HYSEN HY01RF User manual

www.cn-hysen.com
Digital Touch Screen Room Thermostat
HY01RF Manual
Preface
HY01RF/MRF (with-wire /radio frequency / multi-channel RF) series are room thermostats with 7 days
programmable function. This system can completely control the boiler or heating system according to the
program preset when out of the factory or set by the customers themselves. The controller with electricity
supplied by the batteries can be put any where in the ordinary room, which makes the work and life of the
installers and the customers become more simple and comfortable. For HY01RF model, the receiver of this
device is connected directly with the hang boiler or the other heating systems. The transmitter adopts special
radio signal and receiver communication with characteristics of strong wall penetration, stable communication,
no interference and low electric consumption. The HY01MRF model can control independently different
temperature in the maximum4 rooms by the multi-channel RF. The damager of radialization to the body is
lower than using the radiogram or TVset.

www.cn-hysen.com
This product has the following characteristics
1) Heating control
2)programming function of 5 +2 weeks (advanced settings, you can select 6 +1 and 7-day programming function also can canc
el the programming function ),It has 6 setting times for a day
3) 2 sets of permanent programs (factory setting program and self-setting program)
4) Large LCD display
5) The deadzone temperature difference adjustable between off and on;
6) Allowable to calibrate the temperature display;
7) antifreeze temperature;
8) Suitable for the control and energy saving of wall mounted boilers, condensation boilers and individual household mearsuring
heating system;
9) It can realize the function of one receiver controlling many sub-devices and many rooms at the same time;
10) Display adjustable between ℉and℃
11)Only need 2 size AA 1.5V batteries for the power supply;.
12)Three transmission modes for selection, i.e. wired, wireless or multi-channel transmission.
13)Fast and Simple installation.
Fig.1
Display screen symbols (Fig1)
NO: symbols represent
1
programme mode,in this case, the thermostat automatic operates according to the set time interval and
temperature value. Programme mode:one week can be divided into two kinds of periods, they are
“Monday to Friday”and“Saturday to Sunday ”,It’s a 5+2 programme mode.Every period can be
divided into 6 time interval:
2manual mode,control the heating equipment according to the current manual setting temperature 。
3Heating on

4Present time
5
represent keys are locked , press “ ”and“ ”at the same time for over 3 seconds to lock the
operation panel. At the keys locked state, press “ ”and“ ”at the same time for over 5 seconds to
unlock the operation panel
6Present ambient temperature
7Indoor temperature
8Floor temperature
9Temperature setting mode
10 7 days display in a week,,and only the present day is displayed.
11 Celsius degree or Fahrenheit degree
12 Battery conditions
13 1 st ~6th time interval
14
Temporary manual mode, at programme mode,press “ ”
or
“ ”
to adjust the value, it will automatic
enter into temporary manual mode, the temporary setting value will not be stored into the programme
mode. For example, if the thermostat is working at programme mode,and its comfortable temperature is
20℃during 17:00 and 22:00, then the user decrease the temperature to 18℃at 19:00, so the
thermostat’s setting temperature will become 18℃, but it will recover the programme mode after
22:00 ,and the value will be 20℃too during 17:00~22:00
Operation Key
NO: symbols represent
A
set key:short press it to switch programme mode to manual mode. At programme mode, press “ ”or” ” to
adjust the value, it will automatic enter into temporary manual mode
BIncreasing key
Cclock key:short pressing is setting clock,long pressing is setting programme
Keys locked/unlocked:press “ ”and“ ”at the same time for 3 seconds
DDecreasing key
EPower on/off key
Product Specifications
Power: twoAA* 1.5V alkaline batteries
Display accuracy::0.5℃or1℉
Probe sensor::NTC(10k)1%
Contact capacity::5A/250V ;16A/250V;
Working environment temperature::0~50°C/32~122°F
Range of temperature adjustment::5~35°C/41~95°F
Range of temperature display::0~40°C/32~104°F
Output: Switch relay
Insulating condition: Normal environment
Running program: Set per 1 week as a cycle
Frequency:433MHZ(RF/MRF)
Wireless transmission distance::Indoor 16/50M,outdoor
200M
Installation: Wall mounted or on battery seat
Size(mm):130*90*27

Scope of Control Applications
1. Control of wall-mounted boiler
2. Control of Thermal Actuator or electromagnetic valve
3. Control of water pump;
4. Ventilation contro
Run Mode
Factory Preset Mode
Mode explain printscreen
programming
mode
Press“ ”to switch into programme mode(As
shown in picture one)
Programme illustration
5+2 programme function(advanced options contain
of 6+1 and7 days programme function,you can also
cancel this programme function ),that is Monday to
Friday is the same setting value, and Saturday to
Sunday is the same setting value。Every day can be
divided into 6 time interval
Setting the programme value:long press“ ” to
enter into programme setting mode, then short press
“ ”to switch,press“ ”or“ ”to adjust value。
Manual Mode
Press “ ”to enter into manual mode(As shown
in picture two),press“ ”or“ ”to adjust value。
Interval Monday to
Friday
the default
value
Saturday and
Sunday
the default
value
1st 06:00-08:00 20°C 06:00-08:00 20°C
2nd 08:00-11:30 10°C 08:00-11:30 20°C
3rd 11:30-13:30 18°C11:30-13:30 20°C
4th 13:30-17:00 10°C13:30-17:00 20°C
5th 17:00-22:00 20°C 17:00-22:00 20°C
6th 22:00-06:00 18°C 22:00-06:00 18°C

