Honeywell Aquatrol W964F User manual

Honeywell
THE
W964F
AQUATROL
PROVIDES
RESET
CONTROLOF
HYDRONIC
BOILERS
IN
COM-
MERCIAL
BUILDINGS,
MULTI-FAMILY
DWELUNGS,
OFFICES,
SCHOOLS
AND
GAR¬
DEN
APARTMENTS.
THE
W964F
CAN
BE
USED
EITHER
IN
THE
ON-OFF
MODE
TO
DIRECTLY
CONTROL
THE
BURNER,
OR
IN
THE
PROPORTIONAL
PLUS
INTEGRAL
(P+l)
MODE
TO
CONTROL
A
MOTORIZED
3-WAY
MIXING
VALVE.
FEATURES
□
Field
selection
of
on-off
or
proportional
+
integral
(P+l)
operation.
P+l
provides
stable
temperature
control
without
offset.
□
Selectable
outdoor
reset
ratio
from
1:3
to
2.5:1.
□
Selectable
parallel
adjustment
to
accom¬
modate
individual
building
construction.
□
7-day
quartz
clock
with
50-hr
battery
backup
for
programmable
setback
schedules.
□
Adjustable
differential,
from
7
F
to
30
F
[4
C
to
16
C]
in
on-off
mode,
to
match
burner
operation
with
boiler
characteristics.
□
Adjustable
motor
timing
to
1
or
4
minutes
in
P+l
mode.
□
Line
or
low
voltage
output,
no
external
transformer
needed
to
power
motor.
□
Indicating
LEDs
on
panel
show
when
valve
is
opening
or
closing.
□
Solid
state
balance
circuit
provides
P+l
control
for
use
with
Modutrol
motors
without
balance
relays,
or
with
S684
Step
Controller.
□
Options
include
remote
control
panel
or
space
temperature
compensating
sensor.
■
nils
III
Jill
5SSISS
ms
NMMi
MitoKi
llilllillipill
'./
/
■■■
%
'
•
P.G.
Rev.
2-89
Form
Number
63-2036—4
©
Honeywell
Inc.
1989

MODELS:
W964F1037
Aquatrol
panel
with
7-day
programmable
timer.
W964F1045
Aquatrol
panel
without
programmable
timer.
AMBIENT
TEMPERATURE
RATING:
36
F
to
122
F
[2
C
to
50
C].
AMBIENT
RELATIVE
HUMDITIY
RATING:
20
to
90%
RH.
ELECTRICAL
RATINGS:
Input
Voltage—120
Vac
Output
Voltage—24
Vac
or
120
Vac
Frequency—50/60
Hz
Power—2.5
VA
Relay
Output
Rating—1.25
AFL
at
120
Vac
Internal
Low
Voltage
Transformer
Output—20
VA
at
24
Vac,
60
Hz.
RESET
RATIO:
Adjustable
from
1:3
to
2.5:1
(ratio
of
change
in
outdoor
air
temperature
to
change
in
heating
water
temperature).
INITIAL
CONTROL
POINT:
70
F
[21
C].
NIGHT
SETBACK
OF
DISCHARGE
WATER:
Adjustable
from
0
F
to
75
F
[0
C
to
42
C].
OUTDOOR
TEMPERATURE
RANGE:
-22
F
to
68
F
[-30
C
to
20
C].
PARALLEL
SHIFT:
Adjustable
from
+35
F
to
-35
F
[-19
C
to
+19
C].
ACTUATOR
MOTOR
SPEED:
Selectable,
1
or
4
minutes
in
P+l
mode.
DIFFERENTIAL:
Adjustable
from
7
F
to
30
F
[4
C
to
17
C]
in
on-off
mode.
TIMER/PROGRAMMER:
Programmable
setback
periods;
7-day
or
24-hour
available.
Accuracy
±5
sec
per
month.
Battery
backup
time—50
hr.
Minimum
stage
operation—3
hr.
SENSORS:
See
Table
1.
DIMENSIONS:
See
Fig.
1.
FIG.
1—W964F
DIMENSIONS
IN
in.
[mm
IN
BRACKETS].
TABLE
1—SENSOR
CHARACTERISTICS
MODEL
DESCRIPTION
TEMPERATURE
RANGE
F[C]
RESISTANCE
Ohms
@
77
F
[25
C]
T7043B1013
Outdoor
Sensor
680
T7044A1014
Indoor
Sensor
(strap-on)
68
to
212
[20
to
100]
4100
T7043A1023
Indoor
Sensor
(immersion)
68
to
212
[20
to
100]
4100
continued
on
page
3
WHEN
PURCHASING
REPLACEMENT
AND
MODERNIZATION
PRODUCTS
FROM
YOUR
TRADELINE
WHOLESALER
OR
YOUR
DISTRIBUTOR,
REFER
TO
THE
TRADELINE
CATALOG
OR
PRICE
SHEETS
FOR
COMPLETE
ORDERING
NUMBER,
OR
SPECIFY—
1.
Order
number.
4.
Indoor
sensor,
immersion
or
strap-on
type.
2.
With
or
without
clock.
5.
Additional
accessories.
3.
Outdoor
Sensor.
IF
YOU
HAVE
ADDITIONAL
QUESTIONS,
NEED
FURTHER
INFORMATION,
OR
WOULD
LIKE
TO
COMMENT
ON
OUR
PRODUCTS
OR
SERVICES,
PLEASE
WRITE
OR
PHONE:
1.
YOUR
LOCAL
HONEYWELL
BUILDING
CONTROLS
SALES
OFFICE
(CHECK
WHITE
PAGES
OF
YOUR
PHONE
DIRECTORY).
2.
BUILDING
CONTROLS
DIVISION
CUSTOMER
SERVICE
HONEYWELL
INC.,
1885
DOUGLAS
DRIVE
NORTH
MINNEAPOLIS,
MINNESOTA
55422-4386
(612)
542-7500
(IN
CANADA—HONEYWELL
LIMITED/HONEYWELL
LIMITEE,
740
ELLESMERE
ROAD,
SCARBOROUGH,
ONTARIO
M1P
2V9)
INTERNATIONAL
SALES
AND
SERVICE
OFFICES
IN
ALL
PRINCIPAL
CITIES
OF
THE
WORLD.
2

