HP 6236A Service manual

HP Archive
This vintage Hewlett Packard document was
preserved and distributed by
www.hparchive.com
Please
visit
us
on the web !
Scanned by on-line curator: Tony Gerbic
** For FREE Distribution Only ***

HP
Part No. 5950-1737
TRIPLE
OUTPUT
POWER
SUPPLY
MODELS
6236A
AND
6237
A
OPERATING
AND
SERVICE
MANUAL
FOR;
MODEL 6236A, SERIALS 1507A-00141
AND
ABOVE
MODEL 6237A, SERIALS 1507A-00101
AND
ABOVE
*For Serials above 1507A-00141
or
1507A-00101,
achange page may be included.
Hewlett-Packard
Printed: February 1975

tions
in additiola
to
the
standard
104-127Vac
47-63Hz
unit
and
is
furnished
with
a
permanently
attached
5-foot
3-wire
grounding-type
line
cord.
1-8 SPECIFICATIONS
1-9
Table
1-1
lists
detailed
specifications
for
the
power
supply.
SECTION I
GENERAL
INFORMATION
I
INTRODUCTION
1-1
1-2 This manual covers
two
triple
output
power
supply
models,
the
6236A
and
the
6237
A. Both models are
com-
pact
general
purpose
bench
supplies
that
are
particularly
useful for
powering
developmental
IC
circuits,
both
linear
and
digital. Unless
one
model
or
the
other
is
specifically
identified,
all
information
in
this
manual applies
to
both
the
6236A
and
the
6237
A.
1-10 OPTIONS
---
CAUTION
---
Carefully read Sections
II
and
III
of
this
manual before
attempting
to operate the
power
supply.
1-11
Options
are
factory
modifications
of
a
standard
instrument
that
are
requested
by
the
customer.
The
follow-
ing
options
are available
for
the
instrument
covered
by
this
manual.
OPTION NO.
OESCR
IPTION
---CAUTION---
1-13 ACCESSORIES
The
user can
convert
an
instrument
from
one
line voltage
option
to
another
by following
the
instructions
in
Para-
graph 3-4.
1-12 Before
the
supply
is
shipped
from
the
factory,
an
internal line voltage
selector
switch
is
set
and
the
proper
fuse installed
for
the
line voltage specified
on
the
order.
A
label
on
the
rear
heat
sink identifies this line voltage
option.
Input
Power:
87-106Vac,47-63Hz,
single-phase.
Input
Power:
191-233Vac,47-63Hz,
single-phase.
Input
Power:
208-250Vac,
47-63Hz,
single-phase.
220
240
100
Before
applying
power
to
the supply, make cer-
tain
that
its line voltage selector switch (S3)
is
set
for
the line voltage to be
used.
(See
CA UTION
notice
in Paragraph 3-2
for
additional
information
on S3).
1-5
All
controls,
meters,
and
output
terminals
are loca-
ted
on
the
front
panel.
Two
single-turn
potentiometers
con-
trol
the
+6V
(or
+18V)
and
±20V
outputs.
A
three-position
meter
switch selects
one
of
the
supplies for display
of
its
voltage
and
current
on
two
dual-range meters.
The
+6V
(or +18V)
and
±20V
outputs
share a
common
output
ter-
minal which
is
isolated
from
chassis
ground.
1-3 DESCRIPTION
1-4 Both models have adual
output
of
0
to
±20
volts
at
0
to
0.5amps.
The
voltages
of
the
two
20-volt
outputs
are
adjusted
by a
si
ngle
front-panel
control
and
track
one
another
within
1
%.
The
+20V
and
-20V
outputs
can
also be
used
in
series for asingle 0
to
40V
0.5A
output.
The
third
output
differs
in
the
two
models
and
is
0
to
+6 volts
at
up
to
2.5amps
in
the
6236A
and
0
to
+18
volts
at
0
to
1
amp
in
the
6237
A /
1-6
All
outputs
are
protected
against
overload
or
short-
circuit
damage.
The
+18V
output
in
the
6237
A
and
the
±20V
outputs
in
both
models are
protected
by
circuits
which limit
output
current
to
110%
of
its nominal
maximum.
The overload
protection
circuit
for
the
+6V
output
in
the
6236A
has a
current
foldback
characteristic
which
reduces
the
output
current
as an overload increases until only 1A
flows
through
a
short
circuit.
For
this
output,
the
current
limit
depends
on
the
output
terminal
voltage
and
varies
linearly
between
2.75A
at
6V
and
1A
at
zero
volts.
1-7 The
instrument
is
available
in
three
line voltage op- 1-14
The
accessories listed
below
may
be
ordered
from
your
local
Hewlett-Packard
field sales
office
either
1-1

with
the
power
supply
or
separately.
(Refer
to
the
list
at
the
rear
of
the
manual
for
addresses.)
HP
PART
NO.
14513A
14523A
DESCRIPTION
Rack
Mounting
Kit
for
mounting
one
3
1/2"
high
supply
in a
standard
19"
relay rack.
Rack
Mounting
Kit
for
mounting
two
3
1/2"
high
supplies
side
by
side
in
a
standard
19"
relay rack.
ture.
The
first
two
digits
indicate
the
year
(10
=
1970,
11
=
1971,
etc.)
the
second
two
digits
indicate
the
week,
and
the
letter"
A"
designates
the
U.S.A. as
the
country
of
manufac-
ture.
The
second
part
is
the
power
supply
serial
number;
a
different
sequential
number
is
assigned
to
each
power
sup-
ply,
starting
with
001
01.
1-17
If
the
serial
number
on
your
instrument
does
not
agree
with
those
on
the
title
page
of
the
manual,
Change
Sheets
supplied
with
the
manual
or
Manual Backdating
Changes
define
the
difference
between
your
instrument
and
the
instrument
described
by
this
manual.
1-15 INSTRUMENT AND
MANUAL
IDENTIFICATION 1-18 ORDERING
ADDITIONAL
MANUALS
1-16
Hewlett-Packard
power
supplies
are
identified
by
a
two
part
serial
number.
The
first
part
is
the
serial
number
prefic, a
number-letter
combination
that
denotes
the
date
of
a
significant
design
change
and
the
country
of
manufac-
1-19
One
manual
is
shipped
with
each
power
supply.
Additional
manuals
may
be
purchased
from
your
local Hew--
lett-Packard field
office
(see
the
list
at
the
rear
of
this
manual
for
addresses).
Specify
the
model
number,
serial
number
prefix,
and
the
HP
Part
number
provided
on
the
title
page.
NOTE
Table
1-1.
Specifications,
Models
6236A
and
6237
A
TRACKING:
The
+20V
and
-20V
outputs
track
within
1
%.
Specifications
apply
to
both
models
unless otherwise indicated.
INPUT POWER:
Standard
Option:
104:127Vac
(120Vac
nominal),
47-
63Hz,
single-phase, 112W,
140VA
(Other
line voltage
options
are listed in Paragraph 1-11.)
DC
OUTPUT
AND
OVERLOAD
PROTECTION:
o
to
±20V
Outputs:
Maximum
rated
output
current
is
0.5A.
Short
circuit
output
current
is
0.55A
±5%
and
a
fixed
current
limit
circuit
limits
the
output
of
each
sup-
ply
to
this
maximum
at
any
output
voltage
setting.
Unbal-
anced
loads
within
current
rating are
permitted.
Model
6236A
o
to
+6V
Output:
Maximum
rated
output
current
is
2.5A
at
6V.
The
maximum
available
output
current
decreases
with
the
output
voltage
setting.
A
current
foldback
current
limits
the
output
to
2.75A
±5%
at
6volts and,
with
decreasing
voltage,
reduces
the
current
limit
linearly
to
1A ±15%
at
zero
volts
(short
circuited).
Model
6237A
o
to
+18V
Output:
Maximum
rated
output
current
is
1.0A.
Short
circuit
output
current
is
1.1 A±5%
and
a
fixed
current
limit
circuit
limits
the
output
to
this
maximum
at
any
output
voltage
setting.
1-2
LOAD
EFFECT
(Load
Regulation):
All
Outputs:
Less
than
0.01 %plus
2mV
for
afull
load
to
no
load
change
in
output
current.
SOURCE
EFFECT
(Line
Regulation):
All
Outputs:
Less
than
0.01%
plus
2mV
for
any
line
voltage
change
within
rating.
PARD
(Ripple
and
Noise):
All
Outputs:
Less
than
0.35mV
rms
and
1.5mV
p-p
(20
Hi
to
20
MHz).
DRIFT
(Stability):
All
Outputs:
Less
than
0.1 %plus
5mV
(0
to
20
Hz)
during
8
hours
at
constant
line,
load,
and
ambient
after
an
initial
warm-up
time
of
30
minutes.
LOAD
TRANSIENT
RECOVERY
TIME:
All
Outputs:
Less
than
50psec
for
output
recovery
to
within
15mV
of
nominal
output
voltage
following
aload
change
from
full
load
to
half load (or vice versa).
OUTPUT
VOLTAGE
OVERSHOOT:
All
Outputs:
During
turn-on
or
turn-off
of
ac
power,
output
plus
overshoot
will
not
exceed
1V if
the
output
control
is
set
for
less
than
1
V.
If
the
control
is
set
for
1V
or
higher,
there
is
no
overshoot.

