manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Security Sensor
  8. •
  9. Honeywell FIRE-LITE ALARMS W-SD355 User manual

Honeywell FIRE-LITE ALARMS W-SD355 User manual

FL-400-004 1 I56-4081-000R
This sensor must be installed in compliance with the control panel system
installation manual and the SLC Wireless Gateway Manual. The installation
must meet the requirements of the Authority Having Jurisdiction (AHJ). Sen-
sors offer maximum performance when installed in compliance with the Na-
tional Fire Protection Association (NFPA); see NFPA 72.
GENERAL DESCRIPTION
Model W-SD355 and W-SD355T are plug-in type smoke sensors that combine
a photoelectronic sensing chamber with wireless communication. The sensors
transmit a digital representation of smoke density through a wireless mesh
to a gateway. The gateway will send the information to the panel when re-
quested. Rotary decade switches are provided for setting the sensor’s address.
(Figure 1)
Two LEDs on the sensor are controlled by the panel to indicate sensor status.
Model W-SD355T combines a photoelectronic sensing chamber and 135°F
(57.2°C) fixed temperature heat detector.
Fire-Lite panels offer different features sets across different models. As a re-
sult, certain features of the W-SD355 and W-SD355T may be available on
some control panels, but not on others. The possible features available in the
W-SD355 and W-SD355T, if supported by the control unit are:
• The panel controls the LED operation on the sensor. Operational modes
include red, green and amber colors in various solid or blink patterns.
Please refer to the operation manual for the UL listed control unit for specific
operation of the W-SD355 and W-SD355T.
The W-SD355 and W-SD355T require compatible addressable communica-
tions to function properly. Connect these sensors to listed-compatible control
panels only.
SPACING
Fire-Lite recommends spacing sensors in compliance with NFPA 72. In low
air flow applications with smooth ceilings, space sensors 30 feet apart. For
specific information regarding sensor spacing, placement, and special appli-
cations, refer to NFPA 72 or the System Smoke Detector Application Guide,
available from Fire-Lite.
NOTE: Do not attach the base and detectors to temporary structures such as
removable ceiling tiles such that the placement could be altered. To prevent
changes in device placement, permanently secure the structure or mount the
detector across the ceiling panel support as shown in Figure 2.
BATTERY REPLACEMENT
Low battery levels on the wireless devices are displayed as a trouble on the
FACP. Therefore when the message “TROUBLE BATTERY LOW” is displayed,
replace the battery in the device. This message is an indication that approxi-
mately one week of battery life remains.
W-SD355 and W-SD355T Wireless
Intelligent Photoelectric Smoke Sensor
I56-4081-000R
INSTALLATION AND MAINTENANCE INSTRUCTIONS
SPECIFICATIONS
Operating Voltage Range: 3.3 VDC
Standby Current: 210µA @ 3.3 VDC (one communication every 23.8 seconds with LED blink enabled)
Maximum Alarm Current (LED on): 5 mA @ 3.3 VDC LED on
Maximum Transmit RF Power: 17dBm
Radio Frequency Range: 902-928 MHz
Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing
Operating Temperature Range: 32°F to 120°F (0°C to 49°C),W-SD355; 32°F to 100°F (0°C to 38°C),W-SD355T
Battery Type: 4 Panasonic CR123A or 4 Duracell DL123A
Battery Life: 1 year minimum
Battery Replacement: Upon TROUBLE BATTERY LOW display and/or during annual maintenance
Height: 2.4in. (61 mm) installed in B501W Base
Diameter: 4.0in. (102 mm) installed in B501W Base
Weight: 8.1 oz. (230 g) installed in B501W base with 4 batteries
To replace the batteries in a wireless device use the following steps:
1. Have 4 CR123A (or DL123A) batteries available
2. The system allows 200 seconds to replace the batteries before the device is
noted as missing and will activate the Rescue Mode within the wireless system.
3. Remove the detector from the base.
4. Open the battery compartment refer to Figure 3. Note: The battery compart-
ment cover may be left attached at the hinges during battery replacement.
5. Remove the used batteries and replace with new batteries. The battery
compartment is designed such that the batteries can only align in the ap-
propriate direction. Do not force the batteries into the openings.
6. Replace the battery compartment cover.
7. Return the device to its original location.
CAUTION
Dust covers provide limited protection against airborne dust particles during ship-
ping. Dust covers must be removed before the sensors can sense smoke. Remove
sensors prior to heavy remodeling or construction.
TENS ONES
9
10
11
12
13
14
15
8
7
6
5
4
3
210
9
8
7
6
5
4
3
210
C0162-00
FIGURE 1. ROTARY ADDRESS SWITCHES:
One FireLite Place
Northford, CT 06472
Phone: 203.484.7161
MANUFACTURER MODEL
Home Safeguard Industries 25S and 30S
SDi CHEK02 and CHEK06
SDi SOLOA4
SDi SMOKESABRE-01
When used properly, the canned smoke agent will cause the smoke detector
to go into alarm. Refer to the manufacturer’s published instructions for proper
use of the canned smoke agent.
CAUTION
