Gude Expert PDU basic 8110 User manual

© 2010 Gude Analog- und Digitalsysteme GmbH
Expert PDU basic 8110/8111

Expert PDU basic 8110/8111
© 2010 Gude Analog- und Digitalsysteme
GmbH
26.08.2010

3ContentExpert PDU basic 8110/8111
Expert PDU basic 8110/8111
Table of content
Chapter 1 Security Advise 4
Chapter 2 Description 4
Chapter 3 Hardware 4
4
3.1 Content of delivery
5
3.2 Connections
5
3.3 Installation
Chapter 4 Configuration 6
6
4.1 DHCP
6
4.2 Network settings with GBL_Conf
6
4.3 Configuration via webinterface
4.3.1 Configuration - IP address 7
4.3.2 Configuration - IP ACL 8
4.3.3 Configuration - HTTP 8
4.3.4 Configuration - Messages 9
4.3.5 Configuration - SNMP 10
4.3.6 Configuration - SNMP Trap Receiver List 11
4.3.7 Configuration - Syslog 11
Chapter 5 Operation 12
12
5.1 Sensor
Chapter 6 Features 13
13
6.1 Bootloader mode
13
6.2 Firmware update
13
6.3 Technical information
13
6.4 Fabrique settings
Chapter 7 Support 14
Chapter 8 Declarations of conformity 15

4
Expert PDU basic 8110/8111 Security Advise
1 Security Advise
The device must be installed only by qualified personnel according to the following installation and operating instructions.
The manufacturer does not accept responsibility in case of improper use of the device and particularly any use of equipment
that may cause personal injury or material damage.
The device contains no user-maintenable parts. All maintenance has to be performed by factorytrained service personnel.
Check if the power cord, the plug and the socket are in proper condition.
The device can be connected only to 230V AC (50 or 60 Hz) sockets.
Always connect the device to properly grounded power sockets.
The device is intended for indoor use only. Do NOT install them in an area where excessive moisture or heat is present.
Because of safety and approval issues it is not allowed to modify the device without our permission.
Please note the safety advises and manuals of connected devices, too.
The device is NOT a toy. It has to be used or stored out or range of children.
Packaging material is NOT a toy. Plastics has to be stored out of range of children. Please recycle the packaging materials.
In case of further questions, about installation, operation or usage of the device, which are not clear after reading the manual,
please do not hesitate to ask our support team.
2 Description
Expert PDU basic 8110/8111 is a 19“ device which allows to monitor the power distribution of up to 8 electrical devices via
TCP/IP.
For installation, Expert PDU basic 8110/8111 is simply connected to a power supply and to the local network. After
allocating a free IP address to Expert PDU basic 8110/8111, the device can be monitored from any computer in the same
LAN via web browser.
Expert PDU basic 8110/8111 offers the possibility to use SNMP and Syslog. Furthermore, access to the device can be
controlled via IP access control list (IP-ACL) and HTTP password.
3 Hardware
3.1 Content of delivery
Included in delivery are:
Expert PDU basic 8110/8111
Short manual

5
Expert PDU basic 8110/8111 Hardware
3.2 Connections
1) Display
2) Ethernet connector (RJ45)
3) TEMP connector for Sensor
4) Aux connector for serial interface (RS232-PS2 cable) or Sensor
5) Status LED
6) Button "ok"
7) Button "select"
8) 8 Power Ports (IEC C13, max. 10A)
9) Power Supply socket (IEC C20, max. 16A)
3.3 Installation
1.) Connect the power supply cable to the at the rear side (Expert PDU basic 8110) or front side (Expert PDU basic 8111 )
of Expert PDU basic 8110/8111 and a socket. Expert PDU basic 8110/8111 now is booting and shortly after ready for
usage.
2.) Plug the Ethernet cable into the ethernet connector (RJ45) of Expert PDU basic 8110/8111 and connect it to your
Ethernet.
3.) Connect the clients to the Power Ports at the rear side (Expert PDU basic 8110) or front side (Expert PDU basic 8111 )
of the device.

6
Expert PDU basic 8110/8111 Configuration
4 Configuration
4.1 DHCP
After switch-on Expert PDU basic 8110/8111 looks for a DHCP server and requests an available IP address .
Please check the IP address allocated to Expert PDU basic 8110/8111 in the DHCP server settings to make sure that the
same address is used at every reboot.
4.2 Network settings with GBL_Conf
For changing the network properties manually, the program GBL_Conf.exe is required. This tool is available for free on our
website www.gude.info.
Furthermore GBL_Conf.exe enables you to install firmware updates and to reset Expert PDU basic 8110/8111 to its factory
settings.
Activate bootloader mode of Expert PDU basic 8110/8111 and run GBL_Conf.exe. The program will look automatically for
connected devices and will display their network configuration.
If the displayed IP address accords with the factory settings (192.168.0.2), there is either no DHCP server available in the
network or no free IP address could be allocated.
Enter a free IP address and the according netmask in the entry mask, then save these changes by clicking on Program
Device SaveConfig.
Restart the firmware of Expert PDU basic 8110/8111, so that the changes will take effect. Now click on Search in order to
have the new network configuration displayed.
4.3 Configuration via webinterface
Go to the website of Expert PDU basic 8110/8111. Enter the IP address of Expert PDU basic 8110/8111 into the address
line of your internet browser:
http://”IP address of Expert PDU basic 8110/8111”/
and press LOGIN.
To enter the configuration menu, click on „Configuration“ on the upper left side of the screen.

