Hobo RXW TEROS-12 User manual

HOBOnet® Wireless Sensor Network
RXW TEROS-12 Soil Moisture EC Temp Sensor (RXW-T12-xxx) Manual
24747-A
This sensor measures soil moisture, temperature, and electrical conductivity (EC) in numerous
soil types, including high salinity and sandy soil. It is designed to work with the HOBOnet (HOBO
RX) Wireless Sensor Network in which data is transmitted wirelessly from the sensor mote
across the network to the station and then uploaded to HOBOlink® web-based software. With
HOBOlink, you can monitor sensor readings, view graphs, set up alarms, download data, and
more.
Specifications
Soil Moisture
: Volumetric Water Content (VWC)
Measurement Range
* 0.00 to 0.70 m³/m³ in mineral soils
Accuracy
±0.030 m³/m³ (±3%) typical from 0 to 50°C (32 to 122°F); ±0.020 m³/m³
(±2%) with soil specific calibration
Resolution
0.001 m³/m³
Dielectric Measurment
Frequency
70 MHz
Temperature
**
Measurement Range
-40 to 60°C (-40 to 140°F)
Accuracy
±0.5°C (0.9°F) from -40 to 0°C (-40 to 32°F)
±0.3°C (0.54°F) from 0 to 60°C (32 to 140°F)
Resolution
0.1°C (0.18°F)
Bulk Electrical Conductivity (EC)
Measurement Range
0 to 20 dS/m (bulk)
Accuracy
±5% of reading + 0.01 dS/m from 0 to 10 dS/m
±8% of reading from 10 to 20 dS/m
Resolution
0.001 dS/m
Wireless Mote
Operating Temperature
Range
Sensor: -40 to 60°C (-40 to 140°F)
Mote: -25° to 60°C (-13° to 140°F) with rechargeable batteries
-40 to 70°C (-40 to 158°F) with lithium batteries
Radio Power
12.6 mW (+11 dBm) non-adjustable
Transmission Range
Reliable connection to 457.2 m (1,500 ft) line of sight at 1.8 m (6 ft) high
Reliable connection to 609.6 m (2,000 ft) line of sight at 3 m (10 ft) high
Wireless Data Standard
IEEE 802.15.4
Radio Operating
Frequencies
RXW-T12-900: 904–924 MHz
RXW-T12-868: 866.5 MHz
RXW-T12-921: 921 MHz
RXW-T12-922: 916–924 MHz
Modulation Employed
OQPSK (Offset Quadrature Phase Shift Keying)
Data Rate
Up to 250 kbps, non-adjustable
Duty Cycle
<1%
Maximum Number of
Motes
50 motes per one HOBOnet Wireless Sensor Network
Battery Type/
Power Source
Two AA 1.2V rechargeable NiMH batteries, powered by built-in solar
panel or two AA 1.5 V lithium batteries for operating conditions of -40 to
70°C (-40 to 158°F)
Battery Life
With NiMH batteries: Typical 3–5 years when operated in the temperature
range -20° to 40°C (-4°F to 104°F) and positioned toward the sun (see
Deployment and Mounting), operation outside this range will reduce the
battery service life
With lithium batteries: 1 year, typical use
Memory
16 MB
RXW Soil Moisture EC
Temp Sensor
Models:
•RXW-T12-900 (US)
•RXW-T12-868 (Europe)
•RXW-T12-921 (Taiwan)
•RXW-T12-922
(Australia/NZ)
Included Items:
•Cable ties
•Screws

