Model TC844A1007 Filtrex™Intelligent Photoelectronic Sensor
Installation Instructions
Before installing sensors, please thoroughly read the Guide for Proper Use of System Smoke Detectors, which provides detailed infor-
mation on sensor spacing, placement, zoning, and special applications. Copies of this guide are available from Honeywell.
NOTICE: This manual should be left with the owner/user of this equipment.
IMPORTANT: This sensor must be tested and maintained regularly following NFPA 72 requirements. It should be cleaned at least once
a year.
GENERAL DESCRIPTION
Filtrex® uses a small air intake fan and a high density replaceable filter. Air and smoke are drawn into a photoelectric sensing cham-
ber while airborne particulate and water mist are removed. The addressable-analog detector transmits an analog representation of
smoke density over a communication line to a control panel. Rotary-decade switches are provided for setting the sensor’s address.
Two LEDs on the sensor are controlled by the panel to indicate sensor status.
The Filtrex smoke detector is intended for use in normal environmental conditions, where dust and other airborne particulate are pres-
ent at elevated levels. These elevated levels tend to cause false alarms and high maintenance in standard detectors. Filtrex provides
a protective enclosure for a photoelectric smoke detector chamber and allows smoke detection in areas where heat detection was the
only practical alternative for fire sensing.
Filtrex requires compatible addressable communications to function properly. Connect this detector to listed-compatible control panels
only.
SPECIFICATIONS
Operating Voltage Range: 15 to 32 VDC
Detector Current: 230 µA @ 24 VDC (without communication)
285 µA @ 24 VDC (one communication every 5 sec. with LED enabled)
Auxiliary Power Supply Voltage: 15 to 30 VDC filtered; Ripple voltage may not drop below 15 volts.
Auxiliary Power Supply Current –
Peak: 123 mA max.
Average: 27 mA max.
Operating Humidity Range: 10% to 93% Relative Humidity, noncondensing
Operating Temperature Range: 0° to 50°C (32° to 122°F)
Height: 2.8 inches (43 mm)
Diameter: 6.1 inches (155 mm) installed in 14507371-008
4.0 inches (102 mm) installed in SSDB524FTXE
Weight: 7.3 oz. (207 g)
Mounting Base: Requires 14507371-008 (U.S.), SSDB524FTXE (Europe)
H400-22-00 1 I56-1326-006R
Honeywell, 1985 Douglas Drive North, Golden Valley MN 55422
LISTED COMPATIBLE CONTROL PANEL
AUX.
POWER
SUPPLY
+
+
–
–
AUX+
AUX–
AUX+
AUX–
2(–)3(RA) 4(S)
1(+)
1(+)
2(–)3(RA)4(S)
Figure 1. Wiring diagram:
C0121-00
WARNING
Filtrex is not designed to operate in explosive environments.
WIRING INSTRUCTIONS
All wiring must be installed in compliance with the National Electrical Code, applicable local codes, and any special requirements of
the Authority Having Jurisdiction. Proper wire gauges should be used. The installation wires should be color-coded to limit wiring mis-
takes and ease system troubleshooting. Improper connections will prevent a system from responding properly in the event of a fire.
NOTE: Although the TC8441007A is an intelligent sensor, a separate pair of wires is required for power. This power must be provided
from a listed fire alarm power supply.
Remove power from the communication line before installing detectors.
All wiring must conform to applicable local codes, ordinances, and regulations.
1. Wire the sensor base per the wiring diagram, please see Figure 1.
2. Set the desired address on the sensor address switches, please see Figure 2.
3. Insert 5-wire connector on mounting base into 5-pin connector on Filtrex unit. Install the detector into the sensor base. Push the
detector into the base while turning it clockwise to secure it in place. (Please see Figure 5 and INSTALLING FILTREX INTO BASE
on page 4 for specific directions.)
4. After all detectors have been installed, turn on the detector power supply, then apply power to the control unit and activate the
communication line.
5. Test the detector(s) as described in the TESTING section of this manual.
CAUTION
Dust cover must be removed before the detector can sense smoke.
TESTING
