manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Control Unit
  8. •
  9. Honeywell LCBS Connect User manual

Honeywell LCBS Connect User manual

INSTALLATION INSTRUCTIONS
31-00084-01
LCBS Connect Wall Module
PRODUCT DESCRIPTION
The LCBS Connect Wall Module is a Sylk bus
communicating device which is exclusively compatible
with the LCBS Connect controller. It contains integral
temperature and humidity sensors to control any given
space’s comfort. This device enables local controller
configuration through an easy-to-use touch screen
interface with menu driven selections. The wall module
communicates and is powered by the Sylk bus, so no
additional wiring is necessary.
Dimensions
The TS120 consists of a back plate and a front cover which
contains a circuit board.
Fig. 1. Dimensions in in. (mm).
INSTALLATION
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check ratings given in instructions and on the prod-
uct to ensure the product is suitable for the applica-
tion.
3. Installer must be a trained, experienced service tech-
nician.
4. After installation is complete, check out product
operation as provided in these instructions.
MOUNTING
Mount the wall module on an inside wall approximately 48
in (1.2m) from the floor (or in the specified location) to
allow for exposure to the average zone temperature. Do
not mount the device on an outside wall, on a wall
containing water pipes or near air ducts. Avoid locations
that are exposed to discharge air from registers or
radiation from appliances, lights or the sun.
M36282
4-49/64
(121)
3-5/16
(84)
53/64
(21)
LCBS CONNECT WALL MODULE
31-00084—01 2
Do not install the wall module where it can be affected by:
— drafts or dead spots behind doors and in corners.
— hot or cold air from ducts.
— radiant heat from sun or appliances.
— concealed pipes and chimneys.
— unheated (uncooled) areas such as an outside wall
behind the thermostat.
WHEN USED TO SENSE ROOM TEMPERATURE
Install the wall module about 4 ft. (1.2m) above the floor in
an area with good air circulation at average temperature.
(See Fig. 2.) Confirm mounting height meets Americans
with Disabilities Act requirements.
WHEN NOT USED TO SENSE ROOM TEMPERATURE
When using the remote-mounted temperature (and
humidity) sensor(s) to sense ambient conditions, install
the wall module in an area that is accessible for setting
and adjusting the temperature and settings.
Fig. 2. Typical location of wall module
or remote-mounted sensor.
When mounting the wall module to the wall, note the
arrows indicating which direction is up, as indicated on
the inside of the back plate. The wall module can only be
mounted horizontally, so it is important to properly
identify a suitable mounting location.
The wall module can be mounted on a wall, on a standard
utility conduit box using No. 6 (3.5 mm) screws or on a 60
mm wall outlet box (see Fig. 3). When mounting directly on
a wall, use screws appropriate for the wall material. Use a
wall plate, 50028399-001, to cover any visible screw
holes.
Fig. 3. Mounting the wall module to electrical boxes.
WIRING
The wall module is shipped with the front cover and
subbase assembled together. These two parts need to be
separated (see Fig. 4) in order to properly wire the device.
There are no field adjustable/replaceable components
inside the module.
Fig. 4. Separate the front cover from the subbase.
IMPORTANT
All wiring must comply with local electrical codes
and ordinances or as specified on wiring diagrams.
CAUTION
Improper Electrical Contact Hazard
Screw-type terminal blocks are designed to accept
no more than one 14AWG (2.5mm sq) conductor.
4 FEET
(1.2 METERS)
YES
NO
NO
NO
M36229
M36283
SCREW
SCREW
STANDARD UTILITY
CONDUIT BOX
SCREW
WALL
OUTLET BOX
SCREW
M36296
LCBS CONNECT WALL MODULE
331-00084—01
Wire the terminal block as shown in Fig. 5:
1. For single wires, strip 3/16 in. (5 mm); for multiple
wires going into one terminal, strip 1/2 in. (13 mm)
insulation from the conductor.
2. Insert the wire in the required terminal location and
tighten the screw to complete the termination.
3. Review and verify the terminal connection wiring
illustrated in Fig. 5.
Fig. 5. Connecting wires to the terminal block.
4. See Fig. 6 for wiring multiple Sylk devices.
Fig. 6. Options for wiring multiple Sylk devices.
5. When wiring is complete, align the pins from the
front cover to the terminal block on the subbase.
6. Firmly push the front cover onto the subbase. If the
wall module is powered, a loading screen will be dis-
played.
Sylk Bus
The wall module communicates with the LCBS Connect
controller via Sylk, which is a two-wire, polarity-insensitive
bus that provides both 18 Vdc power and
