Connect the grounding cable to a grounding point before installing the switch in the rack.
为了防止机箱安装到机柜后无法安装接地线,请先将接地线安装到交换机侧面的接地点上。
The switch provides a grounding sign at the primary grounding point but not at the auxiliary
grounding point.
交换机主接地点标有接地标识,备用接地点上无接地标识。
The grounding screws provided with the switch are applicable to both the primary and auxiliary
grounding points.
交换机随机附带的接地螺钉同时适用于主接地点和备用接地点。
Mounting brackets installed near the port side
挂耳安装在靠近端口侧
Mounting brackets installed near the power module side
挂耳安装在靠近电源侧
Install the chassis rails at c or d. The chassis rails can be installed reaching out of the chassis or not
reaching out of the chassis.
挂耳安装在靠近电源侧时,滑道导轨可安装在c或d任意一处,可采用正装方式,也可采用反装方式。
Install the chassis rails at a or b. The chassis rails can be installed reaching out of the chassis or not
reaching out of the chassis.
挂耳安装在靠近端口侧时,滑道导轨可安装在a或b任意一处,可采用正装方式,也可采用反装方式。
Installing the switch in a 19-inch rack
19
The installation procedure is the same for using long and short chassis rails. The following procedure
uses the short chassis rails as an example.
采用长滑道短导轨安装交换机到机柜与采用短滑道长导轨安装交换机到机柜的方式相同,本文以采用
长滑道短导轨安装交换机到机柜为例。
4
Installing the mounting brackets and short slide rails
2
If the rack depth is in the range of 401 to 692 mm (15.79 to 27.24 in), purchase long chassis rails and
short slide rails Yourself for installation. You need to install the long chassis rails as follows based on
the rack depth:
如果机柜前后方孔条间距在401~692mm范围内,请使用选配的短滑道长导轨配合安装。因短滑道配
套的长导轨有正装(导轨不会超出设备)和反装(导轨会超出设备)之分,用户可以根据机柜方孔条
之间的距离灵活选择安装方式。
Not reaching out of the chassis for a rack with the depth in the range of 401 to 498 mm
(15.79 to 19.61 in).
当机柜前后方孔条间距在401~498mm范围内,请使用长导轨正装方式安装。
Not reaching out or reaching out of the chassis for a rack with a depth in the range of 499 To
565 mm (19.66 to 22.24 in).
当机柜前后方孔条间距在499~565mm范围内,长导轨正装和反装都可以。
Reaching out of the chassis for a rack with the depth in the range of 566 to 692 mm
(22.28 to 27.24 in).
当机柜前后方孔条间距在566~692mm范围内,请使用长导轨反装方式安装。
For device stability, make sure the slide rails slide a minimum length of 90 mm (3.54) into the chassis
rails when rack-mounting the switch.
为保证设备安装后的稳定性,当滑道与滑道导轨安装完成后,请确保滑道的头部进入滑道导轨的最小
深度为90mm。
The device uses M5 grounding screws. You can use a grounding cable with a single-hole or dual-hole
grounding lug to ground the device. If the grounding cable or grounding lug you receive does not meet
the requirement, you can make a grounding cable on site or contact H3C Technical Support.
设备侧接地点支持单孔端子和双孔端子的接地电缆安装,接地螺钉为M5螺钉。如果您收到设备的接地电
缆长度或者端子类型不满足要求,可以现场制作合适的线缆解决或者联系H3C技术支持解决。
ab
(chassis rail not reaching
out of the chassis)
正装
(chassis rail reaching out
of the chassis)
反装
a
a
3
(Connect a grounding cable
with a dual-hole lug)
安装双孔接地端子地线
(Connect a grounding cable
with a single-hole lug)
安装单孔接地端子地线
cd
(chassis rail not reaching out
of the chassis)
正装
(chassis rail reaching out
of the chassis)
反装
d
d
(Connect a grounding cable with
a single-hole lug)
安装单孔接地端子地线
(Connect a grounding cable with
a dual-hole lug)
安装双孔接地端子地线