RXW TEROS-12 Soil Moisture EC Temp Sensor (RXW-T12-xxx) Manual
1-800-LOGGERS 2 www.onsetcomp.com
Specifications (continued)
Dimensions
Sensor: 7.47 x 9.4 x 2.39 cm (2.94 x 3.7 x 0.94 inches)
Sensor needle length: 5.4 cm (2.13 inches)
Sensor needle diameter: 0.32 cm (0.13 inches)
Cable length: 5 m (16.4 ft)
Mote: 16.2 x 8.59 x 4.14 cm (6.38 x 3.38 x 1.63 inches)
Weight
RXW-T12-xxx sensor and cable: 245 grams (8.64 oz)
Mote: 223 g (7.87 oz)
Materials
Sensor: ASA plastic body with polyurethane epoxy filling and stainless steel
pins
Cable: PVC, UV resistant and rodent repellent
Mote: PCPBT, silicone rubber seal
Environmental Rating
Mote: IP67, NEMA 6
Compliance Marks
RXW-T12-900: See last page
RXW-T12-868: The CE Marking identifies this product as
complying with all relevant directives in the European Union
(EU).
RXW-T12-921: See last page
RXW-T12-922: See last page
* The sensor data can be post-calibrated if necessary (e.g. the sensor is used in non-mineral soil types or higher than
standard accuracy is required). Users can apply a calibration equation to the data exported from HOBOlink. The VWC
range will depend on the calibration equation.
** Temperature measurement, for applicable sensors, may not be accurate if sensor is not fully immersed in medium of
interest, due to longer equilibration time.
Mote Components and Operation
Sensor Mote Closed, Front Sensor Mote Closed, Back
Sensor Mote Opened
Mounting Tab: Use the tabs at the top and bottom of the mote
to mount it (see Deploying and Mounting).
Solar Panel: Position the solar panel towards the sun to charge
the mote batteries (see Deploying and Mounting).
Sensor Cable: This is the cable that connects the mote to the
sensor.
Eyelet: Use this eyelet to attach a 3/16 inch padlock to the
mote for security.
Latch: Use the two latches to open and close the mote door.
Ground Wire Port: Use this port to connect a ground wire (see
Deploying and Mounting).
Antenna: This is the built-in antenna for the radio
communications across the RX Wireless Sensor Network.
LEDs: There are two LEDs to the left of the LCD screen. The
green LED blinks during the process of joining a network,
blinking quickly while the mote searches for a network and
then slowly as the mote registers with the network. Once the
network registration process is complete, the blue LED blinks at
4 seconds to indicate normal operation. If the mote is not
currently part of a network, the blue LED will be off. If the blue
LED is on and not blinking, there is a problem with the mote.
Contact Onset Technical Support.
Solar Panel Cable: This cable connects the built-in solar panel
to the mote circuitry.
Battery Holder: The location where the batteries are installed
as shown (see Battery Information).
USB Port: Use this port to connect to the mote to a computer
via USB cable if you need to update the firmware (see Updating
Mote Firmware).
Button: Push this button for 1 second to illuminate the LCD or 3
seconds for the mote to search for a HOBOnet Wireless Sensor
Network to join (see Adding the Mote to the HOBOnet Wireless
Sensor Network).
LCD Screen: The mote is equipped with an LCD screen that
displays details about the current status. The following example
Mounting
Tab
Solar Panel
Latch
Eyelet
Ground Wire
Port
Sensor Cable
Solar Panel Cable
Button
USB Port
Battery Holder
LCD Screen
Antenna
LEDs

