3.2.5 Orientation
TheSearchlineExcelCross-Ductunitsshouldbemountedonvertical,atsurfacessuchthattheopticalaxis
ishorizontal.Ensurethesurfaceisrigidandstable.Fitadditionalsupportspriortoinstallationifnecessary
(see note on Vibration, above).
TheHeatedReectorPanelshouldbemounteddirectlyopposite,andperpendiculartotheopticalaxisofthe
Transmitter and Receiver unit. If the duct walls are not exactly vertical or parallel, the position of the cut out
for the retro panel must be adjusted to compensate.
It is not advisable to install the Cross-Duct Excel on the top or bottom of the duct. In this orientation the
ReectorPanelortheTransmitterandReceiverunitwillbevulnerabletothebuildupofcontamination.
3.2.6 Access for Cleaning
SearchlineExcelCross-DuctTransmitterandReceiverunitandHeatedReectorPanelwillneedtobecleaned
regularly.InthecaseoftheReectorPanelitmayneedtoberemovedfromtheducttocleanthewindow.It
isadvisabletoprovideanaccesspointintheduct,adjacenttothereectorpanel,toallowittobecleaned.
3.3 Electrical Connections
3.3.1 General
Searchline Excel Cross-Duct complies with the EN50270. In order to maintain compliance with these standards
it is essential that the electrical installation of Excel is engineered correctly.
Electrical installation standards vary for different countries, companies and applications and it is the responsibility
of the installation design authority to determine the applicable standards and ensure compliance with them.
WhendesigningelectricalinstallationsforExcel,HoneywellAnalyticsrecommendthattheinstallationdesign
authorityconsidersthefollowing:
a. The unit cases should not, if possible, be connected to electrically noisy (dirty) metalwork or conductors.
Preferably, the case (internally connected to the green/yellow GND wire) should be connected to a low
noise instrument (clean) earth. See also para e. below. In order to facilitate electrical isolation of the
SearchlineExcelfromanoisyearthanisolationkitissupplied.Thiskitshouldbettedasstandardunless
local regulations forbid this.
b. Theentirelengthoftheeldcablingconnectedtoeachunitshouldbefullyshielded.Thisshouldbeconnected
to a low noise (clean) earth.
c. The low noise instrument (clean) earth system should only be connected to safety earth (usually dirty)
at a single point on the entire site/installation. This connection should be made in such a manner that it
does not introduce noise onto the low noise instrument earth. Star earthing arrangements minimise earth
current crosstalk.
d. Theshieldsoftheeldcablingshouldnotbeconnectedsuchthatearthloopsareproduced,orinamanner
that will result in the shields carrying large currents from heavy plant or equipment.
e. Ideally,theeldcableshieldshouldbeconnectedtotheunitsgreen/yellowGNDwire,providingasingle,
continuous earth shield. This connection must not be allowed to complete an earth loop.
f. The earth bonding arrangement must ensure that the maximum peak voltage between the unit case earth
andanyeldcableconductorislessthan350V.Voltagesinexcessofthiscancausepermanentdamage
totheunitsRFIprotectionlters.
g. The use of a single, screened cable for each gas detector ensures maximum screening and minimum
crosstalk. Cabling arrangements which use a single cable for connecting a number of eld devices
compromise screening, increase the potential for crosstalk and prevent implementation of true star earthing.
3. Installation and Operation