4.4 SYSTEM SETTINGS.
Access to the system settings: ( ) + Settings.
• Date and time.
Set the day and then conrm. Do the same for
the month, year, hour and minute.
• Operating time.
is parameter denes the operating time slots
of the heat pump, of the electrical integration,
and if present, of the hydraulic auxiliary device
according to the hot water requirements:
24/24 continuously Start at any time of
the day.
Scheduling Start in scheduled pe-
riods.
• Language.
Possible settings in French, English, Dutch,
Spanish, Portuguese, German, Italian and
Polish.
• Electrical integration.
It allows you to activate or not the electrical
integration support. If it is o, the device will
never use the electrical integration; in case of
low temperatures it is then possible a shortage
of hot water.
4.5 PARAMETERS TO BE ADJUSTED
UPON INSTALLATION.
(If not set at the time of commissioning)
e parameters can be accessed in INSTALLER
MODE.
Hold down the Menu button (2 Fig. 4-1) and
turn the selector switch (1 Fig. 4-1) by a half
turn to the right.
To exit the installer mode, proceed in the same
way or wait for 3 minutes.
Access to the system settings: ( )
Settings .
• Air ducts (aeraulic operation).
is parameter denes the aeraulic connection
type realized:
Inside / Inside Suction and return not
connected to air ducts
(ambient air)
Outside /
Outside
Suction and return con-
nected to air ducts (coated
air)
Inside /
Outside
Return connected to an air
duct (semi-coated)
• Installation (for products with coil).
Heat pump
only
e indoor heat exchanger
is not used
Connection
with boiler
e indoor heat exchanger
is connected to a boiler
controlled through the
device
Connection
with solar
system
e indoor heat exchanger
is connected to a solar
energy system
In "Boiler integration" it is asked to dene a
preference relating to the operation of priorities
between the boiler and the heat pump according
to 4 levels:
HP priority
The integration will be
only active at the end of
the heating for very low air
temperatures (<7°C)
HP
optimization
The integration will be
only active until the end
of the heating and ± early
depending on the air tem-
perature
Boiler
optimization
e heat pump is activated
at the end of the heating
and ± soon as a function
of air temperature
Boiler priority
e heat pump is active at
the beginning of heating
and for air temperature
>10°C.
•PV Photovoltaic system/Smart-grid.
is parameter allows to activate the device
coupled with a photovoltaic system. This
operating mode generates the forced starting
of the heat pump when the boiler receives a
signal coming from the photovoltaic system.
The setting automatically returns to the
previously selected mode aer 30 minutes if
the photovoltaic system signal is lost. While
receiving the signal the set point temperature
is automatically set at 62°C (not adjustable).
• Ventilation.
It allows you to turn on the air extraction
function (2 speeds: 300 or 390 m3/h). When
the unit does not heat domestic water, the
fan turns on to evacuate the ambient air to
the outside (only activated when the aeraulic
connection type is Indoor/Outdoor).
• Anti-legionella.
It allows you to turn on the water disinfection
function several times a month. e water
temperature reaches 62°C 1-4 times a month
depending on the desired setting.
• Emergency mode.
Enabling this mode allows continuous opera-
tion only with the electrical integration.
• Recirculation loop.
is mode should be strictly activated when
a domestic water recirculation system is
installed. e set point temperature is 65°C
and the operation of the heat pump adjusted
accordingly. e unit is authorized to operate
continuously (programming is not available).
4.6 SELECTION OF OPERATING
MODES.
e pressure on the button ( ) allows you to
access the menu Mode .
•In AUTO mode (only available on "ermo-
dynamic only” systems).
is operating mode automatically manages
the energy choice that allows maximum sav-
ings while guaranteeing an adequate comfort
in terms of hot water. e boiler analyses the
consumption of the previous days to adapt
the production of hot water according to
needs. It reacts to unexpected events to en-
sure the hot water making relaunches during
the day. erefore, the set point temperature
is automatically adjusted between 50 and
62°C according to the consumption prole.
e boiler operates preferably through the
heat pump. e electrical integration can be
automatically selected to ensure a sucient
volume of hot water.
PLEASE NOTE: this mode is not available on
the “Connection to the boiler” and “Connec-
tion to the solar system” plants.
• e MANUAL mode.
is mode allows you to dene the desired
amount of hot water by choosing the set
point. is set point is also represented as an
equivalence of number of showers (about 50
litres of hot water).
If the ECO mode is not active, the boiler fa-
vours operation with heat pump only. Howev-
er, if the air temperature is low or consumption
remarkable, the electrical integration (or boil-
er) can be authorized as a support at the end
of heating to reach the temperature set. If the
ECO mode is active, the boiler only works with
the heat pump at an air temperature ranging
between -5 and +43°C. erefore, the electri-
cal integration is not authorized at the time
of heating. is feature optimizes the savings,
but can cause hot water shortages. Regardless
of the ECO adjustment, if the air temperature
exceeds the operating time slots, the electrical
integration will be automatically selected to
ensure a sucient volume of hot water.
PLEASE NOTE: the ECO active/non active
modes are not available on “Connection to
the boiler” plants.
PLEASE NOTE: MANUAL modes and
“Connection to the solar system” plants: this
mode also allows the operation of the heat
pump in addition to the solar system. e
contemporary prolonged operation of the heat
pump and of the solar system may damage the
product. It is therefore necessary to allow the
operation of the heat pump only in the absence
of solar energy (use the time programming of
the heat pump).
• e BOOST mode.
is mode activates the heat pump and all
other available sources of energy (if declared
boiler integration, electrical integration)
simultaneously to the maximum set point
of 62°C.
• e ABSENCE mode.
is mode maintains the sanitary water tem-
perature above 15°C using the heat pump.
e boiler and electrical integrations can be
activated if the heat pump is not available.
•e RECIRCULATION mode.
is mode allows the heat pump to operate
continuously to reach the set point of 62°C.
e integrations (if declared boiler and elec-
tric) are activated aer 7 hours of heating with
the heat pump.