HPE R/T2200 G4 User manual

HPE R/T2200 G4 UPS, R/T3000 G4 UPS,
and ERM User Guide
Part Number: 792519-001R
November 2017
Edition: 1
Abstract
This document is for the person who installs, administers, and troubleshoots power products.
Hewlett Packard Enterprise assumes you are qualified in the servicing of high-voltage equipment
and trained in recognizing hazards in products with hazardous energy levels..

Page 2 792519-001 Edition 2
ENGLISH
Special Symbols
The following are examples of symbols used on the UPS or accessories to alert you to important
information:
RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electric shock symbol.
Important instructions that must always be followed.
Do not discard the UPS or the UPS batteries in the trash.
This product contains sealed lead acid batteries and must be disposed as it's explain in this manual.
For more information, contact your local recycling/reuse or hazardous waste center.
This symbol indicates that you should not discard waste electrical or electronic equipment (WEEE)
in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center.
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS. This manual contains important instructions
that should be followed during installation and maintenance of the UPS and batteries.
The 2U UPS models that are covered in this manual are intended for installation in an environment
within 0 to 40°C/32 to 104°F, free of conductive contaminant.
For HPE R/T3000 HV NA/JP and HPE R/T3000 G4 INTL UPS models:
• FCC/EN55022 Class B IEC62040-2 C1
For HPE R/T2200 G4 NA/JP and HPE R/T3000 G4 LV NA/JP UPS models:
• FCC/EN55022 Class A, IEC62040-2 C2
Certification Standards
• UPS directives: UL 1778 4th edition (UL listed).
• Performance: IEC 62040-3: 2001.
• Radiated emission: FCC CFR 47 part 15 subpart B (Class A or Class B, depending on model).
• Surges withstand ability: IEEE ANSI C62.41 Category A2 (UL Listed).
Regulatory Notices
See HPE EG regulatory notices at http://www.HPE.com/support/Safety-Compliance-EnterpriseProducts.

ENGLISH
Page 3 792519-001 Edition 2
ENGLISH
Personal Safety
• The system has its own power source (the battery). Consequently, the power outlets may be energized,
even if the system is disconnected from the AC power source.
• Dangerous voltage levels are present within the system. It should be opened exclusively by qualified service person-
nel.
• The system must be properly grounded.
• The battery supplied with the system contains small amounts of toxic materials.
• There are no user serviceable parts inside except for the replaceable battery.
• To avoid accidents, the directives listed below must be observed:
- Servicing of batteries should be performed or supervised by personnel knowledgeable about batteries and the
required precautions.
- When replacing batteries, replace with the same type and number of batteries or battery packs.
- Do not dispose of batteries in a fire. The batteries may explode.
- Batteries constitute a danger (electrical shock, burns). The short-circuit current may be very high.
• Precautions must be taken for all handling:
• Wear rubber gloves and boots.
• Do not lay tools or metal parts on top of batteries.
• Disconnect charging source prior to connecting or disconnecting battery terminals.
• Determine if battery is inadvertently grounded. If inadvertently grounded, remove source from ground. Contact with
any part of a grounded battery can result in electrical shock. The likelihood of such shock can be reduced if such
grounds are removed during installation and maintenance (applicable to equipment and remote battery supplies not
having a grounded supply circuit).
Product Safety
• The UPS should only power IT equipment.
• Do not plug laser printers into the UPS output receptacles. The instantaneous current drawn by this type of printer can
overload the UPS.
• The UPS connection instructions and operation described in the manual must be followed in
the indicated order.
• A protection circuit breaker must be installed upstream and be easily accessible.
The system can be disconnected from the AC power source by opening this circuit breaker.
• Check that the indications on the rating plate correspond to your AC powered system and to
the actual electrical consumption of all the equipment to be connected to the system.
• For PLUGGABLE EQUIPMENT, the socket-outlet shall be installed near the equipment and shall
be easily accessible
• Never install the system near liquids or in an excessively damp environment.
• Never let a foreign body penetrate inside the system.
• Never block the ventilation grates of the system.
• Never expose the system to direct sunlight or source of heat.
• If the system must be stored prior to installation, storage must be in a dry place.
• The storage temperature range is -15 to +50ºC/5 to 122°F.
Special Precautions
• All handling operations will require at least two people (unpacking, installation in rack system).
• Before and after the installation, if the UPS remains de-energized for a long period, the UPS must be
energized for a period of 24 hours, at least once every 6 months (for a normal storage temperature
less than 25°C/77°F). This charges the battery, thus avoiding possible irreversible damage.
• During the replacement of the Battery Module, it is imperative to use the same type and number of
element as the original Battery Module provided with the UPS to maintain an identical level of
performance and safety. For questions, contact your HPE representative.
Important: Replace the battery module with the same type battery module, available from HPE.

