INIM SmartLoop Series User manual

2Copyright
Installation manual
Copyright
The information contained in this document is the sole property of INIM Electronics s.r.l. No part may be
copied without written authorization from INIM Electronics s.r.l.
All rights reserved.
European directive compliance
This control panel has been designed and developed to the highest standards of quality and performance
implemented by INIM Electronics s.r.l.
This control panel must be installed in accordance with the instructions described in this manual and in
compliance with the laws in force.
All control panels from the SmartLoop series are EN54-2 and EN54-4 compliant.
All control panels from the SmartLoop series, and all accessory items and special functions have IMQ-
Security systems certification, unless otherwise stated.

Installation manual
Table of contents 3
Table of contents
Copyright ............................................................................ 2
European directive compliance ............................................... 2
Table of contents.................................................................. 3
Chapter 1 Introduction......................................................................... 5
1.1 Application and use 5
1.2 Other parts of the system 7
1.3 In order to validate the IMQ-SECURITY SYSTEMS certification, and in compliance
with EN54-2 regulations: 8
1.4 About the SmartLoop fire alarm panel series 8
1.5 Description of the models 8
1.6 Features 9
Chapter 2 General information ............................................................ 10
2.1 Documentation supplied 10
2.2 Manual details 10
2.3 Firmware information 10
2.4 Operator classification - Access Levels 10
2.5 Intellectual property rights 11
2.6 Disclaimer 11
2.7 Recommendations 11
2.8 Testing the system 11
2.9 Note to the installer 11
2.10 Technical support 11
2.11 Conventions 11
2.12 Device identification details 12
2.13 Warranty 13
2.14 Safety laws 13
Chapter 3 Device management ........................................................... 15
3.1 Product handling and storage 15
3.2 Environmental conditions 15
3.3 Unpacking the device 15
Chapter 4 Technical description........................................................... 16
4.1 Panel 16
4.2 The motherboard 16
4.3 LED panel 18
4.4 Technical specifications 19
Chapter 5 Accessory devices............................................................... 21
5.1 Attachment boards 21
5.2 SmartLoop/PRN Printer 25
5.3 The SmartLetUSee/LCD and SmartLetUSee/LED Repeater panels 26
Chapter 6 Installation ........................................................................ 27
6.1 Choosing the mounting location 27
6.2 Installation flow, guidelines and testing 27
6.3 Connecting the SmartLoop/PRN printer module 28
Chapter 7 Connections....................................................................... 29
7.1 Note to the Installer regarding wiring and connection compliancy 29
7.2 About the circuitry 29
7.3 Loop Connections 29
7.4 NAC Outputs (Notification Application Circuit) 32
7.5 PL Terminal 32
7.6 AUX output 33
7.7 AUX-R output 33

4Table of contents
Installation manual
7.8 Alarm relay 33
7.9 Fault relay 33
7.10 Connecting devices to the RS485 BUS 33
7.11 Connecting the SmartLoop/NET module 35
7.12 Connecting the SmartLoop/INOUT Board 35
7.13 Connecting to a PC 36
7.14 Connecting a SmartLAN (or SmartLAN/SF) equipped control panel to a PC 37
7.15 Connecting a serial printer 37
7.16 Batteries 37
7.17 Connecting the thermal probe 38
7.18 Connecting the mains power source 39
Chapter 8 Powering up the system ...................................................... 40
8.1 Testing wiring integrity 40
8.2 First power up 40
Chapter 9 Maintenance ...................................................................... 42
Chapter 10 Troubleshooting ................................................................. 43
10.1 Fault NAC, alarm or fault output trouble 43
10.2 LOOP fault 43
10.3 Fault on devices connected to the RS485 BUS 44
10.4 Battery Fault 44
10.5 SmartLoopNET Fault 44
Appendix A Enea devices...................................................................... 46
Appendix B Argus Devices .................................................................... 49
Appendix C Apollo Devices ................................................................... 53
Appendix D Order Codes ...................................................................... 57
Appendix D Notes: .............................................................................. 58

Installation manual
Introduction 5
Chapter 1
Introduction
Note:
The control panels described in this manual have been designed and developed to the highest standards of
quality, reliability and performance. All product components are capable to application requirements and
able to operate in compliance with the related technical specifications when the temperature external to
their casing complies with Category 3k5 of EN60721-3-3:1995.
Danger: The GAS control function is not EN54-2 compliant, as this feature is not mentioned in the
aforesaid standard.
Danger: In order to validate the IMQ-SECURITY SYSTEMS certification, and in compliance with EN54-
2 regulations, all the manual alarm buttons and fire detectors employed in the system must
be associated with fire detection and alarm functions.
1.1 Application and use
The SmartLoop analogue-addressable fire alarm panel manages up to eight loops. The SmartLoop is
capable of working in a network environment (maximum configuration 30 nodes arranged in a token ring).
The loops accommodate different types of fire-security devices (detectors, input and output modules,
callpoints, fire bells, etc.). The maximum loop wire length is 2000 m. The SmartLoop also provides
supervised outputs which guarantee full control of peripheral device functions (e.g. fire bells). The panel
identifies and signals alarm, pre-alarm, fault, early warning, bypassed zone, test and monitoring
conditions. The system status is indicated on the display and on the system status LEDs. The SmartLoop
panel supports up to 14 Repeater panels (accessory items) which replicate system signals/data and allow
building occupants with Level 2 authorization to silence and reset the system. The panel can also be
connected to a PC or printer.
The self-addressing feature and reduced-complexity point programming allow fast and easy installation.
Figure 1 - Example configuration: 6 node token-ring network layout (Hornet)
A
D
B
C
E
PSTN
line
Internet