ACCESSORIES:
1.
W9260A1014
Digital
Remote
Control
Unit
with
digital
24-hour
clock.
2.
T7160A1004
Space
Compensation
Sensor.
3.
197918
Concealed
Set
Point
Cover
for
T7160A1004.
4.
7617ADR
Conduit
Adapters
(2),
convert
com¬
pression
fittings
on
sensors
to
1
/2
in.
conduit.
5.
197943
24-hour
Quartz
Timer/Programmer.
6.
T
238
Outdoor
Thermostat
controls
circulating
pump
in
response
to
outdoor
temperature.
REPLACEMENT
PARTS:
1.
F
u
s
es
(Purchase
from
electrical
wholesaler.)
Main,
1/4
amp
slow-blow—MDL
1/4
(Littlefuse
213.250
or
equivalent).
See
Fig.
18
for
location.
Output,
1
amp
slow-blow—MDL
1
(Littlefuse
213.001
or
equivalent).
See
Fig.
18
for
location.
WHEN
INSTALLING
THIS
PRODUCT
.
.
.
1.
Read
these
instructions
carefully.
Failure
to
follow
them
could
damage
the
product
or
cause
a
hazardous
condition.
2.
Check
the
ratings
given
in
the
instructions
and
on
the
product
to
make
sure
the
product
is
suitable
for
your
application.
3.
Installer
must
be
a
trained,
experienced
service
technician.
4.
After
installation
is
complete,
check
out
product
operation
as
provided
in
these
instructions.
CAUTION
Disconnect
power
supply
before
making
wiring
connections
to
prevent
electrical
shock
and
equipment
damage.
NSTALLING
SENSORS
To
properly
install
and
check
out
the
T7043A1023
(immersion,
indoor),
T7043B1013
(outdoor)
or
T7044A1014
(strap-on,
indoor)
sensors,
refer
to
the
instructions
provided
with
the
sensors
or
the
instructions
supplied
with
the
W964F.
The
following
graphical
in¬
formation
provides
resistance
versus
temperature
data
for
measuring
the
sensor’s
thermistor
resistance
(see
Figures
2
and
3).
INSTALLING
W964F
AQUATROL
PANEL
(Figs.
4,5)
Perform
the
following
installation
steps
in
sequence.
Where
additional
information
is
required,
references
are
given
to
appropriate
sections
of
this
specification.
1.
Select
a
location
for
the
Aquatrol
panel
that
will
provide
access
to
controls
for
adjustment
and
service.
2.
Detach
Aquatrol
panel
and
barrier
plate
from
subbase.
3.
For
surface
mounting,
attach
subbase
to
wall
using
two
No.
10
screws
provided.
For
flush
mounting,
cut
panel
hole
(Fig.
5)
and
mount
Aquatrol
using
two
special
clamps
provided.
4.
Connect
wiring
as
shown
in
appropriate
system
diagram
(Figs.
6-18)
in
Wiring
section.
Knockouts
are
provided
in
subbase
for
1
/2
and
3/4
in.
conduit.
BEFORE
APPLYING
POWER
TO
SYSTEM
5.
On
back
of
Aquatrol
panel,
select
mode
of
operation
(on-off
or
P+l).
Set
boiler
water
differential
if
in
on-off
mode;
select
motor
timing
if
in
P+l
mode.
See
Mode
Selection,
Boiler
Water
Differential
Selection,
and
motor
timing
in
Settings
and
Adjustments
section.
6.
On
subbase,
select
mode
of
operation
(on-off
or
P+l)
and
voltage
(line
or
low).
See
Mode
Selection
in
Settings
and
Adjustments
section.
7.
After
settings
and
adjustments
are
made
on
subbase,
attach
barrier
plate
to
subbase
(single
screw
through
center).
3
63
-
203
6—4

FIG.
4—W964F
SURFACE
MOUNTING.
FIG.
5—W964F
FLUSH
MOUNTING.
8.
Attach
Aquatrol
panel
to
subbase
(two
screws
Adjustments
section.
through
panel).
10.
Attach
cover
to
panel
and
if
restriction
of
function
9.
Before
securing
cover
to
panel,
set
timer/pro-
knob
is
desired,
engage
locking
pin.
grammer,
reset
ratio,
function
switch,
parallel
shift
and
11.
Check
operation
of
system
as
shown
in
Checkout
setback.
Refer
to
appropriate
portion
of
Settings
and
section.
4

