Honeywell MZ-PCSV74 Technical manual

Dell T130 Honeywell Server Planning, Installation and
Service Guide
HWDOC-X450-en-D
November 2019

Disclaimer
This document contains Honeywell proprietary information. Information contained herein is to be used
solely for the purpose submitted, and no part of this document or its contents shall be reproduced,
published, or disclosed to a third party without the express permission of Honeywell International Sàrl.
While this information is presented in good faith and believed to be accurate, Honeywell disclaims the
implied warranties of merchantability and fitness for a purpose and makes no express warranties
except as may be stated in its written agreement with and for its customer.
In no event is Honeywell liable to anyone for any direct, special, or consequential damages. The
information and specifications in this document are subject to change without notice.
Copyright 2018 - Honeywell International Sàrl
- 2 -

Contents 3
Chapter 1 - About this Document 5
Chapter 2 - Planning 8
2.1 Overview 8
2.1.1 Software requirement 8
2.1.2 BIOS configuration 9
2.2 Description 9
2.2.1 Honeywell server model number 9
2.2.2 Electronics configuration 9
2.2.3 Electronics module 9
2.2.4 Standard features of Dell T130 10
2.2.5 Slots configuration 11
2.2.6 Optional features 11
2.2.7 Power cords 11
2.3 Platform information 11
2.3.1 Honeywell documentation 11
2.3.2 Dell documentation 11
2.4 Experion nodes slot requirement 13
2.4.2 FTE supervisory (Default) 13
2.4.3 Cnet configuration using PCIC interface 13
2.5 Memory configuration for Dell T130 13
2.5.1 8 GB, consisting of two 4 GB ECC DDR4 UDIMM 2133 MHz or faster 13
2.6 System specifications 14
2.6.18 Hard disk drive specifications 19
2.6.19 Removable media specifications 19
2.6.20 Storage and media devices 19
2.6.21 Mouse and keyboard 20
2.6.22 Monitor 20
2.6.23 Video cable 20
2.7 Industrial regulatory compliance 20
2.7.1 Electromagnetic Compatibility 20
2.7.2 Safety compliance 21
2.8 Light industrial regulatory compliance 21
2.8.1 Electromagnetic Compatibility 21
2.8.2 Safety compliance 22
Chapter 3 - Installation 23
- 3 -

3.1 Tasks for installing the server 23
3.1.1 Before you begin 23
3.2 Power and grounding requirements 23
3.3 Cabinet spacing requirements 24
3.4 Installing Dell T130 server and connecting cables 25
3.4.1 Honeywell server back panel connections 25
3.4.2 Connecting the cables 26
3.5 Starting the server 27
3.5.1 Turning on the power 27
Chapter 4 - Operation 28
4.1 Server overview 28
4.1.1 Front view of Dell T130 28
4.1.2 Rear view of Dell T130 29
4.2 Network connections 30
4.2.1 Ethernet network 30
4.2.2 MAU connection 30
4.2.3 ControlNet Network 30
4.3 Configuring ControlNet interface card 31
4.3.1 Installing ControlNet card inside Magma chassis 31
Chapter 5 - Servicing 33
5.1 Removing the Side Cover 33
5.2 Servicing the hard disk drives and power supply 34
5.3 Servicing Honeywell options 35
5.3.1 Slot requirements for General Ethernet and FTE node setup 35
5.4 Adding additional memory 36
5.5 Installing PCIC card in Dell T130 server using Magma 37
5.6 Verifying correct BIOS settings 40
5.6.1 Entering the BIOS 40
5.6.2 BIOS settings for Tab 51156307-100 40
5.6.3 BIOS settings for Tab 51156307-200 47
5.6.4 Exiting the BIOS 54
5.7 Spare parts 54
5.8 Troubleshooting 54
- 4 -