6Introduction
Installation manual
[A] Loop
All the peripheral devices of the system must be connected in parallel to the loop circuit (2 pole STP). The
loop is a closed electrical circuit in which a wide variety of alarm devices can be accommodated. Opening or
closing the circuit at any point will generate a fault signal. The loop circuit communication path starts on
the Loop-Out terminals and ends on the Loop-In terminals. The panel controls and communicates with the
loop devices via digital protocol. The loop utilizes the same two poles for the power supply to the system
devices and the two-way communication channel. The loop accommodates:
1. Detectors: A smoke detector is an active fire protection device that detects smoke or flames and
issues an alarm thereby alerting building occupants to the danger of fire. Detectors can be:
- Optical smoke detectors which look for the presence of visible by-products of combustion in the
detection chamber (Tyndall effect).
- Optical/Heat detectors which operate as per optical smoke detectors but also sense for increase in the
environment temperature. The combination of both sensing methods (smoke and heat) provides faster
detection and reduces the false alarm rate.
- Heat detectors: sense for an increase in the temperature in the protected environment. There are two
types of heat detector: Fixed temperature — that signal alarm when the temperature exceeds the
predefined threshold; and Rate-of-rise which, as well as monitoring the predefined fixed temperature,
also respond to rapid increase in temperature.
- Ionization smoke detectors: feature a harmless radioactive source within a dual detection chamber.
They operate by sensing for a change in electrical conductivity across the detection chamber.
- CO detectors: sense the levels of carbon monoxide given off by all carbon-based materials in the
smoldering stages of a fire (often combined with heat detection sensor).
2. Input Module: a device which monitors the status of another device (callpoint, detector, etc.) and
sends the respective information to the panel. The Input module allows the loop to accommodate any
type of device.
3. Output Module: provides a supervised ancillary output. The cause of activation of this output can be
defined during the system configuration phase. The output module interfaces all types of loop devices
(bells, signaling devices, fire door magnets, etc.).
4. Callpoint: a clearly labeled fire button with instructions for use in the event of fire. Usually placed near
building entrances/exits. These push-button alarm-trigger devices allow building occupants to activate
system alarms.
5. Sounder/Flasher: audible/visual alarm signaling devices.
For the list of the devices the loop accommodates, and for details regarding their wiring and operating
principles, refer to Appendix A - Enea devices, Appendix B - Argus Devices and Appendix C - Apollo
Devices.
The loop circuit configuration (as required by the local Fire code in force) is a fault-tolerant circuit which, in
the event of short-circuit or loop interruption, allows the panel to continue to communicate and drive the
elements on either side of the interruption.
Isolator
In order to provide a fault-tolerant loop circuit that is Fire code compliant, isolator modules must be
installed in series with the loop circuit. Isolators modules detect short-circuit conditions and consequently
interrupt the loop circuit. If a short-circuit occurs, the two isolators adjacent to the shorted section will
open and split the loop in such way as to allow the panel to drive the elements on either side of the
interruption. No more than 32 detectors/devices should be installed between two isolator modules.
Note:
Many detectors/devices have built-in isolators and therefore do not require isolator modules. Refer to
Appendix A, Appendix B and Appendix C for further details.
[B] Repeater SmartLetUSee/LCD (accessory item)
This optional system enhancement tool (equipped with keypad, LEDs, fast buttons and display) replicates
all the system data. The panel supports 14 repeaters connectable via RS485 BUS (maximum cable length
1000m from panel). Repeaters should be located at building entrances/exits in such way as to allow
persons in charge to view the system status without going too far inside the building.
[C] SmartLevel power-supply stations (accessory item)
The SmartLevel is the ideal power source for all devices located in the area protected by the detection
system. Its internal board satisfies all EN54 requirements and provides complete supervision of the power