Disconnect
power
supply
before
making
wiring
con¬
nections
to
prevent
electrical
shock
and
equipment
damage.
All
wiring
must
comply
with
applicable
electrical
codes,
ordinances
and
regulations.
Connect
W964F
Aquatrol
Panel,
sensors
and
acces¬
sories
as
shown
in
typical
system
diagrams.
For
on-off
control
applications,
refer
to
Figs.
6-8.
For
3-way
mixing
valve
(P+l)
applications,
refer
to
Figs.
9-16.
For
hookup
of
optional
W9260A
Remote
Control
Panel
and
T7160A
Space
Temperature
Compensating
Unit,
refer
to
Fig.
16.
When
replacing
a
Honeywell
W902
Panel
with
a
W964F
Panel,
refer
to
Fig.
17.
In
systems
with
valve
ports
A
and
B
reversed,
refer
to
Fig.
18.
W9260A
(OPTION)
SYSTEM.
FIG.
8—HOOKUP
OF
W964F
TO
TYPICAL
FLAME
SAFEGUARD
DEVICE
ON-OFF
SYSTEM.
A
A\
POWER
SUPPLY.
PROVIDE
DISCONNECT
MEANS
AND
OVERLOAD
—
PROTECTION
AS
REQUIRED.
/2\
ADD
LINK
FOR
ON/OFF
MODE.
/3\
THERMOSTAT
TERMINALS
ON
BOILER
CONNECTION
PANEL.
/4\
TERMINALS
B
TO
A
MAKE
ON
TEMPERATURE
FALL.
E1040B
r=-1
W9260A
I'-
1
»—
I
(OPTION)
AQUATROL
I
l/vj
T7160A
OUTDOOR
RESET]
|-^(OPTION)
SENSOR
CONTROLLER
I
j
T7043B
W964F
I
|
FIG.
7—HOOKUP
OF
W964F
TO
TYPICAL
BOILER
1-1
WITH
LOW
VOLTAGE
THERMOSTAT
TERM-
FIG.
9—HOOKUP
FOR
W964F
IN
TYPICAL
3-WAY
INALS—ON-OFF
SYSTEM.
MIXING
VALVE
SYSTEM.
5
63
-
20
3
6
—4

E>
W964F
MAX.
15
V
FIG.
10—HOOKUP
FOR
W964F
AND
M944B
LOW
VOLTAGE
MOTORS.
FIG.
12-HOOKUP
FOR
W964F
AND
M644A,C,D,E
LOW
VOLTAGE
MOTORS
USING
TRANS¬
FORMER
IN
W964F.
FIG.
11—HOOKUP
FOR
W964F
AND
M644A,C,D,E
LOW
VOLTAGE
MOTORS
USING
SEPARATE
TRANS¬
FORMER.
FIG.
13—HOOKUP
FOR
W964F
AND
M644B
LINE
VOLTAGE
MOTORS—MOTOR
POWERED
FROM
SEPARATE
LINE
VOLTAGE
SUPPLY.
6

/l\
POWER
SUPPLY.
PROVIDE
DISCONNECT
MEANS
AND
OVERLOAD
—
PROTECTION
AS
REQUIRED.
A
MOVE
LINK
BD
TO
BL.
/3\
TERMINALS
B
TO
A
MAKE
ON
TEMPERATURE
FALL.
TERMINALS
B
TO
C
MAKE
ON
TEMPERATURE
RISE.
E1Q34
FIG.
14—HOOKUP
FOR
W964F
AND
M644B
LINE
VOLTAGE
MOTORS—MOTOR
POWERED
FROM
W964F.
l
~3||£-24
V,
20
VA
MAX.~]
!
ji
+
°
f
-
A
|
i
1
1
1
D
=
MAX.
j
1
PfWcnQ
1
120
V,
!
1
1
I
I
1
1
125
afl
W964F
l|n
D
|
C
|
B
|
A
|
3
2
1
4
4A
5
6
7
T2
T2
T3
T3
HEATING
STAGES
*
12
3
4
ZlA
5
■
1
W
R
B
G
T
V
NC
NO
NC
NO
NC
NO
NC
NO
NC
NO
6
LI
L2
3
4
P
N
24
V
-1
A
FM
770438
n\
POWER
SUPPLY.
PROVIDE
DISCONNECT
MEANS
AND
OVERLOAD
PROTECTION
AS
REQUIRED.
/2\
SWITCHES
SHOWN
WITH
DEVICE
DEENERGIZED.
A
S684F
HAS
10
SWITCHES.
/A\
HOOK
UP
SHOWN
IS
FOR
HEATING.
/5\
REMOVE
JUMPER
AND
CONNECT
ON-OFF
SWITCH
HERE
IF
S684
MUST
RETURN
TO
START
POSITION
DURING
OFF
CYCLE.
/6\
IF
SEPARATION
OF
SWITCHING
STAGES
AND
CONTROL
OPERATION
IS
DESIRED,
CLIPOUT
JUMPER
(TERMINAL
6
TO
LI)
AND
CONNECT
SEPARATE
POWER
SUPPLY.
,
DIRECTION
OF
MOTOR
ROTATION
IS
AS
VIEWED
FROM
THE
MOTOR
OR
POTENTIOMETER
END.
1L
—
CW
LIMIT
SWITCH
2L
-
CCW
LIMIT
SWITCH
1M
-
CW
MOTOR
WINDING
2M
-
CCW
MOTOR
WINDING
1
R--
RECYCLING
RELAY
^
TERMINALS
G.
T
AND
Y
NOT
USED.
^
REMOVE
LINK
B
TO
D.
k
TERMINALS
B
TO
A
MAKE
ON
TEMPERATURE
FALL.
TERMINALS
B
TO
C
MAKE
ON
TEMPERATURE
RISE.
y,
V4044
DIVERTING
VALVES
BYPASS
RETURN
WATER
AROUND
BOILER
NOT
FIRING.
E1033
FIG.
15—W964F
USED
WITH
S684D,F
STEP
CONTROLLER
IN
MULTISTAGE
HEATING
SYSTEM.
7
63
-
2
0
3
6
—4