Table 1-1. Specifications, Models
6236A
and
6237A
(Continued)
TEMPERATURE
COEFFICIENT:
All
Outputs:
Less
than 0.02% plus 1
mV
voltage change
per degree Celsius over the operating
range
from
0
to
40°C
after 30 minutes warm-up.
*OUTPUT
IMPEDANCE
(typical):
o
to
+20V
Output:
0.5mn
plus 1.5/lH
o
to
-20V
Output:
0.5mn
plus 1.5/lH
Model
6236A
o
to
+6V
Output:
0.3mn
plus 1/lH
Model
6237A
o
to
+18V
Output:
0.3n
plus 1.5/lH
*Operating characteristics listed
as
typical
are
provided
for
the user's
information
only
and
are
not
warranteed specifi-
cations.
RESOLUTION:
(Minimum
output
voltage change obtainable using
front
panel voltage
control)
o
to
±20V
Outputs: 70mV
Model
6236A
o
to
+6V
Output:
20mV
Model
6237A
o
to
+18V
Output:
70mV
1-3
TEMPERATURE
RANGES:
Operating: 0
to
+40°C ambient.
At
higher temperatures,
output
current
is
derated linearly
to
50%
at 55°C.
Storage:
-40°
C
to
+75°
C.
METER RANGES:
o
to
+20V
Output:
0-25V,O-0.6A
o
to
-20V
Output:
0-25V,O-0.6A
Model
6236A
o
to
+6V
Output:
0-7V,
0-3A
Model
6237A
o
to
+18V
Output:
0-21
V, 0-1.2A
METER
ACCURACY:
±4%
of
full
scale
DIMENSIONS:
3
15/32
H x
87/32
W x
129/16
D
(88mm Hx208mm Wx319mm D)
WEIGHT:
9.5 Ib (4.3kg)

SECTION II
INSTALLATION
2-1
INITIAL
INSPECTION
2-2 Before
shipment,
this
instrument
was
inspected
and
found
to
be free
of
mechanical
and
electrical
defects.
As
soon
as
the
instrument
is
unpacked,
inspect
for
any
damage
that
may
have
occurred
in
transit.
Save all
packing
materials
until
the
inspection
is
completed.
If
damage
is
found,
file
claim
with
carrier
immediately.
The
Hewlett-Packard
Sales
and
Service
office
should
be
notified
as
soon
as possible.
2-3 Mechanical Check
2-4 This
check
should
confirm
that
there
are
no
broken
knobs
or
connectors,
that
the
cabinet
and
panel surfaces are
free
of
dents
and
scratches,
and
that
the
meter
is
not
scratch-
ed
or
cracked.
NOTE:
ACCESSORY
KITS
FOR
19
INCH
RACK
IIOUNTIIG
AIlE:
HI'
IIOOEL
1451~
FOR
CIlE
SUI'l\.Y
HP
lOlELl4523A RJlTlI09..PPL£S
$10£
VIEW
2-5 Electrical Check Figure 2-1. Outline Diagram
2-6
The
instrument
should
be
checked
against
its elec-
trical
specifications.
Section
Vincludes an
"in-cabinet"
per-
formance
check
to
verify
proper
instrument
operation.
2-7
INSTALLATION
DATA
2-8
The
instrument
is
shipped
ready
for
bench
opera-
tion.
Before
applying
power
to
the
instrument,
see
the
CAUTION
notice
in Paragraph 3-2.
2-9 Location
2-11
Outline Diagram
2-12
Figure
2-1
illustrates
the
outline
shape
and
dimen-
sions
of
this
supply.
Figure 2-2. Rack
Mounting,
One
Unit
Figure 2-3. Rack
Mounting,
Two
Units
Rack Mounting
2-10
This
instrument
is
air
cooled.
Sufficient
space
should
be
allotted
so
that
afree
flow
of
cooling
air
can
reach
the
rear
of
the
instrument
when
it
is
in
operation.
It
should
be
used
in
an
area
where
the
ambient
temperature
does
not
exceed
40°C
(up
to
55°C
with
derating).
2-13
2-14
This
instrument
may
be
rack
mounted
in
a
standard
19-inch
rack
panel
either
by itself
or
alongside asimilar
unit.
Figures 2-2
and
2-3
show
the
components
of
the
rack
mount-
ing kits available
for
this
power
supply.
Ordering
informa-
tion
for
rack
mounting
accessories
is
given in Paragraph 1-13.
2-1

2-15
Input
Power Requirements
2-16 Depending
on
the
line voltage
option
ordered,
the
supply
is
ready
to
be
operated
from
one
of
the
power
sources
listed in
Table
2-1.
The
input
voltage range,
and
the
input
current
and
power
at
high line voltage
and
full load
is
listed
for
each
option.
Alabel
on
the
rear
heat
sink
identifies
the
line voltage
option
of
your
supply.
All
options
of
this
model
operate
from
a
47-63
Hz
single-phase line.
2-17
If
desired,
the
user
can
easily
convert
the
unit
from
any
of
these
options
to
another
by following
the
instructions
in Paragraph 3-4. A
unit
is
converted
by
resetting
an internal
line voltage
selector
switch,
replacing
the
fuse,
and
changing
the
line voltage tag.
2-20
To
preserve
the
protection
feature
when
operating
the
instrument
from
a
two-contact
outlet,
use a
three-prong
to
two-prong
adapter
(if
permitted
by local regulations) and
connect
the
green lead
on
the
adapter
to
ground.
2-21 Model
6236A
and
6237
Asupplies are
equipped
at
the
factory
with
a
power
cord
plug
appropriate
for
the
user's
location.
Figure 2-4 illustrates
the
standard
configu-
rations
of
power
cord
plugs used by HP. Above each draw-
ing
is
the
HP
option
number
for
that
configuration
of
power
connector
pins. Below each drawing
is
the
HP
part
number
for a
replacement
power
cord
equipped
with
aplug
of
that
configuration.
Notify
the
nearest
HP Sales
and
Service
Office if
the
appropriate
power
cord
is
not
included
with
the
instru
ment.
2-22 Repackaging
for
Shipment
--
CAUTION
--
If
the
supply
might
possibly have been
converted to aline voltage
option
other
than the one
marked
on its
identifying
label
without
being relabeled
in
some way,
check the setting
of
the line voltage selector
switch
and
the fuse rating before
applying
power.
(See
CAUTION
in
Paragraph 3-2)
2-23
To
insure safe
shipment
of
the
instrument,
it
is
recommended
that
the
package designed
for
the
instrument
be used.
The
original packaging material
is
reusable. If it
is
not
available,
contact
your
local Hewlett-Packard field
office
to
obtain
the
materials. This office will also furnish
the
address
of
the
nearest
service office
to
which
the
instru-
ment
can
be
shipped
and
provide
the
Authorized
Return
label necessary
to
expedite
the
handling
of
your
instrument
return.
Be
sure
to
attach
atag
to
the
instrument
which
specifies
the
owner,
model
number,
full serial
number,
and
service
required,
or
abrief
description
of
the
trouble.
2-18 Power Cable
8120-0050
OPTION
903
8120-1691
OPTION
902
8120-1369
OPTION
901
Figure 2-4.
Power
Cord
Configurations
8120-1351
OPTION
900
2-19
To
protect
operating
personnel,
the
National
Electrical
Manufacturers
Association (NEMA)
recommends
that
the
instrument
panel
and
cabinet
be
grounded.
"This
instrument
is
equipped
with
a
three
conductor
power
cable.
The
third
conductor
is
the
ground
conductor
and
when
the
cable
is
plugged
into
an
appropriate
receptacle,
the
instru-
ment
is
grounded.
The
offset
pin
on
the
power
cable
three-
prong
connector
is
the
ground
connection.
In
no
event
shall
this
instrument
be
operated
without
an
adequate
cabi
net
ground
connection.
Table
2-1.
Input
Power
Requirements
Option
Line Voltage Range
Input
Current
Input
Power
100
(100
Vac)
87-106
Vac
1.3A
140
VA
Standard
(120
Vac)
104-127
Vac
1.1A
140
VA
220
(220
Vac)
191-233
Vac
0.6A
140
VA
240
(240
Vac)
208-250
Vac
0.55A
140
VA
2-2

SECTION
III
OPERATING INSTRUCTIONS
3-1
m
=~=::
OU~~~/~~2~:
"If"
_---
........
1
Figure 3-1. Controls and Indicators
TURN-ON CHECKOUT PROCEDURE
a.
Connect
line
cord
to
power
source
and
turn
LINE
switch
G)
on.
LINE ON
indicator
®will light.
b.
Set
METER
switch
®
to
the
+6V
position
and,
with
no
load
connected,
vary
+6V
VOLTAGE-control
@over
its range
and
check
that
the
voltmeter
responds
to
the
con-
trol
setting
and
the
ammeter
indicates
zero.
c.
Set
the
+6V
VOLTAG E
control
for
a
6-volt
meter
indication
and
short
the
+6V
output
terminal
to
COM
(common)
terminal
®
with
an
insulated
test
lead.
The
ammeter
should
indicate
a
short-circuit
output
current
of
approximately
1.0A
(1.1A
in
the
6237A).
Remove
the
short
from
the
output
terminals.
d.
Set
the
METER
switch
to
the
+20V
position
and,
with
no
load
connected,
vary
±20V
VOLTAGE
control
®
over its range
and
check
that
the
voltmeter
responds
to
the
control
setting
and
the
ammeter
indicates
zero.
3-2
The
following
steps
describe
the
use
of
the
Model
6236A
or
6237
A
front
panel
controls
and
indicators
illus-
trated
in Figure 3-1
and
serve as a
brief
check
that
the
sup-
ply
is
operational.
This
checkout
procedure
or
the
more
detailed
performance
test
of
Paragraph 5-6
should
be follow-
ed
when
the
instrument
is
received
and
before
it
is
connect-
ed
to
any
load
equipment.
Proceed
to
the
more
detailed
procedures
beginning in Paragraph 5-6 if
any
difficulties
are
encountered.
--
CAUTION--
e.
Set
the
±20V
VOLTAGE
control
for
a
20-volt
meter
indication
and
short
the
+20V
output
terminal
to
the
com-
mon
terminal
with
an
insulated
test
lead.
The
ammeter
should
indicate
a
short-circuit
output
current
of
O.55A
±5%.
Remove
the
short
from
the
output
terminals.
f.
Repeat
steps
(d)
and
(e),
but
substitute
the
-20V
position
of
the
METER
switch
and
the
-20V
output
ter-
minal.
Figure 3-2. Line Voltage Selector (Set for
120
Vac)
Before applying power to the supply, make certain
that its line voltage selector switch
(53)
is
set
for
the line voltage to be used. This switch
is
mounted
on the circuit board behind the voltmeter and
is
visible through the perforations in the top cover.
The positions
of
the two white marks on the switch
indicate the switch setting
(see
Figure 3-2).
If
the
switch setting does
not
correspond to the intended
power source, proceed to
Paragraph
3-4 before
applying power.
.r--
240----,
(
r-
220
----,
0_
0
L-,OO--.J
'---120
---J
t
FRONT
OF
SUPPLY
NOTE
For the Model 6237A, substitute. +18V
for +6Vin the following steps.
3-1
3-3
If
this
brief
checkout
procedure
or
later
use
of
the
supply
reveals apossible
malfunction,
see
Section
V
of
this
manual
for
detailed
test,
troubleshooting,
and
adjustment
procedures.