Installation manual
Introduction 7
station. The device can be connected to the control panel loop via an input/output module (not included),
installed inside the box, or by means of the RS485 BUS, thus allowing the complete supervision of the
power station and control of the 3 outputs.
[D] SmartLine-EXT fire-extinction panel (optional)
SmartLine-EXT fire-extinction panels are based on SmartLine conventional fire detection panels (4-zones).
These control panels provide all the functions of SmartLine conventional fire-detection panels plus 1
SmartLetLoose/ONE extinction channel.
They interface with SmartLoop control panels via a built-in RS485 BUS. It is possible to programme the
SmartLine-EXT fire-extinction control panel to activate its functions in response to “local” data/signals
(conventional zones, extinguishant terminals, Stop extinction, etc.), or in response to “remote” data/
signals coming from the SmartLoop control panel.
[E] Sounderflashers
These audible/visual signaling devices connect to the control panel outputs and activate when specific
conditions occurs. The cause of activation (alarm, pre-alarm, early warning, etc.) can be defined during the
system configuration phase.
1.2 Other parts of the system
Point: synonym and definition of a loop device (detector, etc.).
Zone: a group of points (detectors, etc.). The points can be assigned to the zones during the configuration
phase. Consult your local Fire code for the rules regulating automatic fire detection installations and for full
details regarding zone limitations.
Power Supply: a module, connected to the mains 230 Vac, that provides a stabilized voltage @ 24 V
(27.6 V) to the system and the charge source to the batteries. The EN54-4 compliant power-supply module
is housed below the motherboard. The mains voltage (230 Vac) is the primary power source of the system.
Refer also to paragraph 7.18 Connecting the mains power source.
Batteries: the secondary power source of the system. The panel houses two lead batteries @ 12V 17Ah
(connected in series). The system monitors the battery status (efficiency and charge). In the event of
inefficient or low battery conditions, the system will signal battery fault. If primary (230 Vac) power failure
occurs, the batteries will take over, however, they will shutdown automatically if the blackout persists. The
automatic battery shutdown feature prevents irreparable damage to the batteries. Refer also to paragraph
7.16 Batteries.
Thermal probe: an accessory tool, to be connected to the panel and attached to the battery pack. This
device monitors the temperature of the external battery pack and regulates the battery charge accordingly.
Refer also to paragraph 7.17 Connecting the thermal probe.
RS485 Bus: 4 wire BUS for the Repeater connections. Four pole twisted shielded cable must be used for all
connections. Refer also to paragraph 7.10 Connecting devices to the RS485 BUS.
Timer: a logical entity (the panel provides 8 timers) for automatic time-management of preset intervals (2
intervals per day) on preset days of the week and specific dates. The timers can be used in equations and/
or to manage predefined operations.
Equation: a group of logical conditions defined by the installer. An equation comprises a series of
operators (AND, OR, +, etc.) and a series of operands (Points, Zones, Timers, etc.). An equation can be
associated with an output that will activate when the equation is satisfied.
Holidays: a list of days defined during the system configuration phase that can be associated with the
timers.
Early Warning: a signal generated by detectors with the early-warning feature (to be defined during the
system configuration phase). The detector senses for a level of smoke or heat that exceeds its early
warning threshold (each detectors can be set separately). This signal indicates that the person/s
responsible for the safety of the building and its occupants should verify the alarm or check the
functionality of the detector concerned.

8Introduction
Installation manual
1.3 In order to validate the IMQ-SECURITY SYSTEMS certification, and in
compliance with EN54-2 regulations:
• All the manual alarm buttons and fire detectors employed in the system must be associated with fire
detection and alarm functions.
• The functions associated with the programmable LEDs on the control panel frontplate (Keypad/Display
board and LED board), and on SmartLetUSee/LCD and Smart LetUSee/LED Repeaters must be set up in
accordance with the colour of the LEDs.
- Red: fire alarm
- Yellow: fault, test and disabled status
Note:
The GAS control function is not EN54-2 compliant, as this feature is not mentioned in the aforesaid
standard.
1.4 About the SmartLoop fire alarm panel series
There are 3 expandable models (expandable to 8 loops by means of 3 SmartLoop/2L expansion boards). All
have 2 loops and are housed in the same sized enclosure. Each expandable model has a technically-
downsized version (in same-sized enclosure) with 1 loop for reduced complexity applications.
All models manage the same functions and support a full spectrum of hardwired and wireless devices.
The SmartLoop fire alarm panel series provides the following models:
•SmartLoop1010/P - fully-equipped frontplate model with 1 loop
•SmartLoop2080/P - fully-equipped frontplate model with 2 loops expandable to 8
•SmartLoop1010/G - keypad and display model with 1 Loop
•SmartLoop2080/G - keypad and display model with 2 loops expandable to 8
•SmartLoop1010/S - flush front model with 1 loop
•SmartLoop2080/S - flush front model with 2 loops expandable to 8
Figure 2 - SmartLoop Series
1.5 Description of the models
The “/P” model is equipped with a keypad, display, fault LEDs, fast buttons and a Zone status LED pad.
This model is suitable for locations where extended visual signals and manual control are necessary. This
model can be enhanced with the SmartLoop/PRN thermal printer (accessory item).
SmartLoop1010/P
SmartLoop2080/P
SmartLoop1010/G
SmartLoop2080/G
SmartLoop1010/S
SmartLoop2080/S

