Zero/Span
Adjustment
Green LED is turned on
when the power is connected
and wiring properly.
▷ Steps 2 and 3 can be
▷ For the zero
▷ For the span
Caution: Incorrect
and then off.
■ Offset
Adjust the error of
Press the + buttons for
to turn on the red LED.
▷ Offset adjustment is available regardless of float position.
■ Simulation Current Out
When the check of correct output (4~20mA) between M
s below.
Press + buttons at once for
about 1 sec. then 4mA will be out
for 5 sec.
▷ After 5 seconds, it will be returned to actual float sensing mode.
▷ It can be tested regardless
2 and 3 can be interchanged.
zero (0%) setting, proceed with Step 1 à Step 2 à
span (100%) setting, proceed with Step 1 à Step 3
Caution: Incorrect setting may lead to an incorrect range setting with
Adjust the error of measuring device or fine tuning of level.
With the button pressed, press the
/ button for fine tuning .
Offset adjustment is available regardless of float position.
Press the button
with the float at
0% position.
Press the button
with the float at
100% position.
With the button pressed, press the
/ button for fine tuning .
Simulation Current Out
the check of correct output (4~20mA) between M-100R and PLC required, test it a
Press + buttons at once for
about 1 sec. then 4mA will be out
After 5 seconds, it will be returned to actual float sensing mode.
It can be tested regardless of the wiring of the sensor.
Press + buttons at once for
about 1 sec. then 4mA will be out
for 5 sec.
Press + buttons at once for
about 1 sec. then 4mA will be out
for 5 sec.
HT-100F Series
HITROL CO., LTD. 7
Press and hold the button for 1s
to finish zero/span setting with
the green LED on and then off.
Step 4.
3 à Step 4.
range setting with the orange LED on
Press the + buttons for 1s
to finish the offset with
the green LED on and then off.
100R and PLC required, test it a
After 5 seconds, it will be returned to actual float sensing mode.
Press + buttons at once for
about 1 sec. then 4mA will be out
for 5 sec.