3-4
LINE
VOLTAGE
OPTION CONVERSION
3-5
To
convert
the
supply
from
one
line voltage
option
to
another,
the
following
three
steps
are necessary:
1.
After
making
certain
that
the
line
cord
is
discon-
nected
from
a
source
of
power,
remove
the
top
cover
from
the
supply
and.
set
the
two
sections
of
the
li:1e
voltage selec-
tor
switch
for
the
desired
line voltage (see Figure 3-2),
2.
Check
the
rating
of
the
installed fuse
and
replace
it
with
the
correct
value, if necessary.
For
Options
100
or
120,
use a
normal
time-constant
2-amp
fuse (HP
Part
No.
2110-0002);
for
Options
220
or
240,
use a
normal
time-
constant
1-amp
fuse (HP
Part
No.
2110-0001).
3. Mark
the
instrument
clearly
with
a
tag
or
label
indicating
the
correct
line voltage
to
be used.
3-6
OPERATION
3-7 This
power
supply
can
be
operated
individually
or
in parallel
with
another
supply
(see Paragraph
3-17).
All
output
terminals
are
isolated
from
ground.
The
±20V
and
+6V
or
+18V
outputs
use asingle
common
output
terminal.
This
common
(COM)
terminal
or
anyone
of
the
other
output
terminals
may
be
grounded
to
the
chassis
at
the
front
panel
ground
terminal
(
G)
in Figure
3-1),
or
all
outputs
may
be
left
floating. Loads can be
connected
separately
between
each
of
the
0
to
20V
output
terminals
and
the
COM ter-
minal,
or
between
the
-20V
and
the
+20V
terminals
for
a
o
to
40V
output.
3-8 Overload Protection Circuits
3-9
±20-Volt
Current
Limit.
The
+20V
and
-20V
outputs
are individually
protected
against
overload
or
short-
circuit
damage
by
separate
current
limit
circuits
which
are
adjusted
at
the
factory
to
limit
the
output
current
to
0.55A
±5%. (This
is
110%
of
the
rated
maximum
output
of
0.5A.)
The
current
limits can be
set
by
adjusting
resistor R6
for
the
+20V
output
and
R26
for
the
-20V
output.
(See Paragraph
5-47
for
current
limit
calibration
instructions.)
No
deteri-
oration
of
supply
performance
occurs
if
the
output
current
remains
below
the
current
limit
setting.
If asingle load
is
connected
between
the
+20V
and
-20V
outputs,
the
circuit
set
for
the
lesser
current
limit
will
limit
the
output.
3-10
+6V
Current
Foldback
(Model
6236A).
The
over-
load
and
short-circuit
protection
circuit
for
the
+6V
output
of
the
Model
6236A
reduces
the
output
current
limit
as
the
output
terminal
voltage decreases.
(The
operating
region
of
the
+6V
output
is
enclosed
by
heavy lines in Figure 3-3).
The
maximum
rated
output
current
is
2.5A
and
the
current
limit
is
factory-adjusted
to
operate
at
2.75A
±5%
when
the
3-2
output
is
6volts.
At
lower
output
voltages,
the
circuit
reduces
the
maximum
obtainable
output
current
linearly
until 1A
±15%
flows vvhen
the
output
is
shorted.
The
short-
circuit
current
cannot
be
adjusted,
but
R46
can
be
set
to
limit
the
maximum
current
at
6V
to
2.75A
±5%. (See Para-
graph
5-47
for
current
limit
calibration
instructions.)
3-11
+18-Volt
Current
Limit
(Model
6237
A).
The
+18-
volt
output
of
the
Model
6237
A
is
protected
by
a
fixed
cur-
rent
limit
circuit
which
operates
at
1.1 A
(110%
of
its max-
imum
rated
output
of
1.0A).
The
circuit
is
similar
to
the
ones
in
the
±20-volt
supplies. (See Paragraph 5-47
for
cal ibrati
on
i
nstructi
ons.)
3-12 Operation Beyond Rated
Output
3-13
The
supply
may
be
able
to
provide
voltages
and
currents
greater
than
its
rated
maximum
outputs
if
the
line
voltage
is
at
or
above
its
nominal
value.
Operation
can
ex-
tend
into
the
shaded
areas
on
the
meter
faces
without
dam-
age
to
the
supply,
but
performance
cannot
be
guaranteed
to
meet
specifications.
If
the
line voltage
is
maintained
in
the
upper
end
of
the
input
voltage range,
however,
the
supply
probably
will
operate
within
its
specifications.
3-14 Connecting Loads
3-15
Each
load
should
be
connected
to
the
power
supply
output
terminals
using
separate
pairs
of
connecting
wires.
This
minimizes
mutual
coupling
between
loads
and
takes
full
advantage
of
the
low
output
impedance
of
the
power
supply.
Connecting
wires
to
the
load
must
be
of
adequately
heavy gage
to
maintain
satisfactory
regulation
at
the
load.
Each pair
of
connecting
wires
should
be as
short
as possible
and
twisted
or
shielded
to
reduce
noise
pickup.
If
shielded
wire
is
used,
connect
one
end
of
the
shield
to
the
power
supply
ground
terminal
and
leave
the
other
end
unconnect-
ed.
3-16
If
load
considerations
require
that
the
output
power
distribution
terminals
be
remotely
located
from
the
power
supply,
then
the
power
supply
output
terminals
should
be
connected
to
the
remote
distribution
terminals
by
a
pair
of
twisted
or
shielded
wires
and
each
load
separately
connect-
ed
to
the
remote
distribution
terminals.
3-17 Parallel Operation
3-18
Two
or
more
power
suppl
ies
can
be
connected
in
parallel
to
obtain
a
total
output
current
greater
than
that
available
from
one
power
supply.
The
total
output
current
is
the
sum
of
the
output
currents
of
the
individual
power
supplies.
The
output
voltage
controls
of
one
power
supply
should
be
set
to
the
desired
output
voltage,
and
the
other
power
supply should
be
set
for
aslightly larger
output
volt-

NOTE:
THE LOWER END -POINT
OF
THE
CURRENT
LIMIT
LINE
IS
NOT
AD-
JUSTABLE;
THE UPPER END-POINT
IS SET AT THE FACTORY
FOR
2.75A
±
5%.
BETWEEN ITS
END-
POINTS,
THE ACTUAL CURRENT
LIMIT
IS
A
STRAIGHT-LINE FUNCTION.
OPERATING
REGION
+6V
SUPPLY,
MODEL
6236A
2V
IV
5V
~-----+------+------+------+---~~-,4
__
--------4
4V
~-----+------+-----+------+-~~-+-"---+-------4
3V
OUTPUT
TERMINAL
VOLTAGE
6V
OUTPUT
CURRENT (AMPERES)
o
0.5
t
1.0
\
0.85A
115A
SHORT
CIRCUIT CURRENT
MAY
VARY
±15%
FRav1
UNIT
TO
UNIT.
1.5
2.0
2.5
3.0
Figure
3-3:
Current
Limit
Characteristics
of
the
6V
Supply
(Model
6236A)
3-21
Output
Capacitance.
An internal
capacitor
across
the
output
terminals
of
the
power
supply
helps
to
supply
high-current
pulses
of
short
duration
during
constant
volt-
age
operation.
Any
capacitance
added
externally
will im-
prove
the
pulse
current
capability,
but
will decrease
the
load
protection
provided by
the
current
limiting circuit. A
3-20
Pulse Loading.
The
power
supply
will
automati-
cally cross over
from
constant
voltage
to
current
limit
operation
in
response
to
an increase
in
the
output
current
over
the
preset
limit.
Although
the
preset
limit
may
be
set
higher
than
the
average
output
current,
high
peak
currents
as
occur
in
pulse loading
may
exceed
the
preset
current
limit
and cause crossover
to
occur
and
degrade
performance.
age.
The
supply
set
to
the
lower
output
voltage will
act
as
a
constant
voltage
source,
while
the
supply
set
to
the
higher
output
will
act
as a
current-limited
source,
dropping
its
out-
put
voltage until
it
equals
that
of
the
other
supply.
The
constant
voltage
source
will deliver
only
that
fraction
of
its
total
rated
output
current
which
is
necessary
to
fulfill
the
total
current
demand.
3-19 Special Operating Considerations
high-current
output
pulse
may
damage load
components
before
the
average
output
current
is
large
enough
to
cause
the
current
limiting
circuit
to
operate.
3-22
Reverse
Current
Loading. An active load
connect-
ed
to
the
power
supply
may
actually
deliver areverse cur-
rent
to
the
power
supply
during
a
portion
of
its
operating
cycle. An
external
source
cannot
be allowed
to
pump
cur-
rent
into
the
supply
without
loss
of
regulation
and
possible
damage
to
the
output
capacitor.
To
avoid
these
effects,
it
is
necessary
to
preload
the
supply
with
a
dummy
load
resistor so
that
the
power
supply
delivers
current
through
the
entire
operating
cycle
of
the
load device.
3-23
Reverse Voltage
Protection.
Internal
diodes
con-
nected
with
reverse
polarity
across
the
output
terminals
protect
the
output
electrolytic
capacitors
and
the
driver
transistors
from
the
effects
of
areverse voltage applied
across a
supply
output.
Since series
regulator
transistors
cannot
withstand
reverse voltage
either,
diodes
are also
connected
across
them.
When
operating
supplies in parallel,
these
diodes
protect
an
unenergized
supply
that
is
in para-
llel
with
an energized
supply.
3-3