Canned aerosol simulated smoke (canned smoke agent) formulas will vary by
manufacturer. Misuse or overuse of these products may have long term ad-
verse effects on the smoke detector. Consult the canned smoke agent manufac-
turer’s published instructions for any further warnings or caution statements.
C. Direct Heat Method (Hair dryer of 1000-1500 watts).
A hair dryer of 1000-1500 watts should be used to test the thermistors. Di-
rect the heat toward either of the two thermistors, holding the heat source
approximately 12 inches from the detector in order to avoid damaging
the plastic housing. The detector will reset only after it has had sufficient
time to cool. Make sure both thermistors are tested individually.
A sensor that fails any of these tests should be cleaned as described under
CLEANING, and retested. If the sensor fails after cleaning, it must be replaced
and returned for repair.
When testing is complete, restore the system to normal operation and notify
the proper authorities that the system is back in operation.
CLEANING
Before removing the detector, notify the proper authorities that the smoke de-
tector system is undergoing maintenance and will be temporarily out of service.
Disable the zone or system undergoing maintenance to prevent unwanted alarms.
1. Remove the sensor to be cleaned from the system.
2. Remove the sensor cover by pressing firmly on each of the four removal
tabs that hold the cover in place. (refer to Figure 5).
3. Vacuum the screen carefully without removing it. If further cleaning is
required continue with Step 4, otherwise skip to Step 7.
4. Remove the chamber cover/screen assembly by pulling it straight out.
5. Use a vacuum cleaner or compressed air to remove dust and debris from
the sensing chamber.
6. Reinstall the chamber cover/screen assembly by sliding the edge over the
sensing chamber. Turn until it is firmly in place.
7. Replace the cover using the LEDs to align the cover and then gently
pushing it until it locks into place. Make sure that the thermistors do not
become bent under the cover on the W-SD355T.
8. Reinstall the detector.
9. Test the detector as described in TESTING.
10. Reconnect disabled circuits.
11. Notify the proper authorities that the system is back on line.
SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS
Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.
FL-400-004 2 I56-4081-000R
BATTERY
COMPARTMENT
COVER
FIGURE 2. CEILING PANEL SUPPORT:
FIGURE 3. BATTERY COMPARTMENT:
TAMPER RESISTANCE
W-SD355 and W-SD355T include a tamper-resistant capability that prevents
their removal from the base without the use of a tool. Refer to the base man-
ual for details on making use of this capability. The base also includes a mag-
net for tamper resistance. The magnet activates a supervisory tamper fault at
the panel if the detector is removed from the base.
TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Testing
methods must satisfy the Authority Having Jurisdiction (AHJ). Sensors offer max-
imum performance when tested and maintained in compliance with NFPA 72.
The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-04-01 or M02-09-00)
This sensor can be functionally tested with a test magnet. The test mag-
net electronically simulates smoke in the sensing chamber, as well as
tests the sensor electronics and connections to the control panel.
1. Hold the test magnet in the magnet test area as shown in Figure 4.
2. The sensor should alarm the panel.
Two LEDs on the sensor are controlled by the panel to indicate sensor
status. Coded signals, transmitted from the panel, can cause the LEDs
to blink, latch on, or latch off. Refer to the control panel technical docu-
mentation for sensor LED status operation and expected delay to alarm.
B. Smoke Entry
The GEMINI model 501 aerosol generator can be used for smoke entry
testing. Set the generator to represent 4%/ft to 5%/ft obscuration as de-
scribed in the GEMINI 501 manual. Using the bowl shaped applicator,
apply aerosol until the panel alarms.
Additionally, canned aerosol simulated smoke (canned smoke agent)
may be used for smoke entry testing of the smoke detector. Tested and
approved aerosol smoke products are:
C2015-00
C1092-00
C2013-00
LED TEST MAGNET
POSITION
MAGNET TEST
MARKER
LED
COVER
REMOVAL
TABS
SENSOR
COVER
W-SD355 W-SD355T
SENSING CHAMBER
COVER AND SCREEN
SENSING
CHAMBER
COVER
REMOVA
L
TABS
FIGURE 5. DETECTOR COMPONENTS:
FIGURE 4. MAGNET TEST MARKERS:
C0145-02
FL-400-004 3 I56-4081-000R
FL-400-004 4 I56-4081-000R
©2014 Fire-Lite
FCC STATEMENT
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against
harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful
interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception,
which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
– Reorient or relocate the receiving antenna.
– Increase the separation between the equipment and receiver.
– Connect the equipment into an outlet on a circuit different from that to which the receiver is connected.
– Consult the dealer or an experienced radio/TV technician for help.
Please refer to insert for the Limitations of Fire Alarm Systems

