manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. Honeywell
  6. •
  7. Switch
  8. •
  9. Honeywell Ademco VistaView-100 Assembly instructions

Honeywell Ademco VistaView-100 Assembly instructions

Other Honeywell Switch manuals

Honeywell DG T Series User manual

Honeywell

Honeywell DG T Series User manual

Honeywell PEHA PHC User guide

Honeywell

Honeywell PEHA PHC User guide

Honeywell FF-SNC User manual

Honeywell

Honeywell FF-SNC User manual

Honeywell CSP-C User manual

Honeywell

Honeywell CSP-C User manual

Honeywell C6097B User manual

Honeywell

Honeywell C6097B User manual

Honeywell DCM/SN DIFF User manual

Honeywell

Honeywell DCM/SN DIFF User manual

Honeywell ZW4005 User manual

Honeywell

Honeywell ZW4005 User manual

Honeywell Fema DWAM Series User manual

Honeywell

Honeywell Fema DWAM Series User manual

Honeywell Galaxy 2 Series User manual

Honeywell

Honeywell Galaxy 2 Series User manual

Honeywell S437A Operation manual

Honeywell

Honeywell S437A Operation manual

Honeywell ZW4203 User manual

Honeywell

Honeywell ZW4203 User manual

Honeywell KSL Series Operation manual

Honeywell

Honeywell KSL Series Operation manual

Honeywell krom schroder 03250831 User manual

Honeywell

Honeywell krom schroder 03250831 User manual

Honeywell PLS550A User manual

Honeywell

Honeywell PLS550A User manual

Honeywell C6097 User manual

Honeywell

Honeywell C6097 User manual

Honeywell 968XTP User manual

Honeywell

Honeywell 968XTP User manual

Honeywell Micro Switch 91SE Series User manual

Honeywell

Honeywell Micro Switch 91SE Series User manual

Honeywell NGC Series User manual

Honeywell

Honeywell NGC Series User manual

Honeywell MICRO SWITCH BX Series User manual

Honeywell

Honeywell MICRO SWITCH BX Series User manual

Honeywell CLMSOPS5M User manual

Honeywell

Honeywell CLMSOPS5M User manual

Honeywell IDENT-KEY 3 User manual

Honeywell

Honeywell IDENT-KEY 3 User manual

Honeywell ADEMCO 270R Assembly instructions

Honeywell

Honeywell ADEMCO 270R Assembly instructions

Honeywell RPLS730B User manual

Honeywell

Honeywell RPLS730B User manual

Honeywell C6097A User manual

Honeywell

Honeywell C6097A User manual

Popular Switch manuals by other brands

SMC Networks SMC6224M Technical specifications

SMC Networks

SMC Networks SMC6224M Technical specifications

Aeotec ZWA003-S operating manual

Aeotec

Aeotec ZWA003-S operating manual

TRENDnet TK-209i Quick installation guide

TRENDnet

TRENDnet TK-209i Quick installation guide

Planet FGSW-2022VHP user manual

Planet

Planet FGSW-2022VHP user manual

Avocent AutoView 2000  AV2000BC AV2000BC Installer/user guide

Avocent

Avocent AutoView 2000 AV2000BC AV2000BC Installer/user guide

Moxa Technologies PT-7728 Series user manual

Moxa Technologies

Moxa Technologies PT-7728 Series user manual

Intos Electronic inLine 35392I operating instructions

Intos Electronic

Intos Electronic inLine 35392I operating instructions

Cisco Catalyst 3560-X-24T Technical specifications

Cisco

Cisco Catalyst 3560-X-24T Technical specifications

Asante IntraCore IC3648 Specifications

Asante

Asante IntraCore IC3648 Specifications

Siemens SIRIUS 3SE7310-1AE Series Original operating instructions

Siemens

Siemens SIRIUS 3SE7310-1AE Series Original operating instructions

Edge-Core DCS520 quick start guide

Edge-Core

Edge-Core DCS520 quick start guide

RGBLE S00203 user manual

RGBLE

RGBLE S00203 user manual

Thrustmaster FLIGHT SIMULATOR X quick guide

Thrustmaster

Thrustmaster FLIGHT SIMULATOR X quick guide

Southwire SURGE GUARD 41390 RVC troubleshooting guide

Southwire

Southwire SURGE GUARD 41390 RVC troubleshooting guide

Buhler Nivotemp NT 61 Brief instructions

Buhler

Buhler Nivotemp NT 61 Brief instructions

Kramer VS-41HDCP user manual

Kramer

Kramer VS-41HDCP user manual

Techly IDATA AU-270 user manual

Techly

Techly IDATA AU-270 user manual

Belkin F1U109 user manual

Belkin

Belkin F1U109 user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.