SECTION
IV
PRINCIPLES OF OPERATION
4-1
OVERALL
DESCRIPTION
4-2 This section presents
the
principles
of
operation
of
the
Models
6236A
and
6237
ATriple
Output
Power
Supply.
Throughout
this
section
refer
to
the
combined
schematic
diagram
of
Figure 7-1.
NOTE
All information in this section applies to
both
models unless otherwise indicated.
4-3 The
two
primary
windings
of
the
power
transformer
are
connected
in
one
of
four
different
ways by setting
the
two
slide switches
mounted
on
the
circuit
board. These
switches select
one
of
the
nominal ac
input
voltages
for
which
the
supply
is
designed:
100V,
120V,
220V,
or
240V.
4-4 The
transformer
secondaries,
together
with
recti-
fiers
and
capacitor
filters, provide raw
dc
for
the
three
out-
put
regulator circuits and for
another
regulator which pro-
vides reference and bias voltages
to
the
output
regulators.
4-5
By
comparing
its
output
to
ahigh-stability refer-
ence,
the
0
to
+6-volt regulator (6236A)
or
0
to
+18-volt
regulator
(6237
A) holds its
output
voltage
at
the
value
determined
by a
front
panel
control.
Any
error
in
the
actual
output
as
compared
to
the
desired
output
is
am-
plified by an operational amplifier
and
applied as
fe~dback
to
control
the
conduction
of
aseries
regulator
transistor.
As
aresult,
the
voltage across
the
series
transistor
varies so
as
to
hold
the
output
voltage
constant
at
the
desired level.
The high gain
of
the
voltage
comparison
amplifier
and
the
stability
of
the
reference voltage ensure
that
input
voltage
or load
current
variations have Iittle
effect
on
the
output
voltage.
4-6
The
0
to
+6-volt
output
in
the
Model
6236A
is
protected
by a
current
foldback
limiter which minimizes
dissipation in
the
series regulator
transistor
during
overloads.
In
a
current
foldback
circuit,
the
current
limit
depends
on
the
output
terminal voltage
and
in this
regulator
ranges
from 2.
75A
±5%
at
6volts
to
1A ±15%
with
the
output
short-
ed. (An
output
of
2.
75A
is
110%
of
the
rated
maximum
of
2.5A
at
6volts.)
The
operating region
of
the
+6-volt regu-
lator
output
is
enclosed by aheavy line
in
Figure 3-3.
If
the
operating
point
reaches
the
diagonal
current
limit line,
adecrease in load resistance moves
the
operating
point
4-1
down
the
line, reducing
the
output
voltage
and
current.
Current
foldback
is
controlled
by
a
second
operational
amplifier in
the
regulator which
monitors
the
dc
output
current.
This
current
comparison
amplifier
takes
control
of
the
'output
away
from
the
voltage
comparison
amplifier
when
the
current
reaches
the
design limit. Removing
the
overload restores
constant
voltage
operation
automatically.
4-7
The
+20-volt regulator has afixed
current
limit
at
110%
of
its
0.5
amp
maximum
rated
output
but
is
otherwise
similar
to
the
+6-volt regulator.
4-8
The
0
to
-20-volt
regulator is,
in
turn,
similar
to
the
+20-volt regulator
except
that
it resembles a
complementary
mirror
image
of
the
latter.
The
output
voltages
of
the
+20-
volt
and
-20-volt
supplies are
both
set
by
the
same
front
panel
control
and
track
each
other
within
1%. Precise track-
ing
of
the
two
outputs
is
achieved
by
controlling
the
positive
output
conventionally
and
using
that
output
as
the
reference
voltage
for
the
negative
output.
4-9
The
0
to
+18-volt regulator in
the
Model
6237
A
is
similar
to
the
+20-volt regulator. It has afixed
current
limit
at
110%
of
its
1.0
amp
output.
4-10
The
reference
and
bias
supply
provides reference
and
bias voltages
for
the
output
regulators.
4-11
The
turn-onlturn-off
control
circuit
prevents
out-
put
transients
when
the
supply
is
turned
on
or
off. It does
this by delaying
the
application
of
certain
bias
and
reference
voltages
at
turn-on
and
removing
them
shortly
after
turn-off.
4-12
A
three-position
meter
switch selects which
of
the
supplies has its
output
voltage
and
current
indicated
on
the
front
panel meters.
The
proper
range
of
the
dual-range
meters
is
selected
automatically.
4-13
DETAILED
CIRCUIT
DESCRIPTION
4-14 0To
+20-Volt
Regulator
4-15
Voltage
Comparison
Amplifier.
The
voltage
com-
parison amplifier in
the
+20-volt
supply
controls
the
conduc-
tion
of
series regulator
transistor
Q1
so
that
the
voltages
at
the
two
inputs
of
the
amplifier remain equal. Afixed volt-
age divider holds its inverting
input
(U1-2)
at
-16mV.
Its
non-inverting
input
(U1-3)
monitors
the
output
voltage in

series
with
the
voltage across R1. Since R2
is
connected
between
the
-6.2V
reference
supply
and
a
point
which feed-
back
action
holds near
-16mV,
its
current
remains
constant.
This
current
flows
through
R1
to
produce
avoltage
drop
across
R1
proportional
to
its resistance setting,
thus
the
output
voltage
of
the
supply
is
proportional
to
the
resistance
setting
of
R1.
At
the
output
of
the
voltage
comparison
amplifier (U1-1), apositive voltage change
corresponds
to
a
decrease in
the
conduction
of
Q1.
4-16
CR2
and
CR3
protect
the
input
of
the
amplifier
against
transient
overloads, C2
and
R4
speed
up
loop
re,.
sponse
time,
and
C4
and
R12 stabilize
the
supply's
high
frequency
characteristics.
4-17
OR-Gate.
To
permit
either
the
voltage
comparison
amplifier
or
the
current
comparison
amplifier
to
control
the
series regulator
transistor,
the
outputs
of
both
amplifiers
are
connected
to
the
base
of
driver
Q2
through
an OR-gate
composed
of
CR5
and
CR6.
CR5
is
normally reverse
biased by anegative
output
from
the
current
comparison
amplifier,
permitting
the
voltage
comparison
amplifier
to
drive
Q2
through
CR6. An overload drives
the
output
of
the
current
comparison
amplifier positive,
forward
biasing
CR5
and
reducing
the
supply
output.
When
the
overload
is
removed,
CR5
is
reverse biased again
and
the
voltage
com-
parison amplifier resumes
control
of
the
output.
4-18
Driver
and
Series Regulator.
The
-12.4
V
output
of
the
bias
supply
provides
the
turn-on
bias
for
series regu-
lator
transistor
Q1. Its
complete
current
path
includes
Q15,
CR59,
R14,
and
Q1,
and
returns
to
common
through
current
monitoring
resistor R8. (It
is
because this bias
current
flows
through
R8
that
the
output
ammeter
requires
the
zero
off-
set
bias
circuit
described
in
paragraph 4-43.)
Through
the
OR-gate,
either
the
voltage
or
the
current
comparison
ampli-
fier
controls
the
conduction
of
driver Q2, which regulates
the
flow
of
turn-off
bias
through
Q1's
base-emitter
circuit.
The
algebraic sum
of
the
nearly
constant
turn-on
bias
through
R14
and
the
variable
turn-off
bias
through
Q2
controls
the
conduction
of
series
regulator
transistor
Q1.
4-19
Current
limit
Circuit.
In
the
+20-volt regulator,
the
current
comparison
amplifier
compares
the
voltage
across
current
monitoring
resistor R8
to
the
fixed voltage
across
part
of
current
limit
adjust
potentiometer
R6.
The
current
limit
adjustment
is
set
so
that
the
input
voltage
to
the
current
comparison
amplifier
is
negative in
the
normal
operating
region,
but
becomes zero
when
the
output
current
increases
to
0.55
amps. When
the
amplifier's
input
voltage
reaches zero, it
takes
control
of
the
regulator
output
voltage
and
reduces it as necessary
to
keep
the
output
current
from
exceeding
0.55
amps. When
the
overload
is
removed,
the
output
of
the
current
comparison
amplifier goes negative,
reverse biasing
CR5
and
returning
control
to
the
voltage
4-2
comparison
amplifier.
4-20
Turn-On/Turn-Off
Control.
When
the
power
supply
is
turned
on
or
off,
Q15
in
the
turn-on
control
circuit
with-
holds
turn-on
bias
from
Q1
while
the
regulator
bias voltages
are
too
low. This prevents an
output
voltage
transient
from
occurring before
the
amplifiers are
properly
biased.
The
output
of
the
-6.2V
reference
supply
is
also
temporarily
held
at
alow voltage by
Q14,
which
conducts
to
short
that
output.
4-21 Circuit
Protection
Components.
Diodes CR1,
CR7,
and
CR9
each
protect
the
+20-volt
supply
from
spe-
cific hazards.
Output
diode
CR1
protects
the
supply
com-
ponents
if areverse voltage
is
applied
to
the
output
terminals.
A
common
way
for
this
to
occur
is
for
an unenergized
supply
to
be
connected
in
series
with
another
that
is
energized.
If
the
output
voltage
is
turned
down
quickly
while alarge
capacitor
is
connected
across
the
output,
CR7
protects
driver
Q2
from
excessive dissipation
by
shunting
some
of
its
base
current
to
common.
The
series
regulator
diode,
CR9
protects
the
series regulator
transistor
from
reverse voltage.
Series regulator voltage
could
occur
if adeenergized sup-
ply were
connected
in
parallel
with
an energized one.
4-22 0To
-20-Volt
Regulator
4-23 Instead
of
using an
NPN
driver
and
a
PNP
series
regulator in
the
negative
output
line as
in
the
+20-volt regu-
lator,
the
-20-volt
regulator uses a
PNP
driver
and
an
NPN
series regulator in
the
positive
output
line.
The
-20-volt
regulator
circuit
is
the
complementary
equivalent
of
the
+20-volt
circuit
in
other
respects, as well.
Their
current
limit
circuits
operate
similarly.
At
the
outputs
of
the
current
and
voltage
comparison
amplifiers in
the
-20-volt
circuit, aneg-
ative voltage change
corresponds
to
adecrease
in
series regu-
lator
conduction.
The
turn-on
bias
for
its series regulator
transistor,
Q3,
is
supplied
from
apositive voltage source,
the
+7.5V bias
supply,
and
is
switched
on
and
off
by
Q13
in
the
turn-on
control
circuit.
4-24
The
-20-volt
supply
uses
the
output
of
the
+20-volt
supply
as
its reference voltage. As aresult,
both
outputs
are
set
by asingle
front
panel
control
and
track
each
other
with-
in
1
%.
Two
resistors
in
resistor
network
Z1
are
connected
in
series
between
the
+20-volt
and
-20-volt
outputs.
These
resistors are closely
matched
in
resistance
and
temperature
coefficient
so
that
the
voltage across each
is
exactly
half
of
the
total.
The
midpoint
of
this divider
is
connected
to
the
non-inverting
input
of
the
-20-volt
supply's
voltage com-
parison amplifier.
The
amplifier's inverting
input
is
connect-
ed
to
common
through
R32
to
hold it
at
zero volts.
The
amplifier keeps its differential
input
voltage
at
zero
by
match-
ing
the
output
voltage
of
the
-20-volt
supply
to
that
of
the
+20-volt
supply.

