 250USG/m
4-20mA Flow 4.00
Relays 1 2 3 4 5 6
--Configuration-----
1.18.13
Sonar 1.05
Logger 1.16T
Relays 2
Analog Out 1
}
Utility
--Channel Setup------
Type V-notch
Size 22.5
}
°
--Menu Selections----
Units / Mode
Calibration
Channel Setup
Relay Parameters
Data Logging
Special Functions
Simulation
Configuration
}
--24 hr log----------
Date Feb. 12/2010
Total 50138 USG
Average 34.82 USG/m
Maximum 52.20 USG/m
Max Time 11:08:00
Minimum 0.000 USG/m
Min Time 9:15:00
}

Page 8
OCF 5.0 Open Channel Flow Monitor
RUN
The main display shows the units selected from the Units/Mode menu, Level,
Range, Flow, HRT, and Volume rate being measured, TOTALIZER and RELAY
states. The OCF 5.0 will start-up with this display and will return to this screen
after a timeout if keys are not pressed in other menus.
MESSAGE
Press from the RUN display to view status of the data logger and error/warning
messages provided by the instrument. The word Message will appear on the
RUN display if error messages are being generated by the instrument. Refer to the
manual section Error/Warning Messages for a description. Press to return to the
main display.
STATUS
Press from the RUN display to view instrument status. Range will be displayed
in linear units.
Tot Displays the current totalizer reading.
EC Displays echo confidence.
Relays Energized relays will display as a white character on a black
background.
24 HR LOG
Press from the RUN display to view a formatted flow report from instruments
with a built-in data logger. Press to scroll down one day or repeatedly to scroll
to a specific date. Up to 365 days can be stored. Newest date will overwrite the
oldest. Press to return to the main display.
USG/m
Tot 20130.8 USG
Relays 1 2 3 4 5 6
0.000
--Message-----------
Data log Stopped
Log Used 0%
Maximum 199.45ft /s
Sensor Good
Temperature 21C
³
--Status------------
Range 1.00ft
Tot 0.000ft
EC 100%
Relays123456
}
³
--24 hr log----------
Date Feb. 12/2010
Total 50138 USG
Average 34.82 USG/m
Maximum 52.20 USG/m
Max Time 11:08:00
Minimum 0.000 USG/m
Min Time 9:15:00
}

Page 9
OCF 5.0 Open Channel Flow Monitor
PASSWORD
The Password (a number from 0000 to 9999) prevents unauthorized access
to the Calibration menu.
From the Run display press to get to Password. Factory default password
is 0000 and if it has not been changed press the to proceed to the Menu
Selections screen.
If a password is required, press to place the cursor under the first digit and or
to set the number, then to the second digit, etc. Press or to proceed to
the Menu Selections screen.
A new password can be stored by going to Special Functions/New
Password.
--Password----------
Password 0000

Page 10
OCF 5.0 Open Channel Flow Monitor
UNITS/MODE
From Mode press the and then the or to select Level, Range,
Flow, HRT or Volume.
Range displays distance from the sensor to the target or liquid surface like a
tape measure. Range mode is useful to measure the exact distance
from the sensor to the zero level during calibration.
Level used to measure tank level in linear units, or "Head" in an open
channel for comparison with flow tables.
Volume displays tank inventory in engineering units.
HRT select Horizontal Round Tank mode to calculate and display volume
units in a horizontal round tank.
Flow calculates open channel flow through a flume or weir.
Volume,HRT or Flow gives the additional choice of volumetric units:
ft3 - cubic feet
USG - US gallons
USMG - US million gallons (FLOW only)
IG - Imperial gallons
IMG - Imperial million gallons (FLOW only)
m3 - cubic meters
L - liters
bbl - U.S. oil barrel
Press to store the selection, then to the next menu item and to enter.
Linear press and then or to select units of measurement.
Press to store the selection.
Time press and then or to select day, hr, min or
sec.
Temperature press and then or to select C or F (Centigrade or
Fahrenheit).
Press or to return to the Menu Selections screen.
--Units/Mode--------
Mode Flow
Linear ft
Volume USG
Time min
Temperature C
}
--Units/Mode--------
Mode Flow
Linear i
ft
m
mm
}n
--Units/Mode--------
Volume US
ft3
bbl
L
m3
IMG
IG
USMG
}G
--Units/Mode--------
Temperature C
F
}

