GST DI-9103 User manual

30307774 Issue 1.03
Features
Electronically addressed in field.
2 classes programmable.
Self-diagnostic.
Reed switch testing.
Fire LED allows 360°viewing.
Remote indicator output available.
Designed to comply with EN 54-5 standard.
Description
DI-9103 Digital Dual Heat Detector is a new
addressable fire alarm device cooperating with GST
intelligent fire alarm control panels(FACP) to build a
fire detection system. The detector shows fire alarm
by the LED indicator and transmits the signal to the
FACP.
Connection and Wiring
Fig.1 shows the detector bottom and Fig. 2 DB-01
base.
C
B
100mm
A
Fig. 1 Fig. 2
There are four terminals with numbers on the base.
1&3: Loop connection (polarity-insensitive)
2: Positive terminal of remote indicator
4: Negative terminal of remote indicator
Recommended Wiring
1.0mm2or above fire cable is recommended but
subject to local codes.
Note: It’s recommended to use cables of different
colors to avoid incorrect wiring.
Installation
A fixed installation direction is ensured by the location
elements on the detector and the base. Fix the base
with two tapping screws, and then align mark A on the
detector with B on the base, rotate the detector to align
mark A with mark C (Refer to Fig. 1 and 2 for the
position of the marks), the detector will be fitted to the
base.
Fig. 3 shows the schematic for mounting the detector.
Detector
Base
Conduit
Electric box
51.3mm
Fig. 3
Application
The detector is especially applicable to places where
fire occurs with sharp rise of temperature. Used
together with smoke detectors, it can detect fire with
more reliability to reduce losses.
The detector can be addressed in field by using
P-9910B programmer. Please refer to P-9910B Hand
Held Programmer Installation and Operation Manual
for details.
The default class of the detector is A1R, which can be
modified using the programmer.
When the programmer is in standby state, entering
unlock password and pressing “Clear”, it will be
unlocked. Pressing Function followed by 4, there will
be a “-”at the last digit. Entering different number
corresponding to the classes ( “2”for A1R, “3”for A2S)
followed by “Program”, there will be a “P”shown on
the screen, indicating the class is programmed.
Pressing “Clear”can clear the “P”, and entering
locking password followed by “Clear”will exit.
Testing
Note: Before testing, make sure the detector is
properly installed and powered up. Testing can
only begin after the detector is powered up for 10
seconds.
The detector must be tested after installation and
regular maintenance. The methods are as follows:
(1) Reed switch testing
The testing area of the detector is shown in Fig. 4.
Approach the commission tool to the testing area of
DI-9103
Digital Dual Heat Detector
30307774 Issue 1.03
the detector and hold for several seconds until the
detector alarms.
(2) Temperature test
Approach a heater (such as a hair drier) to the
thermistor of the detector until it alarms.
Testing
Area
Fig. 4
(3) After testing, disconnect the power to the detector
for over 5 seconds to reset it. Notify the proper
authorities that the system is back to normal
operation.
(4) If a detector fails in testing, clean it by the steps in
“Maintenance”, and retest it. If it still fails, return it
for repair.
Maintenance
1. The detector should be installed just before
commission and kept well before installation, taken
correspondingmeasures for dust-proof, damp-proof
and corrosion-proof.
2. The dust cover should not be removed until the
project has been plunged into usage. Otherwise it
may not report alarm normally.
3. The detector should be cleaned at least every year
to ensure normal operation of the system.
4. Before cleaning, notify the proper authorities that
the system is under maintenance and will
temporarily be out of service. Disable the automatic
controls relating to the zone or system under
maintenance to avoid unwanted actions.
5. The detector should be tested after cleaned and
re-installed to ensure normal operation.
6. Protect the conductive metal element on the
detector base from humidity or rigid distortion.
7. Fire simulation test should be done to the detector
at least every 6 months.
Accessories and Tools
Model
Name
Remarks
P-9910B
Hand Held
Programmer
Order separately
DB-01
Base
Order separately
JTY-HM-GST102
Commission
Tool
Order separately
Specification
Limited Warranty
GST warrants that the product will be free of charge
for repairing or replacing from defects in design,
materials and workmanship during the warranty period.
This warranty does not cover any product that is found
to have been improperly installed or used in any way
not in accordance with the instructions supplied with
the product. Anybody, including the agents,
distributors or employees, is not in the position to
amend the contents of this warranty. Please contact
your local distributor for products not covered by this
warranty.
Operating Voltage
Loop 24V
Standby Current
≤0.6mA
Alarm Current
≤1.5mA(without remote indicator)
≤3.5mA(with remote indicator)
Indicator
Red, Flashes in polling, and
illuminates in alarm
Remote indicator
output
Directly connects to remote
indicator (built in 10k resistor in
series. Maximum output current is
2.0mA);
The remote indicator is quiet in
normal and flashing in alarm.
Programming
Method
Electronically programmed
Code Range
One address within 1~242.
Classes and
Setup
2 classes (A1R, A2S)
programmable
Wiring
Non-polarized 2-core for loop.
Polarized 2-core for remote
indicator.
Ambient
Temperature
ClassA1: -10℃~+50℃
ClassA2: -10℃~+50℃
Relative Humidity
≤95%, non condensing
Material of
Enclosure
ABS
Ingress Protection
Rating
IP22
Dimensions
Diameter: 100mm
Height: 51.3mm (with base)
Mounting Hole
Distance
45mm~75mm
Weight
About 110g (with base)
This Data Sheet is subject to change without notice. Please contact GST for more information or questions.
Gulf Security Technology Co., Ltd.
No. 80, Changjiang East Road, QETDZ, Qinhuangdao, Hebei, P. R. China 066004
Tel: +86 (0) 335 8502434 Fax: +86 (0) 335 8502532
service[email protected]tc.com www.gst.com.cn