Page 4 792519-001 Edition 2
ENGLISH
Contents
Table of Contents
Contents.............................................................................................................................4
1. Overview .......................................................................................................................5
1.1 Environmental protection.......................................................................................................................................5
1.2 Weights and dimensions........................................................................................................................................6
1.3 Rear panels ............................................................................................................................................................7
2. User Interface...............................................................................................................8
2.1 Control panel..........................................................................................................................................................8
2.2 LCD window ...........................................................................................................................................................9
2.3 Display functions..................................................................................................................................................10
2.4 User settings ........................................................................................................................................................10
3. Installation ..................................................................................................................12
3.1 Unpacking and contents check ............................................................................................................................12
3.2 Battery module connection ..................................................................................................................................14
3.3 Tower installation.................................................................................................................................................15
3.4 Rack installation...................................................................................................................................................15
3.5 Communication ports ...........................................................................................................................................19
3.6 UPS connection ....................................................................................................................................................20
3.7 Ground connection ...............................................................................................................................................21
3.8 ERM and UPS installation....................................................................................................................................22
4. Operation.....................................................................................................................24
4.1 Start-up and normal operation.............................................................................................................................24
4.2 Starting the UPS on battery .................................................................................................................................24
4.3 UPS shutdown......................................................................................................................................................24
4.4 Operation on battery power.................................................................................................................................24
4.5 Return of AC input power ....................................................................................................................................25
4.6 UPS remote control functions ..............................................................................................................................25
5. Maintenance...............................................................................................................26
5.1 Troubleshooting....................................................................................................................................................26
5.2 Updating the UPS firmware .................................................................................................................................26
5.3 Battery module replacement................................................................................................................................27
5.4 Spares ..................................................................................................................................................................28
6. Technical Specifications..........................................................................................29
6.1 HPE R/T2200 G4 NA/JP UPS and HPE R/T3000 G4 LV NA/JP UPS ....................................................................29
6.2 HPE R/T3000 G4 HV NA/JP UPS and HPE R/T3000 G4 INTL UPS.......................................................................30
7. Support and other resources ...................................................................................31

ENGLISH
Page 5 792519-001 Edition 2
ENGLISH
1. Overview
Save these instructions. This document contains important safety instructions that should be followed during
installation, operation, and maintenance of the UPS and batteries.
1.1 Environmental protection
Products are developed according to an eco-design approach.
Substances
This product does not contain CFCs, HCFCs , or asbestos.
Packing
To improve waste treatment and facilitate recycling, separate the various packing components.
• The cardboard we use comprises over 50% of recycled cardboard.
• Sacks and bags are made of polyethylene.
• Packing materials are recyclable and bear the appropriate identification symbol 01
PET
Materials Abbreviations Number in
the identification symbols
Polyethylene terephthalat PET 01
High-density polyethylene HDPE 02
Polyvinyl chloride PVC 03
Low-density polyethylene LDPE 04
Polypropylene PP 05
Polystyrene PS 06
Follow all local regulations for the disposal of packing materials.
End of life
HPE processes products at the end of their service lives in compliance with local regulations.
HPE works with companies in charge of collecting and eliminating our products at the end of
their service lives.
Product
The product is made up of recyclable materials.
Dismantling and destruction must take place in compliance with all local regulations concerning waste.
At the end of its service life, the product must be transported to a processing center for electrical and
electronic waste.
Battery
The product contains lead-acid batteries that must be processed according to applicable local regulations concerning batte-
ries.
The battery may be removed to comply with regulations and correct disposal.