RXW TEROS-12 Soil Moisture EC Temp Sensor (RXW-T12-xxx) Manual
1-800-LOGGERS 3 www.onsetcomp.com
shows all symbols illuminated on the LCD screen followed by
definitions of each symbol in the table.
LCD Symbol
Description
The battery indicator shows the approximate battery
charge remaining.
This is a signal strength indicator. The more bars, the
stronger the signal between motes. If there is no x
icon next to the signal strength indicator, then the
mote is part of a HOBOnet Wireless Sensor Network.
An empty signal strength icon plus the x icon
indicates that the mote is not currently part of a
network. See Adding the Mote to the HOBOnet
Wireless Sensor Network for details on how to add a
mote to the network.
When the mote is in the process of joining a
network, the signal strength icon will blink and then
the bars in the icon will cycle from left to right. The x
icon will blink during the last step in the network
registration process (see Adding the Mote to the
HOBOnet Wireless Sensor Network for details).
This indicates a problem with the sensor itself (the
mote is operational). Check the sensor and make any
adjustments to it as needed. Contact Onset
Technical Support if the problem persists.
Sensor Components and Operation
The sensor measures soil moisture, temperature, and EC of soil
using stainless steel needles. As shown in the following
diagram, the sensor measures soil moisture between Needle 1
and Needle 2 and measures EC between Needle 2 and Needle
3. Temperature is measured with an embedded thermistor.
A ferrite core positioned on the sensor cable 7.6 cm (3
inches) away from the sensor head is used to isolate the
sensor from any interferences in the system. This
mitigates any potential noise from the system on the
measured sensor data.
Important: Do not attach anything to the section of the
cable between the sensor head and the ferrite core as
this may influence the measurements.
The VWC measurement sensitivity is contained within a 1,010
mL volume roughly depicted in the following VFW volume of
influence figure.
Adding the Mote to the HOBOnet Wireless
Sensor Network
The mote must join a HOBOnet Wireless Sensor Network
before it can begin measuring soil moisture and transmitting
data. This requires accessing the station and the mote at the
same time so it is recommended that you complete these steps
before deploying the mote.
Important: If you are setting up a new station, follow the
instructions in the station quick start before setting up this
mote (go to www.onsetcomp.com/support/manuals/24380-
man-rx2105-rx2106-qsg for RX2105 and RX2106 stations or go
to www.onsetcomp.com/support/manuals/18254-MAN-QSG-
RX3000 for RX3000 stations).
To add a mote to the network:
1. If the LCD is blank on the station, press any button to wake
it up.
2. Press the Select button once (which shows the number of
smart sensors installed) and then press it again to switch to
the module with the manager (module 2 on RX2105 or
RX2106 stations).
Press this button to view the module
Needle 3
Needle 2
Needle 1
Ferrite core
Thermistor in Needle 2
EC
VWC
WARNING: Risk of
personal injury is
present. Sensor needle
points are extremely
sharp and will puncture
skin. Handle with care.
9.3 cm
7.5 cm

RXW TEROS-12 Soil Moisture EC Temp Sensor (RXW-T12-xxx) Manual
1-800-LOGGERS 4 www.onsetcomp.com
3. Press the Search button (the magnifying glass). The
magnifying glass icon will blink while the station is in search
mode.
4. Open the mote door and install the batteries if you have not
already done so.
5. Press the button on the mote for 3 seconds. The signal
strength icon will flash and then cycle.
6. Watch the LCD on the mote.
The green LED blinks quickly while the mote searches for a
network to join and then blinks slowly while it completes
the network registration. Once the mote has finished
joining the network, the green LED turns off and the blue
LED then blinks indefinitely while the mote is part of the
network.
Note: If the mote cannot find the network or has trouble
remaining connected during this process, make sure the
mote is in a vertical, upright position and within range of
the station.
7. Press the Search button (the magnifying glass) on the
station to stop searching for motes.
If you added more than one more mote to the network, then
the total channel count on the station LCD for the manager
module will represent all measurement channels plus a battery
channel for each mote in the network.
Sensor measurements will be recorded at the logging interval
specified in HOBOlink, transmitted to the station, and uploaded
to HOBOlink at the next connection interval (readout). Use
HOBOlink to monitor mote status and health. If a mote is
temporarily offline, any logged data is saved until it is back
online. In addition, if a mote is offline for 30 minutes, the
station will automatically connect to HOBOlink and report the
mote as missing. Once the mote is back online, any logged data
will be uploaded the next time the station connects to
HOBOlink.
See the HOBOlink Help for details on how to change the logging
and connection intervals, view data, check mote status, add the
mote to a map, and more.
Installing the Sensor
There are two installation methods for installing the sensor:
borehole or trench.
Borehole Installation Method
This method allows for a profile of soil moisture sensors to be
installed at different depths within a single augered borehole,
thereby minimizing soil disturbance at the measurement site. A
10-cm (4-inch) borehole is augered vertically at the
measurement location. You can then carefully insert and place
the sensor by hand or buy or rent the Borehole Installation Tool
from Meter (recommended for depths greater than 50 cm (19.7
or renting the tool.
If you are installing the sensor without the Borehole Installation
Tool, look down the hole with a flashlight, reach in with the
Press this button for 3
seconds for the mote to
join the network
This signal strength icon
blinks while searching for
a network.
Press this button so the station is ready
to have motes join the network
Once a network is found,
the icon will stop flashing
and the bars will cycle from
left to right.
Press this button again to
stop searching for motes
c.
d.
This network connection
“x” icon blinks while the
mote completes the
registration process,
which may take up to
five minutes.
Once the mote has finished joining
the network, the “x” icon is
removed and the channel count
on the station LCD increases by
four (three for soil moisture, EC,
and temperature, and one for the
mote battery).
a.
b.

