manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Controllers
  8. •
  9. Honeywell T775A User manual

Honeywell T775A User manual

Other manuals for T775A

3

This manual suits for next models

2

Other Honeywell Controllers manuals

Honeywell ML200 Series User manual

Honeywell

Honeywell ML200 Series User manual

Honeywell V4055A Operation manual

Honeywell

Honeywell V4055A Operation manual

Honeywell DB7110U1000 User manual

Honeywell

Honeywell DB7110U1000 User manual

Honeywell UDC120L User manual

Honeywell

Honeywell UDC120L User manual

Honeywell Air Alert 96d User manual

Honeywell

Honeywell Air Alert 96d User manual

Honeywell T775R 2000 Series User manual

Honeywell

Honeywell T775R 2000 Series User manual

Honeywell UDC3500 User manual

Honeywell

Honeywell UDC3500 User manual

Honeywell Touchpoint Plus User manual

Honeywell

Honeywell Touchpoint Plus User manual

Honeywell TUXWIFIS User manual

Honeywell

Honeywell TUXWIFIS User manual

Honeywell 191238-ZCS Operation manual

Honeywell

Honeywell 191238-ZCS Operation manual

Honeywell KromSchroder IC 40 Manual

Honeywell

Honeywell KromSchroder IC 40 Manual

Honeywell CentraLine EAGLEHAWK NX User manual

Honeywell

Honeywell CentraLine EAGLEHAWK NX User manual

Honeywell SUPER TRADELINE S8610U User manual

Honeywell

Honeywell SUPER TRADELINE S8610U User manual

Honeywell Ex-Or MSM2000D Installation and operation manual

Honeywell

Honeywell Ex-Or MSM2000D Installation and operation manual

Honeywell MN7220 Operation manual

Honeywell

Honeywell MN7220 Operation manual

Honeywell Pressuretrol L404 Series User manual

Honeywell

Honeywell Pressuretrol L404 Series User manual

Honeywell L7124U User manual

Honeywell

Honeywell L7124U User manual

Honeywell Fire Sentry FS7-130-SX User manual

Honeywell

Honeywell Fire Sentry FS7-130-SX User manual

Honeywell V4055F Operation manual

Honeywell

Honeywell V4055F Operation manual

Honeywell AQUASTAT L4188A User manual

Honeywell

Honeywell AQUASTAT L4188A User manual

Honeywell Vista Automation Module User manual

Honeywell

Honeywell Vista Automation Module User manual

Honeywell M6410A User manual

Honeywell

Honeywell M6410A User manual

Honeywell SP10K User manual

Honeywell

Honeywell SP10K User manual

Honeywell BACnet User manual

Honeywell

Honeywell BACnet User manual

Popular Controllers manuals by other brands

Sunricher SR-ZV9003T3-RGBW-US Installation

Sunricher

Sunricher SR-ZV9003T3-RGBW-US Installation

Ksenia intro Installation and configuration manual

Ksenia

Ksenia intro Installation and configuration manual

Inovance CAN200 Series manual

Inovance

Inovance CAN200 Series manual

Gauzy LC6 FLEX Controller Installation and operation guide

Gauzy

Gauzy LC6 FLEX Controller Installation and operation guide

Viking SLP-1 Technical practice

Viking

Viking SLP-1 Technical practice

CKD KBX-30E-U Series instruction manual

CKD

CKD KBX-30E-U Series instruction manual

Sharp Energy Sun Flux User manual & installation guide

Sharp Energy

Sharp Energy Sun Flux User manual & installation guide

Yamaha RCX40 user manual

Yamaha

Yamaha RCX40 user manual

AB Quality PowerFlex 400 Frames D-H Service bulletin

AB Quality

AB Quality PowerFlex 400 Frames D-H Service bulletin

Yamaha MJC8 owner's manual

Yamaha

Yamaha MJC8 owner's manual

AL-KO ATC operating instructions

AL-KO

AL-KO ATC operating instructions

Savant SmartControl 2 Deployment guide

Savant

Savant SmartControl 2 Deployment guide

GameSir T3S user manual

GameSir

GameSir T3S user manual

Kostal inveor operating manual

Kostal

Kostal inveor operating manual

Emerson Yarway 20-55 Operating and safety instructions

Emerson

Emerson Yarway 20-55 Operating and safety instructions

CoCo ACM-LV24 Quick installation guide

CoCo

CoCo ACM-LV24 Quick installation guide

Brooks SLA5810/20 Installation and operation manual

Brooks

Brooks SLA5810/20 Installation and operation manual

SIGMA TEK SR 011 Technical manual

SIGMA TEK

SIGMA TEK SR 011 Technical manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