Page 11
OCF 5.0 Open Channel Flow Monitor
CALIBRATION
Press to Calibration and to enter. Use or to position before
each menu item and to enter. When settings are completed press to store and
return to the Calibration menu.
Min Range Distance from the sensor face to highest expected level.
Max Range Distance from sensor to Zero level.
MaxVol For Volume and HRT mode only. Enter the maximum volume of
the vertical or horizontal tank.
Damping Minimum damping allows fast response to level changes.
Increasing damping slows the OCF 5.0's response to level changes
and is ideal to smooth the display and outputs in turbulent
conditions. Damping value is shown in percent (0-99%). Some
experimentation may be required to select the optimum damping
value. A value of 1% is recommended for most applications and for
fast level changes (up to ½ inch/sec - 13 mm/sec).
LOE Time Press and or to change the number of seconds without
receiving an echo before the OCF 5.0 displays ECHO LOSS, and
Control relays change state as calibrated under Relay Parameters.
Factory default is 30 seconds and is recommended for most
applications, Minimum is 1 second and maximum is 99 seconds.
Press from the Units/Mode display to return to Menu Selections.
--Calibration-------
Min Range 1.000ft
Max Range 12.000ft
Damping 10%
LOE Time 30sec
}

Page 12
OCF 5.0 Open Channel Flow Monitor
CALIBRATION
- for Open Channel Flow
1. Before starting the calibration determine:
a) MAX RANGE = ____________________
(Maximum range = distance from the Sensor to Zero flow point)
b) MAX LEVEL = ____________________
(Maximum level of flow through flume or weir)
c) MIN RANGE = __________________
(Distance from sensor to Max Level)
Minimum range = MAX RANGE - MAX LEVEL
(must be at least 8" / 20.3 cm depending on sensor model).
2. Check the maximum range with the sensor installed by:
a) When liquid is at zero level press to view the Range reading in the
Status menu. Use this range measured by the OCF 5.0 as the Max
Range setting.
or
b) Carefully measure distance from sensor to zero level with a tape measure,
and use this measurement as the Max Range setting.
NOTE: The OCF 5.0 will not detect targets beyond user entered Max Range.
PALMER BOWLUS
SENSOR
ZERO LEVEL
MAX
RANGE
MIN
RANGE
MAX LEVEL
V-NOTCH
SENSOR
ZERO LEVEL
MAX
RANGE
MAX LEVEL
MIN
RANGE

Page 13
OCF 5.0 Open Channel Flow Monitor
CHANNEL SETUP
--Channel Setup------
Type V-notch
Custom
Khafagi
Rect Weir w/EC
Rect Weir
Trapezoidal
Leopld-Lagco
Palmer Bowlus
Parshall
}
--Channel Setup------
Type V-notch
Size 22.5
120
90
60
45
30
}
°
°
°
°
°
°
--Channel Setup------
Type Custom
K0.0000
n 0.0000
}
--Channel Setup------
Type Khafagi
Width 0.000in
}
--Channel Setup------
Type Rect Weir w/EC
Width 0.000in
}
--Channel Setup----
Type Rect Weir
Width 0.000in
}
--Channel Setup------
Type Trapezoidal
Size Extra large 60
Large 60
Small 60
12in 45 SRCRC
2in 45 WSC
8in 60
}
°
°
°
°
°
°
--Channel Setup------
Type Leopld-Lagco
Size 36in
30in
24in
18in
12in
10in
8in
6in
}
--Channel Setup------
Type Palmer Bowlus
Size 48in
42in
36in
30in
27in
24in
21in
18in
15in
12in
10in
8in
6in
4in
}
--Channel Setup------
Type Parshall
Size 12ft
10ft
8ft
6ft
5ft
4ft
3ft
2ft
18in
12in
9in
6in
3in
2in
1in
}

