manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Security Sensor
  8. •
  9. Honeywell Notifier FSP-951AUS User manual

Honeywell Notifier FSP-951AUS User manual

WIRING GUIDE
All wiring must be installed in compliance with the National Electrical Code,
applicable local codes, and any special requirements of the Authority Having
Jurisdiction. Proper wire gauges should be used. The installation wires should
be color-coded to limit wiring mistakes and ease system troubleshooting. Im-
proper connections will prevent a system from responding properly in the
event of a fire.
Remove power from the communication line before installing sensors.
1. Wire the sensor base (supplied separately) per the wiring diagram, Figure 2.
2. Set the desired address on the sensor address switches, see Figure 1.
3. Install the sensor into the sensor base. Push the sensor into the base while
turning it clockwise to secure it in place.
4. After all sensors have been installed, apply power to the control panel and
activate the communication line.
5. Test the sensor(s) as described in the TESTING section of this manual.
CAUTION
Dust covers provide limited protection against airborne dust particles during
shipping. Dust covers must be removed before the sensors can sense smoke.
Remove sensors prior to heavy remodeling or construction.
FIGURE 2. WIRING DIAGRAM
2
31
2
33
1
2
1
(–)
(+)
+ -
Compatible
Control Panel
CAUTION: Do not loop wire under
terminal 1 or 2. Break wire run to
supervise connections.
CLOSE LOOP OPTIONAL WIRING
Remote
Annunciator
(–)
(+)
RA
+–
+
RA
+–
+
RA
+–
+
C0129-10AUS
TAMPER-RESISTANCE
Photoelectric and temperature sensors include a tamper-resistant capability
that prevents their removal from the base without the use of a tool. Refer to
the base manual for details on making use of this capability.
SPECIFICATIONS
Operating Voltage Range: 15 to 32 VDC
Operating Current @ 24 VDC: 200 uA (one communication every 5 seconds with green LED blink on communication)
Maximum Alarm Current: 2 mA @ 24 VDC (one communication every 5 seconds with red LED solid on)
Maximum Current: 4.5 mA @ 24 VDC (one communication every 5 seconds with amber LED solid on)
Operating Humidity Range: 10% to 93% Relative Humidity, Non-condensing
Operating Temperature Range: -10°C to 50°C
Air Velocity: 0 to 1219.2 m/min.
Height: 51 mm installed in B501AUS-W/B501AUS-IV Base
Diameter: 104 mm installed in B501AUS-W/B501AUS-IV Base
Weight: 95 g
Isolator Load Rating: 0.0063*
Applicable Standards: AS 7240.7 and AS 7240.5 (Class A2S)
*Please refer to your isolator base/module manual for isolator calculation instructions.
This sensor must be installed in compliance with the control panel system
installation manual. The installation must meet the requirements of the Au-
thority Having Jurisdiction (AHJ).
GENERAL DESCRIPTION
FSP-951TAUS and FSP-951TAUS-IV are plug-in type multi-sensor smoke sen-
sors that combine a photoelectronic sensing chamber and fixed temperature
heat detector across addressable-analog communications. The sensors trans-
mit an analog representation of smoke density over a communication line
to a control panel. Rotary dial switches are provided for setting the sensor’s
address. (See Figure 1.) The intelligent photoelectric and temperature sensors
also transmit an alarm as per class A2S (AS 7240.5).
FIGURE 1. ROTARY ADDRESS SWITCHES
TENS ONES
910
11
12
13
14
15
8
7
6
5
4
3
210
9
8
7
6
5
4
3
210
C0162-00
Two LEDs on the sensor are controlled by the panel to indicate sensor status.
An output is provided for connection to an optional remote LED annunciator
(P/N RA100Z).
Fire Alarm and Control panels offer different feature sets across different mod-
els. As a result, certain features of the photoelectric and temperature sensors
may be available on some control panels, but not on others. FSP-951TAUS will
support only FlashScan® protocol mode. FSP-951TAUS-IV will support either
FlashScan or CLIP (Classic Loop Interface Protocol) mode. The possible fea-
tures available if supported by the control panel are:
1. The sensor’s LEDs can operate in three ways—on, off, and blinking—and
they can be set to red, green, or amber. This is controlled by the panel.
2. The remote output may be synchronized to the LED operation or con-
trolled independent of the LEDs.
3. Devices are point addressable up to 159 addresses.
Please refer to the operation manual for the control panel for specific op-
eration. The photoelectric and temperature sensors require compatible ad-
dressable communications to function properly. Connect these sensors to
listed-compatible control panels only.
Compatible bases: B501AUS-W/B501AUS-IV.
SPACING
Notifier recommends spacing sensors in compliance with AS 1670.1:2015. All
detectors should be spaced and installed in accordance with the requirements
of the relevant authority having jurisdiction. For specific information regarding
sensor spacing, placement, and special applications, refer to AS 1670.1:2015
or the Smoke Detector Application Guide.
I56-7362-000
INSTALLATION AND MAINTENANCE INSTRUCTIONS
9 Columbia Way
Baulkham Hills NSW 2153
1800 220 345
FSP-951TAUS and FSP-951TAUS-IV
Intelligent Photoelectric
and Temperature Sensors
1 I56-7362-000
Notifier®and FlashScan®are registered trademarks of Honeywell International, Inc.
