manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Grundfos
  6. •
  7. Water Pump
  8. •
  9. Grundfos UP 15 series Manual

Grundfos UP 15 series Manual

NOTE: UPS15-42 does not require manual turning of shaft.
Pump Mounting: For Indoor Use
Arrows on the side or bottom of the pump housing indicate
direction of flow through the pump. GRUNDFOS
circulators can be installed in both vertical and horizontal
lines. The pump must be installed with the motor shaft
positioned horizontally.
Under no circumstances should
the pump be installed with the shaft vertical or where the
shaft falls below the horizontal plane. See Figure 3B.
It is recommend that isolation valves be installed on each
side of the pump. If possible, do not install elbows, branch
tees, and similar fittings just before or after the pump.
Provide support to the pump or adjacent plumbing to
reduce thermal and mechanical stress on the pump.
Installation Requirements
1. Thoroughly clean and flush the system prior to pump
installation.
2. Do not install the pump at the lowest point of the system
where dirt and sediment naturally collect.
3. Install an air vent at the high point(s) of the system to
remove accumulated air.
4. Ensure that water does not enter the terminal box
during the installation process.
5. (Open System) Install the pump in the supply line; the
suction side of the pump should be flooded with water.
Ensure that the static head requirement from Table 2B
is achieved.
6. (Closed System) Install a safety relief valve to protect
against temperature and pressure build-up.
7. If there are excessive suspended particles in the water,
it is recommended that a strainer and/or filter be
installed and cleaned regularly.
8. DO NOT START THE PUMP UNTIL THE SYSTEM
HAS BEEN FILLED AND CHECKED FOR LEAKS OR
OTHER POSSIBLE COMPONENT FAILURES.
Position of terminal box:
Proper installation of the pump will have the terminal box
located to one side of the pump or the other, with the
conduit entry down. See Figure 3A.
If the terminal box position needs to be changed, it is best
to do so before installation. However, if the pump is already
installed, ensure that the line cord is unplugged and close
the isolation valves before removing the Allen screws.
To change terminal box position:
1. Remove the four (4) Allen screws from the pump
housing and stator (4 or 5mm wrench) while supporting
the stator (motor).
2. Carefully separate the stator from the pump housing
and rotate it to the correct terminal box orientation and
reseat it.
3. Replace the Allen screws and tighten diagonally and
evenly (7 ft.-lb. torque).
4. Check that the motor shaft turns freely. Remove the
large screw in the middle of the nameplate, insert a
small flat blade screwdriver into the end of the shaft,
and turn gently (see fig. 7a).
If the shaft does not turn easily, repeat the disassembly/
reassembly process.
Examine the components carefully to make sure no
damage has occurred to the pump during shipment. Care
should be taken to ensure the pump is NOT dropped or
mishandled; dropping will damage the pump.
1. Shipment Inspection
2. Pre-Installation Checklist
Before beginning installation procedures, the
following checks should be made. They are all
important for proper installation of the circulator
pump.
1. Uses:
Model UP 15 series pumps are designed to circulate
water from 50°F to 230°F up to a maximum pressure of
145 psi. If required, a 50% by volume solution of ethylene
or propylene glycol and water can be used, however, a
psi decrease in pump performance may result due to an
increase in the viscosity of the solution. Check with
manufacturer for information regarding suitability of
pumping other fluids.
System Applications: UP15 series pumps with
stainless steel or bronze volutes can be used in both
open and closed systems.
2. MaximumWaterTemperature:
UP15 pump with line cord only. The maximum allowable
water temperature is determined by the ambient or
surrounding air temperature as shown in Table 2A.
Table 2A – Maximum Water Temperature
Ambient (°F) 95 130 140 160 175
Water (°F) 230 220 210 190 175
Although the pump is designed to operate at maximum