Page 14
OCF 5.0 Open Channel Flow Monitor
RELAY PARAMETERS
Relay Press and or to select a relay (2 relays are standard, 4
additional are optional).
Function Press or to select Off, Temperature, Pulse
or Flow.
Temperature Air temperature at the sensor location.
Press and and set the relay On and
Off for specific temperatures.
Pulse Press and set digits to the flow volume
increment required between relay pulses.
Use this feature for remote samplers,
chlorinators or totalizers. Minimum time
between pulses is 2.25 seconds and pulse
duration is 350 milliseconds.
Flow Press to Mode and to select
Pump, Low Alarm or Hi
Alarm.
Note: Function setting Flow will change according to selections made
under Units /Mode eg Level,Range,Volume or HRT.
Press to return to Menu Selections.
LOE Set relay state for ‘echo loss’ event (On, Off or Hold)
Alternate Pumps can be set to alternate when in pump mode.
--Relay Parameters--
Relay 1
Function Flow
Mode Pump
On 10000 USG/m
Off 8000 USG/m
LOE mode Off
Alternate NO
}
--Relay Parameters--
Relay 1
Function Temperature
On 0.0C
Off 9.0C
}
--Relay Parameters--
Relay 1
Function Pulse
On 10.000ft
}
³
--Relay Parameters--
Relay 1
Function Level
Mode Pump
On 12.000ft
Off 3.000ft
LOE mode Off
Alternate NO
}

Page 15
OCF 5.0 Open Channel Flow Monitor
DATA LOGGING
Setup
Select Data Logging from Menu Selections.
Log Site ID Enter a number from 00 to 99. The site ID will
become part of the downloaded file name to help
distinguish downloads from different instruments. Press
to store the setting.
Mode Select Level, Range, Flow, HRT and
Volume. Flow (e.g. USGPM or l/sec). Press to
store the setting.
Set Date Press or to scroll and select Month, Day and Year.
Press to store the setting.
Set Time Press or to select the current time in Hours, Minutes
and Seconds. Press to store the setting.
Interval Press or to select the logging interval. Flow rate
reading will be stored at each time interval. Press to
store the setting.
Note: Press to Log and or to Delete and to
delete the log file. Press and or to Start and to
restart the logger.
Log Stop, Start or Delete the log file. Delete old
file and start a new log to apply any changes that have
been made to the Log Site ID, Mode or
Interval.
RETRIEVE LOG FILE
Plug a USB Flash Memory Drive (not supplied by Greyline) into the USB output
cable from the instrument. The instrument display will show the message
Downloading until the log file is transferred to the memory card and then display
Completed. The USB flash drive may be removed.
Download file names will appear in this format:
--Data Logging-------
Log Site ID 00
99
Mode Level
Range
Flow
HRT
Volume
Set Date Feb 18/2008
Mar 19/2009
Set Time 11:27:40
12:28:41
Interval 10sec
60min
30min
10min
5min
2min
1min
30sec
Log Start
Stop
Delete
}
OCF__00A.LOG
MODEL TAG DOWNLOAD

Page 16
OCF 5.0 Open Channel Flow Monitor
Tag is set according to the Log Site ID entered in the instrument Data Logging
menu.
Download letter will be A for the first download from an instrument. B for the
second, then C etc. At the letter Z a - character will appear indicating that the
maximum number of downloads for that instrument are on the USB flash drive.
Older files can be erased or moved from the flash memory drive or a new memory
drive can be used.
OPENING LOG FILES
Install Greyline Logger on your PC or laptop. Refer to the Help menu in the
program for detailed instructions.
Select File/Open/Instrument Log (.log) to open the log file from your USB flash
drive.

Page 17
OCF 5.0 Open Channel Flow Monitor
SPECIAL FUNCTIONS
Language Select English, French or Spanish and
press .
Analog Out Select 4-20mA or 0-5V mode for the analog output.
Backlight Select High, Medium or Low for continuous
backlight.
Select Key Hi/Lo for high backlight (for 1
minute) after a keypress and then Lo backlight
until a key is pressed again.
Select Key High, Med or Low for backlight
after a keypress and then backlight off until a key is
pressed again.
Reset Totalizer Press and select Yes to erase and restart the
totalizer at zero.
Restore Defaults Select Yes and press to erase all user settings
and return the instrument to factory default settings
New Password Select any number from 0000 to 9999 and press .
Default setting of 0000 will allow direct access to the
calibration menus. Setting of any password greater
than 0000 will require the password to be entered to
access the calibration menus.
Press to return to Menu Selections.
--Special Functions-
Language English
Analog Out 4-20mA
Backlight High
Reset Totalizer NO
Restore Defaults NO
New Password 0000
}
--Special Functions-
Language English
Backlight Hig
Medium
Low
Key Hi/Lo
Key High
Key Med
Key Low
Off
}h

