Interlogix TruPortal TP-ADD-1DIP User manual

P/N 460939301B • REV 01.00 • 30OCT13 1
TruPortal™IP-based Single
Door Controller (IPSDC)
Quick Reference
en-US
Introduction
The TruPortal IP-based Single Door Controller (IPSDC) provides
distributed processing for the interface of access control readers,
digital inputs, and outputs to the TruPortall System Controller.
The IPSDC is pre-configured to use Power-over-Ethernet (PoE),
using electrical power from Ethernet cabling, but can also be
configured to use an auxiliary power supply.
Packing List
• IPSDC printed circuit board (PCB) assembly and overlay
• Hardware kit
- Ground terminal lug
- SEMS screws
- Protection diodes for door strike wiring
- Metal Oxide Varistor (MOV) surge absorbers for door
strike wiring
- Ferrite for use with network cables
- 1K end-of-line resistors
• Lock (quantity = 1)
• Enclosure
• Enclosure mounting template
• Installation screwdriver
•TruPortal IP-based Single Door Controller (IPSDC) Quick
Reference (this document)
Model Numbers
The IPSDC is available in the following configurations:
•TP-ADD-1DIP: TruPortal single-door base kit. Consists of a
TruPortal IPSDC, installed in a UL-listed enclosure.
•TP-ADD-1DIP-BRD:TruPortalIPSDCboardonly.Capableof
controlling one door. No enclosure or readers included.
Installation Procedure
To install the IPSDC, perform the procedures described in the
following sections, in the order in which they are presented.
1. Mount the enclosure.
2. Set the dual in-line package (DIP) switches.
3. Connect the reader(s) and inputs.
4. Connect the door strikes.
5. Connect the power.
6. Verify proper operation on power up.
7. Configure the IP address of the IPSDC and the IP address of
the System Controller (TP-SYS).
WARNING: Circuit board components are vulnerable to damage
by electrostatic discharge (ESD). ESD can cause
immediate or subtle damage to sensitive electronic
parts. An electrostatic charge can build up on the
human body and then discharge when touching a
board. A discharge can be produced when walking
across a carpet and touching a board, for example.
Before handling any board, make sure to dissipate
any charge by touching the ground. This discharges
any static electricity build-up.
WARNING: Do not apply power to any component during
installation. Damage to components may occur if
power is incorrectly applied.
Mounting the Enclosure
1. Using the template provided, mark and then drill the four
mounting holes.
2. Bolt the enclosure securely to the wall, using four #8 thread
lag bolts or equivalent.

