HONEYWELL
EN1B-0031UK07 R0604
191180 / 191238
STEP CONTROLLER 24V & 240V
INSTALLATION / USER GUIDE
COMBINED STEP CONTROLLER INSTALLATION / USER GUIDE
2
PRODUCT PART NUMBER
24V Combined Step Controller 191238-ZCS
FEATURES
•Provides 8 volts-free normally-open relay contacts for
simple step control of up to 8 fans or compressor
stages
•Sequential or cyclic switching sequence
•Easily set switching delays
•Six-minute interval between successive starts of any
compressor stage
•Built-in exercise routines for fault-finding
ZCS
ON
12
3
Bit Switches
Relay
1Relay
8
Relay
7
Relay
2
Relay
6
Relay
3
Relay
4Relay
5
Down Timer
P1
common
Down
Up
N/O
N/C
N/O
N/C
N/O
N/C
N/O
N/C
Fan / Comp. 1
Fan / Comp. 2
Fan / Comp. 3
Fan / Comp. 4 Fan / Comp. 5
N/C
N/O
N/C
N/O
N/C
N/O
N/C
N/O
Fan / Comp. 6
Fan / Comp. 7
Fan / Comp. 8
24Vac Supply to
the board
Pressure
Switch LED
LED
C
C
C
CC
C
C
C
Up Timer
P2
Clockwise = Max.
LED 1 = Power
LED 2 = Up Input Present
LED 3 = Down Input Present
123456
Anti-clockwise = Min.
Potentiometer adjustment:
COMMISSIONING
1. Check all electrical connections (Fig. 2)
2. Make sure that the controller software is ZCS
3. Set the Bit Switches (Fig. 1)
4. Switch the controller ON
5. If you choose normal mode:
The first relay is switched on when there is a demand
increase (pressure switch UP), and will be the last to
be switched off when demand decreases (pressure
switch DOWN)
If you choose cycle mode:
The first relay is switched on when there is a demand
increase (pressure switch UP), and will be the first to
be switched off when demand decreases (pressure
switch DOWN)
6. Set the two potentiometers to put a minimum time limit
(i.e. full anti-clockwise), between steps going up and
going down.
-In Fan mode, pot range = 0 to 180 seconds
-In Compressor mode, pot range 20 to 180 seconds
Note: In Compressor mode, same relay cannot
activate twice in six minutes.
7. Faults ?…See ‘Fault Finding’
FAULT FINDING
To exercise the step controller:
•Switch OFF power to the controller
•Set Bit Switches 1 to 5 OFF
•Set Bit Switch 6 ON – for test mode
•Switch ON power to the controller – Power LED 1
illuminates
•By setting up the combinations of bit switch positions,
shown in the table you can energise each relay
•Switch OFF power to the controller
•If you are not going to check the timers, switch all Bit
Switches OFF now
TO CHECK THE TIMERS
Make sure Bit Switch 6 is ON
•Switch OFF power to the controller
•Switch ON power to the controller – Power LED
illuminates
•Turn Timer 1 (DOWN potentiometer) slowly until Relay
LEDs 1, 2, 3 and 4 illuminate. This should occur
around the centre of the pot range.
Return the pot to the 20 seconds setting. Relay LEDs
1, 2, 3 and 4 will extinguish.
•Turn Timer 2 (UP potentiometer) slowly until Relay
LEDs 5, 6, 7 and 8 illuminate. This should occur
around the centre of the pot range.
Return the pot to the 20 seconds setting. Relay LEDs
5, 6, 7 and 8 will extinguish.
•Switch OFF power to the controller
•After the test, remember to switch Bit Switch 6 OFF to
return to normal operation.
Bit Switch Settings (Fig.1) (Shaded area = Switch position)
Off On
Select maximum
number of steps 1 See table Below
2
3
Normal mode 4 Cycle mode
Compressor mode 5 Fans mode
Normal Operation 6 Test mode
Maximum number
of steps Bit switch 1 Bit switch 2 Bit switch 3
1 OFF OFF OFF
2 ON OFF OFF
3 OFF ON OFF
4 ON ON OFF
5 OFF OFF ON
6 ON OFF ON
7 OFF ON ON
8 ON ON ON
Bit Switch Relay /
LED ON
1 2 3 4 5 6
ON OFF OFF OFF OFF ON 1
ON ON OFF OFF OFF ON 2
ON ON ON OFF OFF ON 3
ON ON ON ON OFF ON 4
ON ON ON ON ON ON 5
OFF ON ON ON ON ON 6
OFF OFF ON ON ON ON 7
OFF OFF OFF ON ON ON 8
OFF OFF OFF OFF ON ON ALL
OFF OFF OFF OFF OFF ON NONE
COMBINED STEP CONTROLLER INSTALLATION / USER GUIDE
PRODUCT PART NUMBER
240V Combined Step Controller 191180-ZCS
FEATURES
•Provides 8 volts-free normally-open relay contacts for
simple step control of up to 8 fans or compressor
stages
•Sequential or cyclic switching sequence
•Easily set switching delays
•Six-minute interval between successive starts of any
compressor stage
•Built-in exercise routines for fault-finding