water temperature of 230°F, it is recommended to
keep the operating temperature as low as possible (i.e.
below 140°F to avoid precipitation of calcium).
3. Inlet Pressure Requirements
The amount of pressure required at the inlet of the pump
is a function of the temperature of the water as shown in
Table 2B.
Table 2B – Inlet Pressure Requirements
Water (°F) 190 165 140
Required Inlet Pressure (ft.) 5 4.5 3
(psi) 2.2 1.9 1.3
In a pressurized system, the required inlet pressure is the
minimum allowable system pressure.
In an open system, the required inlet pressure is the
minimum distance the pump must be located below the
lowest possible water level of the water source (tank,
pool, etc.).
3. Pump Installation
Figure 3A
Recommended Terminal Box Orientation
4. Electrical
SAFE WARNING
Warning - Risk of electrical shock - This pump is supplied
with a grounding conductor. To reduce the risk of electric
shock, be certain that it is connected only to a properly
grounded grounding type receptacle.
The safe operation of this pump requires that it be grounded
in accordance with the National Electrical Code and local
governing codes and regulations.
Electrical Requirements
The operating voltage and other electrical data are marked
on the motor label. Make sure that the motor is suitable for
the electrical supply on which it will be used.
Electrical Connection
Insert the 115V plug on the line cord from the pump into a
properly grounded 115V outlet as shown in Figure 4a.
5. TimerTechnical Data
TIMER CONTROL
Supply Voltage: 115-120 VAC, 60 hertz
Contact Rating: 16 amps
Ambient Temperature: -4°F to 175°F
Shortest Switching Interval: 15 minute increment
Switch Modes: “Timer”, “ON” Override,
“OFF” Override
Protection: Clear plastic cover for dust and
moisture protection of the clock face.
Note: UP15 pump with timer control maximum water tem-
perature: 150°F
6. TimerTechnical Application
The Grundfos timer control is designed only for use with
specified Grundfos Series UP circulators installed in in-
door hot water service systems.
The timer control is designed to turn the circulator on and
off at preset times, allowing the user to select operation of
the circulator during high use periods of the day.
Figure 3B
Acceptable Unacceptable
Page 1 Page 2 Page 3 Page 4
Setting and Operating the Timer Control
and Starting the Pump
NOTE: Before the circulator is started, the system must
be filled with liquid and vented.
1. Set the timer switch to the actual time by turning the
programming ring in the direction of the arrow until
the timing arrow points to the actual time on the ring.
2. Switch on the power supply to the circulator and set
the manual switch to the “ON” position. The circula-
tor will now start.
3. Set the required “ON”/”OFF” times on the program-
ming ring by pushing the programming tabs either
away from or toward the center of the ring. Tabs
pushed away from the center indicate the circulator
is switched ”ON” while tabs pushed toward the cen-
ter indicate the circulator is switched “OFF”.
4. Set the manual switch to the “TIMER” position. The
circulator will now start/stop according to the settings
of the programming tabs.
8. Failure to Operate
When the pump is first started, the shaft may rotate slowly
until water has fully penetrated the bearings. If the pump
does not run, the shaft can be rotated manually. To
accomplish this, switch off the electrical supply, and close
the isolation valves on each side of the pump. Remove
the indicator plug in the middle of the nameplate. Insert
a small flat blade screwdriver into the end of the shaft,
and gently turn until the shaft moves freely (see Figure
7a). Replace and tighten the plug. Open the isolation
valves and wait 2 to 3 minutes for the system pressure
to equalize before starting the pump.
5. For continuous operation, set the manual switch to
the “ON” position. To switch the circulator off, set the
manual switch to the “OFF” position.The “ON”/”OFF”
modes may be used without affecting the function of
either the programming ring or the timer switch.
6. In case of power outage the timer will not keep time.
After power has been restored, the correct time of
