Honeywell SILENT KNIGHT SK-Zone-6 User manual

SPECIFICATIONS
Normal Operating Voltage: 15-32 VDC
Stand-By Current: 2.3 mA @ 24 V
Alarm Current: 40 mA (assumes all six LEDs solid on)
Temperature Range: 32ºF to 120ºF ( 0ºC to 49ºC)
Humidity: 10 to 93% Non-condensing
Dimensions: 6.8˝ H x 5.8˝ W x 1.0˝ D
Accessories: IDP-ACB Cabinet and chassis
Wire Gauge: 12-18 AWG
Max. IDC Wiring Resistance: 25 Ohms
External Power Supply Voltage: Regulated 24 VDC
Ripple Voltage: 0.1 volts RMS maximum
IDC (supervised and power limited)
DC Voltage: 18-28 volts power limited
Frequency: DC
Alarm Current: 90mA per circuit
Standby Current 6 circuits: 42mA Maximum @18 VDC
56mA Maximum @24 VDC
66mA Maximum @28VDC
BEFORE INSTALLING
If the modules will be installed in an existing operational system, inform the
operator and local authority that the system will be temporarily out of service.
Disconnect the power to the control panel before installing the modules. This
system contains static sensitive components. Always ground yourself with a
proper wrist strap before handling any circuits so that static charges are re-
moved from the body. The module housing should also be grounded.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The SK-Zone-6 Six Zone Interface Module is intended for use in an intelli-
gent alarm system. Each module provides an interface between the intelligent
alarm system and a conventional alarm system loop. A common SLC input is
used for all modules, and the initiating device loops share a common super-
visory supply and ground. Otherwise, each monitor operates independently
from the others. Each module has its own unique address.
A pair of rotary code switches is used to set the address of the first module
from 01 to 154. The remaining modules are automatically assigned to the next
five higher addresses. Provisions are included for disabling a maximum of two
unused modules to release the addresses to be used elsewhere. Each mod-
ule also has panel controlled bicolor LED indicators. The panel can cause the
LEDs to blink, latch on, or latch off.
Included:
(5) 1 x 4 Terminal Blocks (2) 1.25" Stand offs (3) Shunts
(4) Machine Screws (2) Nuts (1) Long Power Supply Jumper
(6) 3.9k Ohm End of Line Resistors
C0202-00
Shipped on Board:
(2) Shunts in Class A/B position
(Shipped in Class B position, remove shunts for Class A)
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Silent Knight system control panel (list available from Silent Knight).
A list of compatible two-wire System Sensor Smoke detectors for use with the
SK-Zone-6 is available on the System Sensor website at systemsensor.com.
COMPONENTS
The following is a description of the SK-Zone-6 mounting framework:
• One or two SK-Zone-6 modules can be installed in an IDP-ACB cabinet
FIGURE 1. IDP-ACB CABINET
0
1
2
3
4
56789
0
78
6
5
4
3
21
910
11
12
13
14
15
BASE ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
0
1
2
3
4
56789
0
78
6
5
4
3
21
9
BASE ADDRESS
ADDRESS
DISABLE
NONE
ONE
TWO
THREE
10
11
12
13
14
15
C0234-05
The IDP-ACB cabinet has a built-in chassis that will accommodate one or two
SK-Zone-6 modules. For cabinet dimensions refer to the IDP-ACB instruction
manual.
The front SK-Zone-6 module positions of each chassis are offset below the
rear SK-Zone-6 module positions so that all of the status indicators are visible.
INSTALLATION STEPS
1. Cabinet Mounting
• In a clean, dry area, mount the backbox using the four holes provided
in the back surface of the cabinet (Figure 2).
1 I56-3441-007
7/1/2022
I56-3441-007
INSTALLATION AND MAINTENANCE INSTRUCTIONS
12 Clintonville Road, Northford, CT 06472-1610
Phone: 203-484-7161 Fax: 203-484-7118
www.silentknight.com
SK-Zone-6
Six Zone Interface Module
FIGURE 2. TYPICAL MOUNTING HOLE LOCATIONS
BACKBOX
MOUNTING
HOLES
C0235-00
2. Module Installation
There are two methods for installing a module in the rear position of a chas-
sis. Method one is for installation of a rear module only, when no module will
be installed in front of it. Refer to Figure 3 for instructions. Method two is for
installation of a rear module when another module will be installed in the
chassis position in front of it. Refer to Figures 4a and 4b for method two. All
necessary screws and stand-offs are supplied with the modules.
FIGURE 3. INSTALLATION OF REAR MODULE ONLY, METHOD ONE
2
3
1
