power is supplied to the emergency driver.
2.This product is for use with an LED lighting load and supplies 12 W constant power with output
voltage between 0 VDC and 0 VDC in emergency mode for a minimum of 90 minutes. 1 6
3.Make sure all connections are in accordance with the National Electrical Code or Canadian Electrical Code
and any local regulations.
converter connector of the emergency driver before servicing.
5.This emergency driver is for factory installation and .field Installation
6.This product is suitable for use in damp locations where the ambient temperature is 5ºC minimum, +50ºC
maximum. Product is not suitable for heated air outlets and wet or hazardous locations.
9.Use with grounded, UL Listed, damp location rated fixtures and
10.The Driver is intended for ordinary locations and for permanent
replaceable. Contact the manufacturer for information on service.
12.The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition
16.Equipment should be mounted in locations and at heights where it will not be subjected to
tampering by unauthorized personnel.
Contains LiFePO4
Rechargeable Battery.
Must be recycled or
disposed properly.
STEP 1 INSTALLING THE EMERGENCY DRIVER
> Disconnect AC power from the LED luminaire.
> Mount the emergency LED driver by the mounting tabs using the supplied screws. The luminaire’s
installaion instructions may provide guidance on the recommended mounting location.
>
This product has been designed to reliably interface with a wide selection of LED loads.. However,
compatibility
cannot be guaranteed with all current
Installation of this emergency LED driver will vary based on the luminaire type, however, generally
follow these steps:
NOTE: After installation, it will be necessary to measure the egress lighting illumination levels to ensure it
complies with national, state, and local code requirements.
Make sure the necessary branch circuit wiring is available. An unswitched
source of power is required. The emergency driver must be fed from the same
Installation
If used in conjunction with an AC driver, this distance is up to half the distance the AC driver manufacturer
recommends remote mounting the AC driver from the LED Load. If used without an AC driver, consult
installation into one or more Listed emergency luminaires.
11
1.To prevent high voltage from being present on yellow & orange output leads prior to installation,
converter connector must be open. Do not join converter connector until installation is complete and AC
13.Do not use this product for other than intended use.
8.Do not install near gas or electric heaters,Do not use outdoors.
14.Servicing should be performed by qualified service personnel.
15. branch circuit as
NOTE:
factory for remote mounting distances .
and future LED systems. Compatibility testing
of. the end-use system is suggested. Please contact the factory with any questions.
1. Ensure the LED load’s rated power is greater than or equal to the power output of this emergency LED
driver. This is to ensure that this emergency product will not produce more power than the LED load can
handle, thus ensuring that the LED load will not be damaged when the system is in the emergency mode.
2. Verify that the forward voltage of the luminaire’s LED array is within the limits of this emergency LED
voltage of the LED array is commonly designated as Vf and should be found on the
forward voltage is within the limits of this product. Using
voltage across the LED arrays when operating
driver. The forward
luminaire markings, in the luminaire
a voltage meter, it may be possible to directly measure the
from the AC driver.
3. Ensure the output current of the LED driver does not exceed 3Amps.This is the current into the blue
doing the following:
be biven in lumens per watt (lm/w).
load. In many cases the actual lumen output in emergency mode will be greater than this
b.
calculation gives, however it will provide a good estimate for beginning the lighting design of the system.
C. Using the results of this calculation and industry standard lighting design tools, calculate the
a nticipated illumination levels in the path of egress.
Lumens In Emergency Mode = Lumens per Watt of Fixture * Output Power Emergency LED driver
________________
(Lumens) = (lm/W) * (W)
________________
case should be grounding.
(See electrical data table)
wire.
PLD12MI
EMERGENCY LED DRIVER
Only apply to LED Driver with the output current less than 3.0A. (See electrical data table)
PLD12Ml
This product is suitable for field installation with suitable LED loads including LED luminaires, DC voltage
driven LED replacements for fluorescent lamps and others. There are 4 checks to determine if your luminaire
is eligible for field installation.
Installation Instructions
LED Luminaire Evaluation
The emergency driver with cable conduit is suitable for remote mounting from the luminaire; the emergency driver
without cable conduit is not suitable for remote mounting.
12
(See electrical data table)
STEP 3 WIRING THE EMERGENCY BALLAST
> According wiring diagram to connect the emergency driver to the AC driver and LED load.
Make sure all connections are in accordance with the National Electrical Code and any local regulations.
> After installation is complete, supply AC power to the emergency driver and join the converter connector.
> At this point, power should be connected to both the AC driver and the emergency driver,and the Charging
Indicator Light should illuminate indicating the battery is charging.
Install and wire the test switch per wiring diagrams provided on these instructions.
indicating that the emergency inverter battery is charging.
STEP 2 INSTALLING TEST SWITCH
Mount the supplied illuminated test switch in a location that is visible and
accessible by maintenance personnel. The test switch mounts through a
0.49” hole which may need to be made in the luminaire or could come
pre-punched by the luminaire supplier.
Hex Nut
Illuminated
Test Switch
Fixture Plate
Drill or Punch
a 0.49” Hole
A. Test switch install on switch box, switch box install on wall or ceiling surface.
TO TEST
CHARGE
> A short-term discharge test may be conducted after the emergency driver has been charged for one hour. Charge
for 24 hours before conducting a long-term discharge test. Refer to OPERATION.
> In a readily visible location, attach the label "CAUTION - This Unit Has More Than One Power Connection Point.
To Reduce The Risk Of Electric Shock, Disconnect Both The Branch Circuit-Breakers Or Fuses And Emergency
Power Supplies Before Servicing."
Manual Operation
WHT/BLK
WHT/BLK
GREEN
BROWN
YELLOW
ORANGE
BLUE
TEST SWITCH
LED INDICATOR
BLACK
LED LOAD(+)
LED LOAD(-)
AC LED DRIVER
BLACK
WHITE
NEUTRAL
LIVE
CONVERTER
CONNECTOR
WHT/BLUE
WHT/RED
SWITCH
(OPTIONAL)
RED
Self-Test Option
1. When AC power is supplied to fixture, the unit will automatically initiate a self-test and self-diagnostic
test as follows:
(1) Verifies battery disconnection, charger board failure at every 5 seconds.
(2) 1 minute self-testing every month.
(3) 30 minutes self-testing on every 6 months after installation.
(4) 90 minutes self-testing on every 12 months after installation.
2. Dual color LED lamp indicator shows the following status:
(1) Green color On / Ready
blinking: Testing
(2) Red color (Service Alert)
(3) Service Alert LED Code (Red color LED lamp indicator)
One blink, 4 second pause Battery is not connected
Two blinks, 4 second pause Battery voltage too low
Three blinks, 4 second pause Charger board circuit faiure
Four blinks, 4 second pause Transfer function failure
Five blinks, 4 second pause LED load not connected or failure
NOTICE
After solving the fault of emergency equipment, please press test button for 2 seconds without
releasing to reset. LED indicator will show green.
3. Self-testing / self-diagnostic also have manual test function, press test button as follows:
Press test button once 30 seconds discharge test
Press test button twice within 2 seconds 3 minutes discharge test
Press test button 3 times within 2 seconds 30 minutes discharge test
Press test button 4 times within 2 seconds 90 minutes discharge test
NL
DC+ DC-
ST MT
Maintenance
> Mounting Height: This product meets or exceeds the NFPA minimum light requirements with all loads,
end use verification is necessary. For field installations, when the attached luminaire is mounted at
down to the smallest rated lamp load, at heights up to 7.17ft (2.2m). Many factors influence emergency
illumination levels, such as the lamp load selected, luminare design, and environmental factors therefore
heights greater than 7.17ft (2.2m), the level of illumination must be measured in the end application to
ensure the requirements of NFPA 101 and local codes are satisfied.
PUSH
NOTE: Switch box no provide.
ST: Self-test and Self-diagnostics
Manual testMT:
NOTE: Associated Target Luminaire : Jewoo CULPL66X-BC,Max. mounting height 27ft.
Others luminaire suitable for used shall be selected according to the instruction suggestion.
(See electrical data table)
This emergency driver will operate an LED lighting load; it supplies 12W
constant power with output voltage between 10VDC and 60VDC in emergency mode for minimum 90 minutes.