2 TruPortal IP-based Single Door Controller Quick Reference
Setting the DIP Switches
Set DIP switches before installing and wiring readers. See Figure
10 on page 7 for switch locations.
The following table provides switch settings for input types:
Note: After changing DIP switch settings to modify input types,
be sure to reboot the IPSDC.
Switches SW4—SW7 are right-angle, momentary-contact push
buttons described in the following table and shown in Figure 11 on
page 8.
Note: The reader board address is internally set to Address 1.
Connecting the Readers and Inputs
Use Figure 10 on page 7 to wire the readers and inputs. Refer to
the reader documentation for wiring instructions.
Note the following details:
• IPSDCs do not support the following TruPortal features:
Buzzer actions initiated by action triggers, auxiliary inputs/
outputs, and reader tamper inputs.
• The reader DI port (J2) has two digital inputs which are used
for door status devices (door contacts and exit request input).
The inputs can be configured as supervised or non-
supervised. Inputs configured as supervised digital inputs
require End-of-Line (EOL) resistors.
• The reader interface has built-in pull-up resistors to
accommodate cable lengths over 500 feet (152.4 meters). No
external pull-up resistors are required for the reader interface.
Note: A TruPortal IPSDC Power Requirement Wattage
Calculator is included on the product disc in the
\Documentation\en-US folder for use in determining
peripheral loads.
Switch Purpose
SW1 – Select Custom
Wiegand Card Format[1]
1. Use the System Administration > Card Formats page
in the TruPortal User Interface to configure Wiegand
card formats.
Set SW1-1 to OFF and set SW1-2 thru
SW1-4 to ON.
SW2 Set all four DIP switches to OFF
SW1-5 and SW1-6 SW1-7 SW1-8
Supervised DI/REX 1,
4-State N/A ON N/A
Supervised DI/REX 1,
2-State (default) N/A OFF N/A
Switch Purpose
SW4 – Boot Mode Manually enables the ICT. See the TruPortal
Software User Guide for details.
SW5 – Hardware Reset Reboots the IPSDC. Use this switch only if
performing a controlled manual shutdown, as
instructed by Technical Support.
SW6 – Shutdown Request See Safe Shutdown Procedure on page 5.
SW7 – Restore Defaults Press SW7 for a minimum of five (5) seconds,
thenreleasetoreturn theconfiguration tofactory
default settings:
Primary Connection Type: Ethernet
IPAddress: 192.168.6.6
Subnet Mask: 255.255.255.0
Gateway: 192.168.6.1
Table 1: Maximum Peripheral Loads
Reader/Strike PoE Auxiliary Power Supply
Voltage (DC) 12 24 12 24
Total watts available 8 10 12 20
Table 2: Device Current
Device Operating
Voltage
Average
Measured
Current (mA) Watts
T-100 reader 12 55 .66
T-200 reader 12 55 .66
T-500 reader 12 95 1.14
T-520 reader 12 105 1.26
T-525 reader 12 140 1.68
Securitron M62 Magnalock
strike [1]
1. When using magnetic strikes with auto-voltage select, addi-
tional power allowances must be considered due to auto-
voltage circuitry operation.
12 240 2.88
Securitron M62 Magnalock
strike[1] 24 140 3.36
HES, Inc 5000-12/24D strike 12 230 2.76
HES, Inc 5000-12/24D strike 24 115 2.76
Rutherford 4114x05x32D strike 12 190 2.28
Von Duprin 5100 3FP695
12 VDC 12 290 4.68
Von Duprin 5100 3FP695
24 VDC 24 195 4.68
RCR-REX 12 28 0.34
RCR-REX 24 17 0.41

TruPortal IP-based Single Door Controller Quick Reference 3
Connecting the Door Strikes
One door DO relay is dedicated to the J2 reader port. The door
DO is used for strike control, and may implement an external relay
if necessary.
Figure 1: Door Strike Configuration Using Internal Power (PoE or 24 VDC)
Figure 2: Door Strike Configuration Using External Power
The following table describes connector J2 in Figure 2.
Callout Description
1 Strike Relay Normally Closed (NC)
2 Strike Relay Common
3 Strike Relay Normally Open (NO)
4Protection diode required[1]
1. Use 1N4002, 1N4003, or 1N4004 diodes.
512 or 24 VDC Strike[2]
2. Refer to the TruPortal IPSDC Power Requirements Wattage
Calculator worksheet included on the product disc for strike
type and size.
6 Strike voltage selection. Jumper pins 1 and 2 for 24 VDC strikes;
jumper pins 2 and 3 for 12 VDC strikes.
7 See strike manufacturer’s installation guide for conductor size
(AWG).
Callout Description
1 Strike Relay NC
2 Strike Relay Common
3 Strike Relay NO
4Protection diode required[1]
1. Use 1N4002, 1N4003, or 1N4004 diodes and Metal Oxide
Varistors (MOVs) for AC strikes.
512 or 24 VDC Strike[2]
2. Refer to the TruPortal IPSDC Power Requirements Wattage
Calculator worksheet included on the product disc for strike
type and size.
6 Strike voltage selection. Set jumper to Neutral (no connection)
position.
7 See strike manufacturer’s installation guide for conductor size
(AWG)
8 Strike power supply
9 Provide current restriction device, less than 2 amps through relay.