RXW TEROS-12 Soil Moisture EC Temp Sensor (RXW-T12-xxx) Manual
1-800-LOGGERS 5 www.onsetcomp.com
sensor and push it into to the side of the undisturbed soil. Look
down the hole and make sure it is firmly seated. You can also
consider attaching the sensor to PVC piping or similar material
to aid in placing the sensor. You can then use the PVC as a lever
to assist with pushing the sensor into the undisturbed soil.
Trench Installation Method
This method is best for shallow installations at less than 40 cm
(15.7 inches). This requires digging a trench with a shovel,
excavator, or other tool to the depth of the deepest installed
sensor (if installing more than one in the measurement
location). For deep installations, this may require a large trench.
The sensor is then installed carefully by hand into the
undisturbed soil of the trench sidewall. The trench is carefully
backfilled to preserve the bulk density of the soil and avoid
dislodging the installed sensor by accidentally snagging the
ferrite core.
Sensor Installation Guidelines
Before installing the sensor, follow these guidelines:
•Test the sensor functionality and accuracy using the TEROS
verification clip. Refer to the TEROS verification clip
documentation for details on operation and expected
readings. If you do not have a verification clip, you can
perform a rough check of sensor functionality in air and
water. The sensor will produce readings of ~0.70 m3/m3in
water and ~0.003 m3/m3in air. Use HOBOlink to export or
view the data for your test.
•When creating the hole to install the sensor, avoid
interfering objects. Installation near large metal objects
can affect the sensor function and distort readings. Large
objects like roots or rocks could potentially bend the
needles.
•The sensor may be positioned in any direction. However,
there is less restriction to water flow when the sensor
body is placed in a vertical position as shown below. A
vertical position will also integrate more soil depth into
the soil moisture measurement. Installing the sensor with
the sensor body in a horizontal position will provide
measurements at a more discreet depth.
•Do not touch the sensor needles with an ungloved hand or
bring them in contact with any source of oil or other
nonconducting residue. If the sensor needles are
contaminated with oils from contact with skin or another
source, follow the instructions in the Maintenance section
for cleaning the needles before installing the sensor.
•Avoid any metal located between the sensor and the
ferrite core because it can interfere with VWC
measurements.
•When installing sensors in rocky soils, use care to avoid
bending sensor needles.
•Minimize air gaps around the sensor. Air gaps around the
sensor needles will result in low readings of soil moisture.
•When backfilling the hole, be careful not to snag the
ferrite core on the sensor cable.
•Secure the sensor cable to the mounting pole or tripod
with cable ties.
•Use conduit to protect the cable against damage from
animals, lawn mowers, exposure to chemicals, etc.
Sensor Installation Instructions
1. Auger or dig a hole to the desired sensor depth.
2. Carefully insert the sensor in the hole and push the sensor
so that the needles are inserted into the undisturbed side of
the soil. Check that the sensor is firmly seated.
3. Secure the cable to the mounting pole or tripod and install
flexible conduit before backfilling the hole.
4. Carefully return the soil to the hole, packing it back to its
native bulk density. Do not hit the ferrite core as this could
potentially pull the sensor out of the soil.
Mounting and Positioning the Mote
•Mount the mote to a mast or pipe using cable ties or affix
the mote to a wooden post or flat surface with screws.
Insert the cable ties or screws through the holes on the
mounting tabs.
•Consider using plastic poles such as PVC to mount the
mote as certain types of metal could decrease signal
strength.
•Make sure the mote remains in a vertical position once it
is placed in its deployment location for optimal network
communications.
•Make sure the mote door is closed, with both latches fully
locked to ensure a watertight seal.
•Consider using a 3/16 inch padlock to restrict access to the
mote. With the mote door closed, hook a padlock through
the eyelet on the right side of the door and lock it.
•Position the mote towards the sun, making sure the solar
panel is oriented so that it receives optimal sunlight
throughout each season. It may be necessary to
periodically adjust the mote position as the path of the
sunlight changes throughout the year or if tree and leaf
growth alters the amount of sunlight reaching the solar
panel.
•Make sure the mote is mounted a minimum of 1.8 m (6 ft)
from the ground or vegetation to help maximize distance
and signal strength.