K3992V1 1/00
®
VISTAVIEW-100
Use as a Stand-Alone Module or with Controls That Support
4204 Relay Module Connection Via Keypad (ECP) Bus
INSTALLATION AND SETUP GUIDE
ABOUT VISTAVIEW-100
The VistaView-100 module is a CCTV switcher that accepts
4 video inputs, switching them to 2 video outputs. The
VistaView-100 module features:
•4 video inputs compatible with any standard 75-ohm,
line-locked, black and white or color video camera
•2 video outputs compatible with any standard 75-ohm
video monitor or recorder
•A form-C trigger relay output that may be used to
start/stop recording, or to change from time lapse to
real time recording
•An open collector video loss output that indicates when
video signals are no longer present on one or more
video inputs.
Modes of Operation
Normal Sequencing Mode — automatically sequences
installer selected video inputs to the outputs using a
common installer selected dwell time. This allows cameras
assigned to a given output to be continuously monitored
using a video monitor and/or continuously recorded using a
recorder set for time lapse recording. A control panel is not
required for operation in this mode.
Panel Trigger Mode — switches a specific video input to the
OUTPUT1 line on a momentary basis using a separate
installer selected dwell time, or on a latched basis as
directed by commands received from a control panel. A
control panel that supports the 4204 relay module is
required in this mode. In this mode VistaView-100:
•Receives commands via the control’s ECP bus
•Responds to the same commands that the control uses
to activate the relays on the 4204 relay module
•Allows one specific camera to be monitored by a video
monitor and/or recorded by a recorder set for real time
recording when an installer defined event occurs such
as an alarm or trouble condition on a selected control
panel zone.
HOW TO INSTALL THE VISTAVIEW-100
ULVistaView-100 should be installed by a qualified
service person and its installation should conform to all
local codes.
The VistaView-100 is supplied in a plastic case that may be
wall mounted or placed on a shelf. To mount the case on a
wall:
1. Insert two supplied self-tapping screws into the wall
with a 3-1/4-inch horizontal separation. The screw
heads should project approximately 1/8-inch from the
wall.
2. Remove the VistaView-100 PCB from the case and
position the slotted holes on the case back onto the
screw heads with the holes for the BNC video
connectors facing down.
3. On the inside of the case, remove the plastic strip
covering the remaining unused slotted hole and insert a
screw into this hole to lock the case in position. After
tightening, make sure screw head is flush with case
back to avoid contact with the PCB.
4. Replace the VistaView-100 PCB into the case.
HOW TO CONNECT THE VISTAVIEW-100
When VistaView-100 is used with control panels that have
earth ground fault detection, a ground fault indication will
occur when video monitors, recorders, or cameras are
connected to the VistaView-100 that tie the shell of their
video BNC connector to earth ground via their power cord
or mounting bracket.
UL
Standalone UL Installations
: VistaView-100 is listed as
a standalone unit for CCTV UL2044 applications.
Panel triggered UL Installations
: VistaView-100 may be
connected as a supplemental device to listed fire
and/or burglar alarm control panels that support the
4204 relay module except as noted below.
•In UL installations, VistaView-100 may be
connected to panels that have ground fault
detection only if the local authority having
jurisdiction allows the ground fault detection
feature to be disabled.
•In non-UL installations requiring ground fault
detection, when possible, use cameras powered
by a power source such as a plug-in transformer
that is not earth grounded and isolate the
camera's mounting brackets from earth ground.
Connect a video ground loop isolation device
such as Vicon's V235GLTA Ground Loop
Transformer to the coaxial cable that runs
between VistaView-100 and the video monitor or
recorder (or camera if required) causing the
ground fault. Video ground loop isolation devices
are not UL listed and may not be used in UL
installations.
BNC Connectors
Use for video input and output connections to video
cameras, monitors, and recorders with 75-ohm coaxial
cable. Depending on the devices used, the maximum cable
length running from a camera, through VistaView-100, to a
–2 –
monitor or recorder is typically 500 to 1000 feet when high
quality, low distortion coaxial cable such as RG59B/U is
used. Consult the instructions provided with these devices
for cable length limitations.
Screw Terminals
Use for power source, ECP bus, trigger relay, and video loss
output connections.