Page 6 792519-001 Edition 2
ENGLISH
1. Overview
1.2 Weights and dimensions
Tower installation Rack installation
D
W
H
Description Weights
(kg/lb)
Dimensions (mm/inch)
D x W x H
HPE R/T2200 G4 NA/JP UPS 30.5 kg/67.2 lb 523 x 442 x 86 mm/20.6 x 17.4 x 3.4 in
HPE R/T3000 G4 LV NA/JP UPS 39.9 kg/88.0 645 x 442 x 86 mm/25.4 x 17.4 x 3.4 in.
HPE R/T3000 G4 HV NA/JP UPS 38 kg/83.8 lb 645 x 442 x 86 mm/25.4 x 17.4 x 3.4 in.
HPE R/T3000 G4 INTL UPS 38 kg/83.8 lb 645 x 442 x 86 mm/25.4 x 17.4 x 3.4 in.
HPE R/T2200 G4 ERM 32.2 kg/71.0 lb 508 x 442 x 86 mm/20.0 x 17.4 x 3.4 in
HPE R/T3000 G4 ERM 45.2 kg/99.7 lb 648 x 442 x 86 mm/25.5 x 17.4 x 3.4 in
D
H
W

ENGLISH
Page 7 792519-001 Edition 2
ENGLISH
1. Overview
1.3 Rear panels
HPE R/T2200 G4 NA/JP UPS
8a
8b
HPE R/T3000 G4 LV NA/JP UPS
8a
8b
11
HPE R/T3000 G4 HV NA/JP UPS and HPE R/T3000 G4
INTL UPS
8a 8b
HPE R/T2200 G4 ERM and HPE R/T3000 G4 ERM
(optional battery module) 12 Connectors for battery modules
(to the UPS or to the other battery mod-
ules)
13 Connectors for automatic recognition of
battery modules
1USB communication port
2RS-232 communication port
3Connector for automatic recognition of
an additional battery module
4Slot for optional communication card
5Connector for ROO (Remote On/Off) or
RPO (Remote Power Off) control
6Connector for additional battery module
730A outlet (L5-30R) for connection of
equipment (2U R/T3000 G4 LV NA/JP UPS only)
8a Group 1: Two programmable outlets for
connection of equipment
8b Group 2: Two programmable outlets for
connection of equipment
9Primary Group: outlets for
connection of critical equipment
10 Attached 8-ft. input power cord for AC
power source
5-20P for 2200
L5-30P for 3000
11 LED indicating SWF (site wiring fault)
alarm (Although the LED remains on the
rear panel, this feature is disabled for
low voltage models.)
12 Ground connection
1USB communication port
2RS-232 communication port
3Connector for automatic recognition of an
additional battery module
4Slot for optional communication card
5Connector for ROO (Remote On/Off) or RPO
(Remote Power Off) control
6Connector for additional battery module
716A outlet for connection of equipment (pri-
mary group)
8a Group 1: Two programmable outlets for
connection of equipment
8b Group 2: Two programmable outlets for
connection of equipment
9Primary Group: 4 outlets for
connection of critical equipment
10 Outlet for connection to AC power source
11 Ground connection

Page 8 792519-001 Edition 2
ENGLISH
2. User Interface
2.1 Control panel
The UPS has a five-button graphical control panel.
Power On
Indicator (green)
On battery
Indicator (yellow)
Alarm
Indicator (red)
Normal mode
100%
17min
1ERM
100%
2.7kW
3kVA
Eciency: ~98%
Escape Up Down Enter On/Off
button
The following table shows the indicator status and description:
Indicator Status Description
Green On The UPS is operating normally.
Yellow On The UPS is on Battery mode.
Red
On The UPS has an active alarm or fault. See "5.1
Troubleshooting" on page 26 for additional information.