NOTE:
THE
W9260A
AND
T7160A
CANNOT
BE
USED
TOGETHER.
24
N
L
I
2
3
j
<k>
i
•
1
LoqJ
A\
WHEN
INSTALLING
THE
OPTIONAL
W9260A
DIGITAL
REMOTE
CONTROL
THE
RESISTOR
AND
LINK
MUST
BE
SNIPPED
OFF
THE
SUBBASE
TERMINALS
5,
6
AND
7.
/2\
WHEN
INSTALLING
THE
OPTIONAL
T7160A
ROOM
TEMPERATURE
SENSOR
THE
RESISTOR
MUST
BE
SNIPPED
OFF
THE
SUBBASE
TERMINALS
6
AND
7.
/3\
TO
W964F
TERMINALS.
FIG.
16—HOOKUPS
FOR
OPTIONAL
W9260A
REMOTE
CONTROL
OR
T7160A
ROOM
TEMPER¬
ATURE
SENSOR.
FIG.
17—HOOKUP
FOR
REPLACING
HONEYWELL
W902
PANEL
WITH
W964F
PANEL
OUTDOOR
SENSOR
T7043B
AQUATROL
RESET
CONTROLLER
W964F
AQUATROL
RESET
CONTROLLER
DISCHARGE
SENSOR
M644,
M944.M945
MOTOR
ON
A
CALL
FOR
HEAT
IN
A
NORMAL
V50I3A
OR
B
HOOKUP,
THE
VALVE
STEM
TRAVELS
UPWARD
OPENING
PORT
B
(SUPPLY
LINE
FROM
BOILER).
WITH
REVERSED
PORT
HOOKUP,
MOTOR
CON¬
TROLLER
WIRING
MUST
BE
REVERSED
SO
THAT
ON
A
CALL
FOR
HEAT
PORT
A
OPENS
AND
PORT
B
CLOSES.
E1047
FIG.
18—HOOKUP
FOR
W964F
AND
V5013A,B
IN
SYSTEM
WITH
VALVE
PORTS
A
AND
B
REVERSED.
8

FRONT
PANEL
ADJUSTMENTS
(Fig.
19)
TIMER/
PROGRAMMER
FUNCTION
SWITCH
—
RATIO
ADJUSTMENT
PARALLEL
SHIFT
ADJUSTMENT
■
SETBACK
TEMPERATURE
ADJUSTMENT
SKETCH
ABOVE
SHOWS
A
PROPORTIONAL
+
INTEGRAL
(P
+
I)
CONTROLLER.
WHEN
THE
AQUATROL
IS
CONVERTED
TO
AN
ON/OFF
CONTROLLER
THE
DECAL
(LEFT,
SUPPLIED)
MUST
BE
APPLIED
OVER
THE
EXISTING
DECAL.
El
055
FIG.
19—AQUATROL
FRONT
PANEL
ADJUSTMENTS.
TIMER/PROGRAMMER
-IMPORTANT-
ALWAYS
TURN
TIMER
CLOCKWISE.
Timer
programming
is
based
on
a
24-hour
or
a
24-hour,
7-day
system.
1.
Insert
red
(1)
pins
in
grooves
opposite
day
and
hour
that
each
occupied
period
is
to
start.
2.
Insert
blue
(0)
pins
opposite
day
and
hour
that
each
setback
(unoccupied)
period
is
to
start.
3.
Turn
the
outer
ring
CLOCKWISE
to
set
the
day
and
time
(24-hour
scale)
opposite
the
white
triangle.
4.
Turn
center
knob
CLOCKWISE
to
set
exact
time
on
the
12-hour
inner
dial.
FUNCTION
SWITCH
In
the
proportional
plus
integral
mode,
the
function
switch
provides
a
choice
of
manual
or
automatic
valve
operation,
and
manual
override
of
the
timer
program
as
follows:
1.
Valve
closed-boiler
side
of
valve
is
closed,
pro¬
ducing
continuous
bypass
of
the
system
(heat
off).
2.
Valve
stop—power
is
removed
from
the
actuator,
leaving
the
valve
in
an
intermediate
position.
3.
Valve
opened—actuator
is
driven
to
the
open
position,
providing
no
mixing
of
return
water
(heat
on).
4.
Automatic—normal
operating
position,
allowing
the
timer/programmer
to
switch
between
occupied
and
unoccupied
settings.
5.
Continuous
occupied
setting—overrides
setback,
providing
constant
comfort
discharge
water
tem¬
perature.
6.
Continuous
unoccupied
setting—overrides
tim¬
er/programmer,
providing
constant
setback
discharge
water
temperature.
9
63
-
2
03
6—4

