Catalogue number(s): 0 672 26 - 0 784 86 - 5 740 48/98
Detector switch - Dual Tech
SCS
Technical data sheet: S000077070EN-1 Updated: Created: 17/12/2012
7.SETTINGS (continued)
7.1 Detection parameters (continued)
Detection system:
Initial detection: The load is switched on as soon as the first detection
occurs if the natural light level is below the light level threshold.
Maintain: The load remains active if another presence is detected.
Restart: In manual mode. After switch-off, any new detection within a
30 second period triggers an automatic switch-on.
After 30 seconds the device must be switched on manually.
Alarm: an audible signal is emitted before switch-off. (1 minute before,
then 30 seconds, then 10 seconds).
7.2 Light parameters
Light level threshold: Value at which the load comes on if the
natural light level is less than the setting.
Caution:
The device becomes a motion detector at 1275 lux.
Advanced mode:
Calibration: The surrounding light level measured with a luxmeter
must then be transmitted to the sensor (see data sheet
Cat. No. 0 882 30)
.Regulation: Automatic switch-off of the load 10 minutes after
the light level threshold is exceeded with an additional safety
threshold (to avoid lights switching off at the wrong moment).
Light contribution: Quantity of additional lux provided by the load
being switched on.
When the light contribution parameter is set to "Auto" (value 0) on the
configuration tool Cat. No. 0 882 30 the sensor automatically calculates
the light contribution.
Sensor parameter Default
value
Modifiable
parameters
Configuration
tools
0 882 30 0 882 35
Light level threshold 500 lux
20, 100, 300, 500,
1000 lux −
0 - 1275 lux −
Advanced
mode
Calibration −0 - 99995 lux −
Regulation Inactive Activate/
Deactivate −
Light
contribution Auto Auto - 1275 lux −
7.SETTINGS (continued)
7.3 Modifying the parameters using the configuration tools
• 0 882 35: Simplified configuration tool
• 0 882 30: Advanced configuration tool
When the sensor receives an IR command using the configuration tool
it emits a beep acknowledging the modification.
For more information about setting parameters, refer to the data sheet
for the configuration tool Cat. No. 0 882 30.
Range: 1 m.
- Restore to factory settings:
1st press: Short press on LEARN: the LED flashes slowly.
2nd press: Press and hold down LEARN for 10 seconds until the LED
flashes quickly.
8. CONFIGURATION
8.1 Physical configuration
BUS SCS sensor Physical Configuration
The physical configuration only authorises point-to-point addressing:
one single actuator can be controlled via the sensor.
A: Area (0 –A)
PL: Light point (0 – F)
M: Mode (0 – 4)
S: Sensitivity of the motion detector (0 – 3)
T: Time delay (0 – 9)
D: Light level threshold or daylight set point (0 – 5)
The A and PL configurator: addressing
The A and PL configurators provide the address of the actuator to be
controlled.
NB:
- If the product does not have the A and PL configurators positioned
then it is not configured.
- The configuration A=0 and PL=0 does not exist
The M configurator: the modes
The M configurator allows the user to choose the product's modes of
operation:
Mconfigurator Mode
No configurator Automatic On/Off mode & without setting
range & with presence detection
1Automatic On/Off mode & light level measure
& without presence detection
2Supervision mode
3Automatic On/Off mode & setting range &
with detection
4Automatic On/Off mode & setting range &
without detection