Installation manual
Introduction 9
The “/G” model is equipped with a keypad, display, fault LEDs and fast buttons and is suitable for
installation in locations where visual signals and manual control are necessary. This model can be upgraded
at any time after installation (for example, if moved to a location where extended visual signals and
manual control are necessary) by replacing its door with a “/P” model door that is enhanced with a Zone
status LED pad and thermal printer option.
The “/S” model has an unequipped door (no keypad, display or LEDs) and is suitable for installation in
locations where visual indications and manual control are not required (e.g. basements). This model can
be upgraded at any time after installation (for example, if moved to a location where visual signals and
manual control are necessary) by replacing its door with a “/G” model or “/P” model door.
1.6 Features
- Manages up to 240 zones per panel with network-zone architecture feature
- Network environment capable (maximum configuration 30 panels)
- Group and Zone sharing among panels in the network environment
- Switching power supply 27.6 V @ 4 A with battery charger function
- 2 on-board loops on expandable 2080 models; 1 on-board loop on non-expandable 1010 models
- 3 programmable NAC outputs
- 1 Alarm NAC output
- 1 Fault NAC output
- 1 alarm signalling relay (voltage free)
- 1 fault signalling relay (voltage free)
- RS485 BUS for the connection of up to 14 SmartLetUSee/LCD repeaters, 4 SmartLevel power stations
and 4 SmartLineEXT fire-extinction stations
- 1 power supply output @ 24 V for external devices
- 1 power supply output @ 24 V for external devices with "Power Cutoff" during reset
- RS232 and USB connectors for uploading/downloading programming data
- 2000 event buffer
The motherboard provides housing for:
- 3 SmartLoop/2L loop expansion boards with 2 loops per board (2080 expandable models only)
- 1 SmartLoop/NET network board
- 1 SmartLAN or SmartLAN/SF board
- 1 SmartLoop/PSTN board
- 1 SmartLoop/INOUT Input/Output expansion board
- 1 SmartLoop/LED zone-status LED module (for “/P” models only)
- 1 SmartLoop/PRN thermal printer module (for “/P” models only)
Note:
The 1010 non-expandable models with 1-loop have exactly the same features and components as the
2080 expandable models with 2-loops.

10 General information
Installation manual
Chapter 2
General information
2.1 Documentation supplied
• Installation manual (this manual)
• Programming Manual
•UserManual
The manuals are supplied with the device. For further copies of the Installation Manual, please contact
INIM Electronics s.r.l. offices quoting the order number shown in Appendix D - Order Codes.
2.2 Manual details
• Title: SmartLoop Installation Manual
• Version: 3.02
• Month and year: April 2012
• Code: DCMIINE0SLOOP
• Addressee: installer, technical assistance operator
2.3 Firmware information
• SmartLoop firmware version: 2.0.x
• SmartLoop loop driver firmware version: 2.0.x
• SmartLoop Front Panel Firmware version: FSANN 1.0.x
• SmartLAN/SF firmware version: 4.1.x
• SmartLAN/SF firmware version: 1.0.x
• SmartLoop/PSTN firmware version: 1.0.x
• SmartLoop/2L firmware version: 2.0.x
• SmartLoop/INOUT firmware version: 2.0.x
• SmartLetUSee/LCD firmware version: 1.0.x
• SmartLetUSee/LED firmware version: 1.0.x
2.4 Operator classification - Access Levels
Level 1
All building occupants can view the system status (active events) and events log and silence the panel
beeper.
Level 2
ONLY authorized keyswitch users and PIN users (5 digit codes) can Enable/Disable loop devices, bell outputs,
software zones and network devices, and SILENCE or RESET the system.
Level 3
ONLY authorized technicians, appointed by the Installer company can, by means of a screw driver, remove
the screws and open the fire control panel enclosure to insert the J2 Jumper and then, after entering a 5
digit PIN (5 digit code) access the parameter programming phase and/or carry out maintenance work (for
example, change the battery, replace fuses, etc.).
Level 4
ONLY authorized technicians, appointed by the Manufacturer can, by means of special tools, carry out
repair work on the motherboard (for example, repair or replace SM components).
Note:
The default PIN code is “
00004
”.

Installation manual
General information 11
2.5 Intellectual property rights
The information contained in this document is private property. All rights reserved
No part of this document may be copied or reproduced unless expressly authorized in writing by INIM
Electronics, in particular the parts regarding the device specified in paragraph 4.1 Panel.
2.6 Disclaimer
INIM Electronics s.r.l. shall not be responsible for damage arising from improper application or use.
This control panel should be handled by qualified personnel only. Installation must be carried out strictly in
accordance with the instructions described in this manual, and in compliance with the local fire code in
force.
2.7 Recommendations
INIM Electronics recommends that the entire system be tested on a regular basis (refer to paragraph 2.8
Testing the system).
2.8 Testing the system
This system has been designed to the highest standards of quality and performance. The system may fail
to function as intended due to the failure of a component. Most problems which prevent a fire control
system from operating as intended can be found by regular testing and maintenance of the system devices
(refer to Chapter 9 - Maintenance).
Testing should include all detectors, signaling devices and any other operational devices that are part of the
system.
2.9 Note to the installer
In order to provide adequate protection and instructions for proper use, you (the installer) must be familiar
with the operating procedure of this device. As the only individual in contact with system users, it is your
responsibility to instruct them on how to use this system properly and to bring to their attention that every
fire is different in the amount of smoke and rate of burning. Therefore, smoke and heat detectors may not
provide timely warning of fires caused by violent explosions, escaping gas or improper storage of
inflammable materials.
Regardless of its capabilities, a fire alarm system is not a substitute for the necessary precautions building
occupants must take to prevent or minimize the harmful effects of fire.
2.10 Technical support
Our professional engineers are readily available to assist you. Call our phone number and you will be
connected right away to a person who will answer all your questions and provide you with full technical
support.
2.11 Conventions
2.11.1 Glossary and terminology
Panel, device, system: refer to the items described in paragraph 4.1 Panel.
Left, right, behind, above, below: refer to the directions as seen by the operator in front of the mounted
device.
Communicator (telephone, SMS, digital): synonym of dialer.
STP: synonym of shielded twisted pair cables
Qualified personnel: those persons whose training, expertise and knowledge of the laws and bylaws
regarding service conditions and the prevention of accidents, are able to identify and avoid all possible
situations of danger.
Select: click on and select a specific item (from drop-down menu, options box, graphic object, etc.).
Press: click on a video button, or press a key on the panel keypad.