In
the
on-off
mode,
the
function
switch
provides
a
choice
of
manual
or
automatic
contact
operation,
and
manual
override
of
the
timer
program
as
follows:
1.
Contact
open—burner
off.
2.
Standby.
3.
Contact
closed—burner
on.
4.
Automatic—normal
operating
position,
allowing
the
timer/programmer
to
switch
between
occupied
and
unoccupied
settings.
5.
Continuous
occupied
setting—overrides
setback,
providing
constant
comfort
discharge
water
tem¬
perature.
6.
Continuous
unoccupied
setting—overrides
tim¬
er/programmer,
providing
constant
setback
discharge
water
temperature.
RESET
RATIO
The
reset
ratio
is
the
ratio
of
outdoor
temperature
change
to
the
resulting
change
in
discharge
water
temperature.
Reset
automatically
adjusts
the
boiler
dis¬
charge
water
temperature
in
response
to
changes
in
outdoor
temperature.
When
outdoor
temperature
rises,
water
temperature
is
automatically
lowered,
and
when
outdoor
temperature
falls,
water
temperature
is
raised.
This
saves
energy
by
reducing
transmission
losses,
stack
losses,
and
heat
losses
resulting
from
open
window
control.
The
W964F
provides
continuously
adjustable
reset
ratios
from
1:3
to
2.5:1.
The
1:3
ratio
has
the
greatest
resetting
effect
on
water
temperature
in
that
a
1
degree
change
in
outdoor
temperature
causes
a
3
degree
change
in
water
temperature.
The
2.5:1
ratio
has
the
least
resetting
effect
since
it
requires
a
2.5
degree
outdoor
temperature
change
to
produce
1
degree
change
in
water
temperature.
Note
on
the
ratio
graph
(behind
ratio
dial)
that
the
curve
with
the
1:3
ratio
has
the
steepest
slope,
while
the
2.5:1
ratio
has
the
shallowest
slope.
Reset
is
adjusted
by
means
of
the
front
panel
ratio
dial.
The
ratios
marked
on
the
dial
are
shown
as
curves
on
the
graph
behind
the
dial.
However,
the
dial
can
be
set
between
marked
numbers
and
those
ratios
must
be
interpolated
between
curves
on
the
graph.
Suggested
ratios
for
several
different
heating
systems
and
design
temperatures
are
shown
in
Table
2.
PARALLEL
SHIFT
Parallel
shift
provides
fine
tuning
of
reset
by
creating
a
reset
ratio
curve
parallel
to
the
curve
originally
deter¬
mined
by
the
selected
reset
ratio.
The
amount
of
parallel
shift
is
adjustable
±35
F
[±19
C].
With
the
parallel
shift
set
at
0
F,
all
reset
ratio
curves
relate
to
an
initial
set
point
of
70
F
for
both
outdoor
temperature
and
discharge
temperature.
The
parallel
shift
setting
allows
the
initial
control
point
of
the
dis¬
charge
temperature
(70
F)
to
be
shifted
by
a
maximum
of
±35
F
[±19
C].
For
example,
with
the
parallel
shift
setting
at
+10
F,
the
initial
control
point
of
the
discharge
temperature
would
be
80
F
(refer
to
chart
on
ratio
adjustment
dial
on
face
of
W964F).
Suggested
values
of
parallel
shift
for
several
different
heating
systems
and
design
temperatures
are
shown
in
Table
2.
TABLE
2—RESET
RATIO
AND
PARALLEL
SHIFT
SELECTION
GUIDE
TYPE
RADIATION
HEATING
MEDIUM
TEMPER¬
ATURE
AT
DESIGN
TEMP.
(°F)
DESIGN
TEMPERATURE
-20
F
1
OF_1
+20
F
RESET
RATIO
PARALLEL
SHIFT
RESET
RATIO
PARALLEL
SHIFT
RESET
RATIO
PARALLEL
SHIFT
Direct
Standing
170-190
1:1
+10
F
1:1.5
+10
F
1:2
+15
F
Convector
or
Baseboard
180-200
1:1.5
0
1:2.5
+10
F
1:2.5
+5
F
Fan
Coil
Heating
Only
165-180
1:1
+5
F
1:1.5
+10
F
1:2
0
Heating/Cooling
130-140
1:5.1
+10
F
1:1
0
1:1
+10
Indirect
Floor
Radiant
90
Not
Recom.
—
2.5:1
-25
F
2.5:1
-15
F
Ceiling
Radiant
110
2.5:1
-15
F
2.5:1
-5
F
2.5:1
0
NOTE
ON
SETBACK
TEMPERATURE
ADJUSTMENT
The
Aquatrol
panel
is
a
water
temperature
controller—the
scale
of
the
setback
adjustment
being
calibrated
in
degrees
of
water
temperature.
A
change
of
±4
F
in
water
temperature
is
equivalent
to
a
change
of
±1
F
in
space
temperature.
SETBACK
TEMPERATURE
ADJUSTMENT
The
Aquatrol
maintains
boiler
discharge
water
at
control
point
temperature
during
occupied
periods.
The
control
point
is
determined
by
the
reset
ratio
adjustment,
parallel
shift
adjustment
and
by
outdoor
temperature.
Additional
energy
can
be
saved
by
setting
back
(decreasing)
the
control
point
during
unoccupied
periods.
The
time
of
each
setback
period
is
determined
by
the
placement
of
the
blue
(0)
pins
on
the
tim¬
er/programmer.
To
obtain
the
desired
amount
of
setback,
turn
the
discharge
water
temperature
setback
adjustment
to
the
10

desired
value
within
the
range
of
0
F
to
76
F
[0
C
to
42
C].
A
setback
in
discharge
water
temperature
of
4
degrees
is
approximately
equivalent
to
a
setback
of
1
degree
in
space
temperature.
To
obtain
a
10-degree
setback
in
space
temperature,
the
setback
knob
should
be
set
to
40
F
[22
C].
MOTOR
SPEED
AND
BOILER
DIFFERENTIAL
ADJUSTMENTS
(Fig.
20)
(4CT0
16C)
ei
049
FIG.
20—W964F
PANEL,
REAR
VIEW.
applications,
the
mode
selector
must
be
turned
to
the
on-off
mode
(fully
counterclockwise
position).
A
l\
JUMPER
TERMINALS
D
AND
B.
FIG.
21—W964F
SUBBASE.
ON-OFF
CONTROL
OF
BURNER
A.
Set
mode
selector
to
ON-OFF
mode
(counter¬
clockwise
position).
B.
Set
boiler
water
differential
to
desired
value
within
7
F
to
30
F
[4
C
to
16
C]
range.
An
initial
differential
setting
of
10
F
[5.5
C]
is
recommended
as
the
number
of
degrees
through
which
the
discharge
water
must
pass
between
relay
make
and
break.
C.
Select
line
or
low
voltage
input
to
motor.
The
subbase
is
shipped
with
jumper
in
low
voltage
position
(jumper
between
terminals
D
and
B).
For
low
voltage
input
to
motor,
verify
that
this
jumper
is
in
place.
For
line
voltage
input
to
motor,
remove
jumper
from
D
and
B,
and
connect
jumper
to
L
and
B.
D.
Connect
jumper
between
terminals
1
and
2.
MOTOR
SPEED
SELECTION
In
the
P+l
mode,
the
motor
speed
selector
screw
provides
timing
either
for
4-minute
motors
(fully
clockwise
)
or
for
1
-minute
motors
(fully
counter¬
clockwise
).
Determine
timing
from
the
motor
label.
BOILER
WATER
DIFFERENTIAL
SELECTION
When
Aquatrol
is
used
in
on-off
system
applications,
set
the
boiler
water
differential
screw
to
the
required
differential—within
the
range
of
7
F
to
30
F
[4
C
to
16
C].
An
initial
differential
setting
of
10
F
[5.5
C]
is
recom¬
mended.
MODE
SELECTION
(Figs.
20,
21)
The
Aquatrol
is
shipped
with
the
mode
selector
screw
set
in
the
proportional
plus
integral
mode
(fully
clockwise
position)
to
control
a
motorized
3-way
mixing
valve.
When
aquatrol
is
used
in
on-off
system
P+l
MODE
(For
3-way
mixing
valve
control)
PROPORTIONAL
PLUS
INTEGRAL
(P+l)
CONTROL
Proportional
control
is
corrective
valve
action
that
is
in
proportion
to
the
error
or
deviation
of
the
controlled
medium
temperature
from
set
point
temperature.
Proportional
plus
integral
control
moves
the
valve
at
a
speed
proportional
to
the
error
or
deviation
of
controlled
medium
temperature
from
set
point
temperature.
That
is,
the
valve
is
moved
faster
as
the
error
gets
larger.
This
eliminates
the
offset
error
due
to
load
changes.
A.
Set
mode
selector
to
P+l
mode
(clockwise
position).
B.
Set
motor
speed
selector
to
desired
time
(1
or
4
minutes).
C.
Verify
that
no
jumper
is
connected
between
terminals
1
and
2.
11
63
-
2
036-4

