manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Controllers
  8. •
  9. Honeywell 191238-ZCS Operation manual

Honeywell 191238-ZCS Operation manual

This manual suits for next models

1

Other Honeywell Controllers manuals

Honeywell Centra Line EAGLE Installation and operation manual

Honeywell

Honeywell Centra Line EAGLE Installation and operation manual

Honeywell 190887-EET User manual

Honeywell

Honeywell 190887-EET User manual

Honeywell NOTIFIER NFXI-RM6 User manual

Honeywell

Honeywell NOTIFIER NFXI-RM6 User manual

Honeywell UDC2500 User manual

Honeywell

Honeywell UDC2500 User manual

Honeywell T775 Series 2000 User guide

Honeywell

Honeywell T775 Series 2000 User guide

Honeywell ML6420A3072 User manual

Honeywell

Honeywell ML6420A3072 User manual

Honeywell 1000 Series User manual

Honeywell

Honeywell 1000 Series User manual

Honeywell ICON 100 SERIES User manual

Honeywell

Honeywell ICON 100 SERIES User manual

Honeywell 7800 SERIES RM7895A User manual

Honeywell

Honeywell 7800 SERIES RM7895A User manual

Honeywell UMC800 User manual

Honeywell

Honeywell UMC800 User manual

Honeywell UDC2000 User manual

Honeywell

Honeywell UDC2000 User manual

Honeywell C User manual

Honeywell

Honeywell C User manual

Honeywell CD3200 User manual

Honeywell

Honeywell CD3200 User manual

Honeywell S9201A1010 User manual

Honeywell

Honeywell S9201A1010 User manual

Honeywell Z74S-AN User manual

Honeywell

Honeywell Z74S-AN User manual

Honeywell HC900 User manual

Honeywell

Honeywell HC900 User manual

Honeywell Aquastat L7224U User manual

Honeywell

Honeywell Aquastat L7224U User manual

Honeywell ML6131 Operation manual

Honeywell

Honeywell ML6131 Operation manual

Honeywell VR8104 User manual

Honeywell

Honeywell VR8104 User manual

Honeywell Scan Dome ll HTX-2500 Owner's manual

Honeywell

Honeywell Scan Dome ll HTX-2500 Owner's manual

Honeywell SUPER TRADELINE S8610U User manual

Honeywell

Honeywell SUPER TRADELINE S8610U User manual

Honeywell Pressuretrol L404 Series User manual

Honeywell

Honeywell Pressuretrol L404 Series User manual

Honeywell 7800 SERIES User manual

Honeywell

Honeywell 7800 SERIES User manual

Honeywell ML6425B User manual

Honeywell

Honeywell ML6425B User manual

Popular Controllers manuals by other brands

Sunricher SR-ZV9003T3-RGBW-US Installation

Sunricher

Sunricher SR-ZV9003T3-RGBW-US Installation

Ksenia intro Installation and configuration manual

Ksenia

Ksenia intro Installation and configuration manual

Inovance CAN200 Series manual

Inovance

Inovance CAN200 Series manual

Gauzy LC6 FLEX Controller Installation and operation guide

Gauzy

Gauzy LC6 FLEX Controller Installation and operation guide

Viking SLP-1 Technical practice

Viking

Viking SLP-1 Technical practice

CKD KBX-30E-U Series instruction manual

CKD

CKD KBX-30E-U Series instruction manual

Sharp Energy Sun Flux User manual & installation guide

Sharp Energy

Sharp Energy Sun Flux User manual & installation guide

Yamaha RCX40 user manual

Yamaha

Yamaha RCX40 user manual

AB Quality PowerFlex 400 Frames D-H Service bulletin

AB Quality

AB Quality PowerFlex 400 Frames D-H Service bulletin

Yamaha MJC8 owner's manual

Yamaha

Yamaha MJC8 owner's manual

AL-KO ATC operating instructions

AL-KO

AL-KO ATC operating instructions

Savant SmartControl 2 Deployment guide

Savant

Savant SmartControl 2 Deployment guide

GameSir T3S user manual

GameSir

GameSir T3S user manual

Kostal inveor operating manual

Kostal

Kostal inveor operating manual

Emerson Yarway 20-55 Operating and safety instructions

Emerson

Emerson Yarway 20-55 Operating and safety instructions

CoCo ACM-LV24 Quick installation guide

CoCo

CoCo ACM-LV24 Quick installation guide

Brooks SLA5810/20 Installation and operation manual

Brooks

Brooks SLA5810/20 Installation and operation manual

SIGMA TEK SR 011 Technical manual

SIGMA TEK

SIGMA TEK SR 011 Technical manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