TESTING
Before testing, notify the proper authorities that the system is undergoing
maintenance, and will temporarily be out of service. Disable the system to
prevent unwanted alarms.
All sensors must be tested after installation and periodically thereafter. Testing
methods must satisfy the Authority Having Jurisdiction (AHJ).
The sensor can be tested in the following ways:
A. Functional: Magnet Test (P/N M02-09-00)
This sensor can be functionally tested with a test magnet. The test magnet
electronically simulates smoke in the sensing chamber, testing the sensor
electronics and connections to the control panel.
1. Hold the test magnet in the magnet test area as shown in Figure 3.
2. The sensor should alarm the panel.
Two LEDs on the sensor are controlled by the panel to indicate sensor
status. Coded signals, transmitted from the panel, can cause the LEDs to
blink, latch on, or latch off. Refer to the control panel technical documen-
tation for sensor LED status operation and expected delay to alarm.
B. Smoke Entry
Sensitivity readings are available through the FACP. Refer to the manufac-
turer’s published instructions for proper use.
Additionally, canned aerosol simulated smoke (canned smoke agent) may
be used for smoke entry testing of the smoke detector.
When used properly, the canned smoke agent will cause the smoke detec-
tor to go into alarm. Refer to the manufacturer’s published instructions for
proper use of the canned smoke agent.
CAUTION
Canned aerosol simulated smoke (canned smoke agent) formulas will vary by
manufacturer. Misuse or overuse of these products may have long term ad-
verse effects on the smoke detector. Consult the canned smoke agent manufac-
turer’s published instructions for any further warnings or caution statements.
C. Direct Heat Method (Hair dryer of 1000-1500 watts).
A hair dryer of 1000-1500 watts should be used to test the thermistors. Di-
rect the heat toward either of the two thermistors, holding the heat source
approximately 30 cm from the detector in order to avoid damaging the
plastic housing. The detector will reset only after it has had sufficient time
to cool. Make sure both thermistors are tested individually.
A sensor that fails any of these tests may need to be cleaned as described
under CLEANING, and retested.
When testing is complete, restore the system to normal operation and notify
the proper authorities that the system is back in operation.
CLEANING
Before removing the detector, notify the proper authorities that the smoke
detector system is undergoing maintenance and will be temporarily out of
service. Disable the zone or system undergoing maintenance to prevent un-
wanted alarms.
1. Remove the sensor to be cleaned from the system.
2. Remove the sensor cover by pressing firmly on each of the four removal
tabs that hold the cover in place.
3. Vacuum the screen carefully without removing it. If further cleaning is
required continue with Step 4, otherwise skip to Step 7.
4. Remove the chamber cover/screen assembly by pulling it straight out.
5. Use a vacuum cleaner or compressed air to remove dust and debris from
the sensing chamber.
6. Reinstall the chamber cover/screen assembly by sliding the edge over the
sensing chamber. Turn until it is firmly in place.
7. Replace the cover using the LEDs to align the cover and then gently push-
ing it until it locks into place. Make sure that the thermistors do not be-
come bent under the cover.
8. Reinstall the detector.
9. Test the detector as described in TESTING.
10. Reconnect disabled circuits.
11. Notify the proper authorities that the system is back on line.
Note: Dispose of electronic waste according to national and local regulations
when scrapping or replacing a device. Do not discard as general trash.
SPECIAL NOTE REGARDING SMOKE DETECTOR GUARDS
Smoke detectors are not to be used with detector guards unless the combina-
tion has been evaluated and found suitable for that purpose.
FIGURE 3. FEATURES OF THE PHOTO/HEAT DETECTOR
Magnet
Test
Marker
LED
Base
Alignment
Notch
Magnet Test Marker LED
Base Alignment Notch
C2023-00
FIGURE 4. CLEANING THE PHOTO/HEAT DETECTOR
Cover Removal
Tabs
Sensor Cover
Sensing Chamber
Cover and Screen
Sensing Chamber
ThermistorThermistor
}
C2024-00
ON-SITE SENSITIVITY ADJUSTMENT
The sensitivity for this device is set at FDCIE.
For the AFP-3030 panel, alarm sensitivity levels 1-9 meet the sensitivity level
requirement of the AS 7240.7 standard.
For more information on sensitivity settings refer to the manufacturer's Fire
Alarm Control Panel manual.
Australian
Standard
Lic. SMKH25312
SAI-Global
DEVICE AND SYSTEM SECURITY
Before installing this product ensure that the
tamper seal on the packaging is present and
unbroken and the product has not been tampered
with since leaving the factory. Do not install this
product if there are any indications of tampering.
If there are any signs of tampering the product
should be returned to the point of purchase.
It is the responsibility of the system owner to
ensure that all system components, i.e. devices,
panels, wiring etc., are adequately protected to
avoid tampering of the system that could result
in information disclosure, spoofing, and integrity
violation.
2I56-7362-000
Ver. A