INSTALLATION INSTRUCTIONS
62-0254-13
T775A/B/M Series 2000
Electronic Stand-Alone
Controllers
PRODUCT DESCRIPTION
The T775 electronic stand-alone controllers are the next
generation of commercial and agricultural controls
capable of remote sensing of temperature and providing
switched and/or proportional outputs to various types of
loads.
Five models have analog (modulating) outputs for
actuator and motor control, and NEMA-4 weatherproof
enclosures are available for wet environments.
IMPORTANT
Each T775A/B/M controller is an operating
control, not a limit or safety control. If used in
applications requiring safety or limit controls, a
separate safety or limit control device is
required.
Table 1. T775A/B/M Controller Configurations.
Controller
Modela
aAll models include a digital input for use with the disable or setback option.
Description Replaces
SPDT
Relay
Outputs
Analog
(Mod)
Outputsb
bThe modulating (analog) outputs are 4-20 mA, 0-10 Vdc, 2-10 Vdc, or Series 90 selectable.
Floating
Outputsc
cEach floating output eliminates two SPDT relays.
Sensor
Inputs
Nbr of
Sensors
Included Enclosure
T775A2009 Standard T775A1001 1 None None 1 1 NEMA 1
T775B2016 Standard N/A 2 None 1 21 NEMA 4X
T775B2024 Standard T775C1009 T775D1008 4 None 2 2 1 NEMA 4X
T775B2032 Standard T775A1019 T775B1000 2 None 1 2 1 NEMA 1
T775B2040 Standard T775A1027 T775A1035
T775B1018 T775B1026
T775B1042
4None2 21 NEMA1
T775M2006 Modulating N/A None 2 N/A 2 1 NEMA 1
T775M2014 Modulating T775G1005 T775G1013
T775G1021 T775G1039
42 N/A
2d
dThese models can support a high/low modulating limit at Sensor B for temperature control at Sensor A.
1 NEMA 4X
T775M2022 Modulating N/A 2 2 N/A 2d1 NEMA 4X
T775M2030 Modulating T775E1114 T775F1022
T775F1055 T775F1089
42 N/A
2d1 NEMA 1
T775M2048 Modulating T775E1015 T775E1023
T775E1056 T775E1064
T775E1098
22 N/A
2d1 NEMA 1
This is a legacy product document
supported by Resideo. It is no
longer manufactured
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
62-0254—13 2
Temperature Sensorsa
The controller accepts 1,097 Ohms PTC at 77°F (25°C):
• 50021579-001 – Standard sensor (included with all
models except NEMA 4X models)
• T775-SENS-STRAP– Strap on sensor with wiring box
• T775-SENS-WR – Water resistant with 5 foot leads
(included with NEMA 4X models)
• T775-SENS-WT – Watertight with 6 foot lead
• T775-SENS-OAT – Outdoor air temperature sensor
• C7031B2005 – 6 inch duct mount with wiring box
• C7031D2003 – 5 inch immersion sensor with wiring
box (use immersion well; P/N 50001774-001)
• C7031J2009 – 12 foot duct averaging sensor with
wiring box
• C7046D1008 – 8 inch duct probe with mounting flange
• C7100D1001 – 12 inch fast response, duct averaging
sensor with flange
• C7130B1009 – Room mount sensor
Accessories
• 107324A – Bulb Holder, duct insertion
• 107408 – Heat Conductive Compound, 4 ounce
• 50001774-001 – Immersion Well, stainless steel 304,
1/2 in. threading.
Product Changes
Below are the changes to T775A/B/M models starting with
Series 3 (March 2009). Series 3 can be identified by the