COMMISSIONING
1. Check all electrical connections (Fig. 2)
2. Make sure that the controller software is ZCS
3. Set the Bit Switches (Fig. 1)
4. Switch the controller ON
5. If you choose normal mode:
The first relay is switched on when there is a demand
increase (pressure switch UP), and will be the last to
be switched off when demand decreases (pressure
switch DOWN)
If you choose cycle mode:
The first relay is switched on when there is a demand
increase (pressure switch UP), and will be the first to
be switched off when demand decreases (pressure
switch DOWN)
6. Set the two potentiometers to put a minimum time limit
(i.e. full anti-clockwise), between steps going up and
going down.
- In Fan mode, pot range = 0 to 180 seconds
- In Compressor mode, pot range 20 to 180 seconds
Note: In Compressor mode, same relay cannot
activate twice in six minutes.
7. Faults ?…See ‘Fault Finding’
FAULT FINDING
To exercise the step controller:
•Switch OFF power to the controller
•Set Bit Switches 1 to 5 OFF
•Set Bit Switch 6 ON – for test mode
•Switch ON power to the controller – Power LED 1
illuminates
•By setting up the combinations of bit switch positions,
shown in the table you can energise each relay
•Switch OFF power to the controller
•If you are not going to check the timers, switch all Bit
Switches OFF now
TO CHECK THE TIMERS
Make sure Bit Switch 6 is ON
•Switch OFF power to the controller
•Switch ON power to the controller – Power LED
illuminates
•Turn Timer 1 (DOWN potentiometer) slowly until Relay
LEDs 1, 2, 3 and 4 illuminate. This should occur
around the centre of the pot range.
Return the pot to the 20 seconds setting. Relay LEDs
1, 2, 3 and 4 will extinguish.
•Turn Timer 2 (UP potentiometer) slowly until Relay
LEDs 5, 6, 7 and 8 illuminate. This should occur
around the centre of the pot range.
Return the pot to the 20 seconds setting. Relay LEDs
5, 6, 7 and 8 will extinguish.
•Switch OFF power to the controller
•After the test, remember to switch Bit Switch 6 OFF to
return to normal operation.
Bit Switch Settings (Fig.1) (Shaded area = Switch position)
Off On
Select maximum
number of steps 1 See table Below
2
3
Normal mode 4 Cycle mode
Compressor mode 5 Fans mode
Normal Operation 6 Test mode
Maximum number
of steps Bit switch 1 Bit switch 2 Bit switch 3
1 OFF OFF OFF
2 ON OFF OFF
3 OFF ON OFF
4 ON ON OFF
5 OFF OFF ON
6 ON OFF ON
7 OFF ON ON
8 ON ON ON Bit Switch Relay /
LED ON
1 2 3 4 5 6
ON OFF OFF OFF OFF ON 1
ON ON OFF OFF OFF ON 2
ON ON ON OFF OFF ON 3
ON ON ON ON OFF ON 4
ON ON ON ON ON ON 5
OFF ON ON ON ON ON 6
OFF OFF ON ON ON ON 7
OFF OFF OFF ON ON ON 8
OFF OFF OFF OFF ON ON ALL
OFF OFF OFF OFF OFF ON NONE
COMBINED STEP CONTROLLER INSTALLATION / USER GUIDE
Automation & Control Solutions
Cooling & Refrigeration
Newhouse Industrial Estate
Motherwell
Lanarkshire ML1 5SB
Phone: (44) 01698 481698
Fax: (44) 01698 481699
www.honeywell.com/cooling
Subject to change without notice. Printed in United Kingdom
EN1B-0031UK07 R0604
SPECIFICATION
24V 240V
Product Type Combined Step Controller for small to medium
refrigeration applications Combined Step Controller for small to medium
refrigeration applications
Power Supply 24VAC 198-264VAC, 50Hz, 4VA
Relay Contacts SPNO volts-free 240VAC, 10A resistive, 2A
deductive SPNO volts-free 24VAC, 5A resistive, 2A
deductive
Input External volts-free SPCO, common earth External volts-free SPCO, common earth
Step Interval Adjustable:
Fans – 0 to 3 seconds
Compressors – 20 seconds to 3 minutes
Adjustable:
Fans – 0 to 3 seconds
Compressors – 20 seconds to 3 minutes
Dimensions 112 mm x 93 mm x 30 mm 200 mm x 73 mm x 43 mm
Fixing Four 4 mm holes @ 102 x 83 or DIN rail mounting Four 4 mm holes @ 190 x 60
Reset Controller resets (all output contacts open) when
power is interrupted Controller resets (all output contacts open) when
power is interrupted
ASSOCIATED DOCUMENTS
EN0B-0022UK07 R0604 Combined Step Controller Datasheet
APPLICATIONS
•Industrial or commercial refrigeration packs and condensers.
ORDERING INFORMATION
191238-ZCS Combined Step Controller 24V
191180-ZCS Combined Step Controller 240V