Popular Batteries Pack manuals by other brands

Phonic BP-RG user manual

Phonic

Phonic BP-RG user manual

Ryobi P192 Operator's manual

Ryobi

Ryobi P192 Operator's manual

xtorm FS5100 manual

xtorm

xtorm FS5100 manual

NocoXgrid XGB3 user guide

NocoXgrid

NocoXgrid XGB3 user guide

ROAMER 230SMART3 Safety information

ROAMER

ROAMER 230SMART3 Safety information

Generac Power Systems PWRcell M3 Installation and owner's manual

Generac Power Systems

Generac Power Systems PWRcell M3 Installation and owner's manual

Lipper Curt installation manual

Lipper

Lipper Curt installation manual

Unitree Go2 user manual

Unitree

Unitree Go2 user manual

COMSOL PBW103 user manual

COMSOL

COMSOL PBW103 user manual

Trophy 51.2V300E-3UL manual

Trophy

Trophy 51.2V300E-3UL manual

Mophie powerstation pro AC user manual

Mophie

Mophie powerstation pro AC user manual

Goodwe Pytes E-BOX Series Installation and configuration manual

Goodwe

Goodwe Pytes E-BOX Series Installation and configuration manual

Rohde & Schwarz TSMA6-BP Getting started

Rohde & Schwarz

Rohde & Schwarz TSMA6-BP Getting started

Sennheiser ENERGIEPACKS SK 3063 user manual

Sennheiser

Sennheiser ENERGIEPACKS SK 3063 user manual

iOptron PowerWeight instruction manual

iOptron

iOptron PowerWeight instruction manual

BIX Power BP150 user manual

BIX Power

BIX Power BP150 user manual

Panasonic FZ-VZSU84AU operating instructions

Panasonic

Panasonic FZ-VZSU84AU operating instructions

Linak JUMBO BAJ user manual

Linak

Linak JUMBO BAJ user manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.