sideways 3 after the part number on the device label.
1. Modulating high and low limit now both function in
either the heat or the cool mode.
2. MIN ON added.
3. SYNC added.
4. Differential and throttling range increased to 300°F.
5. Setpoint and Enable options added to the DI
options.
6. HIDE option added to MOD1 and MOD2 (to hide
them on the home screen).
Controller Dimensions
Fig. 1. T775A/B/M Dimensions in inches (mm).
aSee form 62-0265 - Temperature Sensors for the T775
Series 2000 Stand-alone Controller
4 13/32 (112.1) 1/2 (12.4)
3 31/32 (101)
7 23/32
(196)
8 5/32
(207.1)
2 15/16 (74)
7/8 (22.5)
1 (25.5)
4 1/16 (103.4)
4 1/16 (103.4)
1/64 (3.8)
2 11/16 (68.1)
7/8 (22.5)
2 13/16 (71.8)
7/8 (22.5)
1 (25.5)
7/8 (22.5)
M24279
TOP
BOTTOM
LEFT RIGHT
FRONT VIEW
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
362-0254—13
BEFORE INSTALLATION
Review the “SPECIFICATIONS” on page 35 before
installing the controller.
When Installing This Product
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a
hazardous condition.
2. Check ratings given in instructions and on the
product to ensure the product is suitable for your
application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
INSTALLATION AND SETUP
The following installation procedures are typically
performed in the order listed:
1. Mounting — See “MOUNTING” below.
2. Wiring — See “WIRING” on this page.
3. Checkout — See page 11.
4. Programming — See page 14.
5. Scheduling (optional) — See page 30.
Additional topics are:
• Temperature sensor calibration begins on page 11.
• Interface overview begins on page 12.
• Setup (for advanced options) begins on page 17.
• Summary menu begins on page 34.
• Troubleshooting begins on page 34.
MOUNTING
This section describes the mounting procedures for the
controller and temperature sensor(s).
Controller Mounting
IMPORTANT
Avoid mounting in areas where acid fumes or
other deteriorating vapors can attack the metal
parts of the controller circuit board, or in areas
where escaping gas or other explosive vapors
are present.
IMPORTANT
The controller must be mounted in a position that
allows clearance for wiring, servicing, and
removal.
Use a screwdriver to pry out only the knockouts that you
will use.
If mounting on DIN rail, be sure to remove the knockouts
before mounting. See “Controller Wiring” on page 5 and
Fig. 7 on page 6 for recommended knockout usage and
locations. If you do not use an opened knockout be sure
to cover it.
Mount the controller on any convenient interior location
using the four mounting holes provided on the back of the
enclosure using #6 or #8 screws (screws are not provided
and must be obtained separately). Use controller
dimensions in Fig. 1 on page 2 as a guide.
The controller may be mounted in any orientation.
However, mounting in the orientation shown in Fig. 1 on
page 2 permits proper viewing of the LCD display and use
of the keypad.
NEMA 4 Enclosure Mounting
For models with NEMA 4 enclosures, ensure that
waterproof wire/conduit fittings are used at the knockouts