ABOUT THIS DOCUMENT
This document contains installation and service information for the Dell PowerEdge T130 server (T130
Honeywell Server). The instructions and service information contained in this document address the
server itself, and assumes that the associated network communication equipment is pre-installed by
the Honeywell factory or has manuals dedicated to its installation and service. This server is not a
standard Dell model and you cannot order it independently from Dell.
Note: If the Local Control Network (LCN) coaxial based system has been integrated with an Experion
Fault Tolerant Ethernet (FTE) based system, the node (server) may be upgraded to be an Experion
Local Control Network (ELCN) node, which has its ELCN Interface provided via FTE. This node may be
installed as a physical or virtual platform.
If the node is upgraded to an ELCN node, and the node is a physical (a.k.a. bare-metal) platform, a
Local Control Network Processor (LCNP) board coaxial interface to LCN is not used. The LCN MAU is
disconnected, and/or the LCNP board is removed.
Redundant ELCN Bridges are required if the ELCN node is communicating with any other existing,
coaxial-based LCN node.
Some LCN nodes may have been replaced by their ELCN equivalent nodes, and overall system
features/architecture will differ from that of a non-ELCN integrated system (classic LCN/TPN system). In
this case it may be necessary to refer to appropriate ELCN documentation, in addition to the
information provided herein.
NOTE
If the Local Control Network (LCN) coaxial based system has been integrated with an Experion
Fault Tolerant Ethernet (FTE) based system, the node (server) may be upgraded to be an
Experion Local Control Network (ELCN) node, which has its ELCN Interface provided via FTE.
This node may be installed as a physical or virtual platform.
If the node is upgraded to an ELCN node, and the node is a physical (a.k.a. bare-metal)
platform, a Local Control Network Processor (LCNP) board coaxial interface to LCN is not used.
The LCN MAU is disconnected, and/or the LCNP board is removed.
Redundant ELCN Bridges are required if the ELCN node is communicating with any other
existing, coaxial-based LCN node.
Some LCN nodes may have been replaced by their ELCN equivalent nodes, and overall system
features/architecture will differ from that of a non-ELCN integrated system (classic LCN/TPN
system). In this case it may be necessary to refer to appropriate ELCN documentation, in
addition to the information provided herein.
The following table lists Honeywell ELCN/Experion publications that may be useful for references.
ELCN Reference Documents Table for Server/Workstation PSIG Documents
- 5 -
CHAPTER
1

Publication Content Type
Experion LCN Hardware
Upgrade Kit Instructions
(51195195-415)
UEA installation
Experion LCN Quick Start
Guide (EPDOC-X480-en-
510A)
General hardware/software/migration information
Experion Software Installation
User's Guide (EPDOC-X136-
en-510A)
Experion software installation (various methods)
Experion LCN Overview and
Implementation Guide
(EPDOC-X478-en-510A)
Bridge hardware installation, software configuration,
operation, servicing/troubleshooting
Experion LCN Planning,
Installation, and Service Guide
(HWDOC-X479-en-E)
ELCN system planning, hardware/software
installation, servicing/troubleshooting
Experion LCN Specification
(ELCN03)
General ELCN technical specifications
Fault Tolerant Ethernet
Installation and Service Guide
(EPDOC-XX36-en510A)
FTE system installation, servicing/troubleshooting
Universal Embedded
Appliance Hardware
Installation and Maintenance
Guide (HWDOC-X469-en-A)
General UEA planning, installation, and service
information before it is commissioned as an ELCN
appliance.
Integrated Experion-TPS
User's Guide (EPDOC-XX66-
en-510A)
Supplementary installation tasks needed before using
TPS Nodes on an Experion system. Describes
configuration tasks needed for TPS Nodes.
Virtualization Planning and
Implementation Guide
(EPDOC-X147-en-A)
Implementing networks, Preparing ESXi host,
Administering virtualization
Server and Client Planning
Guide (EPDOC-X128-en-
510A)
High-level planning/design for Experion servers,
clients, controllers
Process Operations Manual
(SW11-601)
Process operations, alarm/message handling,
reporting, history functions, system operations,
- 6 -
Chapter 1 - About this Document

