【Before Test Run】
●Before test run, please re-confirm the installation whether there are problems, also confirm the following points.
●In addition, please confirm it with the outdoor unit attached the installation manual.
1) Refrigerant piping and the transmission cable if connected with a different refrigeration cycle, there will be abnormal
operation occurred.
2) Please use the 500V electrical resistance tester to confirm the electrical parts between terminals and earth electrical
resistance must be 1MΩ more than. If 1MΩ or less, that poor the electrical insulation, please do not operation the unit.
(Do not input the power source to the terminal No.1,2 of transmission wiring.)
3) When power source wiring phase error, the unit cannot be operated, and the remote controller display alarm code
﹝ 05 ﹞. Currently, please refer to the electrical box caution nameplate, check the phase of the first side and replace it.
The phase of the replacement work, please process under the power source turn off.
4) Does the oil heater of the outdoor unit have been powered? (Before using, please input power source more than 12
hours.
【Test Run】
●When installation is completed, perform test run according to the following procedure, and make sure that whether the
abnormal operation, then hand over the system to the customer.
1) Outdoor unit the gas stops valve and the liquid stop valve, make sure full open state.
2) Please implement the test run of the indoor unit in turn, confirm the refrigerant cycle system and the electrical wiring
system is the same. (While more than one indoor unit operation, the system is unable to confirm the consistency.)
3) Please according to the following procedure to test run, and make sure that whether the abnormal operation.
3.1 Depress the "MODE" and the "CHECK" switches together for more than 3 seconds. The "TEST RUN" and the counting
number of the connected units are indicated on the remote control switch.
●When cooling operation test run, it should be at room temperature DB 21 ℃, WB 15 ℃, outside air temperature
DB -5 ℃ or more.(Outside air temperature DB -5 ℃ below, air conditioner cannot be operated.)
●Using a remote controller to operation more than one indoor unit, please confirm whether the number of the units
display. If no indication appears or the number of the units indicated is smaller than the actual number of the units, some
abnormalities exist, please confirm it again. Depress the "MODE" switch again to set the desired mode of operation.
3.2 Depress "RUN/STOP" switch.
●The "TEST RUN" operation will be started. (The 2 hours OFF-TIMER will be set, and the "TEST RUN" operation will
be finished after 2 hours unit operation or by depressing the "RUN/STOP" switch again.)
3.3 To end the test run, wait for 2 hours or push "RUN/STOP" switch again.
●Note:After the product stops operation, in order to recover the piping refrigerant to the outdoor unit, the compressor continues to operate a period of
time (most about 10 minutes). Also, when the test run, it is not the product failure or abnormal.
●When test running, the protection device will be activated for some abnormality, the controller's operation indicator is still blinking, display "Alarm"
(abnormality), while the setting temperature display will show alarm code.
●Setting temperature and setting timer display changes:
●At this time, please refer to page 18 of the alarm code to confirm the leading cause and treatment. If you cannot handle, please contact your contractor
for assistance.