•Run wires from VistaView-100’s power input and
ground screw terminals to a 12VDC-power source (such
as the control’s auxiliary power output or supplemental
12VDC-power supply).
•If panel trigger mode will be used, run wires from
VistaView-100's Data In/Out screw terminals to the
corresponding ECP bus terminals on the control.
•If video loss is to be annunciated by the control, the
video loss output must be connected to a zone on the
control having a grounded return. Connect one side of
the zone's EOLR to the control's zone + (or zone Hi)
input. Connect the other side of the EOLR to the
VistaView-100's video loss output. Program the zone for
24-hour trouble (or equivalent) response.
•When powered from a source other than the control (if
using either panel-triggered mode or video-loss
feature), run a wire from VistaView-100 ground screw
terminal to a ground terminal on the control so that
both devices share a common ground reference.
HOW TO PROGRAM THE VISTAVIEW-100
Normal Sequencing Mode
1. Set DIP switches (OUT1 and OUT2) to assign desired
video inputs to OUTPUT1 and OUTPUT2, respectively.
Switches 1-4 on each DIP switch enable INPUT1-
INPUT4 on the corresponding DIP switch output. For
example, turn on switch #3 on the DIP switch OUT1 to
enable INPUT3 on OUTPUT1 and so on.
2. Adjust the NSD trimpot to select desired normal
sequencing dwell time (1 to 30 seconds).
Panel Trigger Mode
1. Set ECP DIP switch to the address that will be used by
the control to communicate with the VistaView-100.
(Refer to the instructions provided with the control
when selecting this address.) The table below shows the
DIP switch settings for each of the 16 possible
addresses that can be selected. Be sure to choose an
address that is different from the addresses of all other
devices, including other VistaView-100 modules, which
are connected to the control’s ECP bus.
2. On some controls, it is necessary to program the
selected address into the control and to assign an
output device type (i.e.: type 4) to this address using the
applicable control programming menu.
3. Program the events that will trigger relay numbers 1
through 4 (corresponding to INPUT1 through INPUT4)
along with the start and stop options for these relays
into the control using the applicable control
programming menu. Video inputs should either be
assigned an "Activate for 2 seconds" start option (this
option does not require a stop option to be programmed)
or an "Activate Steady Until Stopped" start option (this
option requires a stop option to be programmed).
4. If the "Activate for 2 Seconds" start option is used,
adjust the PTD trimpot to select the desired panel
trigger dwell time (2-60 seconds).
VISTAVIEW-100 OPERATION
•When power is applied, VistaView-100 enters normal
sequencing mode where it automatically sequences
through the video inputs selected for each output. The
trigger relay remains inactive in this mode.
•When a command to activate a relay for 2 seconds is
received, the corresponding video input is switched to
OUTPUT1 for the dwell time set by the PTD trimpot.
•When a command to activate a relay steady is received,
VistaView-100 switches the corresponding video input
to OUTPUT1 until it receives another command to
deactivate the relay.
•When a command to activate a second, third, or fourth
relay is received before a previously switched input has
been deactivated, it automatically sequences between
all activated inputs using a fixed 1-second dwell time.
•VistaView-100 activates the trigger relay when one or
more inputs are switched to OUTPUT1 and deactivates
this relay when all inputs have been deactivated.
SPECIFICATIONS
Dimensions 6-7/16 W x 4-3/4”H x 1-1/4”D
Input Voltage: 12VDC nominal, 9.6-14VDC operating
range.
Current: 72mA
Video Inputs: 75-ohm termination, compatible with black
and white or color composite video signals,
BNC connections.
Video Outputs: 75-ohm termination, AC coupled, unity
gain, BNC connections.
Trigger Relay: Form-C contacts rated 1A at 24VAC/ VDC.
Video Loss
Output: 0.7 V through 300 ohms when video is
present on all enabled inputs and open
collector when video is lost (i.e., no sync)
on one or more enabled inputs, or module
has no power.
Agency Listings: UL2044
VistaView-100 Address SettingsDIP Switch
Position 0123456789101112131415
1On Off On Off On Off On Off On Off On Off On Off On Off
2On On Off Off On On Off Off On On Off Off On On Off Off
3On On On On Off Off Off Off On On On On Off Off Off Off
4On On On On On On On On Off Off Off Off Off Off Off Off
–3 –
ADEMCO LIMITED WARRANTY
Alarm Device Manufacturing Company, a Division of Pittway Corporation, and its divisions, subsidiaries and affiliates ("Seller"), 165
Eileen Way, Syosset, New York 11791, warrants its products to be in conformance with its own plans and specifications and to be free
