GST DC-M9103 User manual

30309579 Issue 1.07
Features
Reed switch testing.
Output terminal for remote indicator available.
Rate of rise and fixed temperature, and fixed
temperature programmable.
Complying with UL 521.
Description
DC-M9103 Conventional Rate of Rise and Fixed
Temperature Heat Detector is a new generation
product of GST. With built-in microprocessor, it works
stably by being fixed with highly reliable fire judging
program.
On detecting a fire signal, it can change its own
current to transmit the signal to fire alarm control panel
(FACP) or addressable zone monitor unit. The
detector keeps illuminating fire LED until it is reset by
power-down.
Connection and Wiring
The detector connects with UL-certified products such
as modules and control panels. The detector bottom is
shown in Fig. 1 and the base in Fig. 2.
Fig. 1 Fig. 2
Please install the base according to following steps:
1) Locate mounting holes on the rubber layer of the
base according to the holes on the back box, and
punch the holes with a screwdriver.
2) Count the number of cables needed and punch
correct quantity of holes with a screwdriver on
the rubber layer. Thread the cables through the
cable entry holes.
3) Install the base onto the back box with screws.
Warning: Do not punch mounting holes and cable
entry holes bigger than needed. Do not punch
more holes than needed.
There are four terminals with numbers on the base.
1: Detection zone positive IN
2: Detection zone positive OUT
3: Detection zone negative IN and OUT
2: Positive terminal of remote indicator
4: Negative terminal of remote indicator
It connects a 4.7k/1w resistor between number 2
and 3 at the end of the base. The system
connection is shown in Fig. 3.
Remote Indicator
O-
O+
Module
Conventional Detector
4.7kΩ Resistor
Remote Indicator
Conventional Detector
Fig. 3
Recommended Wiring
1.0mm2 or above fire cable for all terminals laid through
metal conduit or flame retardant conduit, subject to local
codes.
I-M9300 modules connect with 15 conventional devices
at most.
Note: It’s recommended to use cables of different
colors to avoid incorrect wiring.
Installation
Refer to D Series Detector Application Bulletin for
additional installation instructions.
First fix the orientation base with two tapping screws.
Then align A (Fig. 1) on the bottom of the detector to B
(Fig. 2) of the base, and rotate the detector clockwise
to mark C.
Mounting of the detector is shown in Fig. 4.
Detector
Base
Conduit
Electric Box
53.3mm
Fig. 3
Fig. 4
Application
Warning: The alarm current depends on the
current limit of the control panel. 24VDC cannot
power the detector directly. Otherwise the detector
will be blown up for lack of current limit resistor.
The default class 7 of the detector is rate of rise &
fixed temperature, and polling LED status is “ON”,
which can be modified using GST handheld
programmer.
When the programmer is in standby state, entering
unlock password and pressing “Clear”, it will be
unlocked. Pressing Function followed by 4, there will
be a “-”at the last digit. Entering different number
corresponding to the parameters (refer to Table 1)
followed by “Program”, there will be a “P”shown on
the screen, indicating its class is programmed.
Pressing “Clear”can clear the “P”, and entering
locking password followed by “Clear”will exit.
Table 1 Detector setting parameters
Parameters
Class
Polling LED Status
7
Rate of Rise and fixed
temperature
ON
8
Fixed Temperature
ON
135
Rate of Rise and fixed
temperature
OFF
136
Fixed Temperature
OFF
Read Heat Detector Class: When the programmer is
in standby state, pressing “Test”, it will display address
of the detector. Pressing “Up”, it will display sensitivity
level, device type and heat detector parameters in
turn.
Testing
Note: Before testing, make sure the detector is
properly installed and powered up. Testing can
only begin after the detector is powered up for 10
seconds.
Before testing, notify the proper authorities that the
system is undergoing maintenance and will
5
45
75
Cable Entry
Mounting
Hole