7
Expert PDU basic 8110/8111 Configuration
4.3.1 Configuration - IP address
4.3.1.1 Hostname
Enter the host name of Expert PDU basic 8110/8111. Expert PDU basic 8110/8111 uses this name to connect with DHCP
server.
Special signs may destabilize your network.
All changes need a restart of the firmware to get valid.
4.3.1.2 IP Address
Here you can change the IP address of Expert PDU basic 8110/8111.
All changes need a restart of the firmware to get valid.
4.3.1.3 Netmask
Here you can change the netmask of Expert PDU basic 8110/8111.
All changes need a restart of the firmware to get valid.
4.3.1.4 Gateway
Here you can change the standard gateway of Expert PDU basic 8110/8111.
All changes need a restart of the firmware to get valid.
4.3.1.5 Use DHCP
Here you can set, if Expert PDU basic 8110/8111 shall get its TCP/IP settings directly from your DHCP server. If DHCP is
activated, Expert PDU basic 8110/8111 proves if a DHCP server is active inside of your LAN. Then Expert PDU basic
8110/8111 requests TCP/IP settings from this server. If there is no DHCP server inside of your network, we recommend to
deactivate this function.
All changes need a restart of the firmware to get valid.

8
Expert PDU basic 8110/8111 Configuration
4.3.2 Configuration - IP ACL
IP Access Control List (IP ACL) acts as an IP filter for your Expert PDU basic 8110/8111. Wether it is active hosts and
subnets only can contact Expert PDU basic 8110/8111, if their IP adresses are stated in this IP ACL.
e.g.: „http://192.168.0.1“ or „http://192.168.0.1/24“
If you locked yourself out by mistake, please activate the bootloader mode of Expert PDU basic 8110/8111, start Gbl_Conf.
exe and deactivate IP ACL.
You can find more information about configuration of IP ACL or have a look at http://www.gude.info/wiki.
4.3.2.1 Reply ICMP-Ping requests
Here you can set, if Expert PDU basic 8110/8111 shell react on pings.
4.3.2.2 Enable IP Filter
Here you can activate the IP Access Control List (IP ACL) of Expert PDU basic 8110/8111.
If IP ACL is active, DHCP and SNMP only work, if all necessary servers and clients are registered in this list.
4.3.3 Configuration - HTTP

9
Expert PDU basic 8110/8111 Configuration
4.3.3.1 HTTP Port
Here you can enter the HTTP port number, if necessary. Possible numbers are 1 ... 65534 (standard: 80). To get access to
Expert PDU basic 8110/8111, you have to enter the port number behind the IP address of Expert PDU basic 8110/8111, e.
g.: http://192.168.0.2:1720
All changes need a restart of the firmware to get valid.
4.3.3.2 Require HTTP Password
Password protected access can be activated here. In this case, a user and an admin password have to be defined.
Passwords have a maximum lengths of 15 characters.
Administrators are authorized to switch all ports and to modify the settings of Expert PDU basic 8110/8111 and of all ports.
The username of the admin is “admin”.
Users are authorized to switch all ports but are not allowed to modify the settings of neither Expert PDU basic 8110/8111 nor
the ports. The username of the user is “user”.
If you have forgotten your password, activate the bootloader mode of Expert PDU basic 8110/8111, start GBL-Conf.exe and
deactivate the password request.
All changes need a restart of the firmware to get valid.
4.3.3.3 Check Password on start page
If activated, the user has to enter his password, before logging in to the webinterface.
4.3.4 Configuration - Messages
4.3.4.1 Generate Temperature Messages
Here you can configure if and at which Min-/Max-Temperature Expert PDU basic 8110/8111 shell send temperature alerts via
SNMP-Traps and Syslog.
4.3.4.2 Max Temperature
Here you can define the maximum temperature, if the sensor measures this temperature the device will generate an alert via
SNMP and Syslog.

10
Expert PDU basic 8110/8111 Configuration
4.3.4.3 Min. Temperature
Here you can define the minimum temperature, if the sensor measures this temperature the device will generate an alert via
SNMP and Syslog.
4.3.5 Configuration - SNMP
4.3.5.1 Enable SNMP-get
Here you can activate SNMP-get protocol of Expert PDU basic 8110/8111.
Use SNMP only if your network is fitted for.
4.3.5.2 Community public
Here you can enter the SNMP public community.
Use SNMP only if your network is fitted for.
4.3.5.3 Enable SNMP-set
Here you can activate SNMP-set protocol of Expert PDU basic 8110/8111.
Use SNMP only if your network is fitted for.
4.3.5.4 Community private
Here you can enter the SNMP private community.
Use SNMP only if your network is fitted for.
4.3.5.5 Download SNMP MIB
Here you can download the MIBs of Expert PDU basic 8110/8111.
Use SNMP only if your network is fitted for.