This manual suits for next models

1

Other Honeywell Controllers manuals

Honeywell T775A/B/M 2000 Series User manual

Honeywell

Honeywell T775A/B/M 2000 Series User manual

Honeywell HR 80 User manual

Honeywell

Honeywell HR 80 User manual

Honeywell Experion C300 User manual

Honeywell

Honeywell Experion C300 User manual

Honeywell AQUASTAT L4188A User manual

Honeywell

Honeywell AQUASTAT L4188A User manual

Honeywell UDC1200 MICRO-PRO User guide

Honeywell

Honeywell UDC1200 MICRO-PRO User guide

Honeywell Evohome User manual

Honeywell

Honeywell Evohome User manual

Honeywell ControLinks R7999C User manual

Honeywell

Honeywell ControLinks R7999C User manual

Honeywell M7410A Operation manual

Honeywell

Honeywell M7410A Operation manual

Honeywell ML6275 Operation manual

Honeywell

Honeywell ML6275 Operation manual

Honeywell dcp100t User manual

Honeywell

Honeywell dcp100t User manual

Honeywell ML6161E User manual

Honeywell

Honeywell ML6161E User manual

Honeywell M7061 User manual

Honeywell

Honeywell M7061 User manual

Honeywell HVC0001 User manual

Honeywell

Honeywell HVC0001 User manual

Honeywell HC900 Use and care manual

Honeywell

Honeywell HC900 Use and care manual

Honeywell M847D User manual

Honeywell

Honeywell M847D User manual

Honeywell N20010 User manual

Honeywell

Honeywell N20010 User manual

Honeywell Spyder PUL1012S User manual

Honeywell

Honeywell Spyder PUL1012S User manual

Honeywell B User manual

Honeywell

Honeywell B User manual

Honeywell HR 10 F User manual

Honeywell

Honeywell HR 10 F User manual

Honeywell Spyder BACnet PUB1012S User manual

Honeywell

Honeywell Spyder BACnet PUB1012S User manual

Honeywell HON 380 Instruction Manual

Honeywell

Honeywell HON 380 Instruction Manual

Honeywell ControLinks R7999A User manual

Honeywell

Honeywell ControLinks R7999A User manual

Honeywell INCOMM L510 User manual

Honeywell

Honeywell INCOMM L510 User manual

Honeywell WEB-600E User manual

Honeywell

Honeywell WEB-600E User manual

Popular Controllers manuals by other brands

Canon RC-IP100 user manual

Canon

Canon RC-IP100 user manual

Legato GSMS-THR Setup Software guide

Legato

Legato GSMS-THR Setup Software guide

Hach SC4500 User instructions

Hach

Hach SC4500 User instructions

SATA Air regulator belt operating instructions

SATA

SATA Air regulator belt operating instructions

V2 AYROS-24V series manual

V2

V2 AYROS-24V series manual

Seafloor HydroCat-180 TARANIS X7 Start-up

Seafloor

Seafloor HydroCat-180 TARANIS X7 Start-up

Steren REG-1000PRO instruction manual

Steren

Steren REG-1000PRO instruction manual

Luxul XWC-1000 Quick install guide

Luxul

Luxul XWC-1000 Quick install guide

Hitachi H20-T Technical notes

Hitachi

Hitachi H20-T Technical notes

Omron E5CC-U instruction manual

Omron

Omron E5CC-U instruction manual

Mallory 4305M installation instructions

Mallory

Mallory 4305M installation instructions

Genie 36448 A quick start guide

Genie

Genie 36448 A quick start guide

EASTHOUSE EM-1701A-C10 operating instructions

EASTHOUSE

EASTHOUSE EM-1701A-C10 operating instructions

Allen-Bradley CompactLogix 1769-L20 installation instructions

Allen-Bradley

Allen-Bradley CompactLogix 1769-L20 installation instructions

TECSYSTEM T154-4 Setup and Programming

TECSYSTEM

TECSYSTEM T154-4 Setup and Programming

Light Emotion DMX36 User instruction manual

Light Emotion

Light Emotion DMX36 User instruction manual

Fairchild 10BP Installation, operation and maintenance instructions

Fairchild

Fairchild 10BP Installation, operation and maintenance instructions

Sunlight Supply TITAN CONTROLS KRONUS 2 instruction manual

Sunlight Supply

Sunlight Supply TITAN CONTROLS KRONUS 2 instruction manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.