4-25 0To +6-Volt Regulator (Model 6236A)
4-26 Except
for
differing
component
designations and
values, paragraphs
4-15
through
4-18,4-20,
and 4-21,
which
describe the voltage comparison
amplifier,
OR-gate, driver,
series regulator,
turn-on
control,
and
circuit
protection
components
of
the
+20-volt
regulator
circuit,
also apply
to
the
+6-volt
regulator. The
only
difference in
circuit
opera-
tion
lies in the
control
of
the
current
comparison
amplifier,
and thus the
type
of
current
limit
the
supply
has.
4-27
Current
Foldback
Circuit.
(For
this discussion refer
to
the Figure
7-1
schematic and
to
Figure 4-1.) The
differ-
ential
input
signal
to
the
current
comparison
amplifier
is
the
algebraic sum
of
three
circuit
voltages:
1.
The voltage across R49. ER49 remains constant
at
-305mV.
2.
The voltage across the
lower
part
of
R46
(see
Figure
4-1). ER46
is
proportional
to
the regulator
output
voltage and equals
440mV
when the supply
output
is
6volts.
3. The voltage across
current
monitoring
resistor R48.
ER48
is
proportional
to
the sum
of
the regulator
output
current
and the
0.22A
bias
current
that
flows
through
R54 and R48.
-12.4V
Z1
-1
-305mV
30K
g~~~~~TSON
~t---_5"-i+
AMPLIFIER
put.
When this happens, the
output
of
this
amplifier
goes
positive and
forward
biases CR45. Since the
current
through
CR45
tends
to
reduce the
output
of
the supply, the
output
of
the voltage comparison
amplifier
goes
negative in oppo-
sition
to
this change and reverse
biases
CR46
to
leave the
current
comparison
amplifier
in
control
of
the
output.
Now
that
the
current
comparison
amplifier
is
in
control
and
for
as
long
as
the overload remains, the supply's
output
voltage
and
current
vary
so
as
to
maintain this
amplifier's
differen-
tial
input
signal near zero volts. This results in the
output
current
limit
characteristics shown in Figure 3-3.
4-29
If
we
assume
for
example
that
the voltage
control
is
set
for
5volts and the load resistance
is
slowly
decreased,
the supply
goes
into
current
limit
at
about
2.47 amps. Here
is
why
it
occurs at
that
value.
At
a
5-volt
supply
output,
ER46
is
5/6
of
440mV,
or
367mV.
In order
for
the algebraic
sum
of
ER46 and ER48
to
go
as
far
negative
as
-305m
Vand
drive the
amplifier
output
positive, ER48 must reach
-672mV.
Once ER48 reaches this value, the
current
com-
parison
amplifier
controls the series regulator transistor
so
as
to
prevent ER48 (and thus the supply's
output
current)
from
increasing
further.
At
0.25
ohms, R48 develops
-672mV
at
2.69 amps. Since 0.22 amps
of
the
current
through
R48
is
bias
current
for
Q7, the nominal
current
limit
corresponding
to
a5-volt
output
is
2.69 amps minus
0.22
amps,
or
about
2.47 amps.
4-30
If
the load resistance continues
to
decrease,
it
pulls
the
output
voltage lower. This reduces ER46
until
at azero
output
voltage ER46 becomes zero, leaving ER48 equal in
magnitude
to
ER49.This
-305mV
drop
across
R48
corre-
sponds
to
a1.22-amp
current
through
R48 and a1-amp short-
circuit
current
at
the
output
of
the supply.
CR45
U3
CR44
+--looT
6
R49
750
+
R47
23K
R48
_
0.25
+
R46
3K
CURRENT
+}
LIMIT _ER46
ADJ.
+--
lOUT
+0.22A
07
BIAS
0.22A
07
BIAS
Figure 4-1. Foldback
Current
Limit
Circuit
in
6V
Supply
4-31 In the
+6-volt
regulator,
as
in the
+20-volt
regulator,
the
turn-on
bias
current
for
the series regulator transistor
is
switched on and
off
by
Q15
in the
turn-on
control
circuit
to
prevent
output
voltage transients.
4-28 When the supply's
output
current
is
below
the cur-
rent
limit
that
corresponds
to
its
output
terminal
voltage
(see
Figure 3-3), the
inv~rting
input
(U3-6)
of
the
current
•comparison
amplifier
is
more positive than its non-inverting
input
(U3-5),
which
is
held
at
-305mV.
The negative am-
plifier
output
which
results
is
clamped
by
CR44 and reverse
biases
OR-gate diode CR45, leaving the voltage comparison
amplifier
in
control
of
the supply's
output.
If
the load
resis.:
tance
is
decreased, the higher
output
current
increases ER48
until
the algebraic sum
of
E
R48
and ER46 makes the cur-
rent comparison
amplifier's
inverting
input
slightly
more
negative than the
-305mV
potential on its non-inverting in-
4-32 0To +18-Volt Regulator (Model 6237A)
4-33 Except
for
differing
component
designations and
values, paragraphs
4-15
through
4-21,
which
describe the
voltage comparison
amplifier,
OR-gate, driver, series regu-
lator,
current
limit
circuit,
turn-on
control,
and
circuit
protection
components
of
the
+2o-volt
regulator
circuit,
also
apply
to
the
+18-volt
regulator. In the
+18-volt
regulator,
as
in the
+20-volt
regulator, the
turn-on
bias
current
for
the
series regulator transistor
is
switched on and
off
by
Q15
in
the
turn-on
control
circuit
to
prevent
output
voltage
transients.
4-3

4-34 Reference and
Bias
Supply
4-35
The reference
and
bias supply powers
the
operation-
al
amplifiers and provides
the
bias
and
reference voltages used
throughout
the
supply. A
shunt
zener regulates its +7.5V
output.
Aseries transistor regulates its
-12.4
V
output,
using 6.2-volt zener VR1
as
its voltage reference.
The
-12.4V
output
provides a
constant
current
to
VR 1, which
is
the
pri-
mary voltage reference for
the
entire supply.
4-36
Two
equal resistors are
connected
in
series across
the
-12.4V
output.
To
regulate this
output,
voltage com-
parison amplifier
U4
compares
the
voltage across
one
of
these resistors
to
the
-6.2V
reference and controls
the
con-
duction
of
series regulator
011
through driver
012.
The
voltage
drop
across
011
is
controlled by feedback so
that
the
voltages
at
the
two
inputs
of
U4
remain equal. Driver
012
controls
011
by shunting
part
of
the
base bias supplied
by R68.
4-37 During turn-on,
the
-6.2V
reference supply
is
temporarily
shorted
by
014
in
the
turn-on control circuit.
By
trying
to
match this low reference,
011
is
initially
turned
off. While
011
is
turned
off, R69 bypasses
current
to
the
-12.4V
output
until
the
output
reaches
-9
volts and
the
turn-on control circuit removes
the
short
from
the
reference
and enables
the
-12.4-volt
regulator
to
operate
normally.
4-38
Turn-On/Turn-Off
Control
Circuit
4-39 Immediately
after
the
supply
is
energized and until
the
output
of
the
-12.4-volt
regulator reaches
about
-9
volts,
the
turn-on control circuit withholds turn-on bias
from series regulator transistors
01,
03,
and
07
and holds
4-4
the
-6.2V
reference
at
alow value. This prevents an
out-
put
voltage
transient
by ensuring
that
the
operational am-
plifiers are energized and
other
essential bias voltages are
present before
the
series regulator transistors are
turned
on.
The circuit also prevents an
output
transient when
the
sup-
ply
is
turned
off
by removing
the
turn-on bias from
the
se-
ries regulators and shorting
the
-6.2V
reference supply
as
the
voltage
of
the
-12.4
Vsupply falls below
-9
volts.
4-40
013
switches
the
bias
to
the
-20-volt
regulator
on
and off,
014
switches
the
short
across
the
-6.2-volt
refer
...
ence supply, and
015
switches
the
bias
to
the
+20-volt
and
+6-volt
or
+18-volt regulators.
015
remains
turned
off
until
VR2
conducts
at
9volts
to
switch it on. While
015
is
off,
it holds
013
biased
off
and
014
on;
when
015
conducts,
it
turns
013
and
014
off.
4-41 Meter Circuits
4-42
Voltmeter.
Two
of
the
resistors in resistor
network
Z1
are range resistors for
the
voltmeter. The accurate ratio
of these resistors permits asingle calibration
potentiometer,
R58
to
adjust
both
ranges simultaneously.
4-43
Ammeter.
The range switch
connects
the
ammeter
across the
current
monitoring resistor
of
asupply: R48
in
the
+6-volt
or
+18-volt supply, R8
in
the
+20-volt supply,
or
R28
in
the
-20-volt
supply. Each
of
these resistors con-
ducts a
constant
bias
current
for its series regulator transistor
in
addition
to
the
supply's
output
current.
If
no compen-
sation were used, this additional
current
would raise
the
indicated
output
by up
to
8%
of
full scale.
The
resistor net-
works
connected
to
each range
of
the
ammeter
selector
switch apply abias
to
the
meter
to
offset
this error. R59
calibrates
all
ammeter
ranges.