12 General information
Installation manual
2.11.2 Graphic conventions
Following are the graphic conventions used in the text.
Note:
The attached notes contain important information about the text.
Attention: The "Attention" prompts indicate that total or partial disregard of the procedure could
damage the connected devices.
Danger: The danger warnings indicate that total or partial disregard of the procedure could injure the
operator or persons in the vicinity.
2.12 Device identification details
Figure 3 - Data labe
Conventions Example description
Text in Italics Refer to paragraph
2.11.2 Graphic
conventions
Text in italics: indicates the title of a chapter, section, paragraph, table
or figure in this manual or other published reference.
<text> #<CustomerCode> Variable data.
[uppercase
letter] or
[number]
[A] or [1] Representation of a part of the system or video object.
BUTTON CANC, ESC, RESET Computer or control panel keys.
Alimentazione /
LBDTIN4ASLOOP11G
I
1010/G
02/2012
230V~ -15% + 10%
Power / Alimentacion
50/60 Hz
Consumo /
Consumption / Consumo
0.9 A
Isolamento /
Isolation / Aislamiento
Classe
Approvato /
Approved / Aprobado
EN54-2, EN54-4
0051-CPD -0231
MADE IN ITALY
0051
09
0051 - CPD - 0228
Control and signalling system with integrated
power-source.
SmartLoop/1010-S
EN 54-2:1997+A1:2006
EN 54-4:1997+A1:2002+A2:2006
Isolation: Class I
Options with requirements:
- 7.8 Sounder circuits output
- 7.11 Delayed outputs
- 7.12 Alarm on two points activation
- 8.3 Fault from points signal
- 8.9 Monitored output for remote signalling
- 9.5 Points isolation
- 10.0 Test condition
Manufacturer: INIM Electronics s.r.l.
Address: via Fosso Antico, Centobuchi
63076, Monteprandone (AP), Italy
0051
09
0051 - CPD - 0228
Control and signalling system with integrated
power-supply device.
SmartLOOP/1010-S
EN54-4: 1997/ A2: 2006
EN54-4: 1997/ A1: 2006
Isolation: Class I
Options with requirements:
- 7.8 Sounder circuits output
- 7.11 Delayed outputs
- 7.12 Alarm on two points activation
- 8.3 Fault from points signal
- 8.9 Monitored output for remote signalling
- 9.5 Points isolation
- 10.0 Test condition
Manufacturer: INIM Electronics s.r.l.
Address: via Fosso Antico, Centobuchi
63076, Monteprandone (AP), Italy
0051
09
0051 - CPD - 0231
Control and signalling system with integrated
power-supply device.
SmartLOOP/1010-G
EN 54-2:1997+A1:2006
EN 54-4:1997+A1:2002+A2:2006
Isolation: Class I
Options with requirements:
- 7.8 Sounder circuits output
- 7.11 Delayed outputs
- 7.12 Alarm on two points activation
- 8.3 Fault from points signal
- 8.9 Monitored output for remote signalling
- 9.5 Points isolation
- 10.0 Test condition
Manufacturer: INIM Electronics s.r.l.
Address: via Fosso Antico, Centobuchi
63076, Monteprandone (AP), Italy
0051
09
0051 - CPD - 0232
Control and signalling system with integrated
power-supply device.
SmartLOOP/1010-P
EN 54-2:1997+A1:2006
EN 54-4:1997+A1:2002+A2:2006
Isolation: Class I
Options with requirements:
- 7.8 Sounder circuits output
- 7.11 Delayed outputs
- 7.12 Alarm on two points activation
- 8.3 Fault from points signal
- 8.9 Monitored output for remote signalling
- 9.5 Points isolation
- 10.0 Test condition
Manufacturer: INIM Electronics s.r.l.
Address: via Fosso Antico, Centobuchi
63076, Monteprandone (AP), Italy