Chapter 1 - About this Document
Publication Content Type
system menu functions, console/station peripheral
devices
Integrated Experion-TPS
User's Guide (EPDOC-XX66-
en-510A)
Supplementary installation and configuration tasks for
Experion TPS Nodes
Experion PKS R510.1
Migration Planning Guide
(EPDOC-XX70-en-5101A)
Planning information for migration of Experion system
from legacy R4xx system software to Experion
R510.1 software.
Switch Configuration Tool
User's Guide
(EPDOC-X246-en-510A)
Experion switch configuration information
Experion Network Best
Practices (WP-07-02-ENG)
Best practices for planning the installation of Experion
FTE networks, and connecting them into plant IT
networks.
Experion R510 Software
Change Notice (EPDOC-
X166-en-510A)
Describes Experion R510 features/enhancements,
overall product, release interoperabilities, system
dependencies, problem resolutions, known issues,
special considerations
Customer Release Guide
R687 (CRG-687)
TPN/TPS Migration information (ELCN migration
Information included)
TPN R687 Software Change
Notice (TNDOC-X166-en-
6871A)
Document changes, compatibility and
migration/installation processes for the TPS Process
Network Release of R687 software.
Experion Control Building
User's Guide (EPDOC-XX19-
en-510A)
Procedures for basic tasks in the Control Builder
application (configuring hardware devices, continuous
control strategies, sequential control strategies).
1.1 Revision history
Version Date Description
A November 2019 Initial release of the document.
- 7 -

PLANNING
lOverview
lDescription
lPlatform information
lExperion nodes slot requirement
lMemory configuration for Dell T130
lSystem specifications
lIndustrial regulatory compliance
lLight industrial regulatory compliance
2.1 Overview
Platforms sold by Honeywell are engineered for the process control mission of Experion and TPS
systems to provide consistent and robust performance. Through an extensive qualification process,
Honeywell defines specific peripheral devices, slot locations, and BIOS settings for best performance
and reliability, sometimes even adding cooling fans for longer service. Honeywell platforms are then
built to Honeywell specifications by the computer manufacturer.
Honeywell engineering has tested theDell PowerEdge T130 serverwith other Honeywell hardware and
software and has qualified its use for specific configuration items as identified in the Software Change
Notice (SCN). This server is not a standard Dell model and cannot be ordered independently from Dell.
The Technical Assistance Center (TAC) is well trained and supports Honeywell platforms. Use of any
other server including a similar Dell model, is considered a project special and its TAC support is
limited according to the services policy.
The Dell PowerEdge T130 servers are shipped with the Tab number 51156307-100.
lSoftware requirement
lBIOS configuration
2.1.1 Software requirement
The server runs on the following operating system.
lMicrosoft Windows Server 2008 R2 (64 bit)
Microsoft Windows Server 2016
The server platform runs the latest version of the following Experion Server.
- 8 -
CHAPTER
2

lESV
lACE/SCE
lEAS
lEserver
NOTE
51156307-100 do not support T-nodes i.e. ESVT and ACE-T.
2.1.2 BIOS configuration
The BIOS version for the server depends on the Tab numbers. The Tab number for Dell T130 is:
l51156307-100: with BIOS version 1.2.5 or later
2.2 Description
lStandard features of Dell T130
lSlots configuration
2.2.1 Honeywell server model number
This document applies to the Honeywell server platform identified in the following table.
Model
number Description
MZ-
PCSV74
Intel Xeon E3-1220 v5 3.0 GHz,8M Cache / 16 GB UDIMM (2x8 GB) / 500
GB or 1 TBSATA Hard disk drive (QTY 1)
EP-
COAR28
Windows Server 2008 R2 COA
EP-
COAS16
Windows Server 2016 COA
2.2.2 Electronics configuration
The Dell T130-based server is approved for installation in 800 and 1000 mm deep Honeywell LCN
cabinets using either a "fixed" mounting kit, model number TP-SPCMF1, or a "slide" mounting kit, model
number TP-SPCMS1.
2.2.3 Electronics module
The tables in this section provides the electronics module for the Honeywell-based Dell T130 server
- 9 -
Chapter 2 - Planning