HONEYWELL
EN1B-0031UK07 R0604
191180 / 191238
STEP CONTROLLER 24V & 240V
INSTALLATION / USER GUIDE
COMBINED STEP CONTROLLER INSTALLATION / USER GUIDE
2
PRODUCT PART NUMBER
24V Combined Step Controller 191238-ZCS
FEATURES
•Provides 8 volts-free normally-open relay contacts for
simple step control of up to 8 fans or compressor
stages
•Sequential or cyclic switching sequence
•Easily set switching delays
•Six-minute interval between successive starts of any
compressor stage
•Built-in exercise routines for fault-finding
ZCS
ON
12
3
Bit Switches
Relay
1Relay
8
Relay
7
Relay
2
Relay
6
Relay
3
Relay
4Relay
5
Down Timer
P1
common
Down
Up
N/O
N/C
N/O
N/C
N/O
N/C
N/O
N/C
Fan / Comp. 1
Fan / Comp. 2
Fan / Comp. 3
Fan / Comp. 4 Fan / Comp. 5
N/C
N/O
N/C
N/O
N/C
N/O
N/C
N/O
Fan / Comp. 6
Fan / Comp. 7
Fan / Comp. 8
24Vac Supply to
the board
Pressure
Switch LED
LED
C
C
C
CC
C
C
C
Up Timer
P2
Clockwise = Max.
LED 1 = Power
LED 2 = Up Input Present
LED 3 = Down Input Present
123456
Anti-clockwise = Min.
Potentiometer adjustment:
COMMISSIONING
1. Check all electrical connections (Fig. 2)
2. Make sure that the controller software is ZCS
3. Set the Bit Switches (Fig. 1)
4. Switch the controller ON
5. If you choose normal mode:
The first relay is switched on when there is a demand
increase (pressure switch UP), and will be the last to
be switched off when demand decreases (pressure
switch DOWN)
If you choose cycle mode:
The first relay is switched on when there is a demand
increase (pressure switch UP), and will be the first to
be switched off when demand decreases (pressure
switch DOWN)
6. Set the two potentiometers to put a minimum time limit
(i.e. full anti-clockwise), between steps going up and
going down.
-In Fan mode, pot range = 0 to 180 seconds
-In Compressor mode, pot range 20 to 180 seconds
Note: In Compressor mode, same relay cannot
activate twice in six minutes.
7. Faults ?…See ‘Fault Finding’
FAULT FINDING
To exercise the step controller:
•Switch OFF power to the controller
•Set Bit Switches 1 to 5 OFF
•Set Bit Switch 6 ON – for test mode
•Switch ON power to the controller – Power LED 1
illuminates
•By setting up the combinations of bit switch positions,
shown in the table you can energise each relay
•Switch OFF power to the controller
•If you are not going to check the timers, switch all Bit
Switches OFF now
TO CHECK THE TIMERS
Make sure Bit Switch 6 is ON
•Switch OFF power to the controller
•Switch ON power to the controller – Power LED
illuminates
•Turn Timer 1 (DOWN potentiometer) slowly until Relay
LEDs 1, 2, 3 and 4 illuminate. This should occur
around the centre of the pot range.
Return the pot to the 20 seconds setting. Relay LEDs
1, 2, 3 and 4 will extinguish.
•Turn Timer 2 (UP potentiometer) slowly until Relay
LEDs 5, 6, 7 and 8 illuminate. This should occur
around the centre of the pot range.
Return the pot to the 20 seconds setting. Relay LEDs
5, 6, 7 and 8 will extinguish.
•Switch OFF power to the controller
•After the test, remember to switch Bit Switch 6 OFF to
return to normal operation.
Bit Switch Settings (Fig.1) (Shaded area = Switch position)
Off On
Select maximum
number of steps 1 See table Below
2
3
Normal mode 4 Cycle mode
Compressor mode 5 Fans mode
Normal Operation 6 Test mode
Maximum number
of steps Bit switch 1 Bit switch 2 Bit switch 3
1 OFF OFF OFF
2 ON OFF OFF
3 OFF ON OFF
4 ON ON OFF
5 OFF OFF ON
6 ON OFF ON
7 OFF ON ON
8 ON ON ON
Bit Switch Relay /
LED ON
1 2 3 4 5 6
ON OFF OFF OFF OFF ON 1
ON ON OFF OFF OFF ON 2
ON ON ON OFF OFF ON 3
ON ON ON ON OFF ON 4
ON ON ON ON ON ON 5
OFF ON ON ON ON ON 6
OFF OFF ON ON ON ON 7
OFF OFF OFF ON ON ON 8
OFF OFF OFF OFF ON ON ALL
OFF OFF OFF OFF OFF ON NONE
COMBINED STEP CONTROLLER INSTALLATION / USER GUIDE
PRODUCT PART NUMBER
240V Combined Step Controller 191180-ZCS
FEATURES
•Provides 8 volts-free normally-open relay contacts for
simple step control of up to 8 fans or compressor
stages
•Sequential or cyclic switching sequence
•Easily set switching delays
•Six-minute interval between successive starts of any
compressor stage
•Built-in exercise routines for fault-finding