Installation manual
General information 13
Figure 4 - CE Mark
2.13 Warranty
INIM Electronics s.r.l. warrants the original purchaser that for a period of 24 months from the date of final
acceptance, the product shall be free of defects in materials and workmanship. The warranty applies only
to defects in parts and workmanship relating to normal use. It does not cover:
Improper use or negligence
Damage caused by fire, flood, wind or lightning
Vandalism
Fair wear and tear
INIM Electronics s.r.l. shall, at its option, repair or replace any defective products. Improper use, that is,
use for purposes other than those mentioned in this manual will void the warranty. For the full details and
conditions regarding the warranty, refer to the purchase order.
2.14 Safety laws
The aim of the instructions in this section is to ensure that the device is installed and handled properly. This
chapter contains vital information. The installer should be familiar with this section and bring each item to
the attention of the system users.
2.14.1 Compliancy
The design and manufacture of the SmartLoop panel comply with EN 54-2 Fire detection and signaling
systems - Control and signaling panels.
The design and manufacture of the power supply comply with EN 54-2 Fire detection and signaling systems
- Power supply devices.
2.14.2 Managing electronic devices
The normal motions of any person may generate electrostatic potential of thousands of volts. Discharge of
this current through semiconductor devices during handling may cause serious damage which although
may not be immediately evident may reduce the reliability of the circuits.
If located in their housings, the electronic circuits of INIM Electronics products are highly immune to
electrostatic discharge.
Do not expose the circuits to damage by removing the modules unnecessarily from their housings.
0051
09
0051 - CPD - 0226
Control and signalling system with integrated
power-supply device.
SmartLOOP/2080-G
EN 54-2:1997+A1:2006
EN 54-4:1997+A1:2002+A2:2006
Isolation: Class I
Options with requirements:
- 7.8 Sounder circuits output
- 7.11 Delayed outputs
- 7.12 Alarm on two points activation
- 8.3 Fault from points signal
- 8.9 Monitored output for remote signalling
- 9.5 Points isolation
- 10.0 Test condition
Manufacturer: INIM Electronics s.r.l.
Address: via Fosso Antico, Centobuchi
63076, Monteprandone (AP), Italy
0051
09
0051 - CPD - 0225
Control and signalling system with integrated
power-supply device.
SmartLOOP/2080-S
EN 54-2:1997+A1:2006
EN 54-4:1997+A1:2002+A2:2006
Isolation: Class I
Options with requirements:
- 7.8 Sounder circuits output
- 7.11 Delayed outputs
- 7.12 Alarm on two points activation
- 8.3 Fault from points signal
- 8.9 Monitored output for remote signalling
- 9.5 Points isolation
- 10.0 Test condition
Manufacturer: INIM Electronics s.r.l.
Address: via Fosso Antico, Centobuchi
63076, Monteprandone (AP), Italy
0051
09
0051 - CPD - 0228
Control and signalling system with integrated
power-supply device.
SmartLOOP/1010-S
EN54-4: 1997/ A2: 2006
EN54-4: 1997/ A1: 2006
Isolation: Class I
Options with requirements:
- 7.8 Sounder circuits output
- 7.11 Delayed outputs
- 7.12 Alarm on two points activation
- 8.3 Fault from points signal
- 8.9 Monitored output for remote signalling
- 9.5 Points isolation
- 10.0 Test condition
Manufacturer: INIM Electronics s.r.l.
Address: via Fosso Antico, Centobuchi
63076, Monteprandone (AP), Italy
0051
09
0051 - CPD - 0227
Control and signalling system with integrated
power-supply device.
SmartLOOP/2080-P
EN 54-2:1997+A1:2006
EN 54-4:1997+A1:2002+A2:2006
Isolation: Class I
Options with requirements:
- 7.8 Sounder circuits output
- 7.11 Delayed outputs
- 7.12 Alarm on two points activation
- 8.3 Fault from points signal
- 8.9 Monitored output for remote signalling
- 9.5 Points isolation
- 10.0 Test condition
Manufacturer: INIM Electronics s.r.l.
Address: via Fosso Antico, Centobuchi
63076, Monteprandone (AP), Italy

14 General information
Installation manual
1. When removing or handling the boards, hold the board edges only.
2. Do not touch the electronic components, the printed circuits or the metal parts of the connectors.
3. Do not hand the module to another person without first ensuring that you both have the same
electrostatic potential. This can be achieved by simply shaking hands.
4. Place the board on an anti-static surface or a conductor surface with the same potential.
Further information regarding procedures relating to safety when working with electronic devices can be
found in Directive IEC 60147-0F.
2.14.3 Connecting the apparatus
In order to provide adequate protection and instructions for proper use, security professionals (Installers
and maintenance technicians) must be familiar with the operating procedure of this device.
Please read the instructions carefully before installing and/or servicing the system.
Before first power-up, be sure that the earth connection has been completed properly on the respective
terminal.
The recommended minimum wire cross section for the earth connection is 2.5 mm2, that is, unless
otherwise stated in accessory documentation.
2.14.4 Replacement and disposal of used devices
Replacement
When replacing used devices, disconnect the devices concerned then complete the connections of the new
devices in compliance with the instructions printed on the respective leaflets.
Contact your local municipal offices for information regarding the disposal of used electronic devices.
Disposal
Do not burn used electronic devices, or allow them to pollute the environment (countryside, rivers, etc.).
Electronic devices must be disposed of in a safe environment-friendly way. In order to avoid short-circuits,
take all the necessary precautions when removing used batteries. Contact your local municipal offices for
information regarding the disposal of batteries.