for all wiring attachments. Refer to Fig. 7 on page 6 for
knockout locations.
IMPORTANT
For NEMA 4 enclosures, be sure to cover and
seal all unused open knockouts.
Temperature Sensor(s) Mounting
and Location
Temperature sensors may be located up to 1,000 feet
(304 m) from the T775A/B/M controller. Refer to Table 3
on page 11 for calibration guidelines.
The sensors may be mounted on a wall or panel for
sensing space temperature, strapped to a pipe or inserted
in an immersion well (see Fig. 2) for hot or cold water
sensing, or taped to a standard cap or bulb holder for duct
air sensing. To prevent moisture or condensation entering
the sensor through the lead wire holes, mount the sensor
with the lead wires exiting the bottom of the sensor.
NOTES:
1. The included sensor is not designed for very
wet applications. For immersion applications,
an immersion well is used.
2. Heat conductive compound must be used in
immersion wells.
3. Refer to the list of temperature sensors on
page 2 for this type of installation
.
Fig. 2. Sensor Inserted in Immersion Well.
NOTE: Multiple sensors may be parallel-series wired
to sense average temperatures in large
spaces. Refer to Fig. 3 on page 4.
WIRING
All wiring must comply with applicable electrical codes
and ordinances, or as specified on installation wiring
diagrams. Controller wiring is terminated to the screw
terminal blocks located inside the device.
The remainder of this section describes the temperature
sensor wiring and the T775A/B/M controller wiring.
SENSOR
PLACED
IN WELL
IMMERSION
WELL
1/2 NPT
USE HEAT
CONDUCTIVE
COMPOUND
M24470
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
62-0254—13 4
Wiring Connections Access
To access the wiring connections, remove the two screws
on the left side of the enclosure and gently swing open the
top. Be careful to not stress the ribbon cables that connect
the keypad and LCD display to the controller circuit board.
Temperature Sensor Wiring
CAUTION
Electrical Shock Hazard.
Can short equipment circuitry.
Make sure that metal tube of sensor does not
short against T terminals in wall-mounted case.
IMPORTANT
Poor wiring practices can cause erratic readings
from the sensor. Avoid the following to ensure
proper operation:
• Do not route the temperature sensor wiring with
building power wiring.
• Do not locate the temperature sensor wiring next
to control contactors.
• Do not locate the temperature sensor wiring near
electrical motors.
• Do not locate the temperature sensor wiring near
welding equipment.
• Make sure good mechanical connections are
made to both the sensor and the controller.
• Do not mount the sensor with the lead wire end
pointing up in an area where condensation can
occur.
If any of the above conditions cannot be avoided,
use shielded cable.
NOTE: Each T775 controller must be wired to its own
sensor(s). However, a benefit of the T775
controller’s accuracy is that there is no more
than a 2° F (-7° C) differential between any
two T775 controllers.
Multiple Parallel Sensors
Multiple sensors can be parallel-series wired to sense