CHECKOUT
AND
TROUBLE!
CHECKOUT
BEFORE
APPLYING
POWER
TO
THE
SYSTEM
.
.
.
1.
Check
to
be
sure
all
connections
are
correct
and
secure.
2.
Check
all
settings
and
adjustments
(see
Settings
and
Adjustments
section).
3.
T
u
r
n
power
on
and
check
system
operation.
If
trouble
occurs,
refer
to
the
troubleshooting
chart,
Table
3,
for
corrective
action.
TABLE
3—W964F
TROUBLESHOOTING
CHART
SYMPTOM
POSSIBLE
CAUSE
CHECK
CORRECTIVE
ACTION
System
shows
no
sign
of
life.
No
power
to
system.
Check
fuses
and
main
disconnects.
Correct
and
replace
main
fuse
as
necessary
See
“Motor
does
not
move
at
all”
below.
(page
11).
System
blows
main
Faulty
wiring
to
transformer.
Check
line
voltage
wiring.
tuse
(tou
mA)
—located
on
Aquatrol
panel
printed
circuit
board
(page
11).
Faulty
transformer.
Check
transformer
as
follows:
Switch
off
the
unit
and
remove
the
Aquatrol
from
subbase.
Route
2
wires
through
a
wiring
knockout
in
the
subbase
and
connect
them
to
terminals
D
and
3.
Connect
the
free
ends
of
the
wires
to
a
suitable
ac
voltmeter.
Replace
Aquatrol
on
subbase
and
switch
unit
on.
Meter
should
read
approx.
24
Vac.
Remove
wires
from
unit
after
transformer
test.
Replace
Aquatrol
if
necessary.
Panel
powered,
LED’s
light,
but
no
power
on
output
terminals
C
or
A.
Output
fuse
blown
or
faulty
wiring.
Check
fuse
and
wiring.
Replace
output
fuse
(see
page
11).
Correct
wiring.
Motor
does
not
move
at
all
(stopped
in
midstroke).
Failure
in
motor.
Use
function
switch
to
check
motor
action
(positions
1
and
3).
Use
voltmeter
to
check
voltage
at
motor.
Replace
motor
if
necessary.
No
power
to
motor.
If
line
voltage
is
not
supplied
from
Aquatrol,
check
power
supply.
Repair
power
supply
as
necessary.
Component
failure
in
panel.
Function
switch-operates
motor
but
turning
adjustment
knobs
does
not.
Replace
panel.
Linkage
is
jammed.
Inspect
linkage—operate
manually.
Repair
linkage,
valve
damper,
or
sequencer.
Loose
connections.
Check
that
Aquatrol
terminals
C,
A
and
B
are
connected
to
motor.
Correct
wiring
as
necessary.
continued
on
next
page
12