DC-M9103 Conventional Rate of Rise
and Fixed Temperature Heat Detector
30309579 Issue 1.07
temporarily be out of service. Disable the zone or
system undergoing maintenance to avoid unwanted
alarms
The detector must be tested after installation and
regular maintenance. The methods should meet the
requirements from local authority. The detector should
meet NFPA72. The testing methods are as follows:
(1)Reed switch testing
The testing area of the detector is shown in Fig. 5.
Approach the commission tool to the testing area of
the detector and hold for several seconds until the
detector alarms.
30° Testing
Area
Fig. 8
Fig. 5
(2)Temperature test
Approach a heater (such as a hair drier of
1000w-1500w) to the thermistor of the detector until it
alarms. It is 12 inches between the hair drier and the
thermistor to avoid damaging on the plastic enclosure
of the detector
After testing, disconnect power of the detector for over
10 seconds and then reset it. Notify the proper
authorities that the system is back to normal
operation.
Maintenance
The detector should be installed just before
commission and kept well before installation, taken
corresponding measures for dust-proof,
damp-proof and corrosion-proof.
The dust cover cannot be removed until the project
has been plunged into usage.
Do fire simulation test at least once every 6
months.
Before fire simulation test, notify the proper
authorities that the system is undergoing
maintenance and will temporarily be out of service.
Disable the zone or system undergoing
maintenance to avoid unwanted alarms.
Protect the metal component on the PCB against
damp and improper distortion.
Cautions
1. Detector should be firmly installed and the wire
be reliable.
2. LED on the detector should face the main
entrance for people to see it.
3. Be careful not to damage the detector in
maintenance.
4. Heat detector is not suitable for detecting
smoldering fire.
Accessories and Tools
Module
Name
Remarks
P-9910B
Handheld programmer
Order separately
DB-M01
Base
Order separately
T-MT
Commission Tool
Order separately
C-9314P
Passive Remote Indicator
Order separately
BP-9314P
Back Plate for Remote
Indicator
Order separately
Specification
Operating
Voltage
24VDC(16VDC - 28VDC)
Standby Current
≤60μA
Alarm Current
≤55mA
Fire LED
Red, periodically flash once in
polling when the status is set to
“ON”; don’t illuminate when the
status is set to “OFF”. Periodically
flash twice in fault; illuminate in
alarming.
Sensitivity
Action Temperature:135°F
(57.2°C )
Response rate of rise:15°F /min
(8.3°C /min)
Maximum spacing
50 ft. (15.2 m)
Remote
Indication Output
Polarity-sensitive output ,Directly
connecting with remote indicator
(built in 10k resistor in series,
maximum output current is
2.0mA);
The remote indicator does not
illuminate in normal and flashes in
alarm.
Class and Setup
Rate of rise and fixed temperature
(default), and fixed temperature
programmable.
Maximum Ripple
Voltage
2V ( peak-to-peak)
Alarm Reset
Instantaneous cut-out (10s Min,
1.0VDCMax.)
Power-up Time
≤10s
Wiring
Polarized 2-core for loop.
Ingress
Protection Rating
IP2X
UL Temperature
Range
32°F (0°C) - 100°F (37.8°C)
0 - 95%, non-condensing
Operating
Temperature
14°F (-10°C) - 122°F (+50°C)
0 - 95%, non-condensing
Mounting Hole
Spacing
45mm - 75mm
Weight
About 110g (with base)
Limited Warranty
GST warrants that the product will be free from defects
in design, materials and workmanship during the
warranty period. This warranty shall not apply to any
product that is found to have been improperly installed
or used in any way not in accordance with the
instructions supplied with the product. Anybody,
including the agents, distributors or employees, is not
in the position to amend the contents of this warranty.
Please contact your local distributor for products not
covered by this warranty.
This Data Sheet is subject to change without notice. Please contact GST for more information or questions.
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004
Tel: +86 (0) 335 8502434 Fax: +86 (0) 335 8502532
[email protected] www.gst.com.cn