day must be reset by rotating the programming ring
in the direction of the arrow until the timing arrow
points to the actual time on the ring.
7. Timer Operation 9. LimitedWarranty
Products manufactured by GRUNDFOS PUMPS CORPORATION
(GRUNDFOS) are warranted to the original user only to be free of defects
in material and workmanship for a period of 18 months from date of
installation, but not more than 24 months from date of manufacture.
GRUNDFOS' liability under this warranty shall be limited to repairing or
replacing at GRUNDFOS' option, without charge, F.O.B.GRUNDFOS'
factory or authorized service station, any product of GRUNDFOS
manufacture. GRUNDFOS will not be liable for any costs of removal,
installation, transportation, or any other charges which may arise in
connection with a warranty claim. Products which are sold but not
manufactured by GRUNDFOS are subject to the warranty provided by the
manufacturer of said products and not by GRUNDFOS' warranty.
GRUNDFOS will not be liable for damage or wear to products caused by
abnormal operating conditions, accident, abuse, misuse, unauthorized
alteration or repair, or if the product was not installed in accordance with
GRUNDFOS' printed installation and operation instructions.
To obtain service under this warranty, the defective product must be returned
to the distributor or dealer of GRUNDFOS products from which it was
purchased together with proof of purchase and installation date, failure date,
and supporting installation data. Unless otherwise provided, the distributor
or dealer will contact the GRUNDFOS factory or authorized service station
for instructions. Any defective product to be returned to the factory or service
station must be sent freight prepaid; documentation supporting the warranty
claim and/or a Return Authorization must be included if so instructed.
GRUNDFOS WILL NOT BE LIABLE FOR ANY INCIDENTAL OR
CONSEQUENTIAL DAMAGES, LOSSES, OR EXPENSES ARISING
FROM INSTALLATION, USE, OR ANY OTHER CAUSES. THERE ARE
NO EXPRESS OR IMPLIED WARRANTIES, INCLUDING
MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE,
WHICH EXTEND BEYOND THOSE WARRANTIES DESCRIBED OR
REFERRED TO ABOVE.
Some jurisdictions do not allow the exclusion or limitation of incidental or
consequential damages and some jurisdictions do not allow limitations on
how long implied warranties may last. Therefore, the above limitations or
exclusions may not apply to you. This warranty gives you specific legal
rights and you may also have other rights which vary from jurisdiction to
jurisdiction.
II
II
Installation & Operating Instructionsnstallation & Operating Instructions
nstallation & Operating Instructionsnstallation & Operating Instructions
nstallation & Operating Instructions
MM
MM
Maa
aa
ainin
inin
intenance-Ftenance-F
tenance-Ftenance-F
tenance-Frr
rr
ree Cee C
ee Cee C
ee Cirir
irir
irculacula
culacula
culators wtors w
tors wtors w
tors wii
ii
ith Lth L
th Lth L
th Lineine
ineine
ine
CC
CC
Coror
oror
ord andd and
d andd and
d and OptiOpti
OptiOpti
Optionaona
onaona
onall
ll
l
TT
TT
Timer Cimer C
imer Cimer C
imer Con
on
onon
ontrtr
trtr
troo
oo
oll
ll
l
Page 5 Page 6
L-UP-TL-018 02/05
PRINTED IN USA
Shipment Inspection.................... page 1.
Pre-Installation Checklist. ............ page 1.
Pump Installation. ........................ page 2.
Electrical....................................... page 4.
Timer ControlTechnical Data
and Application. ........................... page 4.
Timer Operation. .......................... page 5.
Failure to Operate. ....................... page 6.
Warranty. ....................................... page 7.
Figure 7a
Figure 6b
Figure 6a
PROGRAMMING
RING
TIMING ARROW
MANUAL SWITCH
PROGRAMMING
TABS
Grundfos Pumps Corporation
17100 W.118th Terrace
Olathe, Kansas 66061
Telephone: (913) 227-3400
Fax: (913) 227-3500
Grundfos Canada, Inc.
2941 Brighton Rd.
Oakville, Ontario L6H 6C9
Telephone: (905) 829-9533
Fax: (905) 829-9512
Bombas Grundfos de Mexico, S.A.de C.V.
Boulevard TLC #15, Parque Industrial
Stiva Aeropuerto
C.P.66600 Apodaca, N.L. Mexico
Telephone: 52-81-8144-4000
Fax: 52-81-8144-4010