4 TruPortal IP-based Single Door Controller Quick Reference
Grounding Procedure and Regulatory Information
Note: All bullets must be followed for regulatory compliance.
• All cables connected to the IPSDC must be shielded with
shield terminated as shown in Figure 3. Use #8-32 SEMS
screws provided.
• When wiring readers, ground the shields of the cable at the
IPSDC enclosure grounding studs to avoid electrical noise.
• The IPSDC enclosure must be connected to the nearest
earth ground. (See Figure 4.)
• A convenient earth ground, such as an electrical box or a
ground bus, must be provided to the IPSDC enclosure.
• The earth ground connection must be made to the terminal
lug provided. Mount the terminal lug to the PEM nut on the
bottom of enclosure using the #8-32 SEMS screw provided,
as shown in Figure 4. Use #14-18 AWG wire.
• Before connecting the network cable to connector J10, loop
the cable through ferrite provided as shown in Figure 5.
Note: Ferrite must be installed inside of the enclosure.
Figure 3: Using Shielded Cable and Drain Wire
Figure 4: Wiring Earth Ground
Figure 5: Installing Ferrite
Connecting the Power
The IPSDC provides two methods of connecting power, both of
which are sold separately:
• Network connector J10 as PoE. (See Figure 6).
• Auxiliary power connector J8 with network hub POE device or
24 VDC supply with battery backup (Figure 7).
Figure 6: Connecting Through PoE Hub
Using PoE
Not evaluated by UL.
1. Install a PoE supply (IEEE802.3af 16 watt Class 0 ModeA or
B PoE Power Sourcing Equipment (PSE)) in accordance with
the manufacturer's instructions.
2. By Ethernet standards, the maximum cable length is limited
to 328 ft. (100 m) between the PoE source and the IPSDC.
3. Attach supplied ferrite to the network cable by looping the
network cable through the ferrite as shown in Figure 5.
4. Connect the network cable to connector J10 on the IPSDC.
5. Connect the other end of the network cable to the PoE supply
per the manufacturer’s instructions.

5 TruPortal IP-based Single Door Controller Quick Reference
Figure 7: Connecting Through Network Hub Using PoE or Auxiliary Supply
Using an Auxiliary Power Supply
The IPSDC requires a 24 VDC nominal, 1 amp power supply with
battery backup. The IPSDC, readers, and other devices should be
referenced to the same ground.
For UL-listed installations, the auxiliary power supply must be an
approved UL294 power-limited supply, such as the Altronix Corp.
Model AL176ULX power supply. For UL of Canada (ULC)
installations, the auxiliary power supply must be listed to S319 or
S318.
1. Mount the power supply near the IPSDC enclosure.
2. Run the wire through the knockout hole to connector J8 (see
Figure 8). Pinouts include:
• Pin 1 = +24 VDC
• Pin 2 = – Ground (24 VDC return)
Note: If the polarity is reversed, the fuse blows to prevent
damage. If the fuse blows, it automatically resets within
approximately five (5) seconds.
Figure 8: Auxiliary Power Supply Wiring
Note: For UL-listed installations, Pin 3 is used for AC Power
Fail notifications; Pin 5 is used for Low Battery
notifications.
Configuring the IPSDC
After an IPSDC is installed, follow the instructions in the TruPortal
Software User Guide to use the browser-based Integrated
Configuration Tool (ICT) to:
• Configure the IPSDC to recognize the IP address of the
System Controller (TP-SYS).
• Change the IP address of the IPSDC.
Following is an overview of that procedure; see the TruPortal
Software User Guide or online help for details.
1. Configure a local client workstation for static IP address
192.168.6.1 or a similar valid IP address (e.g., 192.168.6.x
where xis any number between 1 and 254 except 6).
2. Make sure that the PC is not blocked from connecting to IP
address 192.168.6.6. (If the workstation normally connects to
the Internet via a proxy, the proxy settings in the browser may
need to be adjusted.)
3. Open an Internet browser and go to http://192.168.6.6, the
default address of the IPSDC.
4. Type the User ID and Password for the ICT.
The default values are install and install.
5. On the Controller Parameters > Primary Network page,
configure the correct IP address for this IPSDC. A static IP
address is highly recommended. Make a note of the address
for your records. Click Save and then Apply.
6. On the Controller Parameters > Panel Configuration page,
type the IP address of the System Controller. Click Save and
then Apply.
7. Click Restart Application to commit the changes.
After a few minutes, the IPSDC will be accessible via the new
IP address and can be detected by the System Controller
when the [Scan for Hardware Changes] button is clicked in
the TruPortal User Interface.
8. Repeat the procedure for each IPSDC.
Safe Shutdown Procedure
The following procedure can be performed in maintenance mode
or normal operation mode to turn off the IPSDC.
WARNING: Do not reset or restart the IPSDC in the middle of a
firmware update or the IPSDC will become
nonfunctional. Refer to the TruPortal Software User
Guide for more information about firmware updates.
1. Press SW6 and hold the button for three seconds until LEDs
D14 through D21 turn on and stay on. (See Figure 11 for
locations of reset switches and LEDs.)
2. Wait for about five seconds.
3. Remove power to the IPSDC or push SW5 to reset the
IPSDC.
Callout Description Wire Color
1 +24 VDC from auxiliary power supply Red
2 Ground (0V) from auxiliary power supply Black
3 Factory-wired chassis ground. Do not remove. Green
4 +24 VDC auxiliary power supply
Callout Description Wire Color