ENGLISH
Page 9 792519-001 Edition 2
ENGLISH
2. User Interface
2.2 LCD window
The LCD window provides useful information about the UPS, load status, events, measurements, and settings.
As the default, or after five minutes of inactivity, the LCD displays the screen saver.
The backlight LCD automatically dims after 10 minutes of inactivity. Press any button to restore the screen.
Operation Status
Load/equipment Status
Normal mode
100%
17min
1ERM
100%
2.7kW
3kVA
Eciency: ~98%
Battery Status
Efficiency and Load Group Information
The following table illustrates the Operation Status icons that you could see and describes the condition associated with each
icon.
Note: If other indicators appear, see "5.1 Troubleshooting" on page 26 for additional information.
Operation status Possible cause Action
Standby mode The UPS is off, waiting for start-up com-
mand from user.
Equipment is not powered until the but-
ton is pressed.
Normal mode The UPS is operating normally. The UPS is powering and protecting the
equipment.
In Automatic Voltage Regulation
mode
No audio alarm.
The UPS is operating normally, but the
utility voltage is outside normal mode
thresholds.
The UPS is powering the
equipment through an AVR device.
The equipment is still normally
protected.
On Battery
Battery LED is on.
The audio alarm beeps every 10
seconds
A utility failure has occured and
the UPS is in Battery mode.
The UPS is powering the equipment with
the battery power.
Prepare your equipment for
shutdown.
End of backup time
Battery LED is flashing.
The audio alarm beeps every three
seconds
The UPS is in Battery mode and
the battery is running low.
This warning is approximate and the actual
time to shutdown may vary significantly.
Depending on the UPS Load
and number of ERMs, the Battery Low
warning may occur before the
battery reaches 20% capacity.

Page 10 792519-001 Edition 2
ENGLISH
2.3 Display functions
Press the button to activate the menu options. Use the and buttons to scroll through the menu structure. Press the
button to select an option. Press the button to cancel or return to the previous menu.
Menu map for Display Functions.
Main menu Submenu Display information or Menu function
Measurements — Load W VA / Load A pf / Output V Hz / Input V Hz /
Battery V min / Efficiency / Power usage
Control Load Segments Group 1: ON / OFF
Group 2: ON / OFF
These commands overrule user settings for load segments.
Start battery test Starts a manual battery test
Reset fault state Clears active fault (UPS restart required)
Restore factory settings Returns all settings to original values
Reset power usage Clears power usage measurements
Settings Local settings Sets general parameters
Input / output settings Sets Input and output parameters
ON / OFF settings Sets on and off conditions
Battery settings Sets battery configuration
Fault log — Displays event log or alarms
Identification — UPS Type/Part Number/Serial Number/Firmware release/Com card
address
2.4 User settings
The following table displays the options that can be changed by the user.
Description Available settings Default settings
Local settings
Language [English] [French] [German] [Spanish]
[Italian] [Portuguese] [Russian]
Menus, status, notices and alarms, UPS
fault, event log data and settings are in all
supported languages.
English
User selectable when the UPS
is powered the first time.
LCD settings Allows LCD screen brightness and contrast
to be adapted to room light conditions.
—
Audible alarm [Enabled] [Disabled on battery] [Always
disabled]
Allows you to enable or disable the audio
alarm if an alarm occurs.
Yes
In/Out settings
Output voltage* Low voltage: [100V] [120V] [125V]
High voltage: [200V] [208V] [220V]
[230V] [240V]
User selectable when UPS is
powered for the first time.
*Important: The output voltage of the UPS must be set to the same nominal voltage as the facil-
ity input voltage for optimum UPS performance.
Input thresholds [Normal mode] [Extended mode]
Extended mode reduces lower input voltage
to 70V before UPS transfers to battery.
This can be used if the load can
withstand low voltage supply.
Normal mode
Sensitivity [High] [Low]
High: For sensitive equipment, the
UPS will easily transfer to battery when util-
ity conditions deteriorate.
Low: For less sensitive equipment, the UPS
will not transfer to battery when utility con-
ditions deteriorate.
High
Load segments - Auto
start delay
[No Delay] [1 s] [2 s]…[65354 s]
The connected equipment is powered after
the specified delay.
Group 1: 3 s
Group 2: 6 s
Continued
Continued
2. User Interface