communications. This enables a faster and cheaper
installation all while minimizing errors. The recommended
wire for Sylk is 18-24 AWG (0.82 to 0.20 sq mm) single
twisted pair, solid or stranded wire, unshielded for a
maximum distance from the controller of 200ft (60m).
Standard thermostat wire (non-twisted pair) can be used
for runs up to 100ft (30m). See Table 1.
The wall module is intended to always communicate using
Sylk address 1 and is shipped from the factory with this
address configured. Other Sylk sensors are compatible
with the LCBS Connect controller and wall module but
limitations must be observed. Up to FOUR additional Sylk
sensors can be used unless a TR40-H, TR40-CO2 or TR40-
H-CO2 is used. Then the allowed additional sensors drops
to THREE. See Table 2 for a listing of the compatible Sylk
sensors.
Compatibility
The LCBS wall module has been designed specifically for
the LCBS controller. They are a one-to-one pair and
adding an additional LCBS wall module will result in a loss
of operation. Connecting an LCBS wall module to another
Honeywell controller will also result in the loss of
operation for the wall module.
M36289
TO CONTROLLER
TWO WIRES INTO ONE TERMINAL
DAISY-CHAINING MULTIPLE
SYLK DEVICES
HOME RUNNING MULTIPLE
SYLK DEVICES
TO CONTROLLER
TO SYLK DEVICE
1/2
(13)
STRIP 1/2 IN.
(13MM) FROM
WIRES TO BE
ATTACHED AT
ONE TERMINAL.
1.
2. TWIST WIRES
TOGETHER
WITH PLIERS
(A MINIMUM OF
THREE TURNS).
3. CUT TWISTED END OF WIRES TO
3/16 IN. (5 MM) BEFORE INSERTING
INTO TERMINAL AND TIGHTENING
SCREW. THEN PULL ON EACH WIRE
IN ALL TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.
WALL MODULE
TERMINALS
M36315
Table 1. Maximun Distance.
Recommended maximum distance from
controller to any Sylk device
Single twisted pair, non-
shielded, stranded or solid
Standard thermostat wire,
(non-twisted), shielded or
non-shielded, stranded or
solid
18-22 AWG 24 AWG 18-24 AWG
500ft(150m) 400ft(120m) 100ft(30m)
LCBS CONNECT WALL MODULE
® U.S. Registered Trademark
© 2017 Honeywell International Inc.
31-00084—01 M.S. 01-17
Printed in United States
Home and Building Technologies
In the U.S.:
Honeywell
1985 Douglas Drive North
Golden Valley, MN 55422-3992
customer.honeywell.com
By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or
modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any
liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
SPECIFICATIONS
Operating Temperature: 32°F to 122°F (0°C to 50°C)
Shipping Temperature: -4°F to 150°F (20°C to 65°C)
Relative Humidity: 5% to 95%, Non-condensing
Related Parts
Parts that are commonly used with the LCBS Connect
controller and wall module are shown in Table 2.
Approvals
This equipment has been tested and found to comply with
the limits for a Class B digital device, pursuant to part 15
of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference in a
residential installation. This equipment generates uses
and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions,
may cause harmful interference to radio communications.
However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does
cause harmful interference to radio or television
reception, which can be determined by turning the
equipment off and on, the user is encouraged to try to
correct the interference by one or more of the following
measures:
— Reorient or relocate the receiving antenna.
— Increase the separation between the equipment and
receiver.
— Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected.
This device complies with Part 15 of the FCC rules.
Operation is subject to the following two conditions: (1)
this device may not cause harmful interference, and (2)
this device must accept any interference received,
including interference that may cause undesired
operation.
This Class B digital apparatus complies with Canadian
ICES-003.
Cet appareil numérique de la classe B est conforme à la
norme NMB-003 du Canada.
This device complies with Industry Canada license-
exempt RSS standard(s). Operation is subject to the
following two conditions: (1) this device may not cause
interference, and (2) this device must accept any
interference, including interference that may cause
undesired operation of the device.
Table 2. Compatible Sylk Sensors.
Sylk
Device Description
Sylk
Address(s)
YCRL6438SR1000 Controller and Wall
Module Pack
N/A
TR40 Sylk Wall Module with
Temperature Sensor
3, 4, 5, 6
TR40-H Sylk Wall Module with
Temperature & Humidity
Sensors
3 Only
TR40-CO2 Sylk Wall Module with
Temperature & CO2
Sensors
3 Only
TR40-H-CO2 Sylk Wall Module with
Temperature, Humidity
& CO2 Sensors
3 Only
C7400S1000 Sylk Enthalpy Sensor 8, 9
50028399-0001 Wall Plate N/A