6 TruPortal IP-based Single Door Controller Quick Reference
Figure 9: IPSDC Board Layout
The following table lists the items shown in Figure 9.
Callout Description Callout Description
1 IPSDC board with overlay 11 Network (Ethernet) port J10
2 Reader In (Access) J1 12 Console port J9
3 Door Contact, Request to Exit (RTE) and
Strike Relay J2 13 Enclosure tamper W5
4 Strike Voltage Select W2 14 Boot Mode switch SW4
5 Custom Wiegand Card Format DIP switch
SW1 15 Hardware Reset switch SW5
6 Reader Out (Egress) J3 16 Shutdown Request switch SW6
7 DIP Switch 2 (set all to OFF) SW2 17 Restore Defaults switch SW7
8 Status LEDs typical 18 Aux Power Input 24 VDC
Note:Jumpersbetweenpins3and4,andpins4
and 5 must remain in place.
9 UCSIMMPlus Module 19 FireAlarm Control Panel (FACP) Input J6
Note: The IPSDC does not support FACP so
this jumper must remain in place.
10 IPSDC board mounting holes

TruPortal IP-based Single Door Controller Quick Reference 7
The following table lists the items shown in Figure 10.
Callout Description Wire Color
Connector J1
1 Reader 1 (access)
2 +12 VDC Red
3 Ground (0V) Black
4 Reader Data 0 Green
5 Reader Data 1 White
6 Door DO (green LED) Orange
7—9 Not used
10 Drain wire (cable shield)[1]
Connector J2
11 Door DI (DC+)
12 Door DI Return (DC-)
13 Exit DI (REX+)
14 Exit DI Return (REX-)
15 Door Contact[2]
16 REX [2]
17 1K EOL resistors typical[3]
Connector J3
18 Reader 2 (egress)
19 +12 VDC Red
20 Ground (0V) Black
21 Reader Data 0 Green
22 Reader Data 1 White
23 Door DO; green LED Orange
24—26 Not used
27 Drain wire (cable shield). See footnote 1
1. Use 20AWG shielded cable and terminate drain wire
(cable shield) at enclosure (see Figure 3 on page 4).
Use plenum-rated cable if cable will be run above a
false ceiling in the air circulation space.
2. Door or Exit DIs Normally Open or Closed.
3. Include resistors for Wiegand Four-State interface.
For Wiegand Two-State interface, omit resistors.
Callout Description Wire Color
Figure 10: Wiegand Wiring

8 TruPortal IP-based Single Door Controller Quick Reference
Figure 11: IPSDC LEDs and Switches
Callout Description State
LEDs
1 D85 Power On ON: power is present
2 D14 Offline Normally OFF
3 D15Address RX Normally OFF
4 D16 BadgeActivity Normally OFF; flashes when badge is read
5 D17 Database Pending Flashes while waiting to receive database from host
6 D18 File SystemActive Normally OFF
7 D19 Watchdog Flashes one beat per second if watchdog is healthy
8 D20 Flash Upload ON when IPSDC is booting up
9 D21 Shutdown Request Normally OFF/Flashes and then ON
10 D33 StrikeActivated ON during strike activation
11 D24 FACP (not supported by IPSDC) ON = contact open
12 D25 Door Contact ON = contact closed; OFF = contact open; Flashing = fault
13 D26 Door REX ON = contact closed; OFF = contact open; Flashing = fault
14 DS and DS5 Link ON = link activity; OFF = no activity. Flashing = network activity
15 DS4 and DS8 Collision ON = Collision
16 DS3 and DS7 Full Duplex ON = Full duplex; OFF = Half duplex
17 DS2 and DS6 100/10 Mbps ON = 100 Mbps; OFF = 10 Mbps
Switches
18 SW4 Boot Mode Manually enables the ICT.
19 SW5 Hardware Reset Reboots the IPSDC.
20 SW6 Shutdown Request Initiates Safe Shutdown of the IPSDC.
21 SW7 Restore Defaults Returns configuration to factory defaults.

