
IN-GE-TE500ADXXX-01-02 03/19 Page 2
Copyright © Greystone Energy Systems, Inc. All Rights Reserved Phone: +1 506 853 3057 Web: www.greystoneenergy.com
PRINTED IN CANADA
WIRING
Use shielded twisted pair wiring of at least 22 AWG for all connections and do not run the signal or power wires in the same conduit with wiring
used to supply inductive loads such as motors. Disconnect the power supply before making any connections to prevent electrical shock or
equipment damage. Make all connections in accordance with national and local electrical codes.
The transmitter is available with either 4-20 mA, 0-5 Vdc or 0-10 Vdc output signals. Follow the example wiring diagrams to determine the correct
wiring for the product. All models have the same terminal functions. For 4-20 mA loop powered operation, only PWR and OUT are required. The
COM terminal is only used for voltage output types or for AC power.
Ensure the controller Analog Input (AI) matches the transmitter output signal type before power is applied.The device is reverse voltage protected
and will not operate if connected backwards. The voltage output signal has a minimum load that it is able to drive and the current signal has a
maximum load. Follow the ratings in the Specication section or inaccurate readings may result. If the product has a dual sensor probe, connect
the RTD (Red/Black) leads to the SENSOR terminals. The second sensor is Green/White.
OPERATION
The product should be allowed to warm-up for several minutes before attempting to verify accuracy. Allow the transmitter to operate for 20
minutes before any calibration is performed. Operation can be veried by measuring the output signal. For voltage output models, measure the
voltage between the OUT and COM terminals. The voltmeter should read between 0-5 or 0-10 Vdc depending on the model. For current output
models, insert a mA meter in series with the OUT terminal and it should read between 4 and 20 mA.
CALIBRATION
The unit can be calibrated in the eld using precision resistance values equal to the zero and span of the
temperature range. Simply replace the attached probe with the resistor, then adjust the ZERO and SPAN
pots accordingly to obtain the correct output signal. Repeat the adjustments until both values are correct.
For units with 3-wire sensors, remember to jumper the SEN and EXC terminals with a wire.
TYPICAL WIRE RESISTANCE VALUES
When using low resistance sensors (i.e. 100 RTD), long wire runs can add
signicant error to the readings. Use the following chart to determine errors
due to wire resistance or consider using 1000 sensor or a transmitter
for better accuracy. Locate the type of wire being used. Multiply the total
length of the wire (distance from the controller to the sensor and back) by
the number found in the following chart for total resistance.
SPECIFICATIONS
Power Supply..................15-35 Vdc or 12-26 Vac
Sensor Type .....................1000 platinum RTD
Operating Range ...........0 to 70°C (32 to 158°F), 5 to 95 %RH non-condensing
Output Signal..................4-20 mA or 0-5 Vdc or 0-10 Vdc
Output Drive ...................Current: >550
Voltage: 5K min
Wire Connections.......... Screw terminal block (14 to 22 AWG)
Enclosure..........................White ABS, IP20 (NEMA 1)
Dimensions......................70mm W x 114mm H x 30mm D (2.75" x 4.5" x 1.2")
Country of Origin........... Canada
GAGE WIRE TYPE 18 AWG 22 AWG 24 AWG
STRANDED OHMS/FOOT 5.85 m 14.75 m 23.29 m
SOLID OHMS/FOOT 6.4 m 15.85 m 25.72 m
On-board sensor
for space only
DIMENSIONS 31.8 mm
1.25 “
114.3 mm
4.5 “
82.6 mm
3.25 “
69.85 mm
2.75“
Voltage Connection with Controller 24 Vdc Power
Figure 4
+24 Vac/dc
Analog Input (0-5 Vdc)
Common
POWER
OUT
COMMON
Controller
Figure 5
0001228 Rev.2
NEG SEN EXC
POWER
OUT
COMMON
2 wire probe
NEG
SEN
EXC
3 wire probe
NEG
SEN
EXC