Before testing, notify the proper authorities that the system is undergoing maintenance, and will temporarily be out of service. Disable
the system to prevent unwanted alarms.
All detectors must be tested after installation and periodically thereafter. Testing methods must satisfy the Authority Having Jurisdiction
(AHJ). Detectors offer maximum performance when tested and maintained in compliance with NFPA 72.
The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)
This detector can be functionally tested with a test magnet. The test magnet electronically simulates smoke in the sensing cham-
ber, testing the detector electronics and connections to the control panel.
1. Hold the test magnet in the magnet test area as shown in Figure 3.
2. The detector should alarm the panel. Two LEDs on the detector are controlled by the panel to indicate sensor status. Coded
signals, transmitted from the panel, can cause the LEDs to blink, latch on, or latch off. Refer to the control panel technical
documentation for detector LED status operation and expected delay to alarm.
B. Smoke Entry: Aerosol Generator
Aerosol generators for smoke entry testing are available from a number of third party manufacturers (e.g., Gemini Scientific).
Following the manufacturer’s instructions, apply aerosol until the panel alarms.
A detector that fails any of these tests should be retested. If the detector still fails any test, have its filter replaced (see instructions
below) and retested. Finally, if the detector continues to fail after replacing the filter, it must be returned for repair or replacement.
When testing is complete, restore the system to normal operation and notify the proper authorities that the system is back in opera-
tion.
TESTING
The unique design of Filtrex eliminates the need for typical detector cleaning. The only maintenance necessary is replacing the fil-
ter, which is signaled by a trouble condition at the panel (see below).
Filtrex has been designed to maximize the amount of time before maintenance is required. Filtrex utilizes a replaceable filter that may
become clogged over time. Filtrex detector monitors itself to insure that the filter has not become clogged. Because environmental
conditions can vary significantly, the amount of time before maintenance could vary significantly as well. To fully understand mainte-
nance requirements of Filtrex in its installed location, it is recommended that the
following test program be conducted.
1. Install the Filtrex detector in the desired location.
2. Connect the Filtrex detector to the fire alarm control panel.
3. Maintain a record for at least 90 days of any maintenance performed on or required by Filtrex.
4. At the end of the test period, use the record to develop and schedule maintenance. Filtrex should be serviced at regular intervals
to insure that the fire alarm system provides continuous protection
H400-22-00 2 I56-1326-006R
TEST MAGNET
MARKER
TENS ONES
9
8
7
6
5
4
3
210
9
8
7
6
5
4
3
210
REPLACING THE FILTER
IMPORTANT:
When the filter becomes too clogged to draw adequate air
into Filtrex, power is automatically cut from the detector,
sending a trouble signal to the fire control panel. After 5
minutes, power is restored to the detector for 72 hours.
After 72 hours, power is cut again and the detector will
remain off-line until the filter is replaced.
NOTE: The unit has two filters. The replaceable filter is inside the
cover. A permanent filter is mounted to the unit.
1. Grasp the Filtrex housing with one hand and the cover
with the other. Turn the cover counterclockwise fully
(approx. 30 degrees) and remove cover by pulling it
away from detector unit (see Figure 4).
2. Replace with new filter and cover assembly. The cover
is keyed so it fits in place only one way. Turn the cover clockwise
until it stops.
NOTE: The base is equipped with an optional tamperproof feature
which can be used to prevent unintentional removal of Filtrex while
replacing the filter.
If a clogged filter was the cause of the trouble condition, nor-
mal detector operation should resume automatically within five
minutes. If the trouble condition persists, the detector must be
