
Model 182 lA Section III
Paragraphs 3-1 to 3-13
SECTION III
OPERATION
3-1. INTRODUCTION.
3-2. The Model 182 lA produces two linear sweeps
for use as time bases in the Model 180-series Oscil-
loscope. The delayed sweep circuit is armed by the
main sweep after an adjustable delay period. Control
settings determine whether the delayed sweep is auto-
matically triggered immediately after the delay, or if
it is triggered by the next input signal. Waveforms
may be viewed on either time base alone, or on both
time bases combined.
3-3. CONTROLS AND CONNECTORS.
3-4. Locations of controls and connectors are shown
in Figure 3-1 along with abrief description of their
functions. Controls that perform the same function
for both main and delayed sweeps are explained for
main sweep only. The following paragraphs explain
some control functions in more detail.
3-5. SWEEP DISPLAY. The three positions of this
switch are MAIN, MIXED, and DELAYED. The dis-
play obtained in each position is explained below.
a. MAIN. The vertical input signal is displayed
on atime base as set by the Main TIME/DIV control.
With the Delayed TIME/DIV switch set to OFF the en-
tire main sweep display will be of normal intensity.
Any other setting of the Delayed TIME/DIV control will
cause the main sweep to be intensified during the time
the delayed sweep is produced (providing the delayed
sweep is properly triggered).
b. MIXED. In this mode the first part of the pres-
entation is displayed on atime base set by the Main
TIME/DIV switch. The last part of the presentation
is displayed on atime base set by the Delayed TIME/
DIV switch. The delay between the start of the main
sweep and the start of the delayed sweep is determined
in part by DELAY (DIV).
c. DELAYED. The portion of the presentation that
was intensified in MAIN is now displayed on atime
base that is set by the Delayed TIME/DIVcontrol.
3-6. TIME/DIV. The Main and Delayed TIME/DIV
switches determine the time that it takes the main and
delayed sweeps to move one division. The switches
are concentric and interlocked so that the delayed sweep
will always be faster than the main sweep. The Main
TIME/DIV switch can select sweep speeds from 1sec/
div to 0.1 psec/div. The Delayed TIME/DIV switch
can select sweep speeds from 50 msec/div to 0.1
psec/div. The selected main and delayed sweep
speeds may be increased five or ten times by position-
ing MAGNIFIER on the Model 180-series Oscilloscope
to X5 or XIO respectively. The Delayed TIME /DIV
switch should be positioned to OFF to view amain
sweep display of normal intensity.
3-7. VERNIER The Main and Delayed VERNIER
controls provide continuous adjustment of sweep time
between the calibrated steps of their respective
TIME/DIV switches. When the VERNIER control is
settoCAL (fully cw) sweep time can be read directly
from its TIME/DIV switch. As VERNIER is rotated ccw,
the selected TIME/DIV increases. With VERNIER
fully ccw, the TIME/dIV is approximately 2.5 times
greater than the indicated TIME/DIV.
3-8. SWEEP MODE. This lever switch determines
the type of main sweep triggering. The AUTO position
allows the main sweep to free run, providing abright
baseline, in the absence of atrigger signal. Atrigger
signal will override the auto circuit if its frequency is
40 Hz or greater. NORM should be used if the trig-
ger frequency is less than 40 Hz or if triggering is
erratic. NORM, however, will not provide abase-
line in the absence of atrigger. Selecting SINGLE
allow sthe main sweep circuit to be triggered only once.
The sweep circuit must be rearmed manually, by de-
pressing RESET, to be triggered again.
3-9. DELAY (DIV). This control adjusts the delay be-
tween the start of the main sweep and the arming of
the delayed sweep. The delay time is the product of
the DELAY (DIV) setting and the Main TIME/DIV setting.
Note
Asingle DELAY (DIV) reading has little
meaning. Accurate time measurements
can be made only by subtracting one read-
ing from another.
3-10. The delayed sweep starts exactly at the end of
the delay time only if the Delayed Trigger Source switch
is set to AUTO. All other positions of the Delayed
Trigger Source switch cause the delayed sweep to
start on the first trigger after the delay time.
Note
The delayed sweep will not be generated
when DELAY (DIV) is set to less than ap-
proximately 0. 5.
3-11. TRIGGER SOURCE. The Main and Delayed
Trigger Source switches determine the origin of the
main and delayed triggers. WhenINT is selected, the
main and delayed sweeps are triggered by the vertical
deflection signal. When EXT or EXT ~10 is selected
the sweeps are triggered by the signals applied to the
EXT INPUT connectors. EXT 10 attenuates the ex-
ternal trigger and should be used when the trigger sig-
nal is greater than 6vpk-pk.
3-12. Each switch has one position not common to the
other. The LINE position on the Main switch allows
the main sweep to be triggered by the power line wave-
form. The AUTOposition on the Delayed switch causes
the delayed sweep to start precisely at the end of the
delay time set by DELAY (DIV). All other positions of
the delayed switch cause the delayed sweep to start on
the first trigger after the delay time.
3-13. TRIGGER COUPLING. These switches deter-
mine the type of coupling for the main and delayed
02591-3 3-1