Chapter 2 - Planning
platforms.
Typical operating power requirements
Description DC power AC voltage AC RMS current AC power
Electronic assembly N/A 120 (90-132) Vrms
240 (180-260)
Vrms
0.7A
0.3A
72W
72W
Maximum operating power requirements
Description DC power AC voltage AC RMS current AC power
Electronic assembly N/A 120 (90-132) Vrms
240 (180-260)
Vrms
0.9A
0.5A
102W
102W
Weight and dimensions
Description Height Width Depth Weight
Assembly 363.3 mm with rubber pads 175 mm 454 mm 11.5 KGs (25.35 lbs)
2.2.4 Standard features of Dell T130
Following are the list of common features of Dell T130 server:
lIntel Xeon E3-1220 v5 3.0 GHz CPU / 8 GB UDIMM (2x4 GB) / 500 GB SATA Hard disk drive.
lRear Ports: 1 serial, 1 Video, 2 USB V2.0 / 2 USB3.0 / 2 RJ45, 1 ID push button with blue/amber
LED.
lFront Ports: 2 USB 2.0, ID push button with blue/amber LED, 1 system power on/off button.
lBroadcom 5720 1GbE Dual Port Ethernet NIC with failover and load balancing.
lBus Type: PCIe.
lExpansion slots: 4 PCIe slots.
oOne full-height, half-length x8 PCIe Gen3 card slot connected to processor
oOne full-height, half-length x16 PCIe Gen3 card slot connected to processor
oOne full-height, half-length x1 PCIe Gen3 card slot connected to Platform Controller Hub
(PCH)
oOne full-height, half-length x8 PCIe Gen3 card slot connected to PCH
lEnergy Smart – One 295 Watts non redundant Power Supply.
lOne 110 Volt / 230 Volts Power Cord.
- 10 -

l51156307 -100 8GB (2x4GB) DDR4 UDIMM 2133MHz or faster
l51156307 - 200 16GB (2x8GB) DDR4 UDIMM 2133MHz or faster
lSATA DVD-RW Drive.
l2D Matrox®G200 Video.
2.2.5 Slots configuration
An onboard dual NIC is available for FTE. There is no add on NIC support for Dell PowerEdge T130
server.
2.2.6 Optional features
The following is a list of the additional options that can be configured in your platform.
lUniversal ControlNet Interface (using external Magma PCIe to PCI convertor box)
2.2.7 Power cords
The following table lists the AC power cords.
Part description Part number
AC power cord, 220 V 51305557-100
2.3 Platform information
lHoneywell documentation
lDell documentation
2.3.1 Honeywell documentation
The following table lists the Honeywell publications that may be useful when installing or operating your
system.
Publication Contains information about
Fault Tolerant Ethernet Installation and
Service Guide
Installing and using FTE on a TPS or
Experion PKS node.
2.3.2 Dell documentation
The following table lists the Dell publications that may be useful when installing or operating the
- 11 -
Chapter 2 - Planning

Chapter 2 - Planning
system.
Publication Contains information about
Is available
with
Readme files Last-minute updates about technical changes
to the server or advanced technical reference
material for experienced users or technicians.
The drivers and
utilities CD
Dell System
Information Guide
Warranty and safety Packaged with
the computer
www.dell.com
Getting Started With
Your System
Unpacking and connecting the cables. Packaged with
the computer
Quick Installation
Guide
Installing and configuring the server operating
system.
Packaged with
the computer
Product
Documentation
CD
Dell™ PowerEdge™
T130 Systems
Hardware Owner’s
Manual
Removing and replacing the parts. Technical
specifications. Configuring the system.
Troubleshooting.
Product
Documentation
CD
www.dell.com
Rack Installation
Instructions — Sliding
Rails
Installing the server in a server rack or cabinet. Packaged with
the computer
www.dell.com
Windows Installation
Instructions and
Important
Information
Initialization the Windows operating system. Packaged with
the computer
www.dell.com
Dell™ Systems – Raid
Controller
Initialization
Initializing the RAID controller Packaged with
the computer
Dell™ Systems –
Upgrading Raid
Firmware
Upgrading the RAID firmware Packaged with
the computer
Dell™ PowerEdge™
T130 Systems
Hardware Owner’s
Manual
Diagnosing problems
Using status indicators for troubleshooting
Product
Documentation
CD
www.dell.com
- 12 -