C0237-00
Step 1: Insert the bottom of the SK-Zone-6 module down into a rear slot on
the chassis.
Step 2: Carefully swing the upper edge of the board back towards the back of
the chassis until it touches the two stand-offs.
Step 3: Align two 4-40 screws with the two stand-offs and tighten.
Step 4: Address and wire the modules according to the instructions in this
manual.
The steps in Figures 4a and 4b describe and illustrate module installation
when the rear chassis position and the position in front of it will be filled.
Front position installation is possible only if the rear position is filled with a
module.
FIGURE 4A. INSTALLATION OF SK-ZONE-6 MODULE IN A REAR
CHASSIS POSITION, METHOD TWO
1
C0225-00
Step 1: Insert the bottom edge of the SK-Zone-6 module down into a rear slot
of the chassis.
Step 2: Carefully swing the upper edge of the board towards the back of the
chassis until it touches the short stand-off attached to the chassis.
Step 3: Align the long stand-off with the short stand-off and tighten.
FIGURE 4B. INSTALLATION OF SK-ZONE-6 MODULE IN FRONT CHASSIS
POSITION
2
3
1
C0226-00
Step 1: Insert the bottom edge of the SK-Zone-6 module down into a front
slot of the chassis.
Step 2: Carefully swing the upper edge of the board towards the back of the
chassis until it touches the 1.25˝ (32 mm) stand-offs installed on the
rear module.
Step 3: Align two 4-40 screws with the two stand-offs and tighten.
Step 4: Address and wire the modules according to the instructions in this
manual.
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations.
NOTE: All references to power limited represent "Power Limited (Class 2)".
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. All wiring to the SK-Zone-6 is done via terminal blocks. In order to prop-
erly make electrical connections strip approximately 0.25˝ of insulation
from the end of wire, sliding the bare end of the wire under the clamping
plate screw.
3. Set the address on the modules per the job drawing. Use the rotary code
switches to set the address of the first module between 01 and 154.
In Class B operation, the remaining modules are automatically assigned to the
next five higher addresses. For example, if the base address switch is set to 28,
the next five modules will be addressed to 29, 30, 31, 32 and 33.
The module is shipped in Class B position, remove shunts for Class A. When
operating in Class A, alternate modules are paired together (+0/+1, +2/+3,
+4/+5), resulting in a total of three modules. For example, if the base ad-
dress switch is set to 28, then 30 and 32 will be automatically assigned to the
modules while 29, 31 and 33 are available to be used for other modules on the
SLC. For Class A and B operation, DO NOT set the lowest address above 154,
as the other modules will be assigned to nonexistent addresses.
NOTE: The SK-Zone-6 must have power cycled for shunt changes to take effect.
4. A shunt is provided to disable a maximum of two unused modules in
Class B operation and Class A operation. Modules are disabled from the
highest address and work downward. If two modules are disabled, the
lowest four addresses will be functional, while the highest two will be
disabled. For example, in Class B operation, if the shunt for Address Dis-
able is placed on “two” and the base switch is set to 28, the modules will
be assigned to 28, 29, 30 and 31 while disabling the highest two positions.
NOTE: Place unused shunts on single pin to store on board for future use.
WIRING NOTES
• Power-limited circuits must employ type FPL, FPLR, or FPLP cable as
required by Article 760 of the NEC.
• All wiring must be in accordance with the NEC, NFPA 72 and all other
applicable codes and standards. All external power supplies must be
power limited with battery back-up. All external power supplies and
detectors must be UL listed for fire protection signaling applications.
PROGRAMMING
The modules are programmed as devices in each system according to the pro-
gramming instructions in the appropriate FACP manual.
2 I56-3441-007
7/1/2022
FIGURE 5. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS B
C0812-01
FIGURE 6. INTERFACE TWO-WIRE CONVENTIONAL DETECTORS – CLASS A
C0813-01
1. To use a common power supply
between multiple SK-Zone-6 mod-
ules, connect a long power sup-
ply jumper from T5 or T6 to T5
or T6 on the adjacent SK-Zone-6