Other manuals for DC-M9103

2

Other GST Security Sensor manuals

GST C-9103 User manual

GST

GST C-9103 User manual

GST I-9106 User manual

GST

GST I-9106 User manual

GST R6602 User manual

GST

GST R6602 User manual

GST D-9105RExd User manual

GST

GST D-9105RExd User manual

GST GST-AS-200 User manual

GST

GST GST-AS-200 User manual

GST DI-9103E User manual

GST

GST DI-9103E User manual

GST DC-9103 User manual

GST

GST DC-9103 User manual

GST I-9602LW User manual

GST

GST I-9602LW User manual

GST DC-9103 User manual

GST

GST DC-9103 User manual

GST DC-9103E User manual

GST

GST DC-9103E User manual

GST DI-9104Exd User manual

GST

GST DI-9104Exd User manual

GST C-9105R User manual

GST

GST C-9105R User manual

GST DI-M9103 User manual

GST

GST DI-M9103 User manual

GST DC-9103 User manual

GST

GST DC-9103 User manual

GST I-9406 User manual

GST

GST I-9406 User manual

GST DC-M9103 User manual

GST

GST DC-M9103 User manual

GST DC-9105E User manual

GST

GST DC-9105E User manual

GST DI-9103 User manual

GST

GST DI-9103 User manual

GST DI-9103 User manual

GST

GST DI-9103 User manual

GST DC-9103E User manual

GST

GST DC-9103E User manual

GST C-9201 User manual

GST

GST C-9201 User manual

GST DC-9101(Ex) User manual

GST

GST DC-9101(Ex) User manual

GST DI-9104Exd User manual

GST

GST DI-9104Exd User manual

GST I-9105R User manual

GST

GST I-9105R User manual

Popular Security Sensor manuals by other brands

Optex AX-100TFR Series installation instructions

Optex

Optex AX-100TFR Series installation instructions

Interlogix Kalatel 600-9400-IMAG installation guide

Interlogix

Interlogix Kalatel 600-9400-IMAG installation guide

Bornack Stripe Comfort Click user manual

Bornack

Bornack Stripe Comfort Click user manual

BEMKO SES15BL instructions

BEMKO

BEMKO SES15BL instructions

Yale AC-OPIR manual

Yale

Yale AC-OPIR manual

Siemens SICAM V01.00 manual

Siemens

Siemens SICAM V01.00 manual

RKI Instruments 35-3010RKA-04 manual

RKI Instruments

RKI Instruments 35-3010RKA-04 manual

HIOTH TECHNOLOGY CO., LTD CT-SMEA2001-ID user manual

HIOTH TECHNOLOGY CO., LTD

HIOTH TECHNOLOGY CO., LTD CT-SMEA2001-ID user manual

Visonic NEXT PLUS Series installation instructions

Visonic

Visonic NEXT PLUS Series installation instructions

LEGRAND Bticino MyHOME 3518MW instructions

LEGRAND

LEGRAND Bticino MyHOME 3518MW instructions

urmet domus 1051 Installation, programming and functions manual

urmet domus

urmet domus 1051 Installation, programming and functions manual

Uni-Trend UT12B operating manual

Uni-Trend

Uni-Trend UT12B operating manual

Diablo DSP-20-LV user manual

Diablo

Diablo DSP-20-LV user manual

XP DEUS II quick start

XP

XP DEUS II quick start

Omron F3SJ-E0185P25 user manual

Omron

Omron F3SJ-E0185P25 user manual

ATD Tools ATD3698 user manual

ATD Tools

ATD Tools ATD3698 user manual

schmersal BNS 40S operating instructions

schmersal

schmersal BNS 40S operating instructions

United Safety Incorporated Voltek NS user guide

United Safety Incorporated

United Safety Incorporated Voltek NS user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.