2.4 Experion nodes slot requirement
2.4.1 Default configurations for FTE
lBroadcom on-board NICs are enabled without PXE.
lIf you are using FTE slot only, then use on-board NICs.
2.4.2 FTE supervisory (Default)
FTE must be configured on on-board NIC.
Slot number Description Option
Slot 1 PCIe x 8 CPU -
Slot 2 PCIe_G3 x 16 CPU -
Slot 3 PCIe_G3 x 1 PCH -
Slot 4 PCIe_G3 x 8 PCH -
2.4.3 Cnet configuration using PCIC interface
The server does not support PCIC interface, you must use Magma PCIe to PCI converter box.
Slot number Description Option
Slot 1 PCIe x 8 CPU Magma PCIe host card.
Slot 2 PCIe_G3 x 16 CPU -
Slot 3 PCIe_G3 x1 PCH -
Slot 4 PCIe_G3 x 8 PCH -
2.5 Memory configuration for Dell T130
Standard memory for Dell T130 server are 51156307 -100 8GB (2x4GB) DDR4 UDIMM 2133 MHz or
faster and 51156307 - 200 16GB (2x8GB) DDR4 UDIMM 2133 MHz or faster and must be installed in
pairs.
2.5.1 8 GB, consisting of two 4 GB ECC DDR4 UDIMM 2133 MHz or
faster
The following table provides memory configurations layout for 8 GB, consisting of two 4 GB ECC DDR4
- 13 -
Chapter 2 - Planning

Chapter 2 - Planning
UDIMM 2133 MHz or faster.
DIMM socket Memory size Channel
A1 8 GB UDIMM 0
A3
A2 8 GB UDIMM 1
A4
2.6 System specifications
2.6.1 Microprocessor
Microprocessor Tab 100 / Tab 200: Skylake Intel Xeon E3-1220V5 ,3.0 GHz, 8M
cache, 8GT/s.
Intel Smart
Cache
8 MB
Chipset Intel C236 series chipset
PCIe slots
3 PCIe slots 1x8 PCIe 3.0 (x16 connector)
1x4 PCIe 3.0 (x8 connector)
1x1 PCIe 3.0 (x1 connector)
- 14 -

2.6.2 Memory
Architecture lTab 100: 8 GB (2 x 4 GB UDIMM DDR4, 2133 MHz) or faster
lTab 200: 16GB (2x8 GB UDIMM DDR4, 2133MHz) or faster
DIMM sockets lTab 100: 4 UDIMM DDR4
lTab 200: 8GB UDIMM 2133MHz or faster
DIMM capacities 4 GB UDIMM, 2133 MHz
Minimum RAM lTab 100: 8 GB (2 x 4 GB UDIMM DDR4, 2133 MHz) or faster
lTab 200: 16 GB (2 x 8 GB UDIMM DDR4, 2133 MHz) or
faster
Maximum RAM lTab 100: 16 GB (4 x 4 GB UDIMM DDR4 2133 MHz) or
faster
lTab 200: 32 GB (4 x 8 GB UDIMM DDR4 2133 MHz) or
faster
2.6.3 Raid controller
RAID controller Not Applicable
2.6.4 Optical disk drive
DVD drive SATA DVD R/W
2.6.5 Video
Video type Matrox G200 Controller
2.6.6 Network interface
Adapter type On-Board LOM 1GBE Dual Port (BCM5720 GbE LOM)
2.6.7 Power
The following provides the specifications for DC power supply.
Wattage Tab 100 / Tab 200: Single, Cabled Power Supply, 290 Watts.
- 15 -
Chapter 2 - Planning