module.
BASE ADDRESS
TO NEXT DEVICE
–
STATUS
INDICA
TORS
—
+
—
+
+0
+1
IDC
ADDRESS
—
+
—
+
+2
+3
IDC
ADDRESS
—
+
—
+
+4
+5
IDC
ADDRESS
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
3.9K EOL
RESISTOR
(INCLUDED)
CONNECT MODULES TO
LISTED COMPATIBLE
SILENT KNIGHT CONTROL
PANELS ONLY
SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX.
SEE PANEL INSTRUCTION MANUAL
FOR WIRE REQUIREMENTS.
CLASS B IDC (TYPICAL)
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
+
–
+
–
T6 T5
DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE.
INSTALL DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
(–)
(+)
IN
OUT
—
+
—
+
EXTERNAL SUPPLY
POWER-LIMITED
AND SUPERVISED
POWER TO THE NEXT INTERFACE
MODULE MUST BE EXTERNALLY
SWITCHED TO RESET THE DETECTORS.
AN FRM-1 RELAY CONTROL MODULE CAN BE
USED TO SWITCH POWER FROM A
STANDARD POWER SUPPLY. SEE FIGUR 10.
0
1
2
3
456789
0
1
2
3
45678910
11
12
13
14
15
BASE ADDRESS
TO NEXT DEVICE
–
STATUS
INDICA
TORS
—
+
—
+
+0
+1
IDC
ADDRESS
—
+
—
+
+2
+3
IDC
ADDRESS
—
+
—
+
+4
+5
IDC
ADDRESS
SLC
—
+
—
+
+
–
+
FROM PANEL OR
PREVIOUS DEVICE
CONNECT MODULES TO LISTED COMPATIBLE
SILENT KNIGHT CONTROL PANELS ONLY
SIGNAL LINE CIRCUIT (SLC) 32 VDC MAX.
SEE PANEL INSTRUCTION MANUAL
FOR WIRE REQUIREMENTS.
CLASS A IDC (TYPICAL)
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
++IDC 2
IDC 3
(–)
(+)
POWER TO THE NEXT INTERFACE
MODULE MUST BE EXTERNALLY
SWITCHED TO RESET THE DETECTORS.
AN FRM-1 RELA
Y CONTROL MODULE CAN BE
USED TO SWITCH POWER FROM A
STANDARD POWER SUPPLY. SEE FIGURE 10.
T6 T5
IN
OUT
—
+
—
+
EXTERNAL SUPPLY
POWER-LIMITED
AND SUPERVISED
––
DETECTORS MUST BE UL LISTED COMPATIBLE WITH THE MODULE. INSTALL
DETECTORS PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
0
1
2
3
456789
0
1
2
3
45678910
11
12
13
14
15
1. To select Class A, remove the
two shunts from the “A/B se-
lect” positions.
2. To use a common power sup-
ply between multiple SK-Zone-6
modules, connect a long power
supply jumper from T5 or T6
to T5 or T6 on the adjacent
SK-Zone-6 module.
FIGURE 7. RELAY CONTROL MODULE USED TO DISCONNECT A POWER SUPPLY
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
(+)
(–)
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX.
TWISTED PAIR
IS RECOMMENDED
TO NEXT
DEVICE
RELAY CONTROL
MODULE
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY
FROM PANEL
OR PREVIOUS
DEVICE
POWER LIMITED DC
POWER SUPPLY,
LISTED FOR FIRE
PROTECTION WITH
BATTERY BACKUP
C0248-02
3 I56-3441-007
7/1/2022
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must
accept any interference received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used
in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installa-
tion. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try
to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
FCC STATEMENT
FIGURE 8. EXAMPLE OF MULTIPLE BOARDS SHARING SAME EXTERNAL SUPPLY
Refer to figures 8 and 9 for typical wiring. Make certain lip on long power supply jumper engages retaining tab on T5 or T6 as shown in View A-A.
ó
+
ó
+
+0
+1
IDC
ADDRESS
ó
+
ó
+
+2
+3
IDC
ADDRESS
ó
+
ó
+
+4
+5
IDC
ADDRESS
SLC
ó
+
ó
+
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
T6 T5
ó
+
ó
+
+0
+1
IDC
ADDRESS
ó
+
ó
+
+2
+3
IDC
ADDRESS
ó
+
ó
+
+4
+5
IDC
ADDRESS
SLC
ó
+
ó
+
A/B SELECT
A/B SELECT
DISABLE 1
DISABLE 2
T6 T5
IN
OUT
ó
+
ó
+
EXTERNAL SUPPLY
IN
OUT
ó
+
ó
+
EXTERNAL SUPPLY
EXTERNAL
POWER
SUPPLY
ó
+
PCB 1
PCB 2
VIEW A-A
0
1
2
3
4
56789
BASE ADDRESS
0
1
2
3
4
56789
0
1
2
3
4
56789
BASE ADDRESS
0
1
2
3
4
56789
10
11
12
13
14
15
10
11
12
13
14
15
C0142-02
DEVICE AND SYSTEM SECURITY
Before installing this product ensure that the tamper seal on the packaging is present and unbroken and the product has not been tampered with since leaving the factory. Do not
install this product if there are any indications of tampering. If there are any signs of tampering the product should be returned to the point of purchase.
It is the responsibility of the system owner to ensure that all system components, i.e. devices, panels, wiring etc., are adequately protected to avoid tampering of the system that could
result in information disclosure, spoofing, and integrity violation.
4 I56-3441-007
©2022 Honeywell. 7/1/2022
Silent Knight®, System Sensor®, and Honeywell®are registered trademarks of Honeywell International, Inc.