from defects in materials and workmanship under normal use and service for 24 months from the date stamp control on the product or,
for products not having an Ademco date stamp, for 12 months from date of original purchase unless the installation instructions or
catalog sets forth a shorter period, in which case the shorter period shall apply. Seller's obligation shall be limited to repairing or
replacing, at its option, free of charge for materials or labor, any product which is proved not in compliance with Seller's specifications
or proves defective in materials or workmanship under normal use and service. Seller shall have no obligation under this Limited
Warranty or otherwise if the product is altered or improperly repaired or serviced by anyone other than Ademco factory service. For
warranty service, return product transportation prepaid, to Ademco Factory Service, 165 Eileen Way, Syosset, New York 11791.
THERE ARE NO WARRANTIES, EXPRESS OR IMPLIED, OF MERCHANTABILITY, OR FITNESS FOR A PARTICULAR PURPOSE
OR OTHERWISE, WHICH EXTEND BEYOND THE DESCRIPTION ON THE FACE HEREOF. IN NO CASE SHALL SELLER BE
LIABLE TO ANYONE FOR ANY CONSEQUENTIAL OR INCIDENTAL DAMAGES FOR BREACH OF THIS OR ANY OTHER
WARRANTY, EXPRESS OR IMPLIED, OR UPON ANY OTHER BASIS OF LIABILITY WHATSOEVER, EVEN IF THE LOSS OR
DAMAGE IS CAUSED BY THE SELLER'S OWN NEGLIGENCE OR FAULT.
Seller does not represent that the products it sells may not be compromised or circumvented; that the products will prevent any
personal injury or property loss by burglary, robbery, fire or otherwise; or that the products will in all cases provide adequate warning or
protection. Customer understands that a properly installed and maintained alarm may only reduce the risk of a burglary, robbery, fire or
other events occurring without providing an alarm, but it is not insurance or a guarantee that such will not occur or that there will be no
personal injury or property loss as a result. CONSEQUENTLY, SELLER SHALL HAVE NO LIABILITY FOR ANY PERSONAL INJURY,
PROPERTY DAMAGE OR OTHER LOSS BASED ON A CLAIM THE PRODUCT FAILED TO GIVE WARNING. HOWEVER, IF
SELLER IS HELD LIABLE, WHETHER DIRECTLY OR INDIRECTLY, FOR ANY LOSS OR DAMAGE ARISING UNDER THIS LIMITED
WARRANTY OR OTHERWISE, REGARDLESS OF CAUSE OR ORIGIN, SELLER'S MAXIMUM LIABILITY SHALL NOT IN ANY CASE
EXCEED THE PURCHASE PRICE OF THE PRODUCT, WHICH SHALL BE THE COMPLETE AND EXCLUSIVE REMEDY AGAINST
SELLER. This warranty replaces any previous warranties and is the only warranty made by Seller on this product. No increase or
alteration, written or verbal, of the obligations of this Limited Warranty is authorized.
“FEDERAL COMMUNICATIONS COMMISSION (FCC) Part 15 STATEMENT”
This equipment has been tested to FCC requirements and has been found acceptable for use. The FCC requires the following
statement for your information:
This equipment generates and uses radio frequency energy and if not installed and used properly, that is, in strict accordance with the
manufacturer’s instructions, may cause interference to radio and television reception. It has been type tested and found to comply with
the limits for a Class B computing device in accordance with the specifications in Part 15 of FCC Rules, which are designed to provide
reasonable protection against such interference in a residential installation. However, there is no guarantee that interference will not
occur in a particular installation. If this equipment does cause interference to radio or television reception, which can be determined by
turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:
•If using an indoor antenna, have a quality outdoor antenna installed.
•Reorient the receiving antenna until interference is reduced or eliminated.
•Move the receiver away from the control/communicator.
•Move the antenna leads away from any wire runs to the control/communicator.
•Plug the control/communicator into a different outlet so that it and the receiver are on different branch circuits.
If necessary, the user should consult the dealer or an experienced radio/television technician for additional suggestions.
The user or installer may find the following booklet prepared by the Federal Communications Commission helpful: “Interference
Handbook”
This booklet is available from the U.S. Government Printing Office, Washington, DC 20402.
The user shall not make any changes or modifications to the equipment unless authorized by the Installation Instructions or User’s
Manual. Unauthorized changes or modifications could void the user’s authority to operate the equipment.
¬.9Hl
K3992V1 1/00
165 Eileen Way, Syosset, New York 11791
Copyright © 2000 PITTWAY CORPORATION