Chapter 2 - Planning
2.6.8 Environmental
Operating temperature +10 °C to +35 °C (50 °F to 95 °F) with a maximum
temperature gradation of 10° per hour.
Note: For Altitudes above 2950 feet , the maximum
operating temperature is derated 1 °F/550 ft.
All temperature ratings shown are for sea level. An
altitude derating of 1 °C per 300 m (1.8 °F per 1,000 ft)
to 3048 m (10,000 ft) is applicable. No direct sunlight
allowed.
Shipping temperature -30 °C to 50 °C (-22 °F to 122 °F)
Storage temperature –40 °C to 65 °C (–40 °F to 149 °F)
Maximum wet bulb temperature 28 °C (82.4 °F)
ATTENTION
All temperature ratings described previously
are for sea level. An altitude derating of 1 °C
per 300 m (1.8 °F per 1,000 ft) to 3048 m
(10,000 ft) is applicable. Direct sunlight is not
allowed.
Operating humidity 10% to 80% Relative Humidity with 29 °C (84.2 °F)
maximum dew point
Storage humidity 5% to 95% RH with 33 °C (91 °F) maximum dew
point. Atmosphere must be non-condensing at all
times.
ATTENTION
Storing maximum humidity of 95% is based
on a maximum temperature of 45 °C (113
°F). Altitude maximum for storage
corresponds to a pressure minimum of 70
KPa.
Airborne Contaminants Airborne Contaminants < 300 angstroms/month
Copper Reactivity Level Copper Reactivity Level < 3 mm3/m3 parts per billion
H2S Gas concentration H2S Gas concentration < 10 mm3/m3 parts per billion
S02, S03 Gas concentration S02, S03 Gas concentration < 1 mm3/m3 parts per
- 16 -

billion
CI2 Gas concentration CI2 Gas concentration < 50 mm3/m3 parts per billion
NOX Gas concentration NOX Gas concentration < 1 mm3/m3 parts per billion
HF Gas concentration HF Gas concentration < 500 mm3/m3 parts per billion
NH3 Gas concentration NH3 Gas concentration < 2 mm3/m3 parts per billion
O3 Gas concentration Severity
level
G1 mild environment limits as per ANSI/ISA-S71.04-
1985 Standard
ANSI/ISA-S71.01-1985
Environmental Conditions for
Process Measurement and
Control Systems
Temperature and Humidity
ANSI/ISA-S71.04-1985
Environmental Conditions for
Process Measurement and
Control Systems
Airborne Contaminants
2.6.9 Physical – form factor
Height 363.3 mm with rubber pads
Width 175 mm
Depth 454 mm
Weight (Maximum Config) 11.5 kg (25.35 lbs)
2.6.10 Drive bays
Internal Up to 4 x 3.5” HDD
External DVD+/-RW, SATA, Internal
2.6.11 Maximum vibration
Operating 0.26 Grms at 5 Hz to 350 Hz (all operation orientations).
Storage 1.88 Grms at 10 Hz to 500 Hz for 15 min (all six sides tested).
- 17 -
Chapter 2 - Planning

Chapter 2 - Planning
2.6.12 Maximum Shock
Operating Six consecutively executed shock pulses in the positive and negative x, y,
and z axes of 40 G for up to 2.3 ms.
Storage Six consecutively executed shock pulses in the positive and negative x, y,
and z axes (one pulse on each side of the system) of 71 G for up to 2 ms.
2.6.13 Altitude
Operating 3048 m (10,000 ft). This value may be limited by the type and number of
options installed.
Maximum allowable altitude change rate is 457 m/min (1500 ft/min). (that
is 1 °F /167.64 meters that is -17.22 °C / 167.64 meters).
Storage 12,000 m (39,370 ft). Maximum allowable altitude
Change rate is 457 m/min (1500 ft/min).
2.6.14 External peripherals
Keyboard Windows compliant USB (equivalent or better)
Mouse USB (equivalent or better)
2.6.15 Drives
Hard
Drive
Tab 100 / Tab 200: 500 GB 7.2K RPM SATA 3 Gbps 3.5” Cabled Hard
Drive.
2.6.16 External ports
Serial One DB-9 connectors
LAN 2 x RJ-45
SCSI External None
USB Front :Two Hi-Speed USB Hosts (One USB 2.0 and one USB 3.0).
Back :Total Six Hi-Speed USB Hosts (four USB 2.0 and two USB
3.0).
Video 1 VGA port
- 18 -