Temporary
manual mode
at programme mode,press “ ”or“ ” to adjust
the value, it will automatic enter into temporary
manual mode
advanced options
advanced options can be classified to two sets
1) MODE 1:
Hold down and at the same time for 3 seconds,it will display A1-A9,then press
to switch between these options
Displaying
symbol
Option
content Press“ ”or“ ”to adjust value
temperature
compensatio
n(A1)
increment:0.5°C.
Start
differential
temperature
(A2)
Range:1°C~5°C:
1、When the setting temperature is higher than or equal to the sum of indoor
temperature and the start differential temperature, the heating equipment will turn on.
2、When the indoor temperature is higher than or equal to the sum of the setting
temperature and the start differential temperature, the heating equipment will turn off.
Keypad (A3)
0 half locked:all keys are locked except for the on-off key;
1 full locked。all keys are locked including the on-off key。
Sensor
choice(A4)
N1:single build-in sensor;
N2:single build-out sensor;
N3:build-in and build-out sensor。
high
temperature
protection
(A5)
Range:35~70 When the lowest setting temperature is 35°C,press “ ”,it will display
“ ”, high temperature protection function is canceled; if the indoor temperature is
higher than the high temperature protection value,the heating equipment will be cut off.
Default value is =45°C
low
temperature
protection
(A6)
Range:5°C~10°C ;When the highest setting temperature is 10°C,press “ ”,it will
display “ ”, low temperature protection function is canceled; if the indoor
temperature is lower than the low temperature protection value,the heating equipment
will be cut off. Default value is =5°C
setting
temperature
lowest
limiting value
(A7)
Range:1°C~10°C:

setting
temperature
highest
limiting value
(A8)
Range:30°C~70°C
Week
programme
choice(A9)
: represent 7days programme
:represent6+1 programme
:represent5+2 programme
“ ”represent programme is canceled
2) MODE 2:
At power off state, hold down “ ”and “ ” and “ ”at the same time for 3
seconds it will display B1-B3,then press “ ” to switch between these options
Displaying
symbol
Option content
Press“ ”or“ ”to adjust value
Valve control option
(B1)
0 represent valve is controlled by the thermostat ;
1 represent valve is not controlled by the thermostat, it’s always closed。
Antifreezing Descaling
function)function
option(B2)
0 close,1 open。
Antifreezing function:when valve is continuously closed over100 hours,it will
be opened for3 minutes。
GA/GB option(B3)
0=GA:valve switch protection time is about 3 seconds;
1=GB:valve switch protection time is about 15 seconds1;GB no antifreezing
function
°C Or °F(B4)Celsius degree or Fahrenheit degree
Cautions on Installation and Use:
1. To prevent the thermostat display from a high fluctuation, special treatment has been made to the program.
Therefore, it is normal that the thermostat cannot immediately display the sudden change of temperature.
2. The thermostat installed on 1.5m above the ground.
3. For the thermostat installed,please take care not to install it to the wall corner, door / window side or behind the
door or in such unheated area as exterior wall. Avoid hot / cold air duct, radiator, flue or thermal pipe
4. If the wireless thermostat with battery seat is placed at a position where the air ventilation is poor, the
temperature displayed on the thermostat might be inconsistent to the indoor average temperature.
5. Only the professional technicians are permitted to open the transmitting and receiving box of the thermostat
for installation. When installing the power supply, make sure that the power cable is well insulated.
6. To install the receiving box, please install the base plate firstly and then connect the power and signal wire
correctly before installing the upper cover and fix it. The thermostat is unrepairable product. The user shall
not open the internal circuit board.
7. Before installing the thermostat, make sure that the system is disconnected. The maximum voltage of the
system shall meet the requirements specified in the Instruction Manual (Max. AC Voltage: 250V).

Wring Illustration
1、Wiring Terminals
Wiring Terminal Remarks
NAC Neutral
LAC Live
1NO (Normally-Open point)
2COM (Public terminal of relay)
3NC (Normally-Closed point)
2、Symbol Illustration
B:Wall Mounted Gas Boiler
U:Water Pump, Thermal Actuator or electromagnetic valve 3 control picture:
Fig.2: Dimensional Diagram – Length, Width, Thickness, Installing Size
Fig.3: Control of Water Pump, Thermal Actuator or electromagnetic valve for RF model
Fig.4: Control of Wall-mounted Boiler for HY01RFB mode
Fig.5: Control of Under Floor Heating with Wireless 4-channel for MRF mod
This manual suits for next models
1
Table of contents
Other HYSEN Thermostat manuals

HYSEN
HYSEN HY01RF User manual

HYSEN
HYSEN HY08AC User manual

HYSEN
HYSEN HY01WW User manual

HYSEN
HYSEN HY312WE User manual

HYSEN
HYSEN HY02B05RF User manual

HYSEN
HYSEN HY03WE-4 User manual

HYSEN
HYSEN HY06RF-BW User manual

HYSEN
HYSEN HY08AC User manual

HYSEN
HYSEN HY02TPR User manual

HYSEN
HYSEN HY02TP WIFI User manual
Popular Thermostat manuals by other brands

DELTA DORE
DELTA DORE TYBOX 51 manual

Mitsubishi
Mitsubishi RMF-CA200-V1 Installation instructions manual

Siemens
Siemens RDE410/EH operating instructions

Leviton
Leviton Omnistat 3 RC500-2EW installation instructions

Trane
Trane X13511537-01 Setup instructions

OJ Electronics
OJ Electronics NGT-2.0-WiFi installation instructions