returned for repair or replacement.
Installing Filtrex into Base
1. Align the detector at a right angle to the base, with the five
wires and connector adjacent to the connector receptacle as
shown in Figure 5.
2. Plug the wired connector into the receptacle.
3. Rotate the detector into the base, making sure detector and
base keyed fit is lined up. Turn the detector clockwise until it
snaps into place.
IMPORTANT: Filtrex will only operate with 14507371-
008/SSDB524FTXE Mounting Base.
C0146-00
Figure 2. Rotary decade address switches:
Figure 3. Test magnet position:
Figure 4. Replacing the filter cover:
H400-22-00 3 I56-1326-006R
Alignment marks are
provided on the cap
and top of the
permanent filter.
Cover is keyed to
fit into 4 matching
size slots.
Figure 5: Installing Filtrex detector into base:
C0191-00
C0192-00
0845
SYSTEM SENSOR
3825 OHIO AVENUE, ST. CHARLES,
IL, 60174 8021 U.S.A.
0845-CPD-232.1427
EN54-7: 2000
MODEL TC844A1007
Filtrex Point Optical Smoke Sensor for Harsh Areas
TC844A1007 Filtrex™Intelligent Photo Smoke
Sensor Installation in XLS Fire Alarm Systems
Installation Instructions
FCC Statement
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful inter-
ference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Note: This equipment
has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to
provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio fre-
quency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However,
there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television
reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of
the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
GENERAL
The TC844A1007 Filtrex™ Intelligent Photo Smoke
Sensor can be used with the Honeywell XLS1000 fire
alarm control panels. The TC844A1007 is configured in
the SDU data file exactly the same as a TC806 Photo
Smoke Detector. The TC844A1007 is connected to the
3-AADC Analog Addressable Device Controller using the
Honeywell 14507371-008 base.
PRE INSTALLATION
Configure and install the XLS1000 Fire Alarm Control Panel
with a 3-AADC Analog Addressable Device Controller as
described in form no. 95-7545, XLS1000 Installation and
Service Manual. When configuring the database using
the SDU, use the TC806 Photoelectric Smoke Detector
parameters for setting up the TC844A1007 Filtrex™
Intelligent Photo Smoke Sensor. The TC844A1007
responds to the XLS1000 panel the same as a TC806
Photoelectric Smoke Detector.
WIRING
All wiring must conform to applicable local codes, ordi-
nances and regulations.
To wire the TC844A1007 Filtrex™Intelligent Photo Smoke
Sensor:
1. Wire the TC844A1007 Filtrex™Intelligent Photo Smoke
Sensor to the 3-AADC loop by using the Honeywell
14507371-008 Plug-In Detector Base. See Fig. 6.
2. Wire Terminal 1 to the positive polarity (+) side of the
loop.
3. Wire Terminal 2 to the negative polarity (–) side of the
loop.
To use the TC844A1007 Filtrex™Intelligent Photo Smoke
Sensor with the DeltaNet FS90 Fire & Security System,
refer to form no. 95-7421, DeltaNet FS90 Fire & Security
System Installation Instructions.
NOTE: A power source within 15 Vdc to 30 Vdc is required.
This auxiliary power is wired to the AUX + and AUX– ter-
minals of the base. This power can be provided from the
XLS1000 power supply or any other appropriately listed
source.
CHECKOUT
Standard checkout procedures are used for commission-
ing the TC844A1007 Filtrex™Intelligent Photo Smoke
Sensor when used with the XLS1000 and 3-AADC. The
panel should respond to the TC844A1007 the same as it
would for a TC806 Photo Smoke Detector.
H400-22-00 4 I56-1326-006R
© 2005 Honeywell
Please refer to insert for the Limitations of Fire Alarm Systems
+
–
AUX+
AUXñ
AUX+
AUXñ
2(-) 3(RA) 4(S)
1(+)
1(+)
2(-) 3(RA)4(S)
IF SHIELD USED, MUST BE CONTINUOUS AND FREE
FROM EARTH GROUND.
NOTE: ALL WIRING SUPERVISED AND POWER LIMITED.
1
1
REQUIRED FOR
CLASS A ONLY
+
+
+
–
B
–
B
H
S
+
A
–
A N/C
+
B
–
B N/C
LOOP1LOOP1LOOP1
CIRCUIT 1
3-AADC
–
3-PPS/M OR
3-BPS/M
+–+
AUXILIARY POWER
TB1
21
Figure 6. Typical wiring from TC844A1007 to XLS1000
C0120-00
95-7662
TC844A1007 WITH
14507371-008 BASE