RXW TEROS-12 Soil Moisture EC Temp Sensor (RXW-T12-xxx) Manual
1-800-LOGGERS 6 www.onsetcomp.com
•Place the mote so there is full line of sight with the next
mote. If there is an obstruction between two sensor
motes or between the sensor mote and the manager, then
use a repeater mounted on the obstruction. For example,
if there is a hill between the sensor mote and the
manager, place a repeater at the top of the hill between
the sensor mote and the manager.
•There should not be more than five motes in any direction
at their maximum transmission range from the manager.
Data logged by a wireless sensor must travel or “hop”
across the wireless network from one mote to the next
until it ultimately reaches the manager connected to the
station. To make sure the data can successfully travel
across the network, the mote should not be more than
five hops away from the manager.
•The HOBOnet Wireless Sensor Network can support a
maximum of 50 motes.
•Use a #4-40 screw to attach a ground wire to the port on
the back of the mote if you are deploying the mote in a
location where lightning is a concern.
Maintenance
If the sensor needles become contaminated with oils from
contact with skin or another source, it is necessary to clean the
needles to ensure accurate EC readings in salty soils with bulk
EC greater than 10 dS/m.
1. Clean each needle using a mild detergent, such as liquid
dish soap and a nonabrasive sponge or cloth. Avoid
detergents that contain lotions or moisturizers.
2. Rinse the sensor and needles thoroughly with tap or
deionized (DI) water. Do not touch the needles with an
ungloved hand or bring them in contact with any source of
oil or other nonconducting residue.
The mote is designed for outdoor use, but should be inspected
periodically. When inspecting the mote, do the following:
•Verify the mote is free of visible damage or cracks.
•Make sure the mote is clean. Wipe off any dust or grime
with a damp cloth.
•Wipe off any water before opening the mote.
•Make sure the interior seal is intact and the latches are
fully locked when the mote door is closed.
Troubleshooting
If the sensor readings are too low or slightly negative, check for
air gaps around the sensor needles. These could be produced
below the surface of the substrate when the needle contacts a
large piece of material and pushes it out of the way, or if the
sensor is not inserted perfectly linearly.
If the sensor readings are too high, make sure the media was
not packed excessively or insufficiently during sensor
installation. Higher density can cause the sensor readings to be
elevated.
Updating Mote Firmware
If a new firmware version is available for the mote, use
HOBOlink to download the file to your computer.
5. In HOBOlink, go to Devices, then RX Devices, and click your
station name.
6. On the station page, click Overview and scroll down to
Device Information.
7. Click the Wireless tab. This icon appears next to the
mote if there is a new version of firmware available.
8. Click the firmware upgrade link. Click Download and
save the firmware .bin file to your computer.
9. Connect the mote to the computer with a USB cable (open
the mote door and use the USB port to the right of the
LCD). The blue LED is illuminated while connected.
10. The mote appears as a new storage device in the
computer’s file storage manager. Copy the downloaded
firmware file to the new storage device (the mote). The
blue LED will blink slowly while the file is copying.
11. After the file is copied to the mote, the LED will stop
blinking and remain a steady blue. Eject the storage device
from the computer and disconnect the cable from the
mote. The firmware installation process will begin
automatically on the mote. The blue LED will blink rapidly
while the firmware is installed. Once the firmware
installation is complete, the LCD symbols return and the
mote will automatically rejoin the network.
Notes:
•Mac® users: A message may appear indicating the disk
has not ejected properly when disconnecting the mote
from the computer. The mote is operational and you can
ignore the message.
•If the blue LED turns off abruptly while copying the file or
installing the firmware, a problem has occurred. Contact
Onset Technical Support for help.
Battery Information
The mote uses two 1.2 V rechargeable NiMH batteries, charged
by the built-in solar panel. The quality and quantity of solar
light can affect whether the battery is sufficiently charged to
last through the night and cloudy periods. Make sure the mote
is placed in a location that will receive several hours of sunlight
each day. If the mote does not receive enough sunlight to
recharge the batteries, the battery life is estimated at 3–4
months. When batteries are regularly recharged, expected
battery life is estimated at 3–5 years. Battery life varies based
on the ambient temperature where the mote is deployed, the
logging interval, the number of tripped alarms, and other
factors. Deployments in extremely cold or hot temperatures
can impact battery life. Estimates are not guaranteed due to
uncertainties in initial battery conditions and operating
environment.
Mote operation will stop when battery voltage drops to 1.8 V.
Mote operation will return if the battery recharges to 2.3 V. If
the batteries are unable to be recharged, replace them with
fresh rechargeable batteries. Note: if you install used
rechargeable batteries that together are less than 2.3 V, the
mote will not resume operation.
To replace rechargeable batteries:
1. Open the mote door.
2. Remove the old batteries and install fresh ones observing
polarity.