average temperatures in large spaces. To maintain control
accuracy, the number of sensors to be parallel-series
wired must be of the n2power (for example, 4, 9, 16, etc.).
Refer to Fig. 3
.
Fig. 3. Parallel-Series Wiring of Sensors.
Temperature Sensor Wire Type and Size
Temperature sensors use standard AWG 18/2 unshielded
wire. For cable runs greater than 25 feet or where
electrical interference may be a problem, shielded cable is
recommended (See Fig. 4).
Refer to “Temperature Sensor Calibration” on page 11 for
wire size selection where cable runs are longer than 25
feet.
Fig. 4. Sensor Wiring — Showing Shielded Cable Connection to Sensor A.
TO T775 CONNECTIONS (SENSOR A) OR (SENSOR B).
SENSORS
M24471
M24472
SHIELDED
CABLE
SHIELDED
CABLE
SENSOR
SENSOR AAND SENSOR B TERMINAL WIRING IS POLARITY INSENSITIVE.
1
NOTE: SHIELDED CABLE MUST BE
CONNECTED TO AN EARTH
GROUND.
HOWEVER, DO NOT GROUND
SHIELDED CABLE AT SENSOR END.
NOTE: TO MINIMIZE NOISE PICKUP,
MAKE SENSOR CONNECTION FROM
SHIELDED CABLE AS CLOSE AS
POSSIBLE TO SENSOR BODY.
T
T
T
T
SENSOR A
SENSOR B
1
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
562-0254—13
Controller Wiring
WARNING
Electrical Shock Hazard.
Can cause severe injury, death or property
damage.
Disconnect power supply before beginning wiring,
or making wiring connections, to prevent electrical
shock or equipment damage.
CAUTION
Do not use 24 Vac power to power any external
loads if 120 Vac or 240 Vac is used to power
the T775A/B/M controller.
CAUTION
A separate earth ground is required.
Equipment damage can result if the earth ground
is not connected. See Fig. 5 and Table 2 on
page 6.
CAUTION
Equipment Damage Hazard.
Electrostatic discharge can short equipment
circuitry.
Ensure that you are properly grounded before
handling the unit
.
Fig. 5. Earth Ground.
IMPORTANT
Poor wiring practices can cause erratic readings
from the sensor. To ensure proper operation,
ensure that good mechanical connections are
made to both the sensor and the controller.
IMPORTANT
When wiring the input power, only one source of
power can be applied to the T775A/B/M
controller (24 Vac or 120 Vac or 240 Vac).
See Fig. 7 on page 6 for locating the appropriate power
input, remote sensors input, low voltage, contact closure,
and load output terminals.
Access to the terminals can be gained through standard
conduit knockouts (A through E in Fig. 7 on page 6)
located around the perimeter of the enclosure:
• Knockouts A and B should be used only for sensor and
low-voltage wiring.
• Knockouts C, D, and E can be used to gain access to
the load relay output terminals and 120/240 Vac power
wiring.
Controller Wiring Method
Wire the sensors and outputs, then wire the power
connection.
Each terminal can accommodate the following gauges of
wire:
• Single wire – from 14 AWG to 22 AWG solid or
stranded
• Multiple wires – up to two 22 AWG stranded
For 24, 120, or 240 Vac power connections:
• Single wire – from 14 to 18 AWG solid or stranded
Prepare wiring for the terminal blocks, as follows:
1. Strip 1/2 in. (13 mm) insulation from the conductor.