Installation manual
Device management 15
Chapter 3
Device management
3.1 Product handling and storage
This device is safely packed inside a cardboard box, however, care must be taken to avoid accidental
damage during handling. Cartons/boxes should be placed in such a way as to avoid knocks and falls, and
special care must be taken to protect the devices from extreme heat and/or cold.
3.2 Environmental conditions
Temperature limits:
• -10° / +55°C for transport and storage
• -5° / +40°C operating temperature
3.3 Unpacking the device
Take due care when unpacking the product, and dispose of all waste packaging in accordance with the local
method of disposal.
The cardboard box contains the SmartLoop control panel (enclosure in metal).
Note:
All waste packaging must be disposed of in full respect of the local laws in force.
3.3.1 Inside the box
Inside the box you will find
• Metal enclosure containing the motherboard
• Installation Manual
• Plastic bag containing: resistors, diodes, 2032 lithium battery (non-rechargeable), keys, battery
connection wires
Attention: The 2032 lithium battery guarantees data retention. This battery must be fitted properly into
its housing (refer to
paragraph 4.2 - [H]
) with the “+” sign towards you.
The package does not include:
a thermal probe (an accessory device which monitors the temperature of the external battery pack and
regulates the battery charge accordingly), batteries, the SmartLeague software CD. These items must be
purchased separately. Be sure you have these items on hand before starting the installation procedure.
Attention: In order to validate the IMQ-SECURITY SYSTEMS certification and comply with EN 54-4
requirements, installation of a thermal probe is essential.
Be sure you have this item on hand before starting the installation procedure.

16 Technical description
Installation manual
Chapter 4
Technical description
4.1 Panel
Figure 5 - Overview
4.2 The motherboard
The SmartLoop motherboard has a 32 bit microprocessor that controls all the control panel functions, and
2 peripheral microprocessors (one per loop) that manage communications with the system peripherals.
INIM’s R & D professionals have developed and designed the SmartLoop motherboard using ground-
breaking new generation fire technologies that ensure maximum precision and performance. Deployment
of the most advanced reflow technology ensures high-noise immunity and extreme accuracy. Each
connection terminal is protected against electrical surges and is high-noise immune capable. All terminals
on the motherboard are clearly marked and easily identifiable.
The motherboard has been especially designed to accommodate with ease the various SmartLoop
attachment boards.
[A] Front panel with display, keys and signalling LEDs SmartLoop/P and SmartLoop/G only
[B] Key location for the Level 2 access key
[C] LED panel SmartLoop/P only
[D] SmartLoop/PRN Thermal printer
[E] Securing screws for the front cover All models
[F] Cable entries (located on all sides of the enclosure)
[G] Data label
A
B
C
D
E
F
G
E

Installation manual
Technical description 17
Figure 6 - About the motherboard
[A] Connector for the connection with the display board (located on the frontplate)
[B] Loop 1 status LED
[C] Loop 2 status LED
[D] SmartLoop/2L board connector
[E] SmartLAN board connector
[F] Microprocessor reset button
[G] Memory jumper (if removed and the panel is switched Off, the system will restore to factory default settings)
[H] Memory battery (3 V lithium battery)
[I] RS232 COM connector (DB9 male)
[J] USB connector (type B)
[K] SmartLoop/PSTN plug-in module connector
[L] Clear ground-fault jumper (removal of this jumper clears ground faults)
[M] On-panel thermal printer connector
[N] Programming jumper (removal of this jumper blocks access to programming)
[O] ProbeTH Thermal probe board connector (Thermal probe not included)
[P] Switching power-supply module connector
[Q] SmartLoop/NET plug-in module connector
[R] Connector for internal batteries (connection wire included)
[S] SmartLoop/INOUT plug-in module connector
A
BC
D
E
F
G
H
I
J
K
L
M
N
O
P
Q
R
S
U T
WVXZ Y
A1A2A3A4A5A6