2.6.17 Management
Power related Monitoring of voltage, fan, µprocessor and other thermal conditions
Memory Track ECC error reporting
2.6.18 Hard disk drive specifications
For MZ-PCSV75, the Honeywell-based Dell T130 Standard RAID5 Server Tab 100 Platform has one
hard disk drive bay. It uses one 500 GB 7.2k RPM Serial ATA 3Gbps 3.5-in Cabled Hard Drive. The
following table provides the operating power requirements for 500 GB hard drive.
Description Requirement
DC 5 volt Power (typ) 4.5 Watts +/- 5%
DC 12 volt Power (typ) 5 Watts +10%, -8%
Other DC POWER 9.5 W Watts Max, 8.75 W Watts idle
AC Power N/A
The following table provides the maximum weight and dimensions for 500 GB hard drive.
Description Requirement
Height 19.98/0.787 (mm/inch)
Width 101.6/4.0 (mm/inch)
Depth 146.99/5.787 (mm/inch)
Weight 415/0.92 (gms/lbs)
2.6.19 Removable media specifications
The Honeywell-based Dell T130 server has one SATA DVD- RW drive. The SATA DVD-RW drive is
connected to the SATA connector on the motherboard. DC 5 volt power, 6.5 Watts is the operating
power requirement for DVD RW drive.
2.6.20 Storage and media devices
The standard mass storage for the Dell T130 servers are as follows:
l51156307-100/200: 500 GB 7.2K RPM SATA 3.5in Hard Drive
- 19 -
Chapter 2 - Planning

Chapter 2 - Planning
2.6.21 Mouse and keyboard
The USB mouse, a standard cursor control device and an USB standard PC keyboard are included with
the Dell T130.
2.6.22 Monitor
The Honeywell-based Dell T130 server supports industrial standard video format (typically 1024X768 at
a refresh rate of 75Hz). You must use a multisync monitor along with the Dell T130 server platform
operating system. The server can be configured only with a single screen option. In this configuration,
the monitor is connected to the AGP video controller output connector. Note that no touch screen option
is available for this server platform.
2.6.23 Video cable
Correct system startup and operation of the Honeywell-based Dell T130 server platform requires
industry standard VESA DDC interface to the monitor. If either a monitor or video cable that does not
support DDC is attached to the server platform, the display generator defaults to a resolution, which
precludes communication with the system software and stops startup. To determine if a cable is DDC
compatible, ensure that pins 5, 9, and 12 of the HD15 connector are wired. The IS supplied cable
(51196742-200) is DDC compatible.
2.7 Industrial regulatory compliance
The compliance specifications in this section apply to cabinet installations.
WARNING
Honeywell does not claim Safety Compliance or Electromagnetic Compatibility (EMC)
Compliance for system equipment configurations that have not been described in this guide as
standard system configurations. Any equipment configuration other than that described in this
publication decertifies the Safety and EMC compliance of this product.
lElectromagnetic Compatibility
lSafety compliance
2.7.1 Electromagnetic Compatibility
The following table provides the Electromagnetic Compatibility (EMC) specifications (Industrial
Regulatory) for European community.
Element Description
Emissions EN 61326-1:2006 (Industrial Locations, CISPR 11, Class A)
Immunity EN 61326-1:2006 (Industrial Locations)
- 20 -
Table of contents
Other Honeywell Server manuals

Honeywell
Honeywell HUS-D4-E-Pro User manual

Honeywell
Honeywell Aquatrol W964F User manual

Honeywell
Honeywell PE SC1430 Technical manual

Honeywell
Honeywell LANSRLU1 Setup guide

Honeywell
Honeywell HAS-QNH User manual

Honeywell
Honeywell XYR301E User manual

Honeywell
Honeywell AutomationServer User manual

Honeywell
Honeywell HP ProLiant DL360P Gen8 User manual

Honeywell
Honeywell Q7055B1047 User manual

Honeywell
Honeywell T320 Technical manual