General Features
The KYO320 Control panel
rUp to 344 Alarm zones: 8 zones on the Main Board;
192 on 32 M-IN/OUT Expanders programmed as In-
puts (6 zones each) ; 64 on 32 MIA-D Keypads (2
zones per keypad); 16 on 16 ALISON32LP LED
Keypads (1 zone per keypad) and 64 Wireless zones
rUp to 118 Outputs: 6 Outputs on the Main Board (3
Relays and 3 Open-Collectors); 96 on 16 M-IN/OUT
Expanders programmed as Outputs (6 zones each)
and 16 on ALISON32LP LED Keypads
rUp to 32 backlit LCD Keypads for system control
rUp to 32 Digital Key/Card Readers
r195 User Codes with programmable ‘View’ option,
priority and functions
r10000 Event Log with date and time details
rUp to 8 power stations
r4 wire Bus (protected against short-circuit) for pe-
ripherals
rDual branch bus for protection against tamper
rProgrammable Balance, Operating mode and Alarm
type — for all zones
rInput zones can be programmed to send specific
commands to the Control panel
rOutputs can be programmed as bistable or cyclic
with programmable cycle times and standby status
r32 programmable partitions — each with own zones,
keypads, readers, outputs and times
r195 User Codes with programmable priority and
functions
r500 programmable Digital Keys/Cards
r16 character labels (ID) for the partitions, zones,
keypads, readers, codes, keys/cards, etc. — the as-
signed label will be shown on the keypad display dur-
ing the user operations
r10000 Event Log — provides details of the operation
type, time and user
rRS232 Interface for system programming and monitoring
rSoftware (runs under Windows) for Control panel
Programming, Teleservice and Monitoring
Telephone Facilities
rPulse and Touch-tone (DTMF) dialling
r50 Telephone numbers for Telemonitoring,
Teleservice and Voice Calls
rIntegrated Digital Communicator: supports Pulse,
DTMF and FSK Reporting formats
r6 Instant Alarm calls from each Keypad
rProgrammable Test call
rDouble Call
rLine sharing with other Telephone devices
r1200 baud FSK integrated Modem for Teleservice
management
Telephone facilities with K3/VOX2 optional Voice Board
rDialler function: sends recordable voice messages
to up to 32 Telephone numbers
rRemote Inquiry with Voice answer (requires Access
Code)
rRemote control of Outputs, Arm/Disarm operations,
Alarm Reset (requires Access Code)
rRemote Listen-in and multipoint Telephone commu-
nication (Talk/Listen-in)
rAnswerphone function
Scheduler function
rDaily, Weekly and Monthly scheduling
rHoliday and Daylight Saving (BST) changeover
management
rOvertime and Arming delay management
r4 Arm and 4 Disarm operations per day per Partition
r64 independent daily Timer events for KYO320.
Event print-out using optional K3/PRT2 Board
rPrints Events on parallel printer
rReal-time and/or Event Log printout from specified
date to last Event
rEvent filter
The System and Accessories
The Control panel The Control panel is the core of the
system. It has 8-zones (KYO320 expands to 344); 6 Out-
puts (KYO320 expands to 118;) and a 3A Switching Power
Supply (5A accessory item).
M-IN/OUT The M-IN/OUT is an Input/Output Expander
which allows the number of zones and outputs of the
Control panel to be increased. It can be programmed to
function as: 6-zone Input Expander; Output Expander
with 6 Outputs; Input/Output Expander with 4 zones
and 2 Outputs; Input/Output Expander with 2 zones and
4 Outputs. In this manual the term Input Expander will
be used to refer to the M-IN/OUT programmed to func-
tion as an Input Expander or Input/Output Expander;
the term Output Expander will be used to refer to the
M-IN/OUT programmed to function as an Output Ex-
pander or Input/Output Expander. The Control panel
supports up to 32 Input Expanders and up to 16 Output
Expanders.
+An M-IN/OUT programmed as an Input/Output Ex-
pander contributes both to the number of Input Ex-
panders and to the number of Output Expanders
connected to the Control panel.
The zones of the M-IN/OUT can operate in normal
mode, for connecting movement detectors, or as an in-
terface for connecting contacts for Roller blinds. The
M-IN/OUT’s Outputs are of open-collector type, i.e.
floating or connected to Earth. The M-IN/OUT is con-
nected to the 4-wire bus (on the Control panel), through
which it communicates with the Control panel itself and
receives a feed for its own operation. The M-IN/OUT is
provided with a plastic container for flush or surface
mounting and equipped with Anti-tamper and
Anti-snatch devices (excludable).
Control Devices The KYO320 accepts up to 32
ECLIPSE and/or PROXI Digital Key/Card Readers and/or
16 ALISON32LP LED Keypads, and/or up to 32 MIA-D
and/or ALISON-DVP LCD Keypads.
6