Page 18
OCF 5.0 Open Channel Flow Monitor
SIMULATION
Exercises the 4-20mA (0-5V) output, digital display and control relays.
Test Select Maximum and press to simulate maximum Flow, Range or
Level and to output 20mA (5V) to the analog channel.
Select Minimum and press to simulate minimum Flow, Range or
Level and to output 4mA (0V) to the analog channel.
To simulate and intermediate Flow, Range or Level set Test to
Actual and then enter a value for the Flow, Range or
Level. The analog output and control relays will respond to the
simulated value.
--Simulation--------
Test Actual
Flow 250USG/m
4-20mA Flow 4.00
Relays 1 2 3 4 5 6
}

Page 19
OCF 5.0 Open Channel Flow Monitor
SENSOR MOUNTING METHODS
4" OR 6" BLIND FLANGE
TAPPED ¾" NPT
FLEXIBLE
CONDUIT
JUNCTION
BOX
(OPTION JB)
ISOLATION
COUPLING
(SUPPLIED)
MUST BE
USED
DO NOT
CLAMP IN
THIS AREA
¾" NPT
NIPPLE
FLANGE MOUNT
ISOLATION
COUPLING
(SUPPLIED)
MUST BE
USED
DO NOT
CLAMP IN
THIS AREA
CLAMP
3/4"
CONDUIT
CROSS BAR MOUNT
ISOLATION
COUPLING
(SUPPLIED)
MUST BE
USED
DO NOT
CLAMP IN
THIS AREA
3/4" NPT
NIPPLE
ANGLE MOUNT
ISOLATION
COUPLING
(SUPPLIED)
MUST BE
USED
DO NOT
CLAMP IN
THIS AREA
3/4"
CONDUIT
CONDUITMOUNT
Notes:
1. Use the ¾" NPT "Isolation
Coupling" supplied and
only. Do not clamp sensor
body or stem.
2. Locate the sensor 1 ft (30 cm) from
the sidewall or obstruction for every
10 ft (3 m) depth.
3. mount in direct sunlight.
4. Extend sensor cable up to 500 ft
(150 m) with RG62AU coaxial only.
hand
tighten
Do not
GRIND OR FILE
PIPE EDGE
SMOOTH
STAND PIPE MOUNT
STANDPIPE LENGTH
AS SHORT AS POSSIBLE
STANDPIPE DIAMETER
AS LARGE AS POSSIBLE
TYPICAL STANDPIPE:
4” / 100 mm DIAMETER
12” / 300 mm LENGTH
NARROW DIAMETER
STANDPIPES (<4” / 100 mm)
MAY AFFECT ACCURACY
OF READING

Page 20
OCF 5.0 Open Channel Flow Monitor
SENSOR MOUNTING/LOCATION
- Open Channel Flow Applications
Each sensor is equipped with a 3/4 inch isolation coupling which MUST be used in your installation. A
threaded nipple or length of conduit may be used to position the sensor at the desired height. The sensor
should be hand-tightened by turning the sensor stem only. DO NOT use a wrench and do not over
tighten.
IMPORTANT: Follow the flume manufacturer’s directions for transducer location. The transducer
should be centered above the flume approach section and mounted 8"/203 mm (minimum) above the
maximum liquid level (depending on sensor model).
The transducer should be protected from physical damage and the transducer cable should be routed in a
separate metal conduit.
Because the sensor is equipped with a temperature sensor, it should be shielded from direct sunlight.
Use the PVC “isolation coupling” supplied with the sensor and hand-tighten the sensor/coupling
assembly onto your mounting stand. Do not clamp directly to the sensor or to the isolation coupling.
12" 305
12" 305 mm
Table of contents