30307774 Issue 1.03
Features
Electronically addressed in field.
2 classes programmable.
Self-diagnostic.
Reed switch testing.
Fire LED allows 360°viewing.
Remote indicator output available.
Designed to comply with EN 54-5 standard.
Description
DI-9103 Digital Dual Heat Detector is a new
addressable fire alarm device cooperating with GST
intelligent fire alarm control panels(FACP) to build a
fire detection system. The detector shows fire alarm
by the LED indicator and transmits the signal to the
FACP.
Connection and Wiring
Fig.1 shows the detector bottom and Fig. 2 DB-01
base.
Fig. 1 Fig. 2
There are four terminals with numbers on the base.
1&3: Loop connection (polarity-insensitive)
2: Positive terminal of remote indicator
4: Negative terminal of remote indicator
Recommended Wiring
1.0mm2or above fire cable is recommended but
subject to local codes.
Note: It’s recommended to use cables of different
colors to avoid incorrect wiring.
Installation
A fixed installation direction is ensured by the location
elements on the detector and the base. Fix the base
with two tapping screws, and then align mark A on the
detector with B on the base, rotate the detector to align
mark A with mark C (Refer to Fig. 1 and 2 for the
position of the marks), the detector will be fitted to the
base.
Fig. 3 shows the schematic for mounting the detector.
Detector
Base
Conduit
Electric box
51.3mm
Fig. 3
Application
The detector is especially applicable to places where
fire occurs with sharp rise of temperature. Used
together with smoke detectors, it can detect fire with
more reliability to reduce losses.
The detector can be addressed in field by using
P-9910B programmer. Please refer to P-9910B Hand
Held Programmer Installation and Operation Manual
for details.
The default class of the detector is A1R, which can be
modified using the programmer.
When the programmer is in standby state, entering
unlock password and pressing “Clear”, it will be
unlocked. Pressing Function followed by 4, there will
be a “-”at the last digit. Entering different number
corresponding to the classes ( “2”for A1R, “3”for A2S)
followed by “Program”, there will be a “P”shown on
the screen, indicating the class is programmed.
Pressing “Clear”can clear the “P”, and entering
locking password followed by “Clear”will exit.
Testing
Note: Before testing, make sure the detector is
properly installed and powered up. Testing can
only begin after the detector is powered up for 10
seconds.
The detector must be tested after installation and
regular maintenance. The methods are as follows:
(1) Reed switch testing
The testing area of the detector is shown in Fig. 4.
Approach the commission tool to the testing area of
DI-9103