Configuration 15 (46)
Configuration tab fields
Field Description Writable
Readout interval (s) Standard readout cycle of meters (in seconds). Value might be overwritten for each
meter by parameter Cycle in tab Meter
Yes
Description mode Mode of displaying the meter value description.
None No display of description
Standard Display of common value description.
Extended Extended display of value description (if not 0).
Notation: Description [Memory] <Tariff> {min|max|error}
Example: Energy [2] <1> {max}
Extended
with DIF/VIF
Extended display including DIF and VIF raw data.
Notation: Description [Memory] <Tariff> {Value Type} # XX XX XX…
Example: Energy [2] <1> # 8C 11 04
Extended
with raw data
Extended display including raw data of the complete value entry.
Notation: Description [Memory] <Tariff> {Value Type} # XX XX XX…
Example: Energy [2] <1> # 8C 11 04 96 47 06 00
DIF/VIF Display of DIF/VIF raw data
Raw data Displays the raw data of the complete meter value entry.
After changing this parameter a readout is needed to update the
meter list and to display the relevant data.
Yes
Maximum device count Maximum number of meters to scan (0 = no limitation).
Already configured meters are not affected by this parameter.
Yes
Maximum value count Maximum number of meter value entries to read during a readout (0 = no limitation).
Already configured meter value entries are not affected by this parameter.
Yes
RAW log active Activates the raw data log. Yes
M-Bus mode M-Bus scan mode (secondary, reverse secondary or primary search) Yes
Primary start address First address for primary search Yes
Primary final address Last address for primary search Yes
Secondary address
mask
Search mask for secondary search, 8 numerical characters.
Fdefines a wildcard. Missing characters will be filled up with leading zeros
Yes
M-Bus baud rate Baudrate for M-Bus communication (300–19200 baud) Yes
M-Bus timeout M-Bus timeout until reception of first data (ms) Yes
M-Bus idle timeout M-Bus timeout until end of reception (ms) Yes
M-Bus full timeout M-Bus timeout (complete) for reception of a whole data packet (ms) Yes
M-Bus request mode Mode of the M-Bus readout (REQ_UD2)
Standard Readout with REQ_UD2
Extended 1 Readout with Get-All-Data (DIF/VIF 7F 7E) and REQ_UD2
Extended 2 Readout with Get-All-Data (DIF 7F) and REQ_UD2
Yes
M-Bus reset mode Mode of the M-Bus Reset (before scan and readout)
None No reset
Standard Send SND_NKE to primary address of the meter or broadcast
address when using secondary adressing.
Extended 1 Send SND_NKE to primary address FD and SND_NKE to primary
address of the meter or broadcast address when using secondary
addressing.
Extended 2 Send SND_NKE and an Application Reset to primary address FD
and a SND_NKE to the primary address of the meter or to
broadcast address when using secondary addressing.
Yes
M-Bus max. multipage Limits the count of multipage requests Yes
M-Bus to Modbus-TCP Gateway User Manual SCM-1202-0096-EN 2.1