5-1
INTRODUCTION
SECTION V
MAINTENANCE
5-5
Table
5-1
lists
the
test
equipment
required
to
per-
form
the
various
procedures
described
in
this
section.
5-2
Upon
receipt
of
the
power
supply,
the
performance
test
of
Paragraph 5-6 can be
made.
This
test
is
suitable
for
incoming
inspection.
Section
III
contains
a
quick
but
less
comprehensive
checkout
procedure
which
can
be used in
lieu
of
the
performance
test
if desired.
5-3 If a
fault
is
detected
in
the
power
supply
while
making
the
performance
test
or
during
normal
operation:
proceed
to
the
troubleshooting
procedure
in Paragraph 5-32.
After
troubleshooting
and
repair,
repeat
the
performance
test
to
ensure
that
the
fault
has
been
properly
corrected
and
that
no
other
faults
exist. Before
performing
any
mainte-
nance
checks,
turn
on
the
power
supply
and
allow
ahalf-
hour
warm-up.
5-4 TEST EQUIPMENT
REQUIRED
5-6 PERFORMANCE TEST
5-7
The
following
test
can
be
used
as
an
incoming
in-
spection
check
and
appropriate
portions
of
the
test
can
be
repeated
to
check
the
operation
of
the
instrument
after
repairs. If
the
correct
result
is
not
obtained
for
a
particular
check,
proceed
to
the
troubleshooting
procedures
of
Para~
graph
5-32.
--
CAUTION--
Before
applying
power
to the supply, make
certain
that
its line voltage selector
switch
(S3)
is
set
for
the line voltage to be
used.
(See
CA
UTION
notice
in
Paragraph 3-2
for
addi-
tional
information
on S3.)
Table
5-1.
Test
Equipment
Required
REQUIRED
RECOMMENDED
TYPE
CHARACTERISTICS
USE
MODEL
,
Digital
Sensitivity:
100J1V fyll scale Measure DC voltages: HP
3450A
Voltmeter
(min.).
Input
impedance:
calibration
procedures
10
megohms
(min.'.
Variable Range:
90-130
Vac Vary AC
input
------
Voltage
Equipped
with
voltmeter
Transformer
accurate
within
1
volt
Oscilloscope
Sensitivity:
100J1V/cm. Display
transient
re- HP
180A
with
1821A,
Differential
input.
sponse
and
ripple
and
and
1801A
or
1803A
noise
waveforms.
plug-ins.
Repetitive
Rate:
60
Hz,
2J1sec.
Measure
transient
See Figure 5-5.
Load Sw. rise
and
fall
time
response.
Resistive Val ue: See Paragraph 5-11.
Power
supply
load
James
G. Biddle
Loads
Tolerance:
±5% resistor (fixed resistor
("Lubri-Tact"
or
rheostat).
Rheostat)
Current
Value:
See Paragraph 5-13. Measure
output
current
Simpson
Portable
Sampling
Accuracy:
1%
(minimum)
Shunt,
06703.
Resistor
(Shunt)
5-1

5-8 General Measurement Techniques
5-9
Connecting
Measuring Devices.
To
achieve valid
results
when
measuring
the
load
effect,
PARD (ripple
and
noise),
and
transient
recovery
time
of
the
supply,
measuring
devices
must
be
connected
as close
to
the
output
terminals
as
possible. A
measurement
made
across
the
load includes
the
impedance
of
the
leads
to
the
load.
The
impedance
of
the
load leads can easily be several
orders
of
magnitude
greater
than
the
supply
impedance
and
thus
invalidate
the
measurement.
To
avoid
mutual
coupling effects, each
measuring device
must
be
connected
directly
to
the
output
terminals by separate pairs
of
leads.
5-10 When
measurements
are
made
at
the
front
panel
terminals,
the
monitoring
leads
must
be
connected
at
point
A,
as
shown
in
Figure 5-1,
and
not
at
point
B.
Connecting
the
measuring device
at
point
B
would
result
in
ameasure-
ment
that
includes
the
resistance
of
the
leads
between
the
output
terminals
and
the
point
of
connection.
LOAD LEAD
Figure 5-1.
Front
Panel Terminal
Connections
5-11 Selecting Load Resistors. Power
supply
specifica-
tions
are
checked
with
afull load resistance
connected
across
the
supply
output.
The
resistance
and
wattage
of
the
load resistor,
therefore,
must
permit
operation
of
the
supply
at
its rated
output
voltage
and
current.
For
example,
a
supply
rated
at
20
volts
and
0.5
amperes
would
require a
load resistance
of
40
ohms
at
the
rated
output
voltage.
The
wattage
rating
of
this resistor
would
have
to
be
at
least
10
watts.
5-12 Either afixed
or
variable resistor (rheostat) can be
used as
the
load resistance. Using a
rheostat
(alone
or
in
series
with
afixed resistor)
is
often
more
convenient
than
using fixed resistors as loads because
the
latter
may
be
more
difficult
to
obtain
in
the
exact
resistance required. Asup-
plier
of
rheostats
appropriate
for
testing
these
supplies
is
listed
in
Table 5-1.
5-13
Output
Current
Measurements.
For
accurate
out-
put
current
measurements,
a
current
sampling resistor
should
be inserted
between
the
load resistor
and
the
output
of
the
supply. An
accurate
voltmeter
is
then
placed across
the
sampling resistor
and
the
output
current
calculated
by
5-2
dividing
the
voltage across
the
sampling resistor
by
its
ohmic
value.
The
total
resistance
of
the
series
combination
should
be equal
to
the
full load resistance as
determined
in
the
preceding paragraphs.
Of
course,
if
the
value
of
the
sampling resistor
is
very low
when
compared
to
the
full
load resistance,
the
value
of
the
sampling resistor
may
be
ignored.
The
meter
shunt
recommended
in
Table 5-1,
for
example,
has aresistance
of
only
1milliohm
and
can be
neglected
when
calculating
the
load resistance
of
the
sup-
ply.
5-14 Figure 5-2 shows a
four
terminal
meter
shunt.
The
load
current
through
a
shunt
must
be fed
to
the
extremes
of
the
wire leading
to
the
resistor while
the
sampling con-
nections are
made
as close as possible
to
the
resistance
portion
itself.
CURRENT
SAMPLING
TERMINALS
TO UNGROUNDED
TO
GROUNDED
TER
MI
NAL
OF
"-.JV.'(/\r---~\/v\,,-I(",l--'"
TE
RM
IN
AL OF
POWER
SUPPLY
POWER
SUPPLY
Figure 5-2.
Current
Sampling
Resistor
Connections
NOTE
All
instructions in this section apply to Models
6236A
and
6237
Aunless otherwise indicated.
5-15 Rated
Output,
Tracking, Meter Accuracy,
and
Current
limit
5-16
To
check
that
all supplies will furnish
their
maxi-
mum
rated
output
voltage
and
current,
that
the
±20V
out-
puts
track
each
other,
that
the
front
panel meters are accu-
rate,
and
that
the
current
limit circuits
function,
proceed
as follows:
Voltmeter
Accuracy
a. With
no
loads
connected:
energize
the
supply,
con-
nect
adigital
voltmeter
between
the
+6V terminal (+18V
in
Model
6237
A)
and
common
(COM),
and
set
the
+6V
(+18V) VOLTAGE
control
so
that
the
DVM indication
is
as
near
as
possible
to
6volts
(18
volts).
b.
Set
the
METER switch
to
the
+6V (+18V) range
and
check
the
front
panel
voltmeter
indication. It
should
be
within 4%
of
the
DVM indication.
c. Check
the
+20V
and
-20V
ranges
of
the
panel volt-
meter
similarly by
connecting
the
DVM
to
each
of
these
outputs
in
turn,
setting
the
±20V
VOLTAGE
control
for
a

20V
DVM
indication,
and
verifying
that
the
panel
meter
is
accurate
within
4%.
Tracking
d.
Connect
the
DVM
to
the
+20V
output,
set
the
±20V
VOLTAGE
control
for
aDVM
indication
of
20
volts,
and
reconnect
the
DVM
to
the
-20V
output
without
disturbing
the
voltage
control.
The
voltage
at
the
-20V
output
should
be
within
1%
of
the
+20V
output.
Rated
Output
and
Ammeter
Accuracy
e.
Connect
40[2
10W load resistors across
both
of
the
20V
outputs
of
the
supply
and
set
the
±20V
vaL
TAG
E
control
for
a
±20V
output.
(All
three
supplies
must
be
fully
loaded
while
checking
the
rated
output
voltage
and
current
of
each
supply.)
f.
Connect
the
test
setup
shown
in
Figure 5-3
to
the
+6V
(or
+18V)
output.
Make
the
total
resistance
of
RL
and
the
current
sampling resistor
2.4
ohms
for
the
Model
6236A
(or
18
ohms
for
the
6237
A)
to
permit
operating
the
output
at
full load. RL
should
have a
power
rating
of
at
least
20
watts.
g.
Close
the
switch
and
set
the
+6V
(+18V)
VOLTAGE
control
so
that
the
DVM indicates avoltage
drop
across
the
current
sampling resistor
that
corresponds
to
a
current
of
2.5
amps
(6236A)
or
1.0
amp
(6237
A).
h.
Set
the
METER
switch
to
the
+6V (+18V) range
and
verify
that
the
front
panel
ammeter
indication
is
within
4%
of
2.5
amps
((6236A)
or
1.0
amps
(6237
A).
i.
Connect
the
DVM
directly
across
the
output
terminals
of
the
+6V
(+18V)
supply,
record
the
DVM reading,
and
then
open
the
switch
in
the
6V
(18V)
load
circuit
without
disturbing
the
supply's
output
terminals.
The
DVM indica-
tion
should
not
change
by
more
than
2.6mV
(6236A)
or
3.8mV
(6237
A).
j.
Check
the
rated
output
and
ammeter
accur'!cy
of
the
+20V
and
-20V
supplies similarly
by
connecting
the
test
setup
of
Figure 5-3
to
each
output
in
turn.
For
each
20V
supply:
make
the
total
resistance
of
RL
and
the
current
sampling resistor
40
ohms,
set
the
±20V
VOLTAGE
con-
trol
for
a
current
indication
on
the
DVM
of
0.5A,
check
that
the
panel
meter
indication
is
within
4%
of
0.5A,
connect
the
DVM
to
the
fully loaded
output
terminals,
and
compare
the
output
voltage
before
and
after
the
load
circuit
is
opened.
The
voltage
should
not
change
by
more
than
4mV.
While
checking
each
supply,
the
other
two
must
be fully
loaded.
Current
Limit
k.
Disconnect
all loads
from
the
supply.
I.
Connect
the
test
setup
shown
in
Figure 5-3
to
the
+20-
volt
output.
Substitute
a
short
for
RL
and
leave
the
load
circuit
switch
open.
m.
Set
the
voltage
of
the
:t20V
supplies
to
20
volts.
n. Close
the
load
switch
and
determine
the
current
flow
through
the
current
sampling resistor
(meter
shunt)
by
measuring its voltage
drop
with
the
DVM.
The
current
5-3
should
be
0.55A
±5%.
o. Check
the
current
limit
of
the
-20V
supply
in
the
same way. Its
short-circuit
current
should
also be
0.55A
±5%.
p. (Model
6237A
only).
Check
the
current
limit
of
the
+18V
supply
similarly by
setting
its
output
for
18
volts
and
using aDVM
to
measure
the
current
which flows
through
alow-resistance
current
sampling resistor.
The
short-circuit
current
of
the
+18V
supply
should
be 1.1 A±5%.
q. (Steps (q)
through
(s)
apply
to
the
6236A
only.)
Connect
the
test
setup
shown
in Figure 5-3
to
the
+6V
out-
put.
Close
the
switch,
set
the
total
resistance
of
R
Land
the
current
sampling resistor
to
an
initial value
of
2.4
ohms
or
greater,
and
set
the
output
voltage
to
6volts.
r.
Reduce
the
value
of
RL
gradually
while observing
the
output
current
indicated
by
the
DVM.
The
current
should
increase
to
a
maximum
of
2.75A
±5%
before
it begins
to
decrease.
s.
Connect
a
short
across RL
and
then
recheck
the
current
indicated
by
the
DVM.
The
short-circuit
current
of
this
output
should
be 1A ±15%.
Disconnect
the
test
setup
from
the
supply.
5-17 Load
Effect
(Load Regulation)
Definition:
The
change
~EOUT
in
the
static
value
of
dc
output
voltage resulting
from
achange in load
resistance
from
open
circuit
to
avalue which yields maxi-
mum
rated
output
current
(or vice versa).
5-18
To
check
the
load
effect:
a.
Connect
afull load resistance
and
adigital
voltmeter
across
the
output
of
the
+20V
supply.
b.
Turn
on
the
supply
and
adjust
its voltage
to
its
maxi-
mum
rated
value.
c.
Record
the
voltage
indicated
on
the
DVM.
d.
Disconnect
the
load resistance
and
recheck
the
DVM
indication.
It
should
be
within
.01% plus
2mV
of
the
read-
ing
in
step
(c).
e.
Repeat
steps
(a)
through
(d)
for
each
of
the
remain-
ing
supply
outputs.
POWER
SUPPLY
UNDER TEST
-
COM.
+RL
0
()
("\.
)'
TV
1DIGITAL
(RHEOSTAT)
VOLTMETER
CURRENT + - G
SAMPLING
(
(l9
RESISTOR
~
-
f'
.~
-
(SHUNT)
Figure 5-3.
Output
Current,
Test
Setup