RXW TEROS-12 Soil Moisture EC Temp Sensor (RXW-T12-xxx) Manual
1-800-LOGGERS 7 www.onsetcomp.com
3. Make sure the solar panel cable is plugged in.
The mote contacts the network once the new batteries are
installed. The green LED blinks quickly while the mote searches
for a network to join and then blinks slowly while it completes
the network registration. Once the mote has finished joining
the network, the green LED turns off and the blue LED then
blinks indefinitely while the mote is part of the network.
Lithium Batteries
You can use two 1.5 V lithium batteries (HWSB-LI) for operation
at the extreme ends of the mote operating range. Lithium
battery life is an estimated at 1 year, but varies based on the
ambient temperature where the mote is deployed, the logging
interval, the number of tripped alarms, and other factors.
Estimates are not guaranteed due to uncertainties in initial
battery conditions and operating environment. When using
lithium batteries, you must disconnect the solar panel cable
because the batteries will not be recharged.
To install lithium batteries:
1. Open the mote door.
2. Remove any old batteries and install the new ones
observing polarity.
3. Push in the side tab of the solar panel cable connector and
pull the connector out of the cable port.
4. Place the connector in the slot on the inside of the mote
door. Make sure the solar panel cables are tucked inside the
door so that they do not interfere with the interior seal
when the mote is closed.
The mote contacts the network once the new batteries are
installed. The green LED blinks quickly while the mote searches
for a network to join and then blinks slowly while it completes
the network registration. Once the mote has finished joining
the network, the green LED turns off and the blue LED then
blinks indefinitely while the mote is part of the network.
WARNING: Do not cut open, incinerate, heat above 85°C
(185°F), or recharge the lithium batteries. The batteries may
explode if the mote is exposed to extreme heat or conditions
that could damage or destroy the battery cases. Do not mix
battery types, either by chemistry or age; batteries may rupture
or explode. Do not dispose of the logger or batteries in fire. Do
not expose the contents of the batteries to water. Dispose of
the batteries according to local regulations for lithium
batteries.
Store the solar
panel connector
here when using
lithium batteries
Make sure
solar panel
cable is
installed
when using
rechargeable
batteries