Other manuals for LCBS Connect

2

Other Honeywell Control Unit manuals

Honeywell EXCEL 5000 OPEN T7460A User manual

Honeywell

Honeywell EXCEL 5000 OPEN T7460A User manual

Honeywell Compact Corona Series Operation manual

Honeywell

Honeywell Compact Corona Series Operation manual

Honeywell NetAXS-123 User manual

Honeywell

Honeywell NetAXS-123 User manual

Honeywell Braukmann FD300 User manual

Honeywell

Honeywell Braukmann FD300 User manual

Honeywell L5000-Wi-Fi User manual

Honeywell

Honeywell L5000-Wi-Fi User manual

Honeywell 7800 SERIES User manual

Honeywell

Honeywell 7800 SERIES User manual

Honeywell Braukmann DH300 User manual

Honeywell

Honeywell Braukmann DH300 User manual

Honeywell satronic DMG 971 Instructions for use

Honeywell

Honeywell satronic DMG 971 Instructions for use

Honeywell Braukmann T100A Operation manual

Honeywell

Honeywell Braukmann T100A Operation manual

Honeywell VP513A User manual

Honeywell

Honeywell VP513A User manual

Honeywell DR 300 User manual

Honeywell

Honeywell DR 300 User manual

Honeywell VQ400M Series User manual

Honeywell

Honeywell VQ400M Series User manual

Honeywell DirectLine DL423 User manual

Honeywell

Honeywell DirectLine DL423 User manual

Honeywell Resideo ADEMCO 4101SN V-Plex Assembly instructions

Honeywell

Honeywell Resideo ADEMCO 4101SN V-Plex Assembly instructions

Honeywell D05FT User manual

Honeywell

Honeywell D05FT User manual

Honeywell FV300 Technical specifications

Honeywell

Honeywell FV300 Technical specifications

Honeywell NETAXS NX4L1 User manual

Honeywell

Honeywell NETAXS NX4L1 User manual

Honeywell DirectConnect AMX300 User manual

Honeywell

Honeywell DirectConnect AMX300 User manual

Honeywell V4730C User manual

Honeywell

Honeywell V4730C User manual

Honeywell D06F User manual

Honeywell

Honeywell D06F User manual

Honeywell Silent knight 5895XL Operating instructions

Honeywell

Honeywell Silent knight 5895XL Operating instructions

Honeywell NOTIFIER FW-MM User manual

Honeywell

Honeywell NOTIFIER FW-MM User manual

Honeywell 5800WAVE - Ademco Wireless Siren Assembly instructions

Honeywell

Honeywell 5800WAVE - Ademco Wireless Siren Assembly instructions

Honeywell Pro-Watch 6000 User manual

Honeywell

Honeywell Pro-Watch 6000 User manual

Popular Control Unit manuals by other brands

Continental Refrigerator TCAM1NA2 user manual

Continental Refrigerator

Continental Refrigerator TCAM1NA2 user manual

HYDAC International CSM 1000 Series Operating and Maintenance Instrutions

HYDAC International

HYDAC International CSM 1000 Series Operating and Maintenance Instrutions

Keysight Technologies 8495D Operating and service manual

Keysight Technologies

Keysight Technologies 8495D Operating and service manual

Digi XBee3 DigiMesh 2.4 user guide

Digi

Digi XBee3 DigiMesh 2.4 user guide

Samson 9255000053 instruction manual

Samson

Samson 9255000053 instruction manual

Val-Matic 801SSBW Operation, maintenance and installation manual

Val-Matic

Val-Matic 801SSBW Operation, maintenance and installation manual

Burkert 6650 operating instructions

Burkert

Burkert 6650 operating instructions

Kalia 104274 installation instructions

Kalia

Kalia 104274 installation instructions

Viessmann VITOTRANS 353 Installation and service instructions

Viessmann

Viessmann VITOTRANS 353 Installation and service instructions

Monacor PA-1200C Installation and operating instructions

Monacor

Monacor PA-1200C Installation and operating instructions

GE Current Evolve installation guide

GE

GE Current Evolve installation guide

Baker Hughes Masoneilan 35002 Series Camflex II instruction manual

Baker Hughes

Baker Hughes Masoneilan 35002 Series Camflex II instruction manual

RHEONICS DVM-HPHT operating instructions

RHEONICS

RHEONICS DVM-HPHT operating instructions

zeeltronic VCDI-30 user manual

zeeltronic

zeeltronic VCDI-30 user manual

Joy-it StromPi 3 Firmware manual

Joy-it

Joy-it StromPi 3 Firmware manual

Eaton OPTC4 LonWorks user manual

Eaton

Eaton OPTC4 LonWorks user manual

GE MM200 instruction manual

GE

GE MM200 instruction manual

Keba D3-DA 3 Series Project engineering manual

Keba

Keba D3-DA 3 Series Project engineering manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.