Other GST Security Sensor manuals

GST DC-M9103 User manual

GST

GST DC-M9103 User manual

GST DC-9103E User manual

GST

GST DC-9103E User manual

GST R6602 User manual

GST

GST R6602 User manual

GST DC-9104Exd User manual

GST

GST DC-9104Exd User manual

GST GST-AS-200 User manual

GST

GST GST-AS-200 User manual

GST DC-9105E User manual

GST

GST DC-9105E User manual

GST D-9105RExd User manual

GST

GST D-9105RExd User manual

GST DC-M9103 User manual

GST

GST DC-M9103 User manual

GST I-9105R User manual

GST

GST I-9105R User manual

GST C-9201 User manual

GST

GST C-9201 User manual

GST C-9103 User manual

GST

GST C-9103 User manual

GST DC-9103 User manual

GST

GST DC-9103 User manual

GST DC-9103 User manual

GST

GST DC-9103 User manual

GST DC-9103E User manual

GST

GST DC-9103E User manual

GST I-9106 User manual

GST

GST I-9106 User manual

GST DI-M9103 User manual

GST

GST DI-M9103 User manual

GST I-9602LW User manual

GST

GST I-9602LW User manual

GST I-9101 User manual

GST

GST I-9101 User manual

GST I-9406 User manual

GST

GST I-9406 User manual

GST DI-9104Exd User manual

GST

GST DI-9104Exd User manual

GST C-9105R User manual

GST

GST C-9105R User manual

GST D-9107RExd User manual

GST

GST D-9107RExd User manual

GST DI-9103E User manual

GST

GST DI-9103E User manual

GST DC-9101(Ex) User manual

GST

GST DC-9101(Ex) User manual

Popular Security Sensor manuals by other brands

Optex AX-100TFR Series installation instructions

Optex

Optex AX-100TFR Series installation instructions

Interlogix Kalatel 600-9400-IMAG installation guide

Interlogix

Interlogix Kalatel 600-9400-IMAG installation guide

Bornack Stripe Comfort Click user manual

Bornack

Bornack Stripe Comfort Click user manual

BEMKO SES15BL instructions

BEMKO

BEMKO SES15BL instructions

Yale AC-OPIR manual

Yale

Yale AC-OPIR manual

Siemens SICAM V01.00 manual

Siemens

Siemens SICAM V01.00 manual

RKI Instruments 35-3010RKA-04 manual

RKI Instruments

RKI Instruments 35-3010RKA-04 manual

HIOTH TECHNOLOGY CO., LTD CT-SMEA2001-ID user manual

HIOTH TECHNOLOGY CO., LTD

HIOTH TECHNOLOGY CO., LTD CT-SMEA2001-ID user manual

Visonic NEXT PLUS Series installation instructions

Visonic

Visonic NEXT PLUS Series installation instructions

LEGRAND Bticino MyHOME 3518MW instructions

LEGRAND

LEGRAND Bticino MyHOME 3518MW instructions

urmet domus 1051 Installation, programming and functions manual

urmet domus

urmet domus 1051 Installation, programming and functions manual

Uni-Trend UT12B operating manual

Uni-Trend

Uni-Trend UT12B operating manual

Diablo DSP-20-LV user manual

Diablo

Diablo DSP-20-LV user manual

XP DEUS II quick start

XP

XP DEUS II quick start

Omron F3SJ-E0185P25 user manual

Omron

Omron F3SJ-E0185P25 user manual

ATD Tools ATD3698 user manual

ATD Tools

ATD Tools ATD3698 user manual

schmersal BNS 40S operating instructions

schmersal

schmersal BNS 40S operating instructions

United Safety Incorporated Voltek NS user guide

United Safety Incorporated

United Safety Incorporated Voltek NS user guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.