30310837 Issue 1.03
P-9956-Modbus Configurable RS
Modbus Card
Features
Photoelectric isolation RS232, RS485 and
RS422 interfaces.
Supporting for MODBUS RTU
communication protocol.
Description
P-9956-Modbus is an optional card for
GST-IFP4M control panel, providing
photoelectric isolation interfaces of RS232,
RS485 and RS422.
This card shouldn’t be inserted and
removed when it is energized.
Refer to the control panel manual for
following settings.
1) Define the quantity of Modbus cards.
2) The panel address is set to slave rather
than main address.
LEDs
1) P-9956-Modbus has RS485, RS422
and RS232 ports. Illuminating HL1 and
HL2 mean that a port is fault.
2) Flashing HL1 and HL2 mean that
P-9956-Modbus Card works normally.
P-9956-Modbus can be used any port of
RS485, RS422 or RS232 through a jumper.
The loop shouldn’t exceed 1200m when
RS485 or RS422 is used. The loop
shouldn’t exceed 15m when RS232 is used.
A P-9956-Modbus can connect with third
party devices through RS485, RS422 or
RS232. A panel connects up to two
P-9956-Modbus cards. Refer to Fig. 2 for
installation position.
Connection & Wiring
Its connection is shown in Fig. 1 as
P-9956-Modbus is inserted in S2 slot.
GST-IFP4M
motherboard
+ -
-+
S2I S2O
NC
NC
RS485A
RS485B
GST-IFP4M
motherboard
+ -
-+
S2I S2O
GND
NC
RS232Tx
RS232Rx
GST-IFP4M
motherboard
+ -
-+
S2I S2O
RS422Rx-
RS422Rx+
RS422Tx+
RS422Tx-
Fig. 1
Note: Slot S1 is for S1I and S1O, and slot S2 is
for S2I and S2O.