ENGLISH
Page 11 792519-001 Edition 2
ENGLISH
2. User Interface
Description Available settings Default settings
In/Out settings
Load segments - Auto
shutdown delay
[Disable] [0s] [1 s] [2 s]…[65354 s]
During a power outage, this setting enables
the UPS to turn off power to equipment con-
nected to Group 1 and/or Group 2 outlets, or
disables the action.
This feature sheds non-critical loads in
order to conserve battery power for critical
loads connected to the primary group.
Group 1: Disable
Group 2: Disable
Overload
prealarm
[5%] [10%] [15%] [20%] ... [100%] [105%]
Sets alarm for critical percentage of load
where alarm overload occurs.
[105 %]
ON/OFF settings
Cold start [Disable] [Enable]
Enables or disables the product to start on
battery. The first cold start is always dis-
abled.
Enable
Forced reboot [Disable] [Enable]
If enabled and power returns during a shut-
down sequence, the shutdown sequence
will complete and there is a 10 second delay
prior to restart.
If disabled, shutdown sequence does not
complete and restart occurs immediately.
Enable
Auto restart [Disable] [Enable]
Enables or disables the UPS to restart
automatically when power returns after a
complete battery discharge.
Enable
Energy saving [Disable] [Enable]
If enabled, the UPS will shutdown after five
minutes if no load is detected on the output.
Disable
Sleep mode [Disable] [Enable]
If enabled, LCD and communication stays on
1h and 30 min after UPS turns off.
If disabled, LCD and communication will turn
off immediately after the UPS turns off.
Disable
Remote command [Disable] [Enable]
If enabled, shutdown or restart commands
from software are allowed.If disabled, shut-
down or restart commands from software
are not allowed.
Enable
Battery settings
Automatic battery test [No test] [Every day] [Every week] [Every
month]
Available only if Battery Charge mode is set
to constant charge.
Every week
(in constant charge)
otherwise following
ABM
Low battery
warning
[10%] [20%] [30%] [40%] [50%] [60%] [70%]
[80%] [90%]
The alarm occurs when the value set
for the low battery capacity warning is
reached.
20%
Restart battery level [10%] [20%] [30%] [40%] [50%] [60%] [70%]
[80%] [90%] [100%]
If set, automatic restart occurs only when
the percentage of battery charge you speci-
fy is reached.
0%
Battery charge mode [ABM cycling] [Constant charge] ABM cycling
ERM number
setting
[0] [1] [2] [3] [4]
Using standard ERM, the UPS automatically
detects the number of connected ERMs.
ERM automatic detection,
otherwise 0
Deep discharge protec-
tion
[Yes] [No]
If set to Yes, the UPS automatically prevents
the battery from deep discharge by adapting
the end of back-up time voltage threshold.
Yes

Page 12 792519-001 Edition 2
ENGLISH
Packing materials must be disposed of in compliance with all local regulations concerning waste.
Recycling symbols are printed on the packing materials to facilitate sorting.
3. Installation
3.1 Unpacking and contents check
HPE R/T2200 G4 NA/JP UPS and HPE R/T3000 G4 LV NA/JPN UPS
14
15
21
20
18
16 17
(14) HPE R/T2200 G4 NA/JP and HPE R/T3000 G4 LV NA/JPN
(15) Bezel parts
(16) RS-232 communication cable
(17) USB communication cable
(18) Documentation
(20) Mounting brackets, rails, and hardware
(21) Tower stands

ENGLISH
Page 13 792519-001 Edition 2
ENGLISH
HPE R/T3000 G4 HV NA/JPN UPS and HPE R/T3000 G4 INTL UPS
3. Installation
35
39
38
36
32
31
33
34
30
(30) HPE R/T3000 G4 HV NA/JPN and HPE R/T3000 G4 INTL
(31) Connection cable to AC power source
(L6-20P for NA/JP model. Country-specific cord for INTL
model)
(32) Two connection cables for the protected
equipment
(33) RS-232 communication cable
(34) USB communication cable
(35) Two cable locking systems
(36) Documentation
(38) Mounting brackets, rails, and hardware
(39) Tower stands
Packing materials must be disposed of in compliance with all local regulations concerning waste.
Recycling symbols are printed on the packing materials to facilitate sorting.