This manual suits for next models

2

Other Honeywell Security Sensor manuals

Honeywell PANORAMA Series User manual

Honeywell

Honeywell PANORAMA Series User manual

Honeywell TRADELINE C554A User manual

Honeywell

Honeywell TRADELINE C554A User manual

Honeywell FS19X Series User manual

Honeywell

Honeywell FS19X Series User manual

Honeywell EC-P2 Manual

Honeywell

Honeywell EC-P2 Manual

Honeywell FireLite BG-12LSP User manual

Honeywell

Honeywell FireLite BG-12LSP User manual

Honeywell FlexGuard 5853AP User manual

Honeywell

Honeywell FlexGuard 5853AP User manual

Honeywell EC-FX-NH3 Manual

Honeywell

Honeywell EC-FX-NH3 Manual

Honeywell 015610.01 Instruction manual

Honeywell

Honeywell 015610.01 Instruction manual

Honeywell FlexGuard 5853 User manual

Honeywell

Honeywell FlexGuard 5853 User manual

Honeywell DUAL TEC DT-7450 User manual

Honeywell

Honeywell DUAL TEC DT-7450 User manual

Honeywell FIRE-LITE ALARMS SD365CO User manual

Honeywell

Honeywell FIRE-LITE ALARMS SD365CO User manual

Honeywell Viewguard PIR AM FAI Instruction manual

Honeywell

Honeywell Viewguard PIR AM FAI Instruction manual

Honeywell Ex-Or MLS2000DF Installation and operation manual

Honeywell

Honeywell Ex-Or MLS2000DF Installation and operation manual

Honeywell Ex-Or Digital Gold Series Installation and operation manual

Honeywell

Honeywell Ex-Or Digital Gold Series Installation and operation manual

Honeywell Miller Revolution User manual

Honeywell

Honeywell Miller Revolution User manual

Honeywell Vitoject 890 User manual

Honeywell

Honeywell Vitoject 890 User manual

Honeywell HAQSPA User manual

Honeywell

Honeywell HAQSPA User manual

Honeywell BW Solo User manual

Honeywell

Honeywell BW Solo User manual

Honeywell 301W User manual

Honeywell

Honeywell 301W User manual

Honeywell IRD 1020.1 User manual

Honeywell

Honeywell IRD 1020.1 User manual

Honeywell MILLER 1032363 User manual

Honeywell

Honeywell MILLER 1032363 User manual

Honeywell Fire Sentry SS3 User manual

Honeywell

Honeywell Fire Sentry SS3 User manual

Honeywell IS216 Installation and operation manual

Honeywell

Honeywell IS216 Installation and operation manual

Honeywell Eclipse Instruction Manual

Honeywell

Honeywell Eclipse Instruction Manual

Popular Security Sensor manuals by other brands

Interlogix RF-EV1012PI-K4 installation manual

Interlogix

Interlogix RF-EV1012PI-K4 installation manual

HDE V-WATCH Operating instructions manual

HDE

HDE V-WATCH Operating instructions manual

CP EBDHS-KNX Product guide

CP

CP EBDHS-KNX Product guide

AJAX LeaksProtect quick start guide

AJAX

AJAX LeaksProtect quick start guide

Cofem A30X Series Wiring diagram

Cofem

Cofem A30X Series Wiring diagram

Vive LVA1055 user manual

Vive

Vive LVA1055 user manual

Satel APD-100 quick start guide

Satel

Satel APD-100 quick start guide

Novatest ZBL-U5 Series instruction manual

Novatest

Novatest ZBL-U5 Series instruction manual

Siemens FDO421 installation instructions

Siemens

Siemens FDO421 installation instructions

SICK KTX-WB9214125A Series manual

SICK

SICK KTX-WB9214125A Series manual

Lightning Protection International Guardian System 5 installation manual

Lightning Protection International

Lightning Protection International Guardian System 5 installation manual

Online Electronics ID5000A operating manual

Online Electronics

Online Electronics ID5000A operating manual

Stanley S100 user manual

Stanley

Stanley S100 user manual

FCS PCorr+ user guide

FCS

FCS PCorr+ user guide

Apollo ORBIS ORB-OH-13003-APO Product guide

Apollo

Apollo ORBIS ORB-OH-13003-APO Product guide

Siemens Sinteso FD20 Guideline

Siemens

Siemens Sinteso FD20 Guideline

AVS OUTSPIDER PA manual

AVS

AVS OUTSPIDER PA manual

Enerlites HMOS installation instructions

Enerlites

Enerlites HMOS installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.