Table
3
continued
SYMPTOM
POSSIBLE
CAUSE
CHECK
CORRECTIVE
ACTION
System
overheats
in
mild
weather.
Faulty
outdoor
sensor.
Check
outdoor
sensor
resistance
(see
page
3,
Fig.
3).
Replace
if
necessary.
Parallel
shift
set
too
high;
e.g.,
at
+35
F.
Check
operation
with
lower
shift
setting
‘’setting
reset
ratio
and
parallel
shift”
(page
10).
Lower
parallel
shift
setting
if
necessary.
Do
not
alter
ratio
setting.
Outdoor
sensor
improperly
located.
Check
outdoor
sensor
for
ice
or
snow
buildup
or
other
reason
for
cooling.
Relocate
sensor
if
necessary.
Too
little
heat
in
very
cold
weather.
Ratio
setting
or
parallel
shift
setting
too
low;
e.g,-35
F
parallel
shift.
Check
setting
of
reset
ratio
and
parallel
shift
(page
10).
Change
ratio
schedule
or
parallel
shift
to
increase
hot
water
temperature
in
very
cold
weather.
Outdoor
sensor
faulty.
Check
outdoor
sensor
resistance.
Replace
outdoor
sensor
if
necessary.
System
undersized.
Check
for
100%
boiler
operation.
Increase
heating
capacity
if
necessary.
Outdoor
sensor
not
located
properly.
Check
to
see
that
sensor
can
detect
average
outdoor
air
temperature.
Relocate
sensor
if
necessary.
No
reduction
in
flow
water
temperature
during
night
setback
(NSB).
Incorrect
function
switch
setting.
Check
function
switch
is
at
position
4
(automatic)
and
clock
is
set
for
night
setback
period.
Change
function
switch
to
position
4
if
necessary.
Faulty
clock.
Visually
inspect
for:
(
i)
incorrect
time
settings
(ii)
no
clock
movement
(iii)
correct
positioning
of
program
override
switch
(page
9)
could
be
in
(1)
position
(
i)
reset
time
(ii)
replace
clock
(iii)
manually
adjust
override
switch
to
(0)
position
and
check
program
pins
Component
failure.
Adjusting
NSB
control
to
76
F
has
no
effect
on
flow
water
temperature
during
NSB
period.
Replace
panel.
Motor
closes
and
will
not
open
(no
heat).
Function
switch
set
to
position
1
(valve
permanently
closed).
Check
function
switch
setting.
Change
function
switch
setting
to
other
position,
if
necessary.
Sensors
are
incorrectly
wired.
Visual
inspection,
check
wiring
diagram.
Correct
sensor
wiring
or
replace
if
necessary.
Either
sensor
is
shorted
out.
Measure
sensor
resistance.
Correct
sensor
wiring
or
replace
if
necessary.
continued
on
next
page
13
63
-
203
6—4

Table
3
continued
SYMPTOM
POSSIBLE
CAUSE
CHECK
CORRECTIVE
ACTION
Motor
opens
and
will
not
close
(full
heat).
Open
circuit
in
either
sensor.
Measure
sensor
resistance.
Correct
sensor
wiring
or
replace
if
necessary.
Function
switch
set
to
position
3
(valve
permanently
open).
Check
function
switch
setting.
Change
function
switch
setting
to
other
position,
if
necessary.
System
“short
cycles”
(repositions
between
ON
and
OFF
at
very
short
intervals).
Hot
water
sensor
improperly
located.
Check
positioning
of
sensor
relative
to
heat
source.
Relocate
sensor.
Ratio
setting
too
high.
Check
ratio
schedule.
Lower
ratio
setting
by
one
position
and
monitor
system
operation.
Reduce
ratio
setting
by
one
or
more
further
positions
if
required.
Parallel
shift
control
set
too
high;
e.g.,
at
+35
F.
Check
parallel
shift
setting
and
ratio
schedule.
Reduce
the
parallel
shift
setting
by
10
F.
If
system
operation
does
not
improve,
reduce
setting
further.
Do
not
alter
ratio
setting.
Motor
speed
preadjustment
incorrectly
set
to
match
motor
used
in
system.
Check
motor
timing
(see
tag-on
motor).
Set
motor
speed
preadjustment
to
correspond
to
speed
of
motor
used
in
system
(see
page
11).
Valve
greatly
oversized.
Check
rated
output
against
estimated
load
requirement.
Reduce
system
capacity
if
necessary.
Differential
setting.
Check
that
setting
is
not
too
low.
Adjust
as
recommended
on
page
11.
O
PE
RATION
■
".V-
■
GENERAL
Most
boiler
systems
heat
water
to
a
constant
tempera¬
ture
regardless
of
the
outdoor
temperature.
In
fact,
discharge
water
temperatures
in
hydronically
heated
systems
are
set
sufficiently
high
to
heat
a
building
during
the
coldest
outdoor
temperatures.
While
this
setting
is
adequate
for
extreme
settings,
it
wastes
energy
during
mild
weather
by
maintaining
too
much
heat
in
the
system
and
overheating
the
building.
Outdoor
reset
can
result
in
15%
or
20%
savings
in
heating
energy
by
lowering
the
boiler
discharge
water
temperature
as
the
outdoor
air
temperature
increases,
and
by
programming
lower
water
temperatures
during
unoccupied
periods.
These
reset
savings
are
the
result
of
reduced
transmission
losses,
stack
losses,
heat
losses
from
open
window
control,
and
use
of
the
timer
pro¬
grammer
to
set
back
the
boiler
temperature
during
unoccupied
periods.
Transmission
losses
occur
when
heat
is
lost
through
pipes
in
non-air
conditioned
passageways,
ceiling
and
underground
piping
routes.
Stack
losses
occur
in
ail
gas-and
oil-fired
boilers.
Resetting
boiler
water
discharge
temperature
downward
reduces
stack
losses.
For
optimum
savings,
return
water
should
be
piped
around
boilers
that
are
not
firing.
Open
window
control
losses
occur
when
occupants
attempt
to
reduce
the
effects
of
overheating
by
opening
windows.
14