RXW TEROS-12 Soil Moisture EC Temp Sensor (RXW-T12-xxx) Manual
1
-800-LOGGERS (564-4377) • 508-759-9500
www.onsetcomp.com/support/contact
© 2020 Onset Computer Corporation. All rights reserved. Onset, HOBO, and HOBOlink are registered
trademarks of Onset Computer Corporation. Some material reprinted with permission of METER Group, Inc.
Mac is a registered trademark of Apple Inc. All other trademarks are the property of their respective
companies.
24747-A
Federal Communication Commission Interference Statement
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment generates uses and can radiate radio frequency energy and, if not installed and
used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a
particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user
is encouraged to try to correct the interference by one of the following measures:
•Reorient or relocate the receiving antenna
•Increase the separation between the equipment and receiver
•Connect the equipment into an outlet on a circuit different from that to which the receiver is connected
•Consult the dealer or an experienced radio/TV technician for help
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device
must accept any interference received, including interference that may cause undesired operation.
FCC Caution: Any changes or modifications not expressly approved by the party responsible for compliance could void the user's authority to operate this equipment.
Industry Canada Statements
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and
(2) this device must accept any interference, including interference that may cause undesired operation of the device.
Avis de conformité pour l’Industrie Canada
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation est autorisée aux deux conditions suivantes : (1)
l'appareil ne doit pas produire de brouillage, et (2) l'appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d'en compromettre le
fonctionnement.
To comply with FCC and Industry Canada RF radiation exposure limits for general population, the logger must be installed to provide a separation distance of at least 20cm from
all persons and must not be co-located or operating in conjunction with any other antenna or transmitter.
NCC Statement
經型式認證合格之低功率射頻電機,非經許可,公司、商號或使用者均不得擅自變更頻率、加大功率或變更原設計之特性及功能。
低功率射頻電機之使用不得影響飛航安全及干擾合法通信;經發現有干擾現象時,應立即停用,並改善至無干擾時方得繼續使用。前項合法通信,指依電信法規定作
業之無線電通信。低功率射頻電機須忍受合法通信或工業、科學及醫療用電波輻射性電機設備之干擾。
Translation:
Article 12
Without permission granted by the NCC, any company, enterprise, or user is not allowed to change frequency, enhance transmitting power or alter original characteristic as well
as performance to an approved low power radio-frequency device.
Article 14
The low power radio-frequency devices shall not influence aircraft security and interfere with legal communications. If found, the user shall cease operating immediately until no
interference is achieved. The said legal communications means radio communications is operated in compliance with the Telecommunications Act. The low power radio-
frequency devices must be susceptible with the interference from legal communications or ISM radio wave radiated devices.
This manual suits for next models
9
Table of contents
Other Hobo Accessories manuals

Hobo
Hobo RXW series User manual

Hobo
Hobo RXW-THC Series User manual

Hobo
Hobo RXW-THC-B Series User manual

Hobo
Hobo S-WCG-M003 User manual

Hobo
Hobo S-LIA-M003 User manual

Hobo
Hobo RXW-GP3 Series User manual

Hobo
Hobo S-LIA-M003 User manual

Hobo
Hobo RXW-WCF Series User manual

Hobo
Hobo Davis S-RGE-M002 User manual

Hobo
Hobo RXW 10HS User manual