Page 14 792519-001 Edition 2
ENGLISH
3. Installation
3.2 Battery module connection
This operation must be performed when the UPS is switched off and unplugged from the AC source. In addition, do not dis-
connect the connector while the unit is operating from the AC source or in reserve mode.
Note: Before starting the UPS, connect the internal battery. A small amount of arcing may occur when connecting the batte-
ries.This is normal and does not damage the UPS or present any safety concern.
A
C
B
Installing the new battery module
Perform the removal instructions in reverse order.
●To ensure safety and high performance, only use batteries supplied by HPE.
●Take care to firmly press together the two parts of the connector during remounting.
AConnect the battery module.
Never pull on the wires.
BSlide the left-hand side of the bezel to the
right. Ensure that the push button locks.
CAttach the center panel.

ENGLISH
Page 15 792519-001 Edition 2
ENGLISH
3. Installation
3.3 Tower installation
M3 screws
M3 screw
s
3.4 Rack installation
Warning: To reduce the risk of personal injury or damage to the equipment, be sure that:
• The leveling feet are extended to the floor.
• The full weight of the rack rests on the leveling feet.
• The stabilizing feet are attached to the rack if it is a single-rack installation.
• The racks are coupled together in multiple-rack installations.
• Only one component is extended at a time. A rack may become unstable if more than one
component is extended for any reason.
Note: If preparing the rails for integrated shipping, follow the same rack installation instructions.
Note: Mounting hardware for square- and round-holed racks is included in the UPS kit.

Page 16 792519-001 Edition 2
ENGLISH
Installing the mounting rails
Front of rack
2
1
Rear of rack
M6 screws
A Prepare the rail.
1. Loosen the wing nuts or hex
nuts.
2. Extend the brackets to the
appropriate length.
BInsert screws through the rail and
each mounting bracket.
M6 screws
CInstall cage nuts or clip nuts behind
the mouting holes where you will
attach the mounting brackets.
DInsert screws through the mounting
brackets into the cage nuts or clip
nuts.
A
B
C
D
3. Installation

ENGLISH
Page 17 792519-001 Edition 2
ENGLISH
Rear of rack (cont.)
Installing the UPS in the rack
Before installing the UPS, review and adhere to all safety information (see page 2 and page 3). The mounting rails must
be installed before installing the UPS.
Warning: A risk of personal injury or damage to the equipment exists. Uneven loading of
equipment in the rack might cause the rack to become unstable. Install the heavier components
rst, and then continue to populate the rack from the bottom to the top.
M3 screws
M3 screws
M6 screws
M6 screws
ETighten the wing nuts or hex nuts.
AInstall the mounting ears on the
chassis using the provided screws.
BInstall the UPS chassis in the rack.
1. With one person on each side,
lift the chassis to rail level and
slide the chassis on the mount-
ing rails.
2. Attach the chassis to the rack
using the provided screws.
E
3. Installation
B
A

Page 18 792519-001 Edition 2
ENGLISH
Shipping the UPS in the rack
Before shipping the UPS in the rack, you will need to add a rear rail stabilizing bracket and install a protective cover over the
bezel.
Warning: To reduce the risk of personal injury or damage to the equipment, shipping kit part
number L4Q11A is required prior to moving or shipping a rack with an installed UPS.
Install the rear stabilizing rail
Reinstall the UPS
M6 screws
M6 screws
Attach the protective cover
M6 screws
3. Installation
AInstall the rear stabilizing rail.
1. Using two wing nuts, secure the
rear rail stabilizing bracket to
screws in the rail (see diagram
for position). Repeat on the other
rail.
2. Wait until the unit is installed
and the brackets are adjusted
before tightening the nuts. (See
the diagram at the left for inner
and outer rail installation views.)
BReinstall the UPS chassis in the
rack.
1. With one person on each side,
lift the chassis to rail level and
slide the chassis on the mount-
ing rails.
2. Attach the chassis to the rack
using the provided screws.
CAfter the UPS chassis is
installed in the rack, attach the
protective cover over the bezel
using the provided screws.
B
C
A
B
C

