logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. HBX
  6. •
  7. Control Unit
  8. •
  9. HBX CPU-0500 Troubleshooting guide

HBX CPU-0500 Troubleshooting guide

Other manuals for CPU-0500

2

Other HBX Control Unit manuals

HBX ZON-0550 User manual

HBX

HBX ZON-0550 User manual

HBX Modulating Module 0100 User manual

HBX

HBX Modulating Module 0100 User manual

HBX ECO-0600 User manual

HBX

HBX ECO-0600 User manual

HBX ECO-1000 Operating instructions

HBX

HBX ECO-1000 Operating instructions

HBX SNO-0550 User manual

HBX

HBX SNO-0550 User manual

HBX ZON-0500 User manual

HBX

HBX ZON-0500 User manual

Popular Control Unit manuals by other brands

Festo Compact Performance CP-FB6-E Brief description

Festo

Festo Compact Performance CP-FB6-E Brief description

Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

Elo TouchSystems

Elo TouchSystems DMS-SA19P-EXTME Quick installation guide

JS Automation MPC3034A user manual

JS Automation

JS Automation MPC3034A user manual

JAUDT SW GII 6406 Series Translation of the original operating instructions

JAUDT

JAUDT SW GII 6406 Series Translation of the original operating instructions

Spektrum Air Module System manual

Spektrum

Spektrum Air Module System manual

BOC Edwards Q Series instruction manual

BOC Edwards

BOC Edwards Q Series instruction manual

KHADAS BT Magic quick start

KHADAS

KHADAS BT Magic quick start

Etherma eNEXHO-IL Assembly and operating instructions

Etherma

Etherma eNEXHO-IL Assembly and operating instructions

PMFoundations Attenuverter Assembly guide

PMFoundations

PMFoundations Attenuverter Assembly guide

GEA VARIVENT Operating	 instruction

GEA

GEA VARIVENT Operating instruction

Walther Systemtechnik VMS-05 Assembly instructions

Walther Systemtechnik

Walther Systemtechnik VMS-05 Assembly instructions

Altronix LINQ8PD Installation and programming manual

Altronix

Altronix LINQ8PD Installation and programming manual

Eaton Powerware Series user guide

Eaton

Eaton Powerware Series user guide

WAGO 750-407/040-000 manual

WAGO

WAGO 750-407/040-000 manual

Sony CCU-590 Operation manual

Sony

Sony CCU-590 Operation manual

Graco 25D614 instructions

Graco

Graco 25D614 instructions

Task Force Tips YE-RF-900 Instructions for installation, safe operation and maintenance

Task Force Tips

Task Force Tips YE-RF-900 Instructions for installation, safe operation and maintenance

Shini SPV-U Series manual

Shini

Shini SPV-U Series manual

https://manuals.online logo
https://manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

Contact Information
4516-112th Avenue SE
Calgary, Alberta T2C 2K2
CANADA
Phone: +1(403) 720 0029
Fax: +1 (403) 720 0054
Email: [email protected]
CPU-0500 Control
Quick & Easy
Start-Up Guide
Controlling 1 modulating boiler and outdoor reset control
Outdoor
Sensor
Boiler
Sensor
Boiler
Pump
THM-0100
76.0
°F
TARGET
ROOM
85°F
OFF
Outlined fields indicate a mandatory set up.
Design Boiler Temperature
This is the design boiler temperature. It is
used in the outdoor reset design calculation
and is also the maximum setting for the
boiler.
(50°F to 200°F) Default: 190°F
Design Room Temperature
This is the design room temperature. It is
used in the outdoor reset design
calculation. Set it to the approximate
desired room temperature.
(50°F to 120°F) Default: 70°F
Design Outdoor Temperature
This is the design outdoor temperature. It is
used in the outdoor reset design
calculation. Set the maximum temperature
you would like the control to be at.
(-50°F to 150°F) Default: -10°F
Minimum Boiler Temperature
This is the minimum boiler temperature. This
setting will vary depending on the type of
boiler you are running. This is boiler supply
temperature so keep that in mind when
selecting this feature.
If the minimum boiler temperature is set to
OFF then the boiler demand will always be
ON when a heat demand is present.
(OFF / 51°F to 200°F) Default: OFF
Warm Weather Shut Down (WWSD)
This setting is used to set the temperature at
which the CPU-0500 will go into WWSD.
Above this temperature the system will be
shut off.
(20°F to 150°F) Default: 75°F
DHW Target
This setting is used to set the desired DHW
tank temperature.
(OFF/1°F to 200°F) Default: 130 °F
DHW Differential
This is the differential for the DHW tank. Set
this setting to the desired differential for the
DHW tank.
(2°F to 60°F) Default: 6°F
Eg.) 6°F differential would be 3°F
above and 3°F below.
DHW Boiler Setpoint
This setting is used to set the desired boiler
setpoint when there is a DHW demand. This
can be triggered from either a thermistor or
an aquastat.
(50°F to 200°F) Default: 180°F
When stage 2 is selected this can
only be triggered by an aquastat.
DHW Priority
This setting is used to set the DHW priority. If
set to ON then the System Pump will shut off
when there is a DHW call. The priority time is
60 minutes. In Mixing mode the injection
device will shut off in a priority situation.
(ON/OFF) Default: OFF
Heat Demand
1) ON: This setting indicates that the
CPU-0500 is in a permanent heat demand.
Use instead of attaching a thermostat.
2) OFF
(ON/OFF) Default: OFF
Celsius & Fahrenheit
Use this setting to change the display format
from °C to °F.
(°C/°F) Default: °F
Boiler Selection
This setting is used to select what boiler(s)
are connected to the control.
Selection Types:
1: Single Stage ON/OFF Boiler
2RT: 2 Stages of ON/OFF Boiler with Rotation
2: 2 Stage Boiler with No Rotation
MOD: Modulating Boiler
Default:1
Minimum Modulation Percentage
This setting is used to set the lowest
modulation level the boiler can go down to.
(10% to 60%) Default: 20%
Modulating Step Time & Staging
Lag Time
When the boiler is set to MOD mode this
setting sets the time between the steps
when the boiler needs to increase or
decrease the firing rate.
(1s to 300s) Default: 10s
Boiler Pump Selection
1) ON: This setting is used to setup the boiler
pump contact. If this setting is on, then the
boiler pump contact will come on only if the
boiler is being enabled. This setting also
works for modulating boilers.
2) OFF: If this setting is off the boiler pump
contact will come on with the demand.
Default: OFF
The setting can be used as a boiler
enable signal for modulating boilers.