2. Cut a single wire to 3/16 in. (5 mm). Insert the wire
in the required terminal location and tighten the
screw.
3. If two or more wires are being inserted into one
terminal location, twist the wires together a
minimum of three turns before inserting them to
ensure proper electrical contact.
4. Cut the twisted end of the wires to 3/16 in. (5 mm)
before inserting them into the terminal and
tightening the screw.
5. Pull on each wire in all terminals to check for good
mechanical connection
.
Fig. 6. Attaching Two or More Wires at Terminal
Blocks.
C+
W
1
2
M24296
NO HIGH VOLTAGE. CLASS 2 WIRING ONLY.
EARTH GROUND TERMINAL MUST BE CONNECTED
TO CONDUIT CLAMP LOCALLY.
1
2
1/2 (13)
1. STRIP 1/2 IN. (13 MM)
FROM WIRES TO
BE ATTACHED AT
ONE TERMINAL.
2. TWIST WIRES
TOGETHER WITH
PLIERS (A MINIMUM
OF THREE TURNS).
3. CUT TWISTED END OF WIRES
TO 3/16 IN. (5 MM) BEFORE INSERTING
INTO TERMINAL AND TIGHTENING SCREW.
THEN PULL ON EACH WIRE IN ALL
TERMINALS TO CHECK FOR
GOOD MECHANICAL CONNECTION.
M24473
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
62-0254—13 6
Controller Wiring Details
The wiring connection terminals are shown in Fig. 7 and
are described in Table 2.
See Fig. 8 – 22 beginning on page 6 for typical T775A/B/
M wiring applications.
Fig. 7. T775A/B/M Terminal and Feature Locations.
NOTE: Refer to Table 1 on page 1 for the specific
configuration of sensors and outputs
supported by the model you are installing.
NOTE: For NEMA 4 enclosures, use waterproof fit-
tings for wiring/conduit connections at
knockouts.
WIRING APPLICATIONS
(EXAMPLES)
Fig. 8 – 22 illustrate typical controller wiring for various
applications.
NOTE: The electronic Series 90 output provided with
modulating T775 models can not drive elec-
tro-mechanical slidewire devices like older
Series 3 modulating meters (prior to Series
6), V9055s, and S984s.
Fig. 8. Wiring for Two-Stage Control – 24 Vac Input
and 24 Vac Load.
Table 2. Description of Wiring
Terminal Connections.
Connection Terminal Label Description
Sensors
Sensor A T T Temperature Sensor;
polarity insensitive
Sensor B
Outputs
Relay 1
Relay 2
Relay 3
Relay 4
NO
COM
NC
120-240 Vac Relay
Output
Mod 1 + - (Vdc or mA)
W R B (Series 90)aModulating Output
Mod 2
M24474
C
NO
NC
C
NO
NC
C
NC
NO
C
NC
NO
T
T
T
T
B
R
W+
–
+
–
B
R
W+
–
SENSOR A
SENSOR B
MOD 2
MOD 1
KNOCKOUT A
DIGITAL
INPUT
POWER
120/240 VAC
OUTPUT
RELAY 2
KNOCKOUT D
POWER
24 VAC
OUTPUT
RELAY 1
KNOCKOUT C
KNOCKOUT E
SENSORS A AND B USE THE TWO TT CONNECTIONS AND ARE
POLARITY INSENSITIVE.
FOR MOD 1 AND MOD 2 CURRENT (mA) OR VOLTAGE (VDC) OUTPUT,
USE SIGNAL (+) & COMMON (-).
FOR MOD 1 AND MOD 2 SERIES 90 OUTPUT, USE W, R, & B.
A SEPARATE EARTH GROUND IS REQUIRED FOR ANY POWER
SOURCE (24, 120, OR 240 VAC).
1
2
1
2
OUTPUT
RELAY 3
KNOCKOUT B
OUTPUT
RELAY 4
3
3
C
+
120
COM
240
Input
DI + - Digital Input (dry
contact)
24 Vac Power
24V + + 24 Vac Hot
Common C 24 Vac Common
Ground Earth Groundb
120 or 240 Vac Power
120 Vac 120 120 Vac Power
Common COM Common
240 Vac 240 240 Vac Power
aFor Series 90 connections, you must insert a 340 Ohm