18 Technical description
Installation manual
4.2.1 Loop status LED
The loop status LEDs (
paragraph 4.2 - [B] and paragraph 4.2 - [C])
provide visual information relating to
the communications between the control panel and its detectors. They indicate that the panel is
interrogating its devices, the protocol it is using and whether or not the interrogated devices have
responded.
• The green LED on the right will flash each time a loop device responds. The control panel interrogates its
devices at regular intervals, starting from address 1 through to the last address (for information
regarding which devices can be connected to the loop, refer to Appendix A, Appendix B and Appendix C).
• The red LED in the centre will blink each time a command is sent through the loop for a device using
either Enea (Appendix A) or Argus (Appendix B) protocol.
• The red LED on the right will flash each time a command is sent through the loop for a device using
Apollo (Appendix C) protocol.
Under normal operating conditions, the red LED (relating to the protocol in question) will blink rapidly and
the green LED will flicker indicating the device response. The flickering phase depends on the number of
devices connected to the loop. The more devices the longer the LED will flicker.
4.3 LED panel
SmartLoop/P control panel models are equipped with a LED panel (located on the front of the control panel
enclosure) which is connected to the keypad/display board (
paragraph 4.1 - [C])
.
This panel has 48 red LEDs which provide one or more signals (configured during the programming phase).
The On/Off logic of each LED can be set up individually.
[T] PL PL and GND terminals for disconnected-battery signalling In the event of primary and
secondary power failure (mains and batteries), the PL terminal will connect to GND. Under
normal operating circumstances, the PL terminal is disconnected.
[U] AUX 24V output for the external power load, protected by a 1.8A self-resettable fuse
[V] AUX-R 24V output for external loads, protected by a 1.8A self-resettable fuse (with "Power Cutoff"
during reset.) Suitable for powering devices which require power loss in order to reset (e.g.
beam detectors)
[W] RS485
REPEATER
RS485 Bus terminals for repeater connections (accommodate up to 14 Repeaters)
[X] ALARM
RELAY
Alarm relay (voltage free)
[Y] FAULT
RELAY
Fault relay (voltage free)
[Z] FAULT OUT Supervised fault output protected by 1A fuse
[A1] ALARM NAC Supervised alarm NAC output protected by 1A self-resettable fuse
[A2] NAC1,
NAC2,
NAC3
Programmable NAC outputs protected by 1A self-resettable fuse
[A3] LOOP2-I Loop 2 Input terminals
[A4] LOOP2-O Loop 2 Output terminals
[A5] LOOP1-I Loop 1 Input terminals
[A6] LOOP1-O Loop 1 Output terminals

Installation manual
Technical description 19
4.4 Technical specifications
Operating voltage 230 Vac -15% + 10% 50/60Hz
Max current draw on AC input 0.9 A @ 230Vac
Internal power supply output voltage 27.6 Vdc
Internal Power supply MAX current 4 A
Internal Power Supply output ripple MAX 1%
Max current available for the external load (loop devices, external
loads, attachment boards, etc.)
2.8 A
Minimum current (Imin) 600 mA
Low Voltage range 18 ... 27.6 Vdc
Panel Current draw (motherboard+LCD screen on the frontplate)
- standby 200mA
- from battery in the event of mains failure 80 mA
- maximum battery-charge current 1A
Battery specifications 12 V @ 7Ah or 12 V @ 17Ah
(Brand and type) YUASHA (or equivalent)
NP 7 -12 FR or NP 17 -12-FR or similar
Flame Class UL94-V2 or higher
Maximum internal resistance of the batteries (Ri max)2.2Ohm
Operating temperature From -5° to +40° C
Dimensions (Height x Length x Depth) 48 x 47 x 13.5 cm
Weight without battery 8 Kg
Attachment board current draw
SmartLoop/2L (2 Loop expansion board) stby: 20mA MAX:70mA
SmartLoop/INOUT (6 input/output expansion board) stby:40mA MAX:300mA
SmartLoop/NET (Token-ring network adaptor board) stby: 40mA MAX:40mA
SmartLoop/PSTN (PSTN dialler) stby:20mA MAX:60mA
SmartLAN (Ethernet board) stby:200mA MAX:200mA
SmartLoop/LED (48 LED board) stby:40mA MAX:80mA
SmartLoop/PRN (on-panel thermal printer) stby:0 MAX:1A
SmartLetUSee/LCD (LCD repeater) stby: 40mA MAX:50mA
SmartLetUSee/LED (LED repeater) stby: 5mA MAX:50mA
Absolute maximum terminal ratings

20 Technical description
Installation manual
Motherboard
Loop output terminals Max 0.5 A each loop
NAC1, NAC2, NAC3, alarm NAC, fault output 1.3 A MAX
Fault relay, alarm relay Voltage-free contact 5A @ 30V max
RS485 BUS 1.8 A MAX
AUX, AUX-R 1.8 A MAX
Current ripple on AUX and AUX-R outputs 1% MAX
PL Normally Open Contact 5A @ 30Vdc MAX
SmartLoop/INOUT
on each CH 0.9 A MAX
PIN code to access default settings 00004
This manual suits for next models
6
Table of contents
Other INIM Control Panel manuals

INIM
INIM SmartLine 0051 Series User manual

INIM
INIM Previdia Ultra User manual

INIM
INIM SmartLiving 515 Installation guide

INIM
INIM SMARTLOOP 0051-CPR-0225 User manual

INIM
INIM GameOver SmartLiving 505 Assembly instructions

INIM
INIM Previdia-Ultravox User manual

INIM
INIM Prime060S User manual

INIM
INIM SmartLoop2080/S Owner's manual

INIM
INIM Previdia Ultra User manual

INIM
INIM PREVIDIA COMPACT User manual