HT-100F Series
HITROL CO., LTD. 11
Output Hunting Phenomenon
Output Current Holding Phenomenon
Failure Mode
& Actions
Cause Check Point
Incorrect zero measurement range setting Reset
Offset applied Offset default
Loss of buoyancy or damage to the float Replace the float
Damaged diode of the M-100R Replace the M-100R
Cause Check Point
Incorrect span measurement range setting Reset
Offset applied Offset default
Open low cable of sensor Reconnect the sensor
Damaged diode of the M-100R Replace the M-100R
Cause Check Point
When the resistor of the sensor is seriously damaged,
resulting in a short circuit with the pointer positioned on it
Replace the sensor PCB. (If the float is out
of the position, the output will sharply rise
or drop, leading to measurement error.)
When the resistor of the sensor is seriously damaged,
resulting in an open circuit with the pointer positioned on it
Replace the sensor PCB. (If the float is out
of the position, the output will sharply rise
or drop, leading to measurement error.)
When the wire is not wound
Check if any foreign subsidence is in the
wire drum or if the spring is damaged.
Cause Check Point
Temporary over-measurement (approximately 10%) and
noise output shape due to over-current caused when a
diode of the M-100R is damaged
Replace the M-100R
Warranty
and
Contact
■ Warranty and Service
This product is subject to the warranty for 2 years of shipment and unpaid service will
be provided for any damage found under normal operating conditions. If it is not
about the failure of product, the service charge will be payable.
You can request A/S at our website or by contacting our headquarters.
■ Headquarters ․ Factory ․ Laboratory Contact Number
ADRESS
: HITROL CO., LTD 141, Palhakgol-gil, Jori-eup, Paju-si, Gyeonggi-do, Korea
T E L : 031-950-9700 (Headquarters & A/S)
F A X : 031-943-5600 (Headquarters & A/S)
When the output current is below 4mA,
When the output current is above 20mA,