Other Grundfos Water Pump manuals

Grundfos ALPHA+ Series User manual

Grundfos

Grundfos ALPHA+ Series User manual

Grundfos AP80 Vortex User manual

Grundfos

Grundfos AP80 Vortex User manual

Grundfos 2000 Series User manual

Grundfos

Grundfos 2000 Series User manual

Grundfos SEG Series User manual

Grundfos

Grundfos SEG Series User manual

Grundfos UNILIFT AP35B User manual

Grundfos

Grundfos UNILIFT AP35B User manual

Grundfos MAGNA3 25-100 (N) User manual

Grundfos

Grundfos MAGNA3 25-100 (N) User manual

Grundfos MAGNA1 C User manual

Grundfos

Grundfos MAGNA1 C User manual

Grundfos DPK.10.50.075 User manual

Grundfos

Grundfos DPK.10.50.075 User manual

Grundfos UP Series User manual

Grundfos

Grundfos UP Series User manual

Grundfos SCALA1 User manual

Grundfos

Grundfos SCALA1 User manual

Grundfos KPC 600A User manual

Grundfos

Grundfos KPC 600A User manual

Grundfos alpha2 l User manual

Grundfos

Grundfos alpha2 l User manual

Grundfos CMBE User manual

Grundfos

Grundfos CMBE User manual

Grundfos UP MEDIUM User manual

Grundfos

Grundfos UP MEDIUM User manual

Grundfos SEG.40.09 User manual

Grundfos

Grundfos SEG.40.09 User manual

Grundfos UPA 15-90 User manual

Grundfos

Grundfos UPA 15-90 User manual

Grundfos JPC Series User manual

Grundfos

Grundfos JPC Series User manual

Grundfos ZEM 2-13C User manual

Grundfos

Grundfos ZEM 2-13C User manual

Grundfos COMFORT PM B User manual

Grundfos

Grundfos COMFORT PM B User manual

Grundfos seg autoadapt Original operating manual

Grundfos

Grundfos seg autoadapt Original operating manual

Grundfos SD User manual

Grundfos

Grundfos SD User manual

Grundfos SEG Series User manual

Grundfos

Grundfos SEG Series User manual

Grundfos PS.R.05-17 User manual

Grundfos

Grundfos PS.R.05-17 User manual

Grundfos rmq-a User manual

Grundfos

Grundfos rmq-a User manual

Popular Water Pump manuals by other brands

VONROC SP505AC Original instructions

VONROC

VONROC SP505AC Original instructions

Aqua Marin TIPU01 Original instruction manual

Aqua Marin

Aqua Marin TIPU01 Original instruction manual

Graco T2 295616 instructions

Graco

Graco T2 295616 instructions

Intex Quick-Fill AP619-III owner's manual

Intex

Intex Quick-Fill AP619-III owner's manual

Lutz-Jesco MEMDOS SMART LB operating instructions

Lutz-Jesco

Lutz-Jesco MEMDOS SMART LB operating instructions

Enerpac SCH121H instruction sheet

Enerpac

Enerpac SCH121H instruction sheet

vacuubrand VACUU-PURE 10C Instructions for use

vacuubrand

vacuubrand VACUU-PURE 10C Instructions for use

Wilo Stratos GIGA2.0-I installation instructions

Wilo

Wilo Stratos GIGA2.0-I installation instructions

EBARA GS Instruction and maintenance manual

EBARA

EBARA GS Instruction and maintenance manual

dosatron D 45 RE 3000 owner's manual

dosatron

dosatron D 45 RE 3000 owner's manual

Flotec EVOTRONIC 350 instruction manual

Flotec

Flotec EVOTRONIC 350 instruction manual

Denison Hydraulics Goldcup Series Service information

Denison Hydraulics

Denison Hydraulics Goldcup Series Service information

MSI Hybrid Triplex Technical manual

MSI

MSI Hybrid Triplex Technical manual

aquanique FP 450 operating instructions

aquanique

aquanique FP 450 operating instructions

Danfoss H1T 045 Service manual

Danfoss

Danfoss H1T 045 Service manual

Gardner Denver WELCH MPC 301 Zp Ex Operation manual

Gardner Denver

Gardner Denver WELCH MPC 301 Zp Ex Operation manual

CountyLine CLW750 owner's manual

CountyLine

CountyLine CLW750 owner's manual

MAS KMU-V Series operating manual

MAS

MAS KMU-V Series operating manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.