11
Expert PDU basic 8110/8111 Configuration
4.3.6 Configuration - SNMP Trap Receiver List
4.3.6.1 Enable Traps
Here you can activate SNMP-traps. if enabled, Expert PDU basic 8110/8111 will dispatch SNMP-traps to all receivers listed.
Receivers have to be listed as follows: IP address (and, if necessary the HTTP port), e.g.: 192.168.0.2:8000
Use SNMP only if your network is fitted for.
4.3.6.2 Trap Version
Here you can choose between SNMP-traps standard v1 and v2c.
Use SNMP only if your network is fitted for.
More information about the SNMP functions of Expert PDU basic 8110/8111, you can find in chapter SNMP, on http://www.
gude.info/wiki or ask our support team.
4.3.7 Configuration - Syslog
Syslog messages are simple text messages transmitted to a syslog server using UDP.
Linux OS regularly have a syslog daemon installed, e.g. syslog-ng. For Windows there are some freeware tools available.
On following events, Expert PDU basic 8110/8111 will send a syslog message:
- Booting up
- Activation/deactivation of syslog
You can find more information about configuration of Syslog in chapter Configuration - Syslog or have a look at http://www.
gude.info/wiki.

12
Expert PDU basic 8110/8111 Configuration
4.3.7.1 Enable Syslog
Here you can activate Syslog of Expert PDU basic 8110/8111.
4.3.7.2 Syslog Server IP
If syslog is active enter here the IP address of you Syslog server.
4.3.7.3 Syslog Port
If syslog is active enter here the port number, that your Syslog server uses to receive syslog information.
More information about Syslog you can find in chapter Syslog, on http://www.gude.info/wiki or ask our support team.
5 Operation
5.1 Sensor
Connect the temperature sensor with the TEMP and AUX connector at the front of the device. If it is connected exactly, the
recent temperature is displayed in the login window, in the switching window and can be requested via SNMP.
The temperature sensor can be ordered as additional supplies. More information can be found at www.gude.info or requested
Temperature sensor 7001
Hybrid sensor 7002
Temperature sensor 7001
Cable length
˜ 2m
Connection
PS2
Measurement
-10°C bis +70°C bei ±2°C (maximal) und ±1°C (typisch)

13
Expert PDU basic 8110/8111 Operation
Hybrid sensor 7002
Cable length
˜ 2m
Connection
PS2
Measurement
(-40 bis +80 Grad, +- 0,5Grad/ Feuchte 0-100% +-3%)
6 Features
6.1 Bootloader mode
To activate the bootloader mode of Expert PDU basic 8110/8111 the button must be pushed while restarting the device. In
bootloader mode it is possible to disable the password protection, to update the firmware and to restore the default settings by
running the program GBL_Conf.exe.
If the device runs already, press the buttons "select" and "ok" for three seconds. The bootloader mode of Expert PDU basic
8110/8111 is indicated by “BOOT-LDR” appended to the device name in the program window of GBL_Conf.exe.
During bootloader mode an alteration of the relais is not possible.
To restart the firmware, without toggle the Power Ports, press the buttons select and ok for three seconds again.
6.2 Firmware update
In order to update the firmware the program GBL_Conf.exe and the latest firmware are needed.
Start the device in bootloader mode and run the program GBL_Conf.exe. On the left side of the program window all Gude
devices that are in the network are listed. Select the device, that should be updated, click on Program DeviceFirmware
Update and determine the location of the new firmware.
Please note: The up-to-date firmware and GBL_Conf.exe can be found at www.gude.info, free to download.
6.3 Technical information
Connections:
1 x Ethernet (RJ45)
2 x PS2 Connector
8 x Power Ports (IEC C13, max. 10A)
1 x Power supply inlet (IEC C20, max. 16A)
Network:
10/100 MBit/s 10baseT Ethernet
Protocols:
TCP/IP, HTTP,
SNMP v1 und v2c, SNMP traps, Syslog
Power (total):
16 A (~ 3600W)
Power (per port):
10 A (~ 2000W)
Power supply:
IEC C20 (16A, 230V AC)
Operating temperature:
0°C-50°C
Dimensions:
19’’ / 1 rack unit
Total weight:
ca. 1,5 kg
6.4 Fabrique settings
In order to restore the default settings the device must be started in bootloader mode. Besides that the program GBL_Conf.
exe is required.
Run GBL_Conf.exe and select the device whose settings should be restored. Then click on Program Device -> Reset to Fab
default.
Please notice that all current settings will be deleted. The default settings will be loaded when the firmware of the device is
restarted the next time.

14
Expert PDU basic 8110/8111 Support
7 Support
More information, current drivers and software can be found on http://www.gude.info.
In case of further questions, about installation or operation of Expert PDU basic 8110/8111, please have look at www.gude.

15
Expert PDU basic 8110/8111 Support
8 Declarations of conformity

16
Expert PDU basic 8110/8111 Declarations of conformity

17
Expert PDU basic 8110/8111 Declarations of conformity

Expert PDU basic 8110/8111
© 2010 Gude Analog- und Digitalsysteme GmbH
26.08.2010
This manual suits for next models