5-19 Source
Effect
(Line Regulation)
Definition:
The
change,
b.
E
OUT
'in
the
static
value
of
dc
output
vcltage resulting
from
a
change
in ac
input
voltage over
the
specified range
from
low line (typi-
cally
104
Vac)
to
high line (typically
127
Vac),
or
from
high line
to
low line.
rectification),
an oscilloscope display showing a
120
Hz
fundamental
component
is
indicative
of
a
"c1ean"
measure-
ment
setup,
while
the
presence
of
a
60
Hz
fundamental
usually
means
that
an
improved
setup
will result
in
a
more
accurate
(and lower) value
of
measured
ripple.
5-24 Figure
5-48
shows a
correct
method
of
measuring
the
output
ripple
of
a
constant
voltage
power
supply
using
asingle-ended
scope.
The
ground
loop
path
is
broken
by
floating
the
power
supply
output.
To
ensure
that
no
poten-
tial
difference
exists
between
the
supply
and
the
oscilloscope,
it
is
recommended
that
they
both
be plugged
into
the
same
ac
power
bus.
If
the
same bus
cannot
be used,
both
ac
grounds
must
be
at
earth
ground
potential.
5-20
To
test
the
source
effect:
a.
Connect
avariable
autotransformer
between
the
in-
put
power
source
and
the
power
supply
line plug.
b.
Connect
afull load resistance
and
adigital
voltmeter
across
the
output
of
the
+20V
supply.
c.
Adjust
the
autotransformer
for
alow line
input.
d.
Turn
on
the
power,
adjust
the
output
of
the
supply
to
its
maximum
rated
voltage,
and
record
the
DVM indica-
tion.
e.
Adjust
the
autotransformer
for
ahigh line
input
and
recheck
the
DVM
indication.
It
should
be
within
.01 %plus
2mV
of
the
reading
in
step
(d).
f.
Repeat
steps (b)
through
(e)
for
each
of
the
remaining
supply
outputs.
POWER SUPPLY CASE
•
OSCILLOSCOPE CASE
Figure 5-4. Ripple
and
Noise,
Test
Setup
AC-+---
ACC
GND
,..---f-..,.,....,~
AC
ACC
GND
I
I
I
VERTICAL I
.xr-+----~~G
INPUT I
:--~~EG
I
L
~_~~
__
---_J
A.
INCORRECT METHOD -GROUND CURRENT
IG
PRODUCES
60
CYCLE
DROP
IN
NEGATIVE LEAD WHICH
ADDS
TO
THE
POWER
SUPPLY
RIPPLE
DISPLAYED
ON SCOPE.
POWER
SUPPLY
CASE
OSCILLOSCOPE CASE
AC f,C
ACC
ACC
GND
GND
++
-VERTICAL
GGINPUT
POWER SUPPLY CASE OSCILLOSCOPE CASE
AC
AC
ACC ACC
GND
GND ++
-VERTICAL
GG
INPUT
B.
ACORRECT
METHOD
USING A
SINGLE
-ENDED
SCOPE.
OUTPUT FLOATED TO
BREAK
GROUND CURRENT LOOP,
TWISTED
PAIR
REDUCES
STRAY
PICKUP
ON
SCOPE
LEADS.
C.
ACORRECT METHOD USING A
DIFFERENTIAL
SCOPE WITH
FLOATING INPUT. GROUND CURRENT PATH
IS
BROKEN;
COMMON MODE REJECTION
OF
DIFFERENTIAL
INPUT
SCOPE
IGNORES DIFFERENCE IN GROUND
POTENTIAL
OF POWER
SUPPLY 8SCOPE, SHIELDED TWO WIRE FURTHER
REDUCES
STRAY PICKUP
ON
SCOPE LEADS.
5-21 PARD (Ripple and Noise)
Definition:
The
residual ac voltage which
is
super-
imposed
on
the
dc
output
of
aregulated
power
supply.
Ripple
and
noise
may
be specified
and
measured
in
terms
of
its rms
or
peak-to-peak
value.
5-22
Measurement
Techniques.
Figure 5-4A
shows
an
incorrect
method
of
measuring
Pop
ripple. Note
that
acon-
tinuous
ground
loop
exists
from
the
third
wire
of
the
input
power
cord
of
the
supply
to
the
third
wire
of
the
input
power
cord
of
the
oscilloscope via
the
grounded
power
sup-
ply case,
the
wire
between
the
negative
output
terminal
of
the
power
supply
and
the
vertical
input
of
the
scope,
and
the
grounded
scope
case.
Any
ground
current
circulating
in this
loop
as aresult
of
the
difference
in
potential
EG
between
the
two
ground
points
causes an IR
drop
which
is
in
series
with
the
scope
input.
This IR
drop,
normally
having a
60
Hz
Iine
frequency
fundamental,
plus
any
pick-
up
on
the
unshielded
leads
interconnecting
the
power
sup-
ply
and
scope,
appears
on
the
face
of
the
CRT.
The
magni-
tude
of
this
resulting signal can easily be
much
greater
than
the
true
ripple
developed
between
the
plus
and
minus
out-
put
terminals
of
the
power
supply
and
can
completely
in-
validate
the
measurement.
5-23
The
same
ground
current
and
pickup
problems
can
exist
if an rms
voltmeter
is
substituted
in
place
of
the
oscil-
loscope
in
Figure 5-4. However,
the
oscilloscope display,
unlike
the
true
rms
meter
reading, tells
the
observer imme-
diately
whether
the
fundamental
period
of
the
signal dis-
played
is
8.3
milliseconds
(1/120
Hz)
or
16.7
milliseconds
(1/60
Hz). Since
the
fundamental
ripple
frequency
present
on
the
output
of
an HP
supply
is
120
Hz
(due
to
full-wave
5-4