Other Honeywell Control System manuals

Honeywell RP-2002 User manual

Honeywell

Honeywell RP-2002 User manual

Honeywell Tradeline H1008D User manual

Honeywell

Honeywell Tradeline H1008D User manual

Honeywell ACC 50 User manual

Honeywell

Honeywell ACC 50 User manual

Honeywell UMC800 User manual

Honeywell

Honeywell UMC800 User manual

Honeywell EVOTOUCH CONTROLLER User manual

Honeywell

Honeywell EVOTOUCH CONTROLLER User manual

Honeywell W180 User manual

Honeywell

Honeywell W180 User manual

Honeywell Farenhyt Series Operating instructions

Honeywell

Honeywell Farenhyt Series Operating instructions

Honeywell Experion PKS User manual

Honeywell

Honeywell Experion PKS User manual

Honeywell VR8304 User manual

Honeywell

Honeywell VR8304 User manual

Honeywell MRP-2002E User manual

Honeywell

Honeywell MRP-2002E User manual

Honeywell ACC 50 User manual

Honeywell

Honeywell ACC 50 User manual

Honeywell C7400 User manual

Honeywell

Honeywell C7400 User manual

Honeywell Experion LX User manual

Honeywell

Honeywell Experion LX User manual

Honeywell KAP 140 User manual

Honeywell

Honeywell KAP 140 User manual

Honeywell ComfortPoint Open Installation and operation manual

Honeywell

Honeywell ComfortPoint Open Installation and operation manual

Honeywell BCS 3600 User manual

Honeywell

Honeywell BCS 3600 User manual

Honeywell 5704 User manual

Honeywell

Honeywell 5704 User manual

Honeywell W7620 User manual

Honeywell

Honeywell W7620 User manual

Honeywell Excel 800 Installation and operation manual

Honeywell

Honeywell Excel 800 Installation and operation manual

Honeywell SPZ-8000 User manual

Honeywell

Honeywell SPZ-8000 User manual

Honeywell touchpoint Pro User manual

Honeywell

Honeywell touchpoint Pro User manual

Honeywell vk41 series User manual

Honeywell

Honeywell vk41 series User manual

Honeywell Excel 500 User manual

Honeywell

Honeywell Excel 500 User manual

Honeywell Experion MX Manual

Honeywell

Honeywell Experion MX Manual

Popular Control System manuals by other brands

Kval 965X quick start

Kval

Kval 965X quick start

BRAHMA MICROFLAT  Series manual

BRAHMA

BRAHMA MICROFLAT Series manual

DX Engineering DXE-EC-4 manual

DX Engineering

DX Engineering DXE-EC-4 manual

iB TRU 650 user guide

iB

iB TRU 650 user guide

Eagle G920D manual

Eagle

Eagle G920D manual

Davicom Cortex Series reference guide

Davicom

Davicom Cortex Series reference guide

Pilz PNOZ mm0.1p operating manual

Pilz

Pilz PNOZ mm0.1p operating manual

Graco Horizon Fluid Management Systems instructions

Graco

Graco Horizon Fluid Management Systems instructions

Elsner WS1 Color manual

Elsner

Elsner WS1 Color manual

Spohn & Burkhardt SV1C Series operating instructions

Spohn & Burkhardt

Spohn & Burkhardt SV1C Series operating instructions

Mitsubishi Electric AE-200A Instruction book

Mitsubishi Electric

Mitsubishi Electric AE-200A Instruction book

HandyTrac Key Control EASY GUIDE Installation and Operation

HandyTrac

HandyTrac Key Control EASY GUIDE Installation and Operation

DuroZone JTZ-HP manual

DuroZone

DuroZone JTZ-HP manual

Proficient Audio Systems VC60i owner's manual

Proficient Audio Systems

Proficient Audio Systems VC60i owner's manual

Delta NC300 Series quick start

Delta

Delta NC300 Series quick start

Aqua Control DOS CL 2 Deluxe WIFI Salz manual

Aqua Control

Aqua Control DOS CL 2 Deluxe WIFI Salz manual

HIK VISION DS-K3B411SX Series quick start guide

HIK VISION

HIK VISION DS-K3B411SX Series quick start guide

mr. steam iGenie 104129 Installation and operation instructions

mr. steam

mr. steam iGenie 104129 Installation and operation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.