ENGLISH
Page 19 792519-001 Edition 2
ENGLISH
3. Installation
3.5 Communication ports
Connection of RS-232 or USB communication port (optional)
The RS-232 and USB communication ports cannot operate simultaneously.
16
17 34
33
or
or
1. Connect the RS-232( 16 or 33 ) or
USB ( 17 or 34 ) communication
cable to the serial or USB port on
the computer equipment.
2. Connect the other end of the com-
munication cable to the USB 1or
RS-232 2communication port on
the UPS.
The UPS can now communicate with
HPE power management software.
Installation of optional NMC Network Card
It is not necessary to shut down the UPS before installing a communication card.
1. Remove the mounting screws and
remove the slot cover 4.
2. Insert the communication
card in the slot.
3. Secure the card cover with
the screws removed in Step 1.
When a signal is activated, the contact is closed between the common (pin 2) and the pin for the corresponding signal.
Contact characteristics (optocoupler)
• Voltage: 48 Vdc max
• Current: 25 mA max
• Power: 1.2W
Characteristics of the optocoupler RS-232 communications port
• Pins 1, 3, 4, 5, 6, 10: not used
• Pin 2: common (user)
• Pin 7: low battery
• Pin 8: operation on battery power
• Pin 9: UPS on, equipment supplied
no: normally open contact

Page 20 792519-001 Edition 2
ENGLISH
HPE R/T3000 G4 LV NA/JP
Check that the indications on the name plate located on the back of the UPS correspond to the AC-power source and
the true electrical consumption of the total load.
8a
8b
11
3. Installation
3.6 UPS connection
HPE R/T2200 G4 NA/JP UPS
Check that the specifications on the rear UPS name plate correspond to the AC power source and the true electrical
consumption of the total load.
10
98
1. Connect the UPS input plug 10 to the AC
power source.
2. Connect the protected equipment to the
UPS.
It is preferable to connect the
critical loads to the ‘Primary’
outlet group 9and the non-critical loads
to either the Group 1 or Group 2 outlets
8. Group 1 and Group 2 outlets can be
programmed to shed loads as desired.
3. To optimize the available backup time,
user the IN/OUT serttings to program
shutdown of outlets 8during operation
on battery power (see "2.4 User settings"
on page 10).
The UPS charges the battery as soon as it is connected to the AC power source, even if the button is not
pressed.
After the UPS is connected to the AC power source, eight hours of charging is required before the battery can
supply the rated backup time.
1. Connect the UPS input plug 10 to the
AC-power source.
2. Connect the loads to the UPS. It is prefer-
able to connect the critical loads to the
‘Primary’ outlet group shown as 9and
the non-critical loads to either the Group
1 or Group 2 outlets shown as 8a and
8b. Group 1 and Group 2 outlets can be
programmed to shed loads as desired.
Connect any high-power device to the 30
A outlet 7.
3. To optimize the available backup time,
use the in/out settings to program shut-
down of outlets 8during operation on
battery power.
The UPS charges the battery as soon as it is connected to the AC power source, even if the button is not
pressed.
After the UPS is connected to the AC power source, eight hours of charging is required before the battery can
supply the rated backup time.
This manual suits for next models
1
Table of contents
Other HPE UPS manuals

HPE
HPE R/T2200 G5 Assembly instructions

HPE
HPE R1500 G5 Assembly instructions

HPE
HPE G2 R5000 User manual

HPE
HPE R/T3000 G5 Assembly instructions

HPE
HPE R/T3000 G2 User manual

HPE
HPE R1500 User manual

HPE
HPE R/T3000 G5 Assembly instructions

HPE
HPE G2 R5000 3U User manual

HPE
HPE T750 G5 NA/JP Tower User manual