Other Honeywell Security Sensor manuals

Honeywell BW Ultra User manual

Honeywell

Honeywell BW Ultra User manual

Honeywell C7061 A User manual

Honeywell

Honeywell C7061 A User manual

Honeywell Activ8 PIR User manual

Honeywell

Honeywell Activ8 PIR User manual

Honeywell Miller EN 358 User manual

Honeywell

Honeywell Miller EN 358 User manual

Honeywell X-ND100 User manual

Honeywell

Honeywell X-ND100 User manual

Honeywell Sensepoint XCD RFD User manual

Honeywell

Honeywell Sensepoint XCD RFD User manual

Honeywell RAEGuard 2 PID User manual

Honeywell

Honeywell RAEGuard 2 PID User manual

Honeywell LightSpot LS1000R User manual

Honeywell

Honeywell LightSpot LS1000R User manual

Honeywell Series 3000 MkII User manual

Honeywell

Honeywell Series 3000 MkII User manual

Honeywell SiX Series User manual

Honeywell

Honeywell SiX Series User manual

Honeywell 5800COMBO-CN User manual

Honeywell

Honeywell 5800COMBO-CN User manual

Honeywell Ex-Or MLS Series Quick start guide

Honeywell

Honeywell Ex-Or MLS Series Quick start guide

Honeywell PEHA D-LS1000R User manual

Honeywell

Honeywell PEHA D-LS1000R User manual

Honeywell Miller User manual

Honeywell

Honeywell Miller User manual

Honeywell PEHA MLS Digital Hi-Bay D MLS2001AHBF Installation and operation manual

Honeywell

Honeywell PEHA MLS Digital Hi-Bay D MLS2001AHBF Installation and operation manual

Honeywell Miller Scorpion User manual

Honeywell

Honeywell Miller Scorpion User manual

Honeywell Viewguard PIR AM FAI Instruction manual

Honeywell

Honeywell Viewguard PIR AM FAI Instruction manual

Honeywell Sensepoint XCL User manual

Honeywell

Honeywell Sensepoint XCL User manual

Honeywell Miller Twin Turbo G2 Connector Operator's manual

Honeywell

Honeywell Miller Twin Turbo G2 Connector Operator's manual

Honeywell FireLite BG-12LSP User manual

Honeywell

Honeywell FireLite BG-12LSP User manual

Honeywell SPM Flex User manual

Honeywell

Honeywell SPM Flex User manual

Honeywell RAELink3 2.4GHz User manual

Honeywell

Honeywell RAELink3 2.4GHz User manual

Honeywell DUAL TEC DT8050A User manual

Honeywell

Honeywell DUAL TEC DT8050A User manual

Honeywell krom schroder DGS User manual

Honeywell

Honeywell krom schroder DGS User manual

Popular Security Sensor manuals by other brands

STEINEL Multisensor True Presence IP manual

STEINEL

STEINEL Multisensor True Presence IP manual

Siemens DB721 Installation

Siemens

Siemens DB721 Installation

SKF 234-13163-9 Service manual

SKF

SKF 234-13163-9 Service manual

MSA ALTAIR 5X operating manual

MSA

MSA ALTAIR 5X operating manual

Inter-m AFD-614 Service manual

Inter-m

Inter-m AFD-614 Service manual

Alula RE636 Wireless Outdoor Siren Strobe Connect+... quick start guide

Alula

Alula RE636 Wireless Outdoor Siren Strobe Connect+... quick start guide

Optex AX-330PLUS installation instructions

Optex

Optex AX-330PLUS installation instructions

quiko QK-FTP40 Operating and installation instructions

quiko

quiko QK-FTP40 Operating and installation instructions

Retlux RDT 100 user manual

Retlux

Retlux RDT 100 user manual

Bahco BELMS12OBDL Original instructions

Bahco

Bahco BELMS12OBDL Original instructions

Safescan 155 Series manual

Safescan

Safescan 155 Series manual

nedis ZBSD10WT user manual

nedis

nedis ZBSD10WT user manual

brennenstuhl CM L 4050 operating instructions

brennenstuhl

brennenstuhl CM L 4050 operating instructions

HD Electric V-WATCH Operating instructions manual

HD Electric

HD Electric V-WATCH Operating instructions manual

RKI Instruments 35-3001-05-03 Operator's manual

RKI Instruments

RKI Instruments 35-3001-05-03 Operator's manual

Hytronik HIR23 quick start guide

Hytronik

Hytronik HIR23 quick start guide

Capital Safety DBI-Sala Ultra-Lok RSQ 3504553 Specific instructions

Capital Safety

Capital Safety DBI-Sala Ultra-Lok RSQ 3504553 Specific instructions

FootfallCam SpaceSense installation guide

FootfallCam

FootfallCam SpaceSense installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.