This manual suits for next models

1

Other Honeywell Security Sensor manuals

Honeywell One FireLite Alarms SD355 User manual

Honeywell

Honeywell One FireLite Alarms SD355 User manual

Honeywell Notifier FST-951 User manual

Honeywell

Honeywell Notifier FST-951 User manual

Honeywell IQ Force Installation manual

Honeywell

Honeywell IQ Force Installation manual

Honeywell Midas User manual

Honeywell

Honeywell Midas User manual

Honeywell Activ8 BG User manual

Honeywell

Honeywell Activ8 BG User manual

Honeywell Lyric W1 User manual

Honeywell

Honeywell Lyric W1 User manual

Honeywell Ex-Or MR1500P Installation and operation manual

Honeywell

Honeywell Ex-Or MR1500P Installation and operation manual

Honeywell Miller RACDTA-5K6/6FT Operator's manual

Honeywell

Honeywell Miller RACDTA-5K6/6FT Operator's manual

Honeywell DO800M User manual

Honeywell

Honeywell DO800M User manual

Honeywell Minipeeper C7035A Operation manual

Honeywell

Honeywell Minipeeper C7035A Operation manual

Honeywell IS2535T User manual

Honeywell

Honeywell IS2535T User manual

Honeywell 5800-OD User manual

Honeywell

Honeywell 5800-OD User manual

Honeywell 5800COMBO User manual

Honeywell

Honeywell 5800COMBO User manual

Honeywell SS2 Series User manual

Honeywell

Honeywell SS2 Series User manual

Honeywell FIRE-LITE ALARMS H365 User manual

Honeywell

Honeywell FIRE-LITE ALARMS H365 User manual

Honeywell ADEMCO 5808EU User manual

Honeywell

Honeywell ADEMCO 5808EU User manual

Honeywell SC105 Operation manual

Honeywell

Honeywell SC105 Operation manual

Honeywell BW Solo User manual

Honeywell

Honeywell BW Solo User manual

Honeywell HAQSPA-R User manual

Honeywell

Honeywell HAQSPA-R User manual

Honeywell Purple Peeper C7012A User manual

Honeywell

Honeywell Purple Peeper C7012A User manual

Honeywell MultiPro User manual

Honeywell

Honeywell MultiPro User manual

Honeywell EC-P2 User manual

Honeywell

Honeywell EC-P2 User manual

Honeywell FG-730 User manual

Honeywell

Honeywell FG-730 User manual

Honeywell FlexGuard 5853 User manual

Honeywell

Honeywell FlexGuard 5853 User manual

Popular Security Sensor manuals by other brands

SKF LINCOLN Magnetic sensor M G Series Service manual

SKF

SKF LINCOLN Magnetic sensor M G Series Service manual

Profort PirSpot manual

Profort

Profort PirSpot manual

Zipato Multisensor Quad Quick installation guide

Zipato

Zipato Multisensor Quad Quick installation guide

Eminent EM8650 manual

Eminent

Eminent EM8650 manual

OzSpy DSA055UEMR user manual

OzSpy

OzSpy DSA055UEMR user manual

GEZE GC 365 R Original instructions

GEZE

GEZE GC 365 R Original instructions

Det-Tronics X3302 instructions

Det-Tronics

Det-Tronics X3302 instructions

2gig Technologies 2GIG-FT1-345 manual

2gig Technologies

2gig Technologies 2GIG-FT1-345 manual

LEGRAND 0 625 14 manual

LEGRAND

LEGRAND 0 625 14 manual

GST R6602 quick start guide

GST

GST R6602 quick start guide

Inficon HLD6000 installation manual

Inficon

Inficon HLD6000 installation manual

Ametek X-123 quick start guide

Ametek

Ametek X-123 quick start guide

Xtralis VIS-IR Product guide

Xtralis

Xtralis VIS-IR Product guide

teko Astra-517 ver.P user guide

teko

teko Astra-517 ver.P user guide

Aritech 2000 Series Installation sheet

Aritech

Aritech 2000 Series Installation sheet

Diablo DSP-22-2 user manual

Diablo

Diablo DSP-22-2 user manual

Reed Instruments R9200 instruction manual

Reed Instruments

Reed Instruments R9200 instruction manual

AVE AF45 62 Series quick start guide

AVE

AVE AF45 62 Series quick start guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.