c.
Repeat
for
the
remaining
supply
outputs.
OSCILLOSCOPE
RT
(NOTE
4)
NOTES:
I.
THIS
DRAWING
SHOWS
A
SUGGESTED METHOD
OF
BUILDING ALOAD SWITCH.
HOWEVER. OTHER
METHODS
COULD BE USED;
SUCH AS ATRANSISTOR
SWITCHING NETWORK.
MAXIMUM
LOAD RATINGS
OF
LOAD SWITCH ARE:
5AMPS.500V,
250W
(NOT
2500W
l.
2.
USE
MERCURY RELAY
CLARE TYPE HGP
1002
OR
W.E. TYPE
276B.
3.
SELECT CONTACT
PRO-
TECTION NETWORK
ACCORDING
TO
MERCURY
RELAY MANUFACTURERS
INSTRUCTIONS
4.
EACH RT
IS
EQUAL TO
TWICE THE
NORMAL
FULL
LOAD RESISTANCE
(2
XRL)
USED IN PREVIOUS TESTS.
CONTACT
PROTECTION
NETWORK
r-
(NOTE
3)------
r----
-----
IN.C.
I
I
I
I
-,
I
:t :
IN.C. I
I I
I
I
I
I
I
I
II
I
REPETITIVE
I
~~~
~W~~_(!::02.E~)
__
.J
+
POWER SUPPLY
UNDER TEST
Figure 5-5. Load
Transient
Recovery
Time,
Test
Setup
5-29 Load Transient Recovery Time
Definition:
The
time
"x"
for
output
voltage
recovery
to
within
"Y"
millivolts
of
the
nominal
output
voltage following a
"Z"
amp
step
change
in
load
current,
where:
"X"
equals 50J,lsec,
"Y"
equals
15mV,
and
"z"
is
the
specified load
current
change,
equal
to
half
of
the
cur-
rent
rating
of
the
supply.
The
nominal
output
voltage
is
defined
as
the
dc
level
halfway
between
the
static
output
voltage
before
and
after
the
imposed
load change.
5-30
Measurement
Techniques.
Care
must
be
taken
in
switching
the
load resistance
on
and
off. A
hand-operated
switch
in
series
with
the
load
is
not
adequate
since
the
re-
sulting
one-shot
displays are
difficult
to
observe
on
most
oscilloscopes
and
the
arc
energy
occurring
during
switching
completely
masks
the
display
with
anoise burst.
Transistor
load
switching
devices are expensive if
reasonably
rapid load
current
changes are
to
be achieved. Instead, a
mercury-
wetted
relay
should
be used
for
loading
and
unloading
the
supply.
Connect
it in
the
load switching
circuit
shown
in
Figure 5-5. When
this
load
switch
is
connected
to
a
60
Hz
ac
input,
the
mercury-wetted
relay will
open
and
close
60
times
per
second.
The
25K
control
adjusts
the
duty
cycle
of
the
load
current
switching
to
reduce
jitter
in
the
oscillo-
scope display. This relay
may
also be used
with
a
50
Hz
ac
input.
5-25
Either
a
twisted
pair
or,
preferably,
ashielded
two-wire cable
should
be used
to
connect
the
output
termin-
als
of
the
power
supply
to
the
vertical
input
terminals
of
the
scope. When using a
twisted
pair, care
must
be
taken
that
one
of
the
two
wires
is
connected
to
the
grounded
in-
put
terminal
of
the
oscilloscope
to
ensure
that
the
supply
output
is
safely
grounded.
When using shielded two-wire,
it
is
essential
for
the
shield
to
be
connected
to
ground
at
one
end
only
to
prevent
ground
current
flowing
through
this shield
from
inducing asignal in
the
shielded leads.
5-27
In
most
cases,
the
single-ended
scope
method
of
Figure 5-4B will be
adequate
to
eliminate
non-real
compon-
ents
of
ripple so
that
a
satisfactory
measurement
may
be
obtained.
However,
in
more
stubborn
cases (or if high
frequency
noise
up
to
20
MHz
must
be
measured),
it
may
be necessary
to
use adifferential
scope
with
floating
input
as
shown
in
Figure 5-4C. If desired,
two
single-conductor
shielded cables
may
be
substituted
in
place
of
the
shielded
two-wire cable
with
equal success. Because
of
its
common
mode
rejection, a
differential
oscilloscope displays
only
the
difference
in signal
between
its
two
vertical
input
terminals,
thus
ignoring
the
effects
of
any
common
mode
signal pro-
duced
by
the
difference
in
the
ac
potential
between
the
power
supply
case
and
scope
case. Before using adifferen-
tial
input
scope
in
this
manner,
however, it
is
imperative
that
the
common
mode
rejection
capability
of
the
scope'
be verified
by
shorting
together
its
two
input
leads
at
the
power
supply
and
observing
the
trace
on
the
CRT.
it
this
trace
is
a
straight
line,
then
the
scope
is
properly
ignoring
any
common
mode
signal
present.
If
this
trace
is
not
a
straight
line,
then
the
scope
is
not
rejecting
the
ground
signal-and
must
be realigned
in
accordance
with
the
manu-
facturer's
instructions
until
proper
common
mode
rejection
is
attained.
5-26
To
verify
that
the
oscilloscope
is
not
displaying
ripple
that
is
induced
in
the
leads
or
picked
up
from
the
grounds,
the
(+)
scope
lead
should
be
shorted
to
the
(-)
scope lead
at
the
power
supply
terminals.
The
ripple value
obtained
when
the
leads are
shorted
should
be
subtracted
from
the
actual
ripple-measurement.
5-28
Measurement
Procedure.
To
measure
the
ripple
and
noise
on
each
supply
output,
follow
the
steps
below,
If
ahigh
frequency
noise
measurement
is
desired, an oscil-
loscope
with
sufficient
bandwidth
(20 MHz)
must
be used.
Ripple
and
noise
measurements
can
be
made
at
any
input
ac line voltage
combined
with
any
dc
output
voltage
and
load
current
within
rating.
a.
Connect
an oscilloscope
or
rms
voltmeter
across an
output
of
the
supply
as
shown
in
Figures 5-4B
or
5-4C.
b.
Energize
the
supply
and
observe
the
oscilloscope
or
meter
indication.
The
ripple
and
noise
should
not
be
greater
than
0.35mV
rms
or
1.5mV
peak-to-peak.
5-5

5-31
Measurement
Procedure.
To
measure
the
load
transient
recovery
time,
follow
the
steps
below
for
each
supply
output.
Transient
recovery
time
may
be
measured
at
any
input
line voltage
and any
output
voltage
within
rating.
For
this
supply
the
specified load change
is
between
half load
and
full load.
a.
Connect
the
test
setup
shown
in
Figure 5-5. Both
load resistors (RT)are
twice
the
normal value
of
afull load
resistance.
b.
Turn
on
the
supply
and
close
the
line switch
on
the
repeti+ive load switch.
c.
Set
the
oscilloscope
for
internal
sync
and
lock
on
either
the
positive
or
negative load
transient
spike.
d.
Set
the
vertical
input
of
the
oscilloscope
for
ac
coup-
ling so
that
small
dc
level changes
in
the
output
voltage
of
the
power
supply
will
not
cause
the
display
to
shift.
e.
Adjust
the
horizontal
positioning
control
so
that
the
trace
starts
at
a
point
coincident
with
a
major
graticule
division. This
point
then
represents
time
zero.
f.
Adjust
the
vertical
centering
of
the
scope
so
that
the
tail
ends
of
the
no-load
and
full-load
waveforms
are
symmet-
rically displaced
about
the
horizontal
center
line
of
the
oscil-
loscope. This
center
line
now
represents
the
nominal
output
voltage
defined
in
the
specification.
g.
Increase
the
sweep rate so
that
asingle
transient
spike
can
be
examined
in
detail.
h.
Adjust
the
sync
controls
separately
for
the
positive
and
negative going
transients
so
that
not
only
the
recovery
waveshape
but
also as
much
as possible
of
the
rise
time
of
the
transient
is
displayed.
i.
Starting
from
the
major
graticule division representing
time
zero,
count
to
the
right
50psec
and
vertically
15mV.
Recovery
should
be
within
these
tolerances,
as illustrated
in
Figure 5-6.
5-32 TROUBLESHOOTING
5-33 Before
attempting
to
troubleshoot
this
instrument,
ensure
that
the
fault
is
in
the
instrument
itself
and
not
in
an
associated piece
of
equipment.
You can
determine
this
with-
out
removing
the
covers
from
the
instrument
by using
the
appropriate
portions
of
the
performance
test
of
Paragraph
5-6.
5-34 A
good
understanding
of
the
principles
of
opera-
tion
is
ahelpful aid
in
troubleshooting,
and
the
reader
is
advised
to
review
Section
IV
of
the
manual
before
begin-
ning
detailed
troubleshooting.
Once
the
principles
of
oper-
ation
are
understood,
proceed
to
the
initial
troubleshoot-
ing
procedures
in Paragraph 5-35.
--
CAUTION--
Before
applying
power
to the supply, make
certain
that
its line voltage selector switch (S3)
is
set
for
the line voltage to be
used.
(See
CAUTION
notice
in
Paragraph 3-2
for
additional
information
on S3.)
5-35
Initial
Troubleshooting Procedure
5-36 If a
malfunction
is
found,
follow
the
steps below:
a.
Disconnect
input
power
from
the
supply
and
remove
all
loads
from
the
output.
b.
Table
5-2 lists
the
symptoms
and
probable
causes
of
several possible
troubles.
If
the
symptom
is
one
of
those
listed,
make
the
recommended
checks.
c. If
none
of
the
symptoms
of
Table 5-2
apply,
proceed
to
Table
5-3. This
table
provides an initial
troubleshooting
procedure
that
also
directs
you
to
the
more
detailed
pro-
cedures
which
follow
it.
Figure 5-6. Load
Transient
Recovery
Time
Waveforms
POSITIVE
OUTPUT-UNLOADING TRANSIENT LOADING TRANSIENT
NEGATIVE OUTPUT-LOADING TRANSIENT UNLOADING TRANSIENT
Open
Fuse
Troubleshooting
5-38
5-37
The
numbered
test
points
referred
to
in
the
trouble-
shooting
procedures
are
identified
on
the
circuit
schematic
and
on
the
component
location
diagram
at
the
rear
of
the
manual.
5-39
Although
transients
or
fatigue
can
cause afuse
to
blow,
it
is
a
good
idea
to
inspect
the
unit
for
obvious
shorts
such as
damaged
wiring,
charred
components,
or
extraneous
metal
parts
or
wire clippings
in
contact
with
circuit
board
conductors
before
replacing
the
fuse.
The
rating
of
the
correct
replacement
fuse
depends
on
the
line voltage
option
of
the
instrument:
for
Options
100
or
120,
use anormal
time-constant
2-amp fuse (HP
Part
No.
2110-0002);
for
Options
220
or
240,
use a
normal
time-constant
1-amp
fuse (HP
Part
No.
2110-0001).
v
15MV
~
14----.~--
50",
SECONDS
E
NOM
-r--,---------
50",
SECONDS
15
MV
T
5-6
This manual suits for next models
1
Table of contents
Other HP Power Supply manuals

HP
HP HVB Series User manual

HP
HP R6000 series User manual

HP
HP E3610A Service manual

HP
HP 6236B Service manual

HP
HP 6434B Service manual

HP
HP 59501A Service manual

HP
HP A3550A - High Availability Disk Arrays Model 20 Storage... User manual

HP
HP 6104A Service manual

HP
HP A7502 User manual

HP
HP E3633A User manual
Popular Power Supply manuals by other brands

Antec
Antec TruePower Quattro 850 Manual Del Usuario

Whelen Engineering Company
Whelen Engineering Company ISP4HS installation guide

DUNIWAY Stockroom
DUNIWAY Stockroom Terranova 752A instruction manual

Siemens
Siemens SITOP series operating instructions

Endress+Hauser
Endress+Hauser RN 221N operating instructions

TRI tool
TRI tool 765RVC2 Operation manual