Outdoor
reset
also
improves
comfort
control
and
extends
the
life
of
the
burner
and
boiler.
Without
reset,
system
temperatures
are
maintained
too
high
during
mild
weather.
This
produces
uncomfortable
space
temper¬
atures
and
causes
unnecessary
cycling
of
the
burner.
Systems
without
reset
are
susceptible
to
expansion
and
contraction
caused
by
large
changes
in
water
temperature.
This
causes
annoying
noise
and
excessive
system
wear.
Outdoor
reset
reduces
these
undesirable
effects
by
maintaining
lower
and
more
constant
water
temperatures.
The
W964F
Aquatrol
System
senses
both
outdoor
temperature
and
discharge
water
temperature.
As
outdoor
temperature
changes,
the
Aquatrol
resets
the
boiler
water,
following
a
selected
ratio.
ON-OFF
AND
PROPORTIONAL
+
INTEGRAL
(P+l)
CONTROL
The
Honeywell
W964F
Aquatrol
System
is
designed
to
provide
any
commercial
building
with
reliable,
effective
control
over
hydronic
heating
systems.
The
Aquatrol
has
field
selectable
on-off
burner
control
or
P+l
control
of
a
motorized
3-way
mixing
valve.
ON-OFF
CONTROLOF
BOILERS
WITHOUT
DOMESTIC
WATER
HEATING
COILS
On-off
control
of
burners
to
reset
the
boiler
water
temperature
is
used
mostly
with
the
smaller
commercial
boilers.
The
W964F
directly
controls
the
operation
of
the
burner
through
output
contacts,
thereby
controlling
the
temperature
of
the
discharge
water.
W964F
P+l
CONTROL
OF
LARGER
BOILERS
AND
OF
BOILERS
WITH
DOMESTIC
WATER
HEATING
COILS
P+l
control
is
used
to
reset
the
discharge
water
temperature
by
positioning
a
motorized
mixing
valve.
This
valve
bypasses
return
water
around
the
boiler
and
mixes
it
with
the
correct
amount
of
water
leaving
the
boiler
to
provide
the
required
temperature
of
water
being
discharged
from
the
valve
into
the
heating
system.
Mixing
valves
are
used
with
reset
systems
for
three
important
reasons:
1.
Boilers
with
domestic
water
heating
coils
must
be
maintained
at
a
preset
minimum
temperature
to
provide
the
capacity
to
serve
the
domestic
water
needs
of
the
building.
2.
The
manufacturers
of
many
large
fire-tube
boilers
require
the
boiler
to
be
maintained
at
a
present
temperature
(usually
170
F
to
190
F
[77
C
to
88
C])
regardless
of
domestic
water
heating
coils.
3.
P+l
control
of
motorized
3-way
mixing
valves
provides
much
moreaccurate
control
of
discharge
water
temperature
than
either
on-off
control
of
burners
or
conventional
modulating
control
of
mixing
valves.
With
P+l
control,
there
is
zero
offset
of
the
required
discharge
water
temperature.
In
other
words,
the
actual
discharge
temperature
does
not
fall
below
or
rise
above
the
discharge
temperature
required
by
the
reset
sys¬
tem.
This
closer
temperature
control
produces
more
comfort
and
more
energy
savings
than
on-off
or
mod¬
ulating
control.
In
new
installations
with
the
Aquatrol,
any
of
the
Honeywell
series
60
actuators,
such
as
the
M644A-E,
are
used
with
V5013A.B
mixing
valves.
In
retrofit
of
older
installations
using
W902
reset
systems,
the
W964F
may
be
used
to
control
existing
series
90
motors
without
internal
balancing
relays
(M944B,E
or
M945B,C,G).
APPLICATION
VERSATILITY
All
hydronically
heated
buildings,
including
those
with
uncontrolled
radiation,
controlled
radiation,
or
variable
air
volume
can
benefit
from
the
W964F
Aquatrol
System.
UNCONTROLLED
RADIATION
The
Aquatrol
System
can
be
used
to
provide
out¬
door
reset
in
buildings
with
uncontrolled
radiation,
which
includes
standing
radiators,
baseboards
and
convectors.
The
Aquatrol
controls
the
building’s
space
tem¬
perature
and
is
less
expensive
than
zone
control.
The
Aquatrol
saves
energy
by
reducing
overheating
and
providing
night
setback
during
unoccupied
periods.
CONTROLLED
RADIATION
The
W964F
can
also
be
used
to
provide
outdoor
reset
in
buildings
with
controlled
radiation,
which
in¬
cludes
fan
coils,
unit
ventilators,
unit
heaters,
radiator
valves,
and
terminal
reheat.
In
these
applications,
the
Aquatrol
improves
space
temperature
control
by
providing
water
at
a
tem¬
perature
very
close
to
the
heating
requirements.
The
zone
and
room
thermostats
fine
tune
the
water
flow
for
precise
temperature
control.
Reset
ensures
lowered
heating
water
temperature
as
the
weather
becomes
milder.
This
can
speed
the
changeover
from
heating
to
cooling
on
a
two-pipe
fan
coil
system.
(Water
over
90
F
[32
C]
must
not
be
sent
to
the
chiller.)
VARIABLE
AIR
VOLUME
In
variable
air
volume
cooling
with
perimeter
heating
applications,
the
W964F
provides
controlled
heating
of
perimeter
zones
and
reduces
the
conflict
between
the
heating
and
cooling
systems.
Additional
energy
savings
can
be
gained
by
using
the
built-in
night
setback.
If
questions
arise
regarding
this
product,
contact
your
local
distributor
or
Honeywell
representative.
Honeywell
Inc.
International
Sales
Offices
in
all
principal
cities
of
the
world.
Manufacturing
in
Australia,
Canada,
Finland,
1885
Douglas
Drive
N.
France,
Germany,
Japan,
Mexico,
Netherlands,
Spain,
Taiwan,
United
Kingdom,
U.S.A.
Golden
Valley,
MN
55422-4386
PRINTED
IN
U.S.A.
Other manuals for Aquatrol W964F
1
Table of contents
Other Honeywell Server manuals

Honeywell
Honeywell HP ProLiant DL360P Gen8 User manual

Honeywell
Honeywell AutomationServer User manual

Honeywell
Honeywell LANSRLU1 Setup guide

Honeywell
Honeywell T610 Technical manual

Honeywell
Honeywell Uniformance R300 User manual

Honeywell
Honeywell XYR3011 User manual

Honeywell
Honeywell T320 Technical manual

Honeywell
Honeywell MZ-PCSV74 Technical manual

Honeywell
Honeywell Q7055B1047 User manual

Honeywell
Honeywell HAS-QNH User manual