COMMISSIONING
1. Check all electrical connections (Fig. 2)
2. Make sure that the controller software is ZCS
3. Set the Bit Switches (Fig. 1)
4. Switch the controller ON
5. If you choose normal mode:
The first relay is switched on when there is a demand
increase (pressure switch UP), and will be the last to
be switched off when demand decreases (pressure
switch DOWN)
If you choose cycle mode:
The first relay is switched on when there is a demand
increase (pressure switch UP), and will be the first to
be switched off when demand decreases (pressure
switch DOWN)
6. Set the two potentiometers to put a minimum time limit
(i.e. full anti-clockwise), between steps going up and
going down.
- In Fan mode, pot range = 0 to 180 seconds
- In Compressor mode, pot range 20 to 180 seconds
Note: In Compressor mode, same relay cannot
activate twice in six minutes.
7. Faults ?…See ‘Fault Finding’
FAULT FINDING
To exercise the step controller:
•Switch OFF power to the controller
•Set Bit Switches 1 to 5 OFF
•Set Bit Switch 6 ON – for test mode
•Switch ON power to the controller – Power LED 1
illuminates
•By setting up the combinations of bit switch positions,
shown in the table you can energise each relay
•Switch OFF power to the controller
•If you are not going to check the timers, switch all Bit
Switches OFF now
TO CHECK THE TIMERS
Make sure Bit Switch 6 is ON
•Switch OFF power to the controller
•Switch ON power to the controller – Power LED
illuminates
•Turn Timer 1 (DOWN potentiometer) slowly until Relay
LEDs 1, 2, 3 and 4 illuminate. This should occur
around the centre of the pot range.
Return the pot to the 20 seconds setting. Relay LEDs
1, 2, 3 and 4 will extinguish.
•Turn Timer 2 (UP potentiometer) slowly until Relay
LEDs 5, 6, 7 and 8 illuminate. This should occur
around the centre of the pot range.
Return the pot to the 20 seconds setting. Relay LEDs
5, 6, 7 and 8 will extinguish.
•Switch OFF power to the controller
•After the test, remember to switch Bit Switch 6 OFF to
return to normal operation.
Bit Switch Settings (Fig.1) (Shaded area = Switch position)
Off On
Select maximum
number of steps 1 See table Below
2
3
Normal mode 4 Cycle mode
Compressor mode 5 Fans mode
Normal Operation 6 Test mode
Maximum number
of steps Bit switch 1 Bit switch 2 Bit switch 3
1 OFF OFF OFF
2 ON OFF OFF
3 OFF ON OFF
4 ON ON OFF
5 OFF OFF ON
6 ON OFF ON
7 OFF ON ON
8 ON ON ON Bit Switch Relay /
LED ON
1 2 3 4 5 6
ON OFF OFF OFF OFF ON 1
ON ON OFF OFF OFF ON 2
ON ON ON OFF OFF ON 3
ON ON ON ON OFF ON 4
ON ON ON ON ON ON 5
OFF ON ON ON ON ON 6
OFF OFF ON ON ON ON 7
OFF OFF OFF ON ON ON 8
OFF OFF OFF OFF ON ON ALL
OFF OFF OFF OFF OFF ON NONE
COMBINED STEP CONTROLLER INSTALLATION / USER GUIDE
Automation & Control Solutions
Cooling & Refrigeration
Newhouse Industrial Estate
Motherwell
Lanarkshire ML1 5SB
Phone: (44) 01698 481698
Fax: (44) 01698 481699
www.honeywell.com/cooling
Subject to change without notice. Printed in United Kingdom
EN1B-0031UK07 R0604
SPECIFICATION
24V 240V
Product Type Combined Step Controller for small to medium
refrigeration applications Combined Step Controller for small to medium
refrigeration applications
Power Supply 24VAC 198-264VAC, 50Hz, 4VA
Relay Contacts SPNO volts-free 240VAC, 10A resistive, 2A
deductive SPNO volts-free 24VAC, 5A resistive, 2A
deductive
Input External volts-free SPCO, common earth External volts-free SPCO, common earth
Step Interval Adjustable:
Fans – 0 to 3 seconds
Compressors – 20 seconds to 3 minutes
Adjustable:
Fans – 0 to 3 seconds
Compressors – 20 seconds to 3 minutes
Dimensions 112 mm x 93 mm x 30 mm 200 mm x 73 mm x 43 mm
Fixing Four 4 mm holes @ 102 x 83 or DIN rail mounting Four 4 mm holes @ 190 x 60
Reset Controller resets (all output contacts open) when
power is interrupted Controller resets (all output contacts open) when
power is interrupted
ASSOCIATED DOCUMENTS
EN0B-0022UK07 R0604 Combined Step Controller Datasheet
APPLICATIONS
•Industrial or commercial refrigeration packs and condensers.
ORDERING INFORMATION
191238-ZCS Combined Step Controller 24V
191180-ZCS Combined Step Controller 240V