TruPortal IP-based Single Door Controller Quick Reference 9
Specifications Regulatory Information
Contact Information
www.interlogix.com
Customer support: www.interlogix.com/support
© 30OCT13 United Technologies Corporation
Interlogix is part of UTC Climate, Controls & Security, a unit of
United Technologies Corporation. All rights reserved.
Document number: 460939301C - October 2013
Dimensions(Height×
Width × Depth) 10.15 in. x 9.15 in. x 3.04 in.
(258 mm x 232 mm x 77 mm)
Operating
environment
temperature[1]
1. +32° to +120° F (0° to +49° C)
+35 to +122° F (+2 to +50° C)
Humidity range[2]
2. Up to 85% non-condensing
5 to 95% non-condensing
Thermal air cooling At least 6 in. (15.2 cm) of clearance is required on all
four sides of the enclosure.
Power input
requirements IEEE802.3af 16 watt Class 0 ModeA and B PoE/
PSE)onStandard Category5(CAT5) Ethernetcable
Note: By Ethernet standards, the maximum cable
length is limited to 328 ft. (100 m) between the PoE
source and the IPSDC.
-or-
Auxiliary 24 VDC 1A local supply (24 watts).
IPSDC to reader
cabling Reader voltage: 12 VDC
Note: If the cable distance is greater than 500 feet
(152.4 m), but less than or equal to 2000 feet
(609.6m)and/or thecurrent perreader isgreater than
150 mA, use 20AWG shielded cable.
If the cable distance is less than 500 feet (152.4 m),
use 22AWG shielded cable.
Recommended:Use20AWGshieldedcableto wire
reader, DOs, and DIs. Use plenum-rated cable for
applications where cable will run above a false (i.e.,
suspended) ceiling in the air circulation space.
Recommended:Alpha Xtra Guard1 foil shield cable,
non-plenum-rated, or Belden-series security and
alarm cable (commercial applications shielded),
plenum-rated.
Readers Maximum number of readers supported: 2
Reader technology supported: Wiegand
Output devices maximum ratings: Door DO (Reader
LED) = 20.mA @ 12 VDC maximum; Door strike
(DO) relay = 2A @ 28 VDC or 30 VAC maximum
Strikes Maximum current: 390 mA per strike output. See
Table 2 on page 2 for recommended strike models
and associated power requirements.
Network
requirements AlthoughIPSDCs areequipped witha fallbackmode,
theyshould beplaced onanetwork withan adequate
reliability rate. (A network reliability rate of 99.98
percent is typical for mission-critical operations.)
If a typical Mean Time To Repair (MTTR) goal is one
hour, then using the 99.98% reliability rate equates to
a mean network reliability, or Mean Time Between
Failure(MTBF),goalofapproximately5,000hours(or
1hr/.0002). In other words, the network that the
IPSDC is being placed on (from the door controller to
theSystemController),shouldnotfail moreoften than
once every 5,000 hours (or approximately 208 days)
on average.
UL evaluation for UL-Listed Installations:
Manufacturer Interlogix
Headquarters and Regulatory responsibility:
Interlogix
3211 Progress Dr.
Lincolnton, NC 28092 USA
EU authorized manufacturing representative:
UTC Climate, Controls & Security B.V.,
Kelvinstraat 7, 6003 DH Weert,
The Netherlands
Year of
manufacture The first two digits of the product serial number (located
on the product identification label) are the year of
manufacture.
NorthAmerican
standards UL 294
FCC
compliance This device complies with part 15 of the FCC Rules.
Operation is subject to the following two conditions: (1)
This device may not cause harmful interference, and (2)
this device must accept any interference received,
including interference that may cause undesired
operation.
Environmental
Class UL: Indoor dry
Certification
EuropeanUnion
directives We declare under our sole responsibility that this product
is in conformity with Directive 1999/5/EC (R&TTE), 2004/
108/EC (EMC), 2006/95/EC (LVD), and 93/68/EEC
(Marking) based on test results using harmonized
standards in accordance with the Directives mentioned.
This manual suits for next models
1
Table of contents
Other Interlogix Controllers manuals