resistor across terminals R and W. Refer to Fig. 19 on
page 9. The resistor is included with the controller.
bA separate earth ground is required for all installations
regardless of the power source (24, 120, or 240 Vac).
Refer to Fig. 5 on page 5.
Table 2. Description of Wiring
Terminal Connections. (Continued)
Connection Terminal Label Description
L1
(HOT)
L2
24 VAC
COM
NO
COM
NO
M24475A
LOAD 2
LOAD 1
SENSOR A
C
NO
NC
C
NO
NC
T
T
C
+
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
762-0254—13
Fig. 9. Wiring for Four-Stage Control – 24 Vac Input
and 24 Vac Load.
Fig. 10. Wiring for Two-Stage Control with 120 Vac
(120 Vac Input and 120 Vac Load Shown).
Fig. 11. Wiring for Two-Stage Control with 240 Vac.
Fig. 12. Wiring for Four-Stage Control with 120 Vac
(120 Vac Input and 120 Vac Load Shown).
L1
(HOT)
L2
24 VAC
M24476
A
SENSOR A
C
NO
NC
C
NO
NC
C
NC
NO
C
NC
NO
T
T
COM
LOAD
4
NO
LOAD
3
LOAD
2
LOAD
1
C
+
COM
NO
COM
NO
COM
NO
SENSOR A
C
NO
NC
C
NO
NC
T
T
COM
LOAD 2
LOAD 1
NO
COM
NO
COM
120V
M33846
C+
120
COM
240
POWER SUPPLY
L1 (H OT)
L2
SENSOR A
C
NO
NC
C
NO
NC
T
T
COM
LOAD 2
LOAD 1
NO
COM
NO
COM
240V
M33847
C+
120
COM
240
POWER SUPPLY
L1 (H OT)
L2
SENSOR A
C
NO
NC
C
NO
NC
C
NC
NO
C
NC
NO
T
T
COM
120V
M33848
LOAD 1
LOAD
3
LOAD
2
COM
NO
LOAD 4
C+
120
COM
240
COM
NO
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
62-0254—13 8
Fig. 13. Wiring for Four-Stage Control with 240 Vac.
Fig. 14. Wiring for Floating Output (Relay 1 and Relay
2 Pair Shown)
.
Fig. 15. Wiring for ML7984 Valve Actuator
(Using 4 to 20 mA Signal)
.
Fig. 16. Wiring for Digital Input (Dry Contact).
Fig. 17. Wiring for Mod Motor or Direct Coupled
Actuator with 4 to 20 mA Control Input
SENSOR A
C
NO
NC
C
NO
NC
C
NC
NO
C
NC
NO
T
T
COM
240V
M33849
LOAD 1
LOAD
3
LOAD
2
COM
NO
LOAD 4
C+
120
COM
240
COM
NO
C
NO
NC
C
NO
NC
M31361
CLOSE RELAY TO DRIVE DEVICE CLOSED. RELAY 1 SHOWN.
(RELAYS 1 AND 3 ARE USED FOR CLOSE).
CLOSE RELAY TO DRIVE DEVICE OPEN. RELAY 2 SHOWN.
(RELAYS 2 AND 4 ARE USED FOR OPEN).
THE RELAYS MUST BE WIRED IN PAIRS WITH RELAYS 1 AND 2
BEING THE FIRST PAIR, AND RELAYS 3 AND 4 BEING THE SECOND PAIR.
12
1
2
120/240 VAC LINE
CLOSE
DEVICE
COM
OPEN
NO
COM
NO
COM
RELAY 1 RELAY 2
M27228A
MODULATING OUTPUT
TERMINAL (MOD 1)
B
R
W+
–
B
R
W+
–
T1 T2 B WR
C
POWER
ML7984 ACTUATOR
M24482
DIGITAL
INPUT
+
–
USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.
1
M24481A
MODULATING OUTPUT
TERMINAL (MOD 1)
B
R
W+
–
B
R
W+
–
POWER
1
T1 T2
–
+
HONEYWELL MODUTROL MOTOR WITH
4-20 mA MODULATING INPUT
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
962-0254—13
.
Fig. 18. Wiring for Mod Motor or Direct Coupled
Actuator with 0 to 10 Vdc Control Input
Fig. 19. Wiring for Series 90 Modutrol Motor Control
.
Fig. 20. Wiring for Changeover Relay and
Minimum Position Potentiometer Used
with Series 90 Modutrol Motors.
T1 T2 C R
POWER
USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.
1
HONEYWELL MODUTROL MOTOR WITH
VOLTAGE CONTROL INPUT
1
F
M24483A
MODULATING OUTPUT
TERMINAL (MOD 1)
B
R
W+
–
B
R
W+
–
M24484
A
TO VERIFY OUTPUT, TEST OPEN CIRCUIT VOLTAGE BETWEEN
THE MOD 1 TERMINALS W AND R.
- MINIMUM (DRIVE CLOSED) SIGNAL LESS THAN 0.17 VDC
- MAXIMUM (DRIVE OPEN) SIGNAL IS GREATER THAN 1.7 VDC
USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.
INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.
1
2
3
MODULATING
OUTPUT
TERMINAL
(MOD 1)
B
R
W+
–
B
R
W+
–
T1 T2 B WR
POWER
HONEYWELL ELECTRONIC
SERIES 90 MODUTROL MOTOR
1
2
3
M24485A
USE SEPARATE TRANSFORMER FOR T775R WHEN USING 24 VAC.
A 250 OHM RESISTOR PROVIDES 40% AUTHORITY WHEN
USING A 150 OHM MINIMUM POSITION POTENTIOMETER.
INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.
1
2
MODULATING OUTPUT
TERMINAL (MOD 1)
B
R
W+
–
B
R
W+
–
T1 T2 B WR
POWER
2
HONEYWELL
ELECTRONIC SERIES 90
MODUTROL MOTOR
1
W R B
MINIMUM POSITION
POTENTIOMETER
(Q209)
SPDT CHANGEOVER
(H205 OR H705)
3
3
T775A/B/M SERIES 2000 ELECTRONIC STAND-ALONE CONTROLLERS
62-0254—13 10
Fig. 21. Wiring for Three Series 90 Modutrol Motors
.
Fig. 22. Wiring for Unison Control of M9184 or M9185 Modutrol IV Motor Using One Minimum Position
Potentiometer for All Motors.
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
USE A 1300 OHM RESISTOR FOR TWO MOTORS, 910 OHM RESISTOR FOR THREE MOTORS.
THE 407EAU RESISTOR KIT, WHICH IS SHIPPED WITH THE M9184 AND M9185 MOTORS,
INCLUDES BOTH RESISTORS.
INSERT 340 OHM RESISTOR (INCLUDED) ACROSS TERMINALS R AND W.
1
2
1
2
M9184 OR M9185
MODUTROL MOTOR
W
R
B
TR
TR
W
R
B
TR
TR
W
R
B
TR
TR
M9184 OR M9185
MODUTROL MOTOR
M9184 OR M9185
MODUTROL MOTOR
L1
(HOT) L2
M24486
MODULATING OUTPUT
TERMINAL (MOD 1)
B
R
W
+
–
B
R
W+
–
3
3
POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
UP TO SIX SIMILAR MOTORS CAN BE CONNECTED IN UNISON.
USE RESISTOR BETWEEN R AND B ON THE MOD 1 TERMINAL: 1300 OHMS FOR TWO MOTORS; 910 OHMS FOR THREE MOTORS (4074EAU KIT).
IF COMMON TRANSFORMER IS USED, ALL MOTORS MUST BE IN PHASE. CONNECT THE SAME TRANSFORMER LEAD TO T1 ON EACH MOTOR,
CONNECT THE OTHER TRANSFORMER LEAD TO T2 ON EACH MOTOR.
USE TEMPERATURE CONTROLLER SUCH AS H205 OR H705, OR T675A FOR CHANGEOVER CONTROL.
AUTHORITY OF MINIMUM POSITION POTENTIOMETER, IF USED, INCREASES WITH THE NUMBER OF MOTORS IN PARALLEL. WITH ONE MOTOR,
50% STROKE; WITH TWO MOTORS, 100% STROKE; WITH THREE MOTORS, 100% STROKE WITH 1/3 OF FULL POTENTIOMETER ROTATION.
REVERSING THE B AND W TERMINALS ON ONE OR MORE MOTORS WILL NOT AFFECT CONTROL PERFORMANCE ON THE OTHER MOTORS.
THE SYSTEM CAN BE CONFIGURED TO HAVE SOME MOTORS BE REVERSE ACTING AND OTHER MOTORS BE DIRECT ACTING.
USE SEPARATE TRANSFORMER FOR T775 WHEN POWERING FROM 24 VAC.
THE SYSTEM IS SHOWN CONNECTED FOR COOLING. FOR HEATING, REVERSE THE W AND B LEADS OF THE MODULATING OUTPUT ON THE
T775 CONTROLLER.
1
1
2
M9184 OR M9185
MODUTROL MOTOR
W
R
B
TR
TR
W
R
B
TR
TR
W
R
B
TR
TR
M9184 OR M9185
MODUTROL MOTOR
M9184 OR M9185
MODUTROL MOTOR
L1 (HOT) L2
W
R
B
MINIMUM
POSITION
POTENTIOMETER
(Q209/S963)
1
2
3
W
B
R
CHANGEOVER
CONTROLLER
64
2
2
2
5
7
3
9
6
4
5
7
3
8
9
M24487
MODULATING OUTPUT TERMINAL (MOD 1)
B
R
W
+
–
